Banner's DXM Logic Controller integrates Banner's wireless radio, cellular connectivity, and local I/O to provide a platform
for the Industrial Internet of Things (IIoT).
The DXM Controller's wired and wireless connectivity
equipment. The cellular modem option eliminates the need for IT infrastructures to connect remote equipment for sensing
and control. The integrated Sure Cross® wireless radio enables Modbus connectivity to remote sensors, indicators, and
control equipment.
The DXM Controller incorporates several automation protocols into its system, including:
Internet messaging tools share information generated by sensors, indicators, and control equipment with automation
systems and personnel. When Internet messaging is used in combination with the logic controller, the DXM Controller can
generate and send historical data logs, alerts, and alarms using Ethernet or cellular connectivity options. Banner's API
interface allows the user to create connections with web-based automation or business systems.
Program the DXM Controller's logic controller using action rules and text language, which can execute concurrently. The
control functions allow freedom when creating custom sensing and control sequences. The logic controller supports the
Modbus protocol standards for data management, ensuring seamless integration with existing automation systems.
On-board universal and programmable I/O ports connect to local sensors, indicators, and control equipment.
A simple user interface consists of an LCD screen and four LED indicators. Use the LCD to access system status and
setup, view user selectable events or data, and to bind and perform site surveys for Sure Cross radios. Configure the user
programmable LEDs to indicate the status of the DXM Controller, processes, or equipment.
1.2 DXM Automation Protocols
The DXM Controller supports the following automation protocols.
www.bannerengineering.com - Tel: 763.544.31643
options make it easy to share data between local and remote
• Modbus RTU—Integrates into existing RS-485 serial-based Modbus-enabled automation systems.
• Modbus TCP—Uses Ethernet to attach to existing Modbus-enabled automation systems.
• EtherNet/IP—Automation systems that use the EtherNet/IP protocol can directly attach to the DXM Controller using
Ethernet.
Page 4
DXM Controller Modbus Overview
Internal Processor (Modbus SID 199 )
I/O Base (Modbus SID 200)
Display (Modbus SID 201 )
ISM Radio (Modbus SID X)
Ethernet
RS232
RS485 (master)
RS485 (slave)
USB
Action Rules
Script Basic
Rd/Wr Rules
Data
Traffic
Control
Local
Registers
32-bit
Local
Registers
32-bit Float
LED
Display
Registers
Gateway/
MultiHop
Registers
I/O Base
Data
Registers
I/O Base
Config
Registers
DXM100 Controller Instruction Manual
Modbus RTU. The
DXM Controller manages two separate physical ports running the Modbus RTU protocol. The DXM
Controller is the Modbus Master when operating the Modbus master RTU port. The DXM Controller uses the master Modbus
RTU bus to communicate with locally connected Modbus devices or uses the Banner wireless radio to communicate with
remote Modbus devices. The other Modbus RTU port is used by a host system to access the DXM Controller as a slave
device. The slave Modbus RTU port allows access all the internal registers concurrently with the master RTU port. By
default, the Modbus RTU ports are active. Configure the port parameters using the DXM Configuration Tool.
Modbus TCP/IP. A host system acting as a Modbus client can access the DXM Controller using the Modbus TCP/IP
protocol over Ethernet. Standard Modbus port 502 is used by the DXM Controller for all Modbus TCP/IP requests. All
internal registers are available to the host system concurrently with Modbus RTU. By default, Modbus TCP/IP is active.
EtherNet/IP™. The Ethernet port is actively running EtherNet/IP. From the factory the DXM Controller is configured to
read and write registers on DX80 wireless devices 1 through 16. Custom configurations can be set using the DXM
Configuration Tool. By default, EtherNet/IP is active.
1.3 DXM Modbus Overview
The DXM Controller uses internal 32-bit registers to store information. The internal local registers serve as the main global
pool of registers used as the common data exchange mechanism. External Modbus device registers can be read into the
local registers or written from the local data registers.
The DXM Controller, as a Modbus master device or
slave device, exchanges data using the local
registers. Modbus over Ethernet (Modbus/TCP) uses
the local registers as the accessible register data.
Using Action, Read/Write, and Threshold Rules
allows you to manipulate the local registers to
create solutions for applications. The ScriptBasic
programming capabilities extends the use of local
registers with its own variables to create a flexible
programming solution for more complex
applications.
The local registers are divided into two different
types: 32-bit integer and 32-bit floating point.
When using local registers internally, the user can
store 32-bit numbers. Using local registers with
external Modbus devices follows the Modbus
standard of a 16-bit holding register.
Accessing the I/O Base and the LCD display follows
the same communication as an external Modbus
slave device. Each device has a slave ID number to
uniquely identify itself. The I/O base is Modbus
slave ID 200 and the LCD is Modbus slave ID 201.
4www.bannerengineering.com - Tel: 763.544.3164
Page 5
USB
Ethernet
DXM Configuration Software
Local Registers
Register
View Utility
Scheduler
Action Rules
Register Mapping
XML Config File
Script Basic
System
Settings
DXM100 Controller Instruction Manual
1.4 DXM Configuration Tool Overview
The main storage elements for the DXM Controller are its Local
Registers, which can store up to 4-byte values that result from
register mapping, action rules, or ScriptBasic commands.
The Register Mapping function has two main components: a read
rule and a write rule. These rules allow the user to program the ability
to read or write information from Modbus slaves to/from the local
registers.
The Action Rules allow for logic functions and manipulation of local
register data. Action rules are processed autonomously from other
local register functions. There are three types of action rules:
thresholds, register copy, and math/logic.
Use the Scheduler
register during a specific time, day, or week. Events can be
programmed by days of the week with the ability to create holidays
for exception conditions.
Use the Register View Utility to read or write local registers within
the DXM Controller or Modbus Slave devices connected to the DXM
Controller. This allows the user to debug connections to external
devices by viewing live local register data within the controller.
The System Settings define parameters for the DXM Controller,
including email notifications, Cloud settings, time of day settings, local
logging settings, SMS messaging, ScriptBasic programming control,
and Ethernet network settings.
to program when values are sent to a local
The DXM Configuration Tool configures the DXM Controller by creating an XML file that is transferred to the DXM Controller
using a USB or Ethernet connection. The
using a cellular or Ethernet connection.
This configuration file governs all aspects of the DXM Controller operation. The wireless network devices are a separate
configurable system. Use the DX80 User Configuration Tool (UCT) to configure the internal DX80 wireless Gateway and the
attached wireless Nodes. Use the MultiHop Configuration Tool (MCT) if the internal radio is a MultiHop device.
All tools can be connected to the DXM Controller using a USB cable or an Ethernet connection. Each tool can be run
individually or launched through the DXM Configuration Tool.
DXM Controller can also receive the XML configuration file from a Web server
www.bannerengineering.com - Tel: 763.544.31645
Page 6
Cellular Radio Board
SAM4 Processor Board
MultiHop or Gateway
Radio Board
DXM100 I/O Board
Cellular Antenna
Connection
ISM Radio
Antenna
Connection
Housing Catch
DXM100 Controller Instruction Manual
2 DXM Hardware Configuration
2.1 DXM Hardware Configuration Overview
The DXM100 Controller can have multiple configurations. The DXM100 Controller will have a model number label on the
housing. Use the model number and model table above to identify which boards are included in the controller.
When opening the
The DXM100 Controller I/O base board provides connections for all inputs, outputs and power. The base board also
contains a 12 V solar controller that accepts connections to a solar panel and SLA battery. The battery connection can also
be used with line power to provide a battery backup in case of line power outages.
DXM100 Controller, follow proper ESD grounding procedures. Refer to the ESD warning in the appendix.
The ISM radio, either a MultiHop or DX80 Gateway, fits on the base board in the parallel sockets. Install the ISM radio so
the U.FL antenna connection is to the side with the SMA antenna connectors. Connect the U.FL cable from the ISM radio
U.FL to the right side U.FL connector. The ISM radio boards are available with either a 900 MHz radio or a 2.4 GHz radio.
The SAM4 processor board plugs into the base board using the two 20 pin socket connectors. The board sits above the ISM
radio socket and held by the base board standoffs. Position the processor board so the USB and RJ45 Ethernet connection
is to the front, away from the SMA antenna connections.
The top plugin PCB is the optional cellular radio. This plugs into the SAM4 processor board with the U.FL antenna
connection to the left. Attach the antenna cable from the cellular module to the left U.FL connection on the base board.
The top housing contains the LCD display board. The display board is connected to the base board using a ribbon cable
with a 20 pin connector.
In some DXM models, the cellular radio module may be replaced with an ISM radio. The top ISM radio antenna connection
will be to the left SMA connector.
6www.bannerengineering.com - Tel: 763.544.3164
Page 7
5
1
ON
ON
A
D1
B
C
D2
234
678
DXM100 Controller Instruction Manual
2.2 ISM Radio Board (Modbus Slave ID 1)
The ISM radio board may be a MultiHop radio (DX80DR*M-HE5) or a Performance Gateway radio (DX80G*M2S-PE5). Refer
to the model number label on the
DXM100 Controller and the model number table to identify the ISM radio type.
The ISM radio should be plugged into the I/O base board
with the U.FL antenna connector closest to the SMA
connectors.
A - Antenna connector
B - Button
C - LED
D1 and D2 - DIP switches
2.2 MultiHop (HE5) DIP Switch Settings
Switches
Device Settings12345678
Serial line baud rate 19200 OR User defined receiver
slots
Serial line baud rate 38400 OR 32 receiver slotsOFFON
Serial line baud rate 9600 OR 128 receiver slotsONOFF
Serial line baud rate Custom OR 4 receiver slotsONON
Parity: NoneOFF*OFF*
Parity: EvenOFFON
Parity: OddONOFF
Disable serial (low power mode) and enable the
receiver slots select for switches 1-2
Transmit power
900 MHz radios: 1.00 Watt (30 dBm)
2.4 GHz radios: 0.065 Watts (18 dBm) and 60 ms
frame
Transmit power
900 MHz radios: 0.25 Watts (24 dBm)
2.4 GHz radios: 0.065 Watts (18 dBm) and 40 ms
frame
OFF*OFF*
ONON
OFF*
ON
Application mode: ModbusOFF*
Application mode: TransparentON
www.bannerengineering.com - Tel: 763.544.31647
Page 8
1
P2
A
A
B
D
E
C
LED 1
LED 2
LED 3
LED 4
DXM100 Controller Instruction Manual
Switches
Device Settings12345678
MultiHop radio setting: RepeaterOFF*OFF*
MultiHop radio setting: MasterOFFON
MultiHop radio setting: SlaveONOFF
MultiHop radio setting: ReservedONON
2.2 Performance Gateway (PE5) DIP Switch Settings
Switches
Device Settings12
Transmit Power Level: 1 Watt (30 dBm)OFF (default)
Transmit Power Level: 250 mW (24 dBm), DX80 Compatibility ModeON
2.2 Button Operation
Typically you use the DXM LCD to put the device into binding mode, but you may also use the button on the ISM radio
boards to enter binding mode. However, most DXM models will not provide access to this button.
2.2 LED Operation
The LED located on the ISM radio module indicates power and communications traffic.
Solid green DX80 ISM radio LED: Indicates power.
•
• Flashing green MultiHop ISM radio LED indicates operation.
• Red and green combined: Communications traffic and binding.
2.3 SAM4 Processor Board
A - Cellular radio connection
B - Force cloud push/Clear password
C - Boot load jumpers
D - DIP switches
E - Micro SD card
Cellular Radio Connection. Install the cellular modem onto the SAM4 board with the cellular modem's U.FL connector on
the left. The antenna cable will go between the cellular U.FL connector and the left I/O board U.FL connector. Only install/
remove a cellular modem when the power to the device is disconnected.
Force Cloud Push button. Press and hold this button for two seconds to send an immediate push message from the
device (if properly configured).
8www.bannerengineering.com - Tel: 763.544.3164
Page 9
DXM100 Controller Instruction Manual
Clear Password. By default, the
DXM Controller does not require a password to load a configuration file. If a password is
defined, the DXM Controller requires that you enter the password before uploading a configuration file. To change the
password, you must already know the current password. If you do not know the current password, clear the password
from the DXM Controller.
CAUTION: Clearing the password erases the current configuration and any program files, log files, or
history files currently on the
DXM Controller.
Follow these steps to clear the password requirement from your DXM Controller.
Turn off the power.
1.
2. Set DIP switch 4 to the ON position.
3. Press and hold button 'B'.
4. Apply power to the device.
5. After leaving the device powered on for a few seconds, turn off the power again.
6. Set DIP switch 4 to the OFF position.
7. Reload the configuration file before resuming normal operation.
The password is cleared from the system.
2.3 DIP Switch Configuration
Cycle power to the device after making any changes to the DIP switch settings.
Settings
1234
OFF *
Disable Ethernet Port
ON
Disable LCD Display
Not usedOFF *
Bypass XML
DIP Switches
OFF *
ON
OFF *
ON
Bypass XML
Turn to ON to have the XML file ignored at boot time. This is useful for ignoring a corrupt or questionable XML
configuration file. After the device is running, a new XML file can be loaded using the DXM configuration tool. The
factory default position is OFF.
Disable Ethernet Port
Set to ON to power down the Ethernet interface. The factory default position is OFF.
Disable LCD Display
Set to ON to disable the LCD. This DIP switched should be ON when the LCD display board is not connected. The
factory default position is OFF.
2.3 Button Operation
The SAM4 processor button has two functions:
Clearing the access password as explained above.
•
• Pressing the button for 5 seconds forces a Push to the webserver. This assumes a proper configuration for the
webserver.
2.3 LED Operation
By default, the four LEDs indicate the following conditions:
• LED 1 - Heartbeat, indicates the processor is running.
• LED 2 - Indicates the cellular modem power cutoff is active. If the incoming power is less than 11.2 V, the cellular
modem is powered down.
• LED 3 - XML configuration file was rejected.
• LED 4 - ScriptBasic program failed to load.
www.bannerengineering.com - Tel: 763.544.31649
Page 10
ON
ON
1
1
1
1
1
1
1
1
LED2
C95
TB1
C6
R121
FET9
R82
TB4
P2
P4
SW1
C4
P5
P16
SW2
P10
IC18
TB3
P7
TB2
TB9
Y1
SW3
P6
L2
C19
C18
C20
TB5
D3
R118
R122
TVS1
L1
R120
DZ2
R77
C10
D5
D4
P9
P8
P1
LED1
P3
A
B
C
D
E
F
G
H
J
K
L
118
1932
mA
V
A OUT 2
A OUT 1
DXM100 Controller Instruction Manual
2.4 I/O Base Board
For the complete I/O base board definitions, see I/O Base Board Connections on page
ABase board LEDE
BA1. Cellular antennaFRadio Binding ButtonKModbus Slave ID DIP Switches
CRadio LEDGProgramming headerLSAM4 Processor Board Connection
DA2. ISM AntennaHISM Radio Board Connection
2.4.1 DIP Switches for the I/O Board
DXM100 Controller I/O board DIP switches are set from the factory to Modbus Slave ID 200 and should not need to be
The
changed. For more advanced information about the DIP switches, refer to Setting the Modbus Slave ID on the I/O Base
Board on page 11.
2.4.2 I/O Board Jumpers
Hardware jumpers on the DXM I/O board allow the user to select alternative pin operations. Turn the power off to the
device before changing jumper positions.
JumperFunctionPositions
EAnalog output characteristics
10www.bannerengineering.com - Tel: 763.544.3164
for AO2 (pin 19) and AO1 (pin
20)
13.
Jumpers - Configures Analog Out
1 and 2 for mA or V
Defines current (0–20 mA) or voltage (0–10 V) for analog output 1 and 2.
By default, current (0–20 mA) is selected using jumpers 1 and 2 and registers 4008 and
4028 contain a value of 2.
To select voltage (0–10 V) for output Aout1, set jumper 1 in the voltage position (V) and
set Modbus register 4008 on the I/O board (SID 200) to 3.
To select voltage (0–10 V) for output Aout2, set jumper 2 in the voltage position (V) and
set Modbus register 4028 on the I/O board (SID 200) to 3.
JModbus Slave ID DIP Switches
Page 11
DXM100 Controller Instruction Manual
JumperFunctionPositions
MCourtesy power output P3The jumper selects 5 V when in the "a" position and incoming power (pin 2) in the "b"
position.
2.4.3 Setting the Modbus Slave ID on the I/O Base Board
Only DXM Slave models require that the Modbus Slave ID to be adjusted on the I/O base board. The
DXM100 Controller
models use DIP switches J and K to set the Modbus Slave ID. This device can use a Modbus register 6804 in the I/O board
to access the full range of Modbus Slave IDs.
On the DXM100 Controller models, use the DIP switches at location K to define the lower digit of the Modbus Slave ID.
2.4.3 DXM100 Controller Models
DIP Switch location J defines the course group of Modbus Slave IDs. DIP Switch 4 must be set to ON for DXM100-S1 and
DXM100-S1R2 models.
Settings
Modbus Slave ID set to 11 through 19OFFOFF
Modbus Slave ID set to 20 through 29ONOFF
Modbus Slave ID set to 30 through 39OFFON
Modbus Slave ID set to 40 through 49ONON
Not UsedModbus Slave Configuration (S1 model only)
I2C Processor CommunicationOFF
DIP Switches JDIP Switch K, Switches 1, 2, 3, 4 (0 is OFF, 1 is ON)
DXM100 Controller to a Modbus Slave ID of 34, set the following:
Location J DIP switches set to 1=OFF, 2=ON
Location K DIP switches set to 1=OFF, 2=OFF, 3=ON, 4=OFF
The location J DIP switches set the upper Modbus Slave ID digit to 3 while the location K DIP switches set the lower digit to
4.
2.4.3 Setting the DXM I/O Board Modbus Slave ID using Modbus Registers
Write to the I/O board's Modbus register 6804 to set the Modbus Slave ID to any valid Modbus Slave ID (1 through 245).
• For the DXM100 Controller model, all switches on DIP switch K should be in the OFF position to use the Modbus
register slave ID.
1
Must be in the ON position for the -S1 model)
2
Uses value in Modbus register 6804.
www.bannerengineering.com - Tel: 763.544.316411
Page 12
A
DXM100 Controller Instruction Manual
2.5 Cellular Modem Board
The optional cellular modem is installed on the SAM4 processor
board on the two 12-pin sockets. The U.FL connector should be to
the left, with the antenna cable going to the left antenna U.FL
connector.
2.6 DXM100 Dimensions
All measurements are listed in millimeters, unless noted otherwise.
12www.bannerengineering.com - Tel: 763.544.3164
Page 13
ON
ON
1
1
1
1
1
1
1
1
LED2
C95
TB1
C6
R121
FET9
R82
TB4
P2
P4
SW1
C4
P5
P16
SW2
P10
IC18
TB3
P7
TB2
TB9
Y1
SW3
P6
L2
C19
C18
C20
TB5
D3
R118
R122
TVS1
L1
R120
DZ2
R77
C10
D5
D4
P9
P8
P1
LED1
P3
A
B
C
D
E
F
G
H
J
K
L
118
1932
mA
V
A OUT 2
A OUT 1
DXM100 Controller Instruction Manual
3 DXM Connections
3.1 I/O Base Board Connections
1No connection12CT. RS-232 CTS23N3. NMOS OUT 3
PW. 12 to 30 V dc or solar power in
2
(+)
3GD. Ground14S+. Secondary RS-485 +25N1. NMOS OUT 1
4B+. Battery in (< 15 V dc)15CL. CANL26GD. Ground
5GD. Ground16CH. CANH27U4. Universal Input 4
6M-. Primary RS-485 –17GD. GND28U3. Universal Input 3
7M+. Primary RS-485 +18P3. Courtesy Power 5 V29GD. Ground
8GD. Ground19A2. Analog OUT 230P1. Switch Power (5 V or 16 V)
9TX. RS-232 Tx20A1. Analog OUT 131U2. Universal Input 2
10RX. RS-232 Rx21P2. Switch Power (5 V or 16 V)32U1. Universal Input 1
11RT. RS-232 RTS22N4. NMOS OUT 4
ABase board LEDE
BA1. Cellular antennaFRadio Binding ButtonKModbus Slave ID DIP Switches
CRadio LEDGProgramming headerLSAM4 Processor Board Connection
DA2. ISM AntennaHISM Radio Board Connection
www.bannerengineering.com - Tel: 763.544.316413
13S-. Secondary RS-485 –24N2. NMOS OUT 2
Jumpers - Configures Analog Out
1 and 2 for mA or V
JModbus Slave ID DIP Switches
Page 14
DXM100 Controller Instruction Manual
3.2 Applying Power to the DXM100 Controller
Apply power to the DXM100 Controller using either 12 to 30 V dc or a 12 V dc solar panel and 12 V sealed lead acid
operating together.
battery
The DXM100 has three power input and three power output options:
• For inputs
◦12 to 30 V dc
◦12 to 30 V dc solar panel
◦12 V dc sealed lead acid battery with automatic charging
• For outputs
◦One 5 V dc fixed
◦Two 5 V dc or 16 V dc switched
The DXM Controller continuously monitors the health of the power inputs. If a power input fault is detected, the DXM
Controller automatically switches over to battery with continuous uninterrupted operation.
If the incoming voltage drops below 11.2 V, the cellular modem does not turn on and will not turn on until the voltage is
above 11.8 V. A text file (CmVMon.txt) on the internal micro SD card saves the periodic sampling of the incoming voltage.
If cellular operation stops because of voltage, it is logged in this file.
The DXM Controller automatically charges the sealed acid battery. The charging algorithm is designed to work with a
sealed lead acid (SLA) battery only.
• When using 12 to 30 V dc , connect the 12 to 30 V dc + to pin 2 and connect the ground to pin 3.
• When using main dc power with a back up battery (default configuration), connect the incoming main power pin 2
(+) and to pin 3 (-). Connect the 12 V sealed lead acid battery to pin 4 (+) and pin 5 (-). The incoming main power
must be 15 to 30 V dc to charge the battery.
• When using a solar panel, connect the solar panel output to pin 2 and connect the ground to pin 3. Connect the 12
V dc SLA battery to pin 4 (+) and pin 5 (-). To change the charging algorithm, refer to Supplying Power from Solar
(B1 and S1).
PinDescription
Pin 1No connection
Pin 212 to 30 V dc input (+) or solar panel connection (+)
Pins 3, 5, 8, 17, 26, 29Main logic ground for the DXM100 Controller
Pin 4Solar or backup battery positive input. Battery voltage must be less than 15 V dc. Use only a sealed lead acid (SLA)
battery.
3.2 Using Courtesy Power or Switch Power
Pin 18 of the
Pins 21 (switch power 2) and 30 (switch power 1) are switched power outputs. Configure the switched power outputs using
Modbus registers. The output voltage can be either 5 volts or 16 volts and is controlled using a Modbus register on the I/O
board (Modbus slave ID 200).
DXM100 Controller is a constant power source that supplies 5 volts up to 500 mA.
Switch PowerEnable RegisterVoltage Register
1 (pin 30)
2 (pin 21)
2201
Write a 0 to turn OFF
Write a 1 to turn ON (default)
2251
Write a 0 to turn OFF
Write a 1 to turn ON (default)
3601
Write a 0 to select 5 V (default)
Write a 1 to select 16 V
3621
Write a 0 to select 5 V (default)
Write a 1 to select 16 V
3.2.1 Supplying Power from 12 to 30 V dc and a Battery Backup
The factory default setting for the battery charging algorithm assumes you are using
14www.bannerengineering.com - Tel: 763.544.3164
12 to 30 V dc to recharge the battery.
Page 15
DXM100 Controller Instruction Manual
Modbus Slave IDModbus RegisterDescription
200 *6071Battery backup charging algorithm.
0 = Battery is recharged from a solar panel
1 = Battery is recharged from
12 to 30 V dc . (default)
* The Modbus Slave ID for the base board is set at the factory. This may be changed using the base board DIP switch
settings.
3.2.2 Supplying Power from a Solar Panel
To power the
DXM100 Controller from a 12 V dc solar panel, connect the solar panel to power pins 2(+) and 3(-). Connect
a 12 V dc sealed lead acid (SLA) rechargeable battery to pins 4(+) and 5(-).
The factory default setting for the battery charging algorithm assumes you are using 12 to 30 V dc power to recharge the
battery. If the incoming power is from a solar panel, you must change the charging algorithm.
To change the charging algorithm from the menu system:
1. From the LCD menu, select Update > Power.
2. Use the up/down arrows to select "SOLAR" power.
To change the charging algorithm by writing to Modbus register 6071 on the I/O base board (Slave ID 200):
1. Write a 0 to select the solar power charging algorithm.
Modbus Slave IDModbus RegisterDescription
200 *6071Battery backup charging algorithm.
0 = Battery is recharged from a solar panel
1 = Battery is recharged from
12 to 30 V dc . (default)
The following power operating characteristics are stored in Modbus registers.
Battery voltageIf no battery is present, the value in this register is less than 5 V. If the value in this register is
greater than the incoming voltage register, the battery is powering the system.
Battery charging
current
Incoming supply
voltage
The charging algorithm charges the battery when the incoming voltage register value is greater
than the battery voltage register value. This registers shows the charging current in milliamps.
The incoming power can be from a solar panel or from a power supply. The battery is charging
when the incoming voltage register value is greater than the battery voltage register value. The
battery is powering the system when the incoming voltage register value is less than the battery
voltage register value.
On-board
thermistor
temperature
This register stores the on-board thermistor reading in tenths of degrees C, this is not a calibrated
input: divide by 10 to calculate the temperature in degrees C. For calibrated temperature inputs,
define one of the universal inputs as a temperature input.
Modbus Slave IDModbus RegisterDescription
200 *6081Battery voltage (mV)
6082Battery charging current (mA)
6083Incoming supply voltage (mV) (solar or power supply)
6084On-board thermistor temperature (⁰C)
* The Slave ID for the base board is set at the factory. This may be changed using the base board DIP switch settings.
3.3 Connecting the Communication Pins
The base board communications connections to the device are RS-485 (primary), RS-485 (secondary) or RS-232.
RS-485. The primary RS-485 bus is a common bus shared with the ISM radio board (Modbus Slave ID 1) or optional
cellular board. The
the local processor registers (Modbus Slave ID 199), the base I/O controller (Modbus Slave ID 200), and the display board
(Modbus Slave ID 201). When assigning Modbus Slave IDs to externally connected devices, only use IDs 2 through 198.
www.bannerengineering.com - Tel: 763.544.316415
DXM100 Controller is defined as the Modbus Master on this bus. Other internal Modbus slaves include
Running Modbus protocol at 19.2k baud, use this bus to connect to other Modbus
Slave devices. The
Serial RS-232 connection. This bus must use a ground connection between devices to
operate correctly.
The DXM100 Controller is a Modbus slave on this bus (see I/O Base Board Connections
on page 13).
DXM100 Controller is a Modbus Master device on this RS-485 port.
3.3 Modbus RTU Master/Modbus RTU Slave
DXM100 Controller can be a Modbus RTU master device to other slave devices and can be a Modbus slave device to
The
another Modbus RTU master. The DXM100 Controller uses the primary RS-485 port (pins 6 and 7) as a Modbus RTU
master to control external slave devices. The secondary port (pins 11 and 12) is the Modbus RTU slave connection.
• As a Modbus RTU master device, the DXM100 Controller controls external slaves connected to the primary RS-485
port, the local ISM radio, local I/O base board, and the local display board.
• As a Modbus RTU slave device, the DXM100 Controller local registers can be read from or written to by another
Modbus RTU master device.
Use the DXM Configuration Tool to define operational settings for both the Modbus RTU master port and the Modbus RTU
slave port.
3.4 Ethernet
Before applying power to the DXM100 Controller, verify the Ethernet cable is connected. If the Ethernet cable is not
connected when the device powers up, the DXM100 Controller will not recognize the connection.
The Ethernet connection supports the DXM Configuration Tool, Modbus/TCP, and EtherNet/IP. ScriptBasic also has access
to Ethernet for custom programming. Use the DXM Configuration Tool to configure the characteristics of the Ethernet
connection, fixed IP addresses, DHCP, etc. The LCD menu allows the user to change the IP Address.
3.5 Modbus Master Port and Slave Port
There are two RS-485 ports on the DXM Controller, a Modbus master RS-485 port and a Modbus slave RS-485 port.
The Modbus master RS-485 is controlled by the
connected to the master RS-485 port must be slave devices.
The Modbus slave RS-485 port is controlled by another Modbus master device, not the DXM Controller. The slave port is
used by other devices that want to access the DXM Controller as a Modbus slave device. All local registers are available to
be read or written from this slave port. Set the Modbus Slave ID for the secondary RS-485 port using the LCD display
menu: System > DXM Slave ID.
3.5.1 Modbus Master and Slave Port Settings
The basic communications parameters for the RS-485 ports are set in the DXM Configuration Tool and are saved in the
XML configuration file. All basic settings are available under Settings > General screen of the DXM Configuration Tool.
DXM Controller, which acts as the Modbus master. All wired devices
Master port parameters include:
• Baud rate and parity
• Set the Communications Timeout parameter to cover the expected time for messages to be sent throughout the
wireless network. For the DXM Controller, the Communications Timeout parameter is the maximum amount of
time the DXM Controller should wait after a request is sent until the response message is received from the Modbus
slave device.
• Maximum Polling Rate sets the minimum wait time from the end of a Modbus transaction to the beginning of the
next Modbus transaction.
16www.bannerengineering.com - Tel: 763.544.3164
Page 17
Banner Eng .
08:25:45
→ Registers
→ PushS → 08:25:15
→
ISM Radio
→ System
↑
↓
ENTER
BACK
→ System Info
System
08:25:45
→ DXM Slave ID: -1
→ Provision Cell
→ Power: [dc / solar]
→ Restart!
ENTER
BACK
↑
↓
DXM100 Controller Instruction Manual
The Modbus Slave port settings include:
• Baud rate and parity (also set on this screen)
Set the Modbus Slave port ID using the DXM Controller LCD
•
• Set the Wireless Modbus Backbone parameter when there is an ISM radio plugged into the SAM4 processor
board and the Modbus slave port is using the MultiHop radio as the slave port instead of the terminal block
connection.
3.5.2 Modbus Slave Port ID
Set the DXM Modbus slave port using the LCD menu system. On the LCD,
use the down arrow to highlight System. Enter the System menu by
clicking Enter.
To change the DXM Slave ID, highlight DXM Slave ID, then click Enter.
Use the up and down arrow buttons to change the DXM Slave ID.
Press Enter to accept the ID change.
After you change the DXM Slave ID, use the DXM Configuration Tool to cycle power to the device. After cycling power to
the device, the updated DXM Slave ID is listed under the System
menu.
3.6 USB
The USB port is used with the DXM Configuration Tool to program the DXM100 Controller. The USB port is also used as the
console output for the processor and ScriptBasic.
www.bannerengineering.com - Tel: 763.544.316417
Page 18
Ethernet
Modbus RS-485
(slave
port)
Processor Modbus
Control/Data
External
Modbus
Slaves (2-10)
Modbus RS-485
(master port)
Modbus
SID
199
Modbus
SID
1
Modbus
SID
201
Modbus
SID
200
Local
Registers
GW/MH
Radio
DisplayI/O Base
DXM100 Controller Instruction Manual
4 Working with Modbus Devices
4.1 Overview
The DXM Controller has two physical RS-485 connections using Modbus RTU protocol.
The master Modbus RS-485 port is for the
DXM Controller to act as a Modbus master device to control internal and
external Modbus slave devices.
The Modbus master RS-485 port is labeled M+, M- on the DXM Controller. The Modbus slave port is used when another
Modbus master device wants to communicate with the DXM Controller when the DXM Controller is a Modbus slave device.
The Modbus slave RS-485 port is labeled S=, S1 on the DXM Controller.
The DXM Controller has dual Modbus roles: a Modbus slave device and a Modbus master device. These run as separate
processes.
The Modbus slave port allows access into the
Controller needs to be assigned a unique Modbus slave ID as it pertains to the host Modbus network. This slave ID is
separate from the internal Modbus slave IDs the DXM Controller uses for its own Modbus network. The DXM Modbus slave
ID is defined through the LCD menu. Other Modbus slave port parameters are defined by using the DXM Configuration
Tool.
The DXM Controller operates the Modbus master port. Each device on the master port must be assigned a unique slave ID.
There are slave IDs that are reserved for internal devices in the DXM Controller.
Modbus Slave IDDevice
1Gateway (PE5) or MultiHop (HE5) ISM Radio—MultiHop wireless devices connected to the internal MultiHop radio should
199Local Registers—Internal storage registers of the DXM Controller
200I/O Base Board—All data and parameters for each input or output of the DXM Controller.
201LCD Display—The user has access to the LED indicators on the DXM Controller.
4.2 Assigning Modbus Slave IDs
4.2 DXM Modbus Slave ID
Assign the DXM Modbus Slave ID only if a Modbus master device is reading or writing the
data through the Modbus RS-485 slave port (S+, S-).
Set the DXM Slave ID from the LCD menu under System > DXM Slave ID. The DXM Controller can have any unique slave
be assigned Modbus Slave addresses starting at 11.
ID between 1 and 246, depending upon the host Modbus network. Other RS-485 slave port parameters are set in the DXM
Configuration Tool under the Settings > General tab.
18www.bannerengineering.com - Tel: 763.544.3164
DXM Controller local registers. To operate as a Modbus slave device, the DXM
DXM Internal Modbus Slave IDs (factory default)
DXM Controller Local Register
Page 19
DXM100 Controller Instruction Manual
4.2 DXM Master Configuration
The
DXM Controller operates as a Modbus master device, use the DXM Configuration Tool to configure read or write
operations of the DXM Modbus network. The DXM Controller communicates with all internal and external peripheral devices
using the external Modbus bus RS-485 (M+, M-)
There are four internal Modbus slave devices that are configured from the factory with slave IDs. Assign slave IDs of 2
through 10 to Modbus slave devices that are physically wired to the DXM Controller. Assign slave IDs or 11 through 60 to
wireless slaves within the MultiHop network.
Do not assign a slave ID of greater than 10 to Modbus slave devices that are physically wired using the RS-485 port if
there is an internal MultiHop ISM radio in the DXM Controller. The MultiHop ISM radio attempts to send any Modbus data
intended for slaves 11–60 across the radio network, which conflicts with wired slave devices if the slave IDs overlap. The
MultiHop master radio can be changed from the factory default of 11–60 Modbus slave IDs if more hardwired slaves are
required.
4.3 Modbus Operation
All Modbus transactions are managed by a central Modbus engine. If there are Modbus messages intended for a Modbus
slave that doesn't exist, the Modbus engine waits for a response until the timeout period is expired. This slows down the
Modbus polling loop for read and write operations. For this reason, verify all Modbus read and write operations are
intended for Modbus slave devices that are in the network.
If a Modbus slave is not in the network, either a wired or wireless device, the operation of the LCD menu system can be
compromised. Operations like Binding, Site Survey, or accessing the ISM menu may be slower. This is because all internal
devices of the
DXM Controller are also Modbus slaves, ISM radio, I/O base board, LCD, and internal Local registers.
4.4 Wireless and Wired Devices
4.4 Wireless DX80 Gateway
The DX80 Gateway architecture is a star architecture in which all Nodes in the system send their data back to the
Gateway. The host can access the entire network data from the Gateway, which is Modbus slave ID 1.
Because the
be set low (less than 1 second) and it is treated like a directly connected device.
4.4 MultiHop Master
The MultiHop master radio forms a wireless tree network using repeaters and slave devices. Each device in a MultiHop
network must be assigned a unique Modbus Slave ID and is accessed as a separate device.
For the DXM Controller to talk with a MultiHop device in the wireless network, the master MultiHop device interrogates
every message on the RS-485 bus. If they are within the wireless devices range (slave IDs 11 though 60), the message is
sent across the wireless network. To change this range, the user must adjust the offset and range setting in the MultiHop
master radio (Modbus Slave ID 1). Modbus register 6502 holds the Modbus offset, default 11. Modbus register 6503 holds
the number of Modbus slaves allowed (maximum of 100).
Modbus Slave IDDescription
DXM Controller will not be sending any Modbus messages across the wireless link, the timeout parameter can
1Allocated for the internal ISM radio device, either a DX80 Gateway or MultiHop Master
2–10Slave addresses available for direct connected Modbus slave devices to the master RS485 port (M+ , M-)
11–60Allocated for wireless MultiHop radio network devices. If there is not an internal MultiHop in the DXM Controller, these slave
addresses are available to use for directly connected devices.
61–198Available to user for direct connected Modbus slave devices or the expansion of the wireless network slave IDs to go past 50
wireless devices.
199Allocated for internal Local Register
200Allocated for the I/O base board, will be different for special DXM slave only models.
201Allocated for the LCD display board, the user can read/write LEDs.
www.bannerengineering.com - Tel: 763.544.316419
Page 20
DXM100 Controller Instruction Manual
4.5 Modbus Timeouts
A Modbus timeout is the amount of time a Modbus slave is given to return an acknowledgement of a message sent by the
Modbus master. If the Modbus master waits for the timeout period and no response is seen, the Modbus master considers
it a lost message and continues on to the next operation.
The timeout parameter is simple to set for Modbus devices directly connected to the DXM controller, if there are no
MultiHop wireless devices. If a MultiHop network a part of the
set the timeout parameter.
Wireless communications are inherently lossy networks, and controllers operating these networks must be configured to
allow for enough time for hardware transmission retries. Set the Communications Timeout parameter to cover the
expected time for messages to be sent throughout the wireless network. For the DXM Controller, the CommunicationsTimeout parameter is the maximum amount of time the DXM Controller should wait after a request is sent until the
response message is received from the Modbus slave device. Use the DXM Configuration Tool to set the timeout parameter
on the Settings > General screen.
The default setting for the timeout parameter is 5 seconds.
DXM Controller, special considerations need to be made to
4.5 MultiHop Networks vs DX80 Star Networks
The MultiHop wireless architecture is much different from the DX80 star architecture. Although both are wireless networks,
the DX80 star Gateway collects all the data from the Nodes, which allows the host system to directly read the data from
the Gateway without sending messages across the wireless network. This allows for DX80 Gateway to be treated like any
other wired Modbus device.
In a MultiHop network, the data resides at each device, forcing the controller to send messages across the wireless
network to access the data. For this reason, carefully consider the value of the wireless timeout parameter.
4.5 Battery-Powered MultiHop Radios
Battery-powered MultiHop radios are configured to run efficiently to maximize battery life. In optimizing battery life, the
allowed communications window for receive messages is slow (once per 1.3 seconds) and sending message rates are
standard (once per 0.04 seconds). A MultiHop device is set from the factory with the retry parameter set to 8. This means
that under worst-case conditions, a message is sent from the DXM Controller to an end device a total of nine times (one
initial message and eight retry messages. The end device sends the acknowledgement message back to the DXM
Controller a maximum of nine times (one initial message and eight retries). A single Modbus transaction may send up to
two messages + 16 retry messages before the transaction is complete. In addition, the radios randomly wait 0–1 time
period before retransmitting a retry message. So to allow for the random wait time, add one extra time period for each inbetween time of retries.
For a Master radio to a slave radio (no repeaters):
• Slave to Master Send time = (9 × 0.04 sec) + (8 retry wait × 0.04 sec) = 1 second
• Total Send/Receive time = 23 seconds
• Minimum Timeout period = 23 seconds
This calculates the maximum timeout value for a wireless transaction. If the link quality of the network is poor, the
maximum transfer times may happen. Set the timeout parameter to accommodate the maximum number of retries that
may happen in your application.
When MultiHop repeaters are added into the wireless network, each additional level of hierarchical network increases the
required timeout period. Since MultiHop repeaters are running at the highest communications rate, the overall affect is not
as great.
• Master to Repeater Send time = (9 × 0.04 sec) + (8 retry wait × 0.04 sec) = 1 second
• Repeater to Master Send time = (9 × 0.04 sec) + (8 retry wait × 0.04 sec) = 1 second
• Additional Timeout period for a repeater = 2 seconds
Using the timeout calculation above of 23 seconds, if a repeater is added to the network the timeout should be set to 25
seconds. For each additional MultiHop repeater device creating another level of network hierarchy, add an additional two
seconds to the timeout period.
4.5 Line-Powered MultiHop Devices
Line-powered (10–30 V dc) MultiHop devices operate at the maximum communication rate, resulting in a much lower
timeout parameter setting. For each repeater added to the network, increase the timeout parameter 2 seconds.
For a Master radio to a line powered slave radio (no repeaters):
20www.bannerengineering.com - Tel: 763.544.3164
Page 21
DXM100 Controller Instruction Manual
• Master to Slave Send time = (9 × 0.04 sec) + (8 retry wait × 0.04 sec) = 1 second
•
Slave to Master Send time = (9 ×* 0.04 sec) + (8 retry wait × 0.04 sec) = 1 second
• Total Send/Receive time = 2 seconds
• Minimum Timeout period = 2 seconds
4.5 Adjusting the Receive Slots and Retry Count Parameters
The number of receive slots governs how often a MultiHop device can communicate on the wireless network. Batterypowered devices typically have DIP switches that allow the user to set the number of receive slots. (This will directly affect
the battery life of the device.) Adjusting the receive slots changes how often a message can be received. In the battery
power example (default factory settings) the receive slots are 1.3 seconds (receive slots = 4). With the receive slots set to
32, how often a message can be received goes from 1.3 seconds down to 0.16 seconds.
An argument can be made to allow the application accessing the wireless network, in this case the DXM Controller, to
control the retry mechanism. The number of retries can be adjusted in the MultiHop devices by writing Modbus register
6012 to the number of retires desired. The factory default setting is eight.
4.5 DX80 Star Architecture Network Timeouts
The DX80 star network of a Gateway and Nodes can be treated differently with respect to timeout conditions. The DX80
star network is much different from a MultiHop network. In the DX80 network, all Node data is automatically collected at
the Gateway to be read. The DXM Controller does not use the wireless network to access the data, which allows for much
faster messaging and much lower timeout values. For a DXM Controller with an internal DX80 Gateway, set the timeout
value 0.5 seconds. If other Modbus slave devices are connected to the RS-485 lines, the timeout parameter will govern all
communication transactions and must be set to accommodate all devices on the bus.
www.bannerengineering.com - Tel: 763.544.316421
Page 22
Power Select
08:25:45
Power: [DC]
<Ent> Accept
<Back> Previous Menu
Change Power Select
↑
↓
ENTER
BACK
DXM100 Controller Instruction Manual
5 Configuration Instructions
5.1 Working with Solar Power
A reliable solar system requires careful planning and monitoring to size the components correctly. The recommendations
provided are for the
requirements and likely requires increasing the solar system components. Depending upon the geographical location, the
size of the solar panel and battery may vary.
DXM Controller system as an autonomous system. Adding extra components increases the power
5.1 Setting the DXM Controller for Solar Power
By default, the DXM Controller is set from the factory to charge a backup battery from a line power source. Using the LCD
menu on the front of the DXM Controller to change the charging algorithm to solar power.
Go to System > Power Select. Change the Power to Solar.
There are a few DXM configuration tips to help minimize the power consumption.
•
If Ethernet is not being used, save up to 25% of the consumed power by disabling Ethernet on the DXM Controller.
Set DIP switch 1 to the ON position on the processor board then reboot the DXM Controller.
• Instead of powering external devices all the time, take advantage of the switched power mechanisms of the DXM
Controller to turn off devices when possible.
• Minimize the number of cellular transactions and the amount of data pushed across the cellular modem.
5.1 Solar Components
Battery Properties
The DXM solar controller is designed to use a 12 V lead acid battery. The characteristics of a solar system require the
battery to be of a certain type. There are basically two types of lead acid batteries:
• SLI batteries (Starting Lights Ignition) designed for quick bursts of energy, like starting engines
• Deep Cycle batteries - greater long-term energy delivery. This is the best choice for a solar battery.
Since a solar system charges and discharges daily, a deep cycle battery is the best choice. There are different versions of a
lead acid battery: wet cell (flooded), gel cell, and an AGM (absorbed glass mat).
Wet cell batteries are the original type of rechargeable battery and come in two styles, serviceable and maintenance free.
Wet cell batteries typically require special attention to ventilation as well as periodic maintenance but are the lowest cost.
The gel cell and AGM battery are sealed batteries that cost more but store very well and do not tend to sulfate or degrade
as easily as a wet cell. Gel or AGM batteries are the safest lead acid batteries you can use.
Battery Capacity
Battery capacity is a function of the ambient temperature and the rate of discharge. Depending upon the specific battery, a
battery operating at –30 °C can have as much as 40 percent less capacity than a battery operating at 20 °C. Choose
enough battery capacity based on your geographical location.
22www.bannerengineering.com - Tel: 763.544.3164
Page 23
DXM100 Controller Instruction Manual
A larger capacity battery typically lasts longer for a given solar
application because lead-acid batteries do not like deep cycling
Use this as a guide to the approximate state of charge and in
determining when to apply conservation measures.
(discharging a large percentage of its capacity). Depending upon the
battery, a battery discharging only 30 percent of its capacity before
recharging will have approximately 1100 charge/discharge cycles. The
same battery discharging 50 percent of its capacity will have
approximately 500 charge/discharge cycles. Discharging 100 percent
leaves the battery with only 200 charge/discharge cycles.
Batteries degrade over time based on discharge/charge cycles and
environmental conditions. Always monitor the battery system to obtain
the best performance of the solar powered system.
Average Voltage Readings Relative to Battery
Change
State of Charge (%)Open Circuit Voltage
10013.0 or higher
7512.6
5012.1
2511.66
011.4 or less
Solar Panels
Banner solar panels come in two common sizes for the
DXM Controller: 5 Watt and 20 Watt. Both panels are designed to
work with the DXM Controller but provide different charging characteristics. Use the 5 watt panel for light duty operation
and use the 20 watt panel when you require greater charging capabilities.
Solar PanelVoltageCurrentTypical DXM Configurations
5 Watt17 V0.29 ADXM slave controller, ISM radio, I/O base board
20 Watt21 V1 ADXM Controller with ISM radio and Cellular modem
Photovoltaic panels are very sensitive to shading. Unlike solar thermal panels, PV solar panels cannot tolerate shading
from a branch of a leafless tree or small amounts of snow in the corners of the panel. Because all cells are connected in a
series string, the weakest cell will bring down the other cells' power level.
Good quality solar panels will not degrade much from year to year, typically less than 1 percent .
Solar Panel Mounting
To capture the maximum amount of solar radiation throughout the year, mount a fixed solar panel to optimize the sun's
energy throughout the year. For the northern hemisphere, face the panel true south. For the southern hemisphere, face
the panel true north. If you are using a compass to orientate the panels, compensate for the difference between true north
and magnetic north. Magnetic declination varies across the globe.
A solar panel's average tilt from horizontal is at an angle equal to the latitude of the site location. For optimum
performance, adjust the tilt by plus 15 degrees in the winter or minus 15 degrees in the summer. For a fixed panel with a
consistent power requirement throughout the year, adjust the tilt angle to optimize for the winter months: latitude plus 15
degrees. Although in the summer months the angle may not be the most efficient, there are more hours of solar energy
available.
For sites with snow in the winter months, the increased angle helps to shed snow. A solar panel covered in snow produces
little or no power.
5.1 Recommended Solar Configurations
These solar panel and battery combinations assume direct sunlight for two to three hours a day. Solar insolation maps
provide approximate sun energy for various locations. The depth of battery discharge is assumed to be 50 percent.
Solar panel and battery combinations for a DXM Controller system
Solar PanelBattery Capacity
5 watt10 Ahr10 days25 mADXM Slave Controller - ISM radio and I/O base board
20 watt14 Ahr10 days30 mADXM Controller with ISM radio
3
Days of AutonomyDXM mADXM Controller
3
Battery capacity (amp hour) is standard amp rating taken for 20 hours. Battery capacity should be monitored for reliable system power and may
need to be increased for cold weather locations.
www.bannerengineering.com - Tel: 763.544.316423
Page 24
DXM100 Controller Instruction Manual
Solar panel and battery combinations for a DXM Controller system
Solar PanelBattery Capacity
20 watt20 Ahr10 days35 mADXM Controller with ISM radio and Cellular Modem
3
Days of AutonomyDXM mADXM Controller
5.1 Monitoring Solar Operation
The DXM solar controller provides Modbus registers that allow the user to monitor the state of the solar panel input
voltage, the battery voltage, the charging current, and the temperature in °C. The
DXM Controller can be configured to
monitor the health of the charging system as well as send an alert message when the battery is too low.
The charts show a typical charging cycle, with each vertical grid representing about eight hours. The chart shows three
days of charging.
Figure 1. Solar Panel Voltage (mV) -- Cloudy First Day
5.2 Inputs and Outputs
The I/O base board is a Modbus slave device (Slave ID 200) that communicates to the processor board using Modbus
commands. Use the
outputs on the I/O board.
Communication with the I/O board runs at a maximum rate of 10 ms per transaction. The parameter setting for the bus
with the I/O board and the processor board are fixed. External Modbus communication runs at a maximum rate of 50 ms
per transaction. The parameter settings for the external RS-485 buses are controlled by the DXM Configuration Tool.
Refer to the Modbus Registers section for more descriptions of each Modbus register on the DXM100 Controller.
5.2.1 Universal Inputs
The universal inputs on the DXM100 Controller can be programmed to accept several different types of inputs:
• Discrete NPN/PNP
• 0 to 20 mA analog
3
Battery capacity (amp hour) is standard amp rating taken for 20 hours. Battery capacity should be monitored for reliable system power and may
need to be increased for cold weather locations.
24www.bannerengineering.com - Tel: 763.544.3164
DXM Configuration Tool to create a configuration using read/write maps that will access inputs or
Figure 2. Battery Voltage (mV) - Cloudy First Day
Page 25
DXM100 Controller Instruction Manual
• 0 to 10 V analog
•
10k temperature thermistor
• Potentiometer sense
• Bridge
• NPN raw fast
Any input can be used as a synchronous counter by configuring the input as a discrete NPN/PNP input.
Use the DXM Configuration Tool tool to write to the appropriate Modbus registers in the I/O board to configure the input
type. The universal inputs are treated as analog inputs. When the universal inputs are defined as mA, V, or temperature,
use Modbus registers to configure the operational characteristics of the inputs. These parameters are temperature
conversion type, enable full scale, threshold and hysteresis. Refer to the DXM100 Controller Instruction Manual (p/n
190037) for the parameter definitions.
When a universal input is configured as an NPN or PNP input type, it can be enabled to be a synchronous counter. Enable
the counter function by setting Modbus register 'Enable Rising' or 'Enable Falling' to 1. See I/O Base Board (Modbus Slave
200) on page 47 for universal input register definitions.
PinUniv. InputDescription
27Universal Input 4Program the universal inputs to accept input types NPN, PNP, 10k thermistor, 0 to 10 V, 0 to
28Universal Input 3
31Universal Input 2
32Universal Input 1
20 mA, or potentiometer. The default setting is 8: NPN raw fast. To set the input type, write
the following values to the Input Type Modbus registers defined in I/O Base Board (Modbus
Slave 200)
on page 47.
0 = NPN
1 = PNP
2 = 0 to 20 mA
3 = 0 to 10 V dc
4 = 10k Thermistor
5 = Not used
6 = Not used
7 = Bridge
8 = NPN Raw Fast (default)
Thermistor InputA thermistor input must use a 10k temperature thermistor between ground and the universal
input. The thermistor must be a 10k NTC (Banner model number BWA-THERMISTOR-002) or
equivalent. Select the temperature conversion of degrees C (default) or degrees F by writing
Potentiometer
Input
Modbus registers defined in I/O Base Board (Modbus Slave 200)
A potentiometer input is created from three inputs: a voltage source (pin 30) that supplies 5 V to
the potentiometer and two inputs set to voltage inputs to read the voltage across the
on page 47.
potentiometer. See the DXM tech note for setting up a potentiometer.
Bridge InputThe bridge input is not implemented yet.
NPN vs NPN Raw
Fast
Synchronous
Counters
The difference between NPN and NPN Raw Fast is the amount of settling time given to the input.
Switch the input type to NPN if the input is not detecting a transition.
When an input is configured as a counter (inputs set to NPN/PNP), the input counts the input signal
transitions. The count value is stored into two 16-bit Modbus registers for a total count of 32-bits
(unsigned). To program an input to capture the edge transition counts, follow Example: Configure
Input 1 as a Synchronous Counter on page 25.
Synchronous counter sample the inputs every 10 ms. The input logic does not detect rising or
falling edges, but instead samples the input every 10 ms to find level changes. The input signals
must be high or low for more than 10 ms or the input will not detect transitions. Because most
signals are not perfect, a realistic limit for the synchronous counter would be 30 to 40 Hz.
Example: Configure Input 1 as a Synchronous Counter
Launch the DXM Configuration Tool.
1.
2. Click on the Register View tab on the left part of the page.
3. Change the Source Register selection to I/O Board Registers.
4. In the Write Registers area, write Modbus register 4908 to 1 to enable counting on the rising edge of the input signal.
5. Read Modbus registers 4910 and 4911 to get the 32-bit value of the count.
Example: Change Universal Input 2 to a 0 to 10 V dc Input
1. Launch the DXM Configuration Tool tool.
2. Click on the Register View tab on the left part of the page.
3. Change the Source Register selection to I/O Board Registers.
4. Write a 3 to Modbus register 3326 on Modbus Slave ID 200 (I/O board).
www.bannerengineering.com - Tel: 763.544.316425
Page 26
Output
DXM100 Controller Instruction Manual
5. Cycle power to the device.
6.
Using the Register View tab, read register 3326 to verify it is set to 3.
Example: Change Analog Output 1 to a 0 to 10 V dc Output
1. Launch the DXM Configuration Tool tool.
2. Click on the Register View tab on the left part of the page.
3. Change the Source Register selection to I/O Board Registers.
4. Set jumper 1 on the I/O base board to the 0 to 10 V position. Refer to the base board image for the analog output
jumper position.
5. Write a 3 to Modbus register 4008 on Modbus Slave ID 200 (I/O board).
6. Cycle power to the device.
7. Using the Register View tab, read register 4008 to verify it is set to 3.
ON-State Saturation: Less than 0.7 V at 20 mA
ON Condition: Less than 0.7 V
OFF Condition: Open
5.2.3 Analog (DAC) Outputs
The analog outputs may be configured as either 0 to 20 mA outputs (default) or 0 to 10 V outputs.
To change the analog (DAC) output type:
Remove power to the device.
1.
2. Unplug both the USB and Ethernet connections.
3. Remove the DXM cover.
4. Change the hardware jumper position (see the table for the pin number and I/O Base Board Connections on page
13 for the pin locations).
5. Replace the DXM cover.
6. Plug in both the USB and Ethernet connections.
7. Restore power to the DXM.
8. Set the Output Type Select Modbus register (on the I/O board, Slave ID 200) to a value of 2 (default) to select 0 to
20 mA or a value of 3 to select 0 to 10 V. For analog output 1 write to Modbus register 4008, for analog output 2
write to Modbus register 4028 (see the table for the values).
PinOutputModbus
Register
19Analog Output 140080 to 20 mA or 0 to 10 V dc output (I/O board jumper selectable)
20Analog Output 24028
Description
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit
After changing the jumper position, write the appropriate value to the Modbus
registers to define your analog output to match the setting selected by the jumper.
2 = 0 to 20 mA output (default)
3 = 0 to 10 V output
5.3 Scheduler
Use the Scheduler
week, start time, stop time, and register values. Schedules are stored in the XML configuration file, which is loaded to the
DXM Controller. Reboot the DXM Controller to activate a new schedule.
26www.bannerengineering.com - Tel: 763.544.3164
tab to create a calendar schedule for local register changes. Use this tab to define the days of the
Page 27
DXM100 Controller Instruction Manual
5.3 Weekly Schedules
Define weekly events using the weekly events screen.
To create a new rule:
Click on the Add New Rule link.
1.
2. Click on the arrow to the left of the new rule to expand the parameters into view.
3. Enter the local register.
4. Select the days of the week this rule applies to.
5. Use the drop-down list to select the type of Start At time: a specific time or a relative time.
6. Enter the starting time.
7. Enter the starting value for the local register.
8. Enter the end time and end value for the local register.
Register updates can be changed up to two times per day for each rule. Each rule can be set for any number of days in the
week by clicking the buttons M, T, W, Th, F, S, or Su.
If two register changes are defined for a day, define the start time to be before the end time. Select End Value to enable
the second event in a 24 hour period. To span across two days (crossing the midnight boundary), set the start value in the
first day, without selecting End Value. Use the next day to create the final register state.
Start and end times can be specified relative to sunrise and sunset, or set to a specific time within a 24 hour period. When
using sunrise or sunset times, set the GPS coordinates on the device so it can calculate sunrise and sunset.
5.3 One-Time Events
Define one-time events to update registers at any time within a calendar year. Similar to Weekly events, the times can be
specific or relative to sunrise or sunset. Define one-time events using the one-time events screen.
To create a one-time event rule:
1. Click on the Add One Time Event link.
2. Name your one-time event by clicking on the name link and entering a name.
3. Click on the arrow to expand the parameters into view.
4. Enter the local register.
www.bannerengineering.com - Tel: 763.544.316427
Page 28
Banner Eng .
08:25:45
→ Registers
→ PushS → 08 :25:15
→
ISM Radio
→ System
↑
↓
ENTER
BACK
→ System Info
08:25 :45Banner Eng.
12345 Name of Reg1
12345 Name of Reg2
12345 Name of Reg3
12345 Name of Reg4
12345 Name of Reg5
12345 Name of Reg6
↑
↓
ENTER
BACK
Banner Eng.
08:25 :45
→ Trigger Push
Status: ??
Time: ??
↑
↓
ENTER
BACK
DXM100 Controller Instruction Manual
5. Enter the starting time, date, and starting value for the local register.
6.
Enter the ending time, date, and ending value for the local register.
5.3 Create Holiday Schedules
Use the Create Holidays tab to create exception conditions that alter the standard scheduled register changes.
To create a holiday:
Click on the Add New Rule link.
1.
2. Name your new holiday by clicking on the name link and entering a name.
3. Select the start date and time for the new holiday.
4. Select the stop date and time for the new holiday.
5.3 Power Cycling During Schedules
If power is cycled to the DXM Controller in the middle of a schedule, the DXM Controller will look at all events scheduled
that day and process the last event before the current time.
5.4 LCD and Menu System
The LCD has four user-defined LED indicators, four control buttons, and an
LCD display. The four buttons control the menu system on the LCD menu.
The top-level menu always displays the time in a 24-hour format.
•
The up and down arrows scroll through display items.
• The enter button selects the highlighted items on the display
• The back button returns to a previous menu option.
Main MenuSub MenuDescription
Registers
Push
The Registers menu displays the user-defined registers and associated
values. The user-defined registers are set up using the
DXM Configuration
Tool.
The Push
menu displays information about the last data sent to the Web
server.
• The Trigger Push submenu forces an immediate push to the web
server.
• The status and time fields indicate success or failure of the last
attempted push and time of the last attempted push.
→ Controller
→ ISM Radio
→ Push
→ Ethernet
→ Cell
→ I/O Board
→ LCD Board
↑
↓
ENTER
BACK
DXM100 Controller Instruction Manual
Main MenuSub MenuDescription
ISM Radio
The ISM Radio
menu allows the user to set the Modbus Slave ID of the
internal ISM radio, invoke binding, or run a site survey. The controller
automatically detects the ISM Type.
System
Use the System menu to change the Modbus Slave ID of the
DXM
Controller, provision the internal cellular modem, select the incoming
power algorithm for battery charging, or force a restart of the DXM
Controller.
System Info
The System Info menu displays the various settings of the
DXM
Controller, firmware versions, and network settings.
5.5 Authentication Setup
The DXM Controller has three different areas that can be configured to require a login and password authentication.
Webserver/ Cloud Services Authentication
•
• Mail Server Authentication
• DXM Configuration Authentication
The webserver and mail server authentication depends upon the service provider.
5.5 Webserver/Cloud Services Authentication
The DXM Controller can be configured to send login and password credentials for every HTTP packet sent to the webserver.
This provides another layer of security for the webserver data.
Setup requires both the webserver and the DXM Controller to be given the same credentials for the login and password.
The webserver authentication username and password are not stored in the XML configuration file and must be stored in
the DXM Controller.
Ok
Define the login and password using the Settings > Cloud Services
screen
of the DXM Configuration Tool, in the Webserver Authentication section
of the screen.
The first time you select Require Authentication, a pop-up box appears
with additional instructions. Since the data is not stored in the XML
configuration file, it is hidden from view of the DXM Configuration Tool.
After enter the username and password, click on Send Authentication to transmit the data directly to the
DXM
Controller's non-volatile memory. The controller must be connected to the PC for this operation to succeed. If successful, a
pop-up window appears, asking to reboot the device. Select Yes to reboot the device.
www.bannerengineering.com - Tel: 763.544.316429
Page 30
DXM100 Controller Instruction Manual
Set up the webserver with a username and password to accept the DXM
Controller messages. Otherwise, the webserver ignores all messages.
When using the Sensonix website's dashboard, set the authentication by
clicking the edit button next to the appropriate site name. Enter the
Username and Password, then click Save to save your changes.
5.5 Mail Server Authentication
Complete the mail server settings to have the
SMTP password is stored in the DXM Controller, not the XML configuration file. Use the Settings > Mail and Messaging
screen to complete this configuration.
After selecting Enable SMTP Authentication for the first time, a pop-up box appears with additional instructions to
complete the mail server authentication process.
After entering the user name and password, click on Send SMTP Password to save the user name and password to the
DXM Controller
window appears, asking to reboot the device. Select Yes to reboot the device.
. The DXM Controller must be connected to the PC to complete this operation. If successful, a pop-up
DXM Controller send email alert messages or to email the log files. The
5.5 DXM Controller Configuration Authentication
The DXM Controller can be programmed to allow changes to the configuration files only with proper authentication by
setting up a password on the Settings > Administration screen in the DXM Configuration Tool.
With the DXM Controller connected to the PC, click Get Device Status. The
button.
Use the DXM Configuration Tool to:
• Set the Admin Password
• Change the Admin Password
• Remove the Admin Password
30www.bannerengineering.com - Tel: 763.544.3164
DXM Controller status displays next to the
Page 31
Remote DevicesEthernet/USB/Cellular
Processor
Local
Registers
DisplayI/O Base
Internal
Radio
DXM100 Controller Instruction Manual
To change or remove an admin password, the current password must be supplied. The DXM Controller must be connected
to the PC to change the administration password.
The
DXM Controller can be unlocked without knowing the administration password, but doing this erases the configuration
program, logging files, and any ScriptBasic program on the device.
To unlock the hardware without knowing the administration password:
1. Turn off the power to the DXM Controller.
2. Open the controller top to access the button and DIP switches of the SAM4 processor board.
3. Turn on DIP switch 4 (next to the SD card holder).
4. Press and hold the reset button (next to the USB jack) while applying power to the DXM Controller.
5. Release the reset button.
6. After five seconds, turn off the power.
7. Turn off DIP Switch 4.
8. Install the DXM cover and apply power.
The device no longer has an administration password set.
5.6 Register Flow and Configuration
The DXM Controller register data flow goes through the Local Registers, which are data storage elements that reside within
the processor. Using the
Register pool to remote devices, the internal radio, the I/O base, or the display.
DXM Configuration Tool, the controller can be programmed to move register data from the Local
5.6 Basic Approach to Configuration
When programming an application in the
Registers. The Local Registers are the main storage elements in the DXM Controller. Everything goes into or out of the
Local Registers. Start by naming the Local Registers in the application as this helps to provide the beginning structure of
the application.
After you have a basic idea what data values to store, configure the read/write rules to move the data. The Read/Write
rules are simple rules that move data between devices and the Local Registers.
Most applications require the ability to manipulate the Local Register data, not just move data around. Use the Action rules
to make decisions or transform the data after the data is in the Local Registers. Action rules can apply many different
functions to the Local Register data, including conditional statements, math operations, copy operations, or trending.
To perform scheduled events in Local Registers, look under the Scheduler tab in the DXM Configuration Tool. These rules
provide the ability to create register events by days of the week. The scheduler can also create events based on sunrise or
sunset.
www.bannerengineering.com - Tel: 763.544.316431
DXM Controller, the first step is to plan the overall data structure of the Local
Page 32
DXM100 Controller Instruction Manual
5.6 Troubleshooting a Configuration
The built-in Register View utility is found in the
configuration is running on the DXM Controller, this utility can read or write Local Registers to help understand application
operation. The utility can also access data from remote devices, making it easier to troubleshoot a configuration.
Local Registers can be configured to show register data on the LCD menu. This is another method to view Local Register
data without having the controller connected to a PC. On the Local Registers tab, set the read permissions on each
register to be display on the LCD.
DXM Configuration Tool under the Register View tab. When a
5.6 Saving and Loading Configuration Files
The DXM Configuration Tool saves its configuration information in a XML file. Use the File menu to Save or Load
configuration files. Make sure to save the configuration file before attempting to upload the configuration to the DXM
Controller. The DXM Configuration Tool uploads the configuration file saved on the PC to the DXM Controller; it will not
send the configuration loaded in the tool.
5.6 Uploading or Downloading Configuration Files
The DXM Controller requires a XML configuration file to become operational. To upload or download configuration files,
connect a computer to the DXM Controller using the USB port or Ethernet port. Then use the Upload Configuration to
Device or Download Configuration from Device under the Device menu.
5.7 DXM Cellular Modem
The DXM cellular modem provides a remote network connectivity solution for the DXM Controller.
To use the cellular modem, first configure the
connection. Verify the cellular modem is installed and the correct antenna is connected to the cellular antenna port.
5.7 Configure the DXM Controller for a Cellular Modem
DXM Controller to use the cellular network as the external network
Use the DXM Configuration Tool to create a configuration using a cellular connection. Under Settings > Cloud Services,
define the Network Interface as Cell to have all push data, SMS messages, or email alerts to be sent using the cellular
modem. The Cloud Push settings and the Webserver settings are required if the DXM Controller is sending data to a
webserver.
When the DXM Controller is configured to use the cellular modem, the information on the cellular modem is found on the
LCD menu under System Info
complete. If there are no webserver parameters defined, the user must force a push to retrieve the data from the cellular
network. On the LCD menu, select Push > Trigger Data Push.
FWFirewall IP address setting for VPN connection. The user enters the IP address of the host system on the other
end of the VPN connection.
MaskIP mask associated to the firewall IP address
MEIDMobile Equipment Identifier—a unique number for each cellular modem; this is the number the wireless carrier
uses to attach a wireless plan
MDNMobile Device Number—phone number
> Cell. The menu does not display values until a transaction with the wireless cell tower is
32www.bannerengineering.com - Tel: 763.544.3164
Page 33
DXM100 Controller Instruction Manual
SignalSignal Strength between the cellular modem and the wireless network tower; this value ranges between –51
Version Firmware version of the cellular modem; this can only be updated at the factory
and –112 dBm. The more positive number is better, –51 is better than –81.
5.7 Cellular Activation Quick Start Guide
Sensonix CDMA cellular modems (based on the Telit CE910-DUAL) are ready to be activated when they leave the factory.
Successful activation of every device on the cellular network requires two basic steps:
1.
Attaching a data plan to the particular device
2. Completing Over-the-Air Service Provisioning (OTASP)
To attach a cellular data plan:
1. Select a data plan with a carrier that uses the Verizon network, working with Verizon directly or using an MVNO
such as M2MAir or KORE Telematics.
2. Set up an account with the selected carrier.
3. When working with cellular devices you may be required to log into a web portal provided by the carrier and follow
their instructions for device activation.
4. It is very important to make sure the carrier knows that the data plan is being attached to the device known as
SENSX001.
5. Remove the DXM100 housing cover to see the cellular modem. Use the MEID printed on the Telit CE910-DUAL
cellular modem to uniquely identify the device. The carrier requires this number to attach a monthly data plan.
To complete the Over-the-Air Provisioning (OTASP)
1. Once the contract is attached, the DXM Controller must provision the service using OTASP (Over-the-Air Service
Provisioning).
2. Make sure the cellular module is plugged into the DXM Controller and has its antenna properly connected.
3. On the DXM Controller LCD display select menu: System and then Provision Cell.
4. Click Enter on the Provision Cell menu.
5. The next screen will ask if you want to provision the cellular device, click Enter.
6. It will take approximately 60 seconds and will indicate when it has completed.
7. The cellular modem is ready for use.
5.7 DXM Cellular VPN Setup
A software VPN tunnel can be created between a DXM Controller using a cellular modem to a host PC using a private IP or
static wireless cellular plan. The instructions below outline the DXM Controller set up required to become aware of the VPN
connection. The cellular plan provider will have separate instructions for setting up the VPN on the PC side.
1. Establish VPN tunnel on your computer. Instructions should be provided from your VPN provider.
2. From within the DXM Configuration Tool, go to Settings > Network > Cellular Firewall Settings..
3. Fill in the Firewall IP address and Firewall netmask provided by your VPN provider. For M2Mair this was
included in the Routes.cmd file. It opens the device to traffic from 172.16.1.[0-255].
4. Go to Settings > Cloud Services > Network Interface.
5. Select Cell from the drop-down list and select the Enable VPN checkbox.
6. With your VPN tunnel open, select Device > Connection Settings.
7. Select TCP/IP, enter your VPN IP address, check VPN, and click Connect.
5.8 Binding and Conducting a Site Survey with the ISM Radio
The DXM Controller can have an internal MultiHop master radio or DX80 Gateway radio (star architecture) installed. Before
the ISM radio can communicate with DX80 Nodes, the
network. Use the DXM Controller LCD menu to bind radios to the internal DXM radio.
The LCD display and the processor applications share the external Modbus connection. If the processor is configured to
constantly interact with Modbus, it may cause issues with the LCD display attempting to use the functions of the ISM radio.
To alleviate the contention:
• Load a DXM configuration file that slows down the read/write rules.
• Disable the DXM configuration file from loading into the processor by setting DIP switch 4 to ON (on the processor
board). Reboot the device. When the processor starts back up, it will not load the configuration file and remains
idle. See the DXM100 Controller Instructional Manual (190037) for the processor DIP switch location.
DXM Controller must be bound to the other radios in the wireless
www.bannerengineering.com - Tel: 763.544.316433
Page 34
DXM100 Controller Instruction Manual
5.8 Entering Binding Mode
Under the ISM Radio
The ISM Radio menu is slightly different for the two different types of internal radio. The ISM Type displays 'MultiHop'
when the MultiHop radio board is installed and 'DX' when the DX80 star architecture radio board is installed.
Use the up/down arrows to enter the device number to bind to. When binding to devices with rotary dials, the device
number has no effect. To bind to devices without rotary dials, the device number is saved as the device Modbus slave ID in
the MultiHop network or the Node number in a DX80 network.
After entering binding mode on the DXM Controller, put the end device into binding mode to execute the binding process.
Most end devices enter binding by triple-clicking button 2 on the device. For specific instructions on entering binding for a
specific device, refer to the individual datasheet for that device.
To bind more devices, click the back button, change the device number (if needed), then enter binding again.
menu, use the down arrow button to highlight the Binding menu. Click ENTER.
5.8 Conducting a Site Survey
Although the MultiHop and DX80 devices are architecturally different, the site survey process is similar when conducted
from the DXM LCD menu. From the ISM Radio menu, use the down arrow to highlight the Site Survey menu. Click
ENTER.
Use the Up or Down arrows to select the Node number (DX80 network) or Modbus Slave ID (MultiHop network). Click
ENTER to run the site survey with that Node or slave.
For a DX80 network, the Gateway controls the site survey and the results display on the LCD. Running Site Survey on a
DX80 network does not affect the throughput of the DX80 network.
For a MulitHop network, the master device passes the site survey request to the intended Modbus slave device. The Site
Survey runs and the results display on the LCD. Running Site Survey on a MultiHop network stops all network traffic to
that device.
5.9 Setting Up EtherNet/IP
Use the DXM Configuration Tool to configure the DXM Controller to run the EtherNet/IP
™
4
™
protocol.
5.9 Configuring the Host PLC
On the host PLC, install the DXM Controller using an EDS file or by using the following parameters:
The Originator is the host PLC system, and the Target is the DXM Controller. The host system sees the DXM Controller as a
generic device with the product name of Banner DXM (ProdType: 43 - Generic Device, ProdName: Banner DXM).
5.9 Configuring the DXM Controller
Use the DXM Configuration Tool to define each local register to be Originator -> Target or as a Target -> Originator.
• Define a DXM local register as Originator -> Target when the host PLC (Originator) will send data to the DXM
Controller local register (Target).
• Define a DXM local register as Target -> Originator when that register data will be sent from the DXM Controller
(Target) to the host PLC (Originator).
Data from an EIP controller in assembly instance 112 is data destined for the DXM Controller local registers. The first two
bytes of the assembly instance are stored in the first local register defined as an Originator -> Target register. The next
two bytes of the assembly instance are stored in the next local register defined as an Originator -> Target register. For
example, if DXM local registers 5, 12, 13, and 15 are configured as Originator -> Target, the first eight bytes (four
words) of data from the assembly instance are stored into these registers in order (5, 12, 13, and 15). The system ignores
the rest of the bytes in the assembly instance.
Data from the DXM Controller local registers is sent to the EIP controller using assembly instance 100. Each local register
in the DXM Controller defined as Target -> Originator is collected in numerical order and placed into the data buffer
destined for assembly instance 100. DXM local registers are capable of 32-bits, but only the lower 2-bytes for each local
register are transferred. For example, if DXM registers 1, 10, 20, and 21 are defined as Target -> Originator registers,
the assembly instance 100 will have the first eight bytes of data coming from the DXM local registers 1, 10, 20, and 21.
The rest of the data is in assembly instance 100 is zero.
4
EttherNet/IP is a trademark of Rockwell Automation.
34www.bannerengineering.com - Tel: 763.544.3164
Page 35
DXM100 Controller Instruction Manual
The screen shot below shows the DXM Configuration Tool defining register 1 as an Originator -> Target register. The EIP
PLC will write data into register 1.
To send local registers to the EIP controller, define the registers as Target -> Originator.
To change many register parameters at once, use the Modify Multiple Registers screen.
DXM Controller is big endian: the upper bits of a local register (15:8) are stored in the first byte of the assembly
The
instance and the second byte of the assembly instance is stored in the lower bits of a local register (7:0).
Table 1: DXM Local Registers 1, 5, and 10 Written from EIP Assembly Instance 112
Only registers 1, 5, and 10 are defined in the DXM Configuration Tool as Originator -> Target registers.
EIP Assembly Instance 112DXM Local Registers
00110111 22
01220533 44
02331055 66
0344
0455
0566
Table 2: DXM Local Registers 10, 11, and 19 Defined as Target -> Originator
The lower 2-bytes of each register data will be place into assembly instance 100.
EIP Assembly Instance 110DXM Local Registers
00771077 88
01881199 10
02991911 12
0310
0411
0512
5.10 Setting up Email and Text Messaging
The DXM Controller can be configured to send email or SMS messages based on threshold conditions. Internal log files
may be sent using email
www.bannerengineering.com - Tel: 763.544.316435
Page 36
DXM100 Controller Instruction Manual
Cellular-connected systems can use email or SMS. Ethernet-connected systems may only use email, but can send email to
cellular phones as a SMS message depending upon the network carrier. To send email to a Verizon phone, use the phone
number followed by @vtext.com, for example, 1234567890@vtext.com.
Following these instructions using the
1. Set the time on the DXM Controller.
2. Define the Network Interface settings by selecting either Ethernet or Cell on the Cloud Services screen.
3. If you selected Ethernet, configure your Ethernet connection by setting the IP settings on the Network screen.
4. Set the email and message parameters on the Mail and Messaging screen.
5. To send alert messages, define the threshold rule to use email and/or SMS.
6. To send log files, define the log file parameters.
DXM Configuration Tool to program the controller for email and/or SMS.
5.10 Define the Network Interface Settings
On the Cloud Services screen, define the network connection settings by selecting Ethernet or Cell from the Network
Interface drop-down list. This determines how the DXM Controller sends data. When selecting Ethernet, provide the
network parameters on the Network screen. If you don't require pushing data to a web server, set the Cloud Push
interval to zero.
5.10 Configuring your Ethernet Connection
To send email based on a threshold rule or to email log files, first define the network and email servers. In the
Configuration Tool, go to Settings > Network.
1. To define the Ethernet IP address, give the DXM device a static IP address. In most cases you may select the
device to use DHCP and have the IP address automatically assigned.
2. DNS settings are not typically required. The DXM device uses a public service to resolve Domain names, but if the
network connection does not have Internet access, the DNS settings may be required.
DXM
36www.bannerengineering.com - Tel: 763.544.3164
Page 37
DXM100 Controller Instruction Manual
5.10 Configuring your Cellular Connection
A cellular connection does not require any configuration other than being selected as the network connection under the
Cloud Services screen.
5.10 Setting the Email and Messaging Parameters
From the Settings > Mail and Messaging screen, enter the SMPT definition, login, and password for a mail server. You
must supply the SMTP Server, Server Port, and login credentials to send email. When only sending SMS messages over
cellular, the SMTP Server is not required. The default SMTP port is 25 but may need to be adjusted for Ethernet-based
networks. Note that many facilities block port 25. Port 587 is another common SMTP submission port.
The SMTP password is not stored in the XML configuration file, but on the
click on Send SMTP Password to send it to the DXM Controller. The password is stored in non-volatile memory, so reboot
the DXM Controller to recognize the new password.
At the bottom of the screen, define the recipient to receive emails and enter the phone numbers for SMS messages. These
recipients for email or SMS messages can be selected in the threshold definition for sending alert messages.
DXM Controller. After the password is entered,
5.10 Defining Threshold Rules for Email
To define a threshold, go to Action Rules > Thresholds. Depending upon which recipients are defined, select the
appropriate email or SMS checkbox for the threshold rule (under Email/SMS on state transition). When the threshold
rules goes active or inactive, an email is generated.
5.10 Defining Log File Parameters for Emailing Log Files
The DXM Controller
Before emailing log files, set the Mail and Messaging parameters to provide the login credentials. When using Ethernet,
verify the IP address settings are defined on the Network screen. Set the DXM Controller time, under Settings >
General, so that all data is properly time stamped.
www.bannerengineering.com - Tel: 763.544.316437
can email log files generated on the device.
Page 38
DXM100 Controller Instruction Manual
Select the registers to log on the Local Registers > Register Configuration screen. Define the setup of the log file
using the Settings > Logging screen. Typical settings are shown.
1.
Enable the log and timestamp with every entry.
2. Enter the filename, log rate, and the maximum file size to send via email (5 to 10k is an efficient size for a cellular
connection).
3. Define the email address.
4. Define the local register data put into the log file using the Local Registers
> Local Register Configuration
screen, under the Logging and Protocol Conversion section. From the SD Card Logging drop-down list, select
the log file to write to. Log files are written in CSV format.
5. Use the DXM Configuration Tool to read back the log files. Under Settings > Logging, click Refresh List,
highlight the file to download, then click Save Selected.
5.11 Ethernet and Cellular Push Retries
The DXM Controller can be configured to send register data packets to a webserver. When the Ethernet or cell
communications path is not operating, the
outlined below for each configuration.
Regardless of the communications connection (Ethernet or cellular), a failed attempt results in the register data packet
being saved on the local micro SD card
When there is bad cellular signal strength or there is no Ethernet connection, the transmission attempts are not counted as
failed attempts to send data. Only when there is a good network connection and there are 10 failed attempts will the
controller archive the data on the SD card. Data archived on the SD card must be manually retrieved.
5.11 Ethernet
With an Ethernet-based network connection, the
immediately follow each other. After all attempts are exhausted, the register data packet is saved on the micro SD card.
At the next scheduled time, the DXM Controller attempts to send the saved packet as well as the newly created register
data packet. If it cannot send the new register data packet, the new register data packet is appended to the saved file on
the micro SD card to be sent later. After 10 rounds of retries, the data set is archived on the micro SD card under folder
_sxi. No additional attempts to resend the data are made; the data file must be manually retrieved.
Using SSL on Ethernet will have no retries, but will save each failed attempt to the micro SD card until 10 failed rounds. At
this time, the register data packet is archived.
DXM Controller retries the send procedure. The communications retry process is
5
. The number of retries will depend upon the network connection type.
DXM Controller retries a message five times. The five retry attempts
5.11 Cellular
In a cellular-connected system there are no retries. Failed transmissions are saved on the micro SD card.
After 10 successive failed attempts, the data is archived in the _sxi folder. Send attempts with a low signal quality are not
counted against the 10 count limit. For example, if the cellular antenna is disconnected for period that the DXM controller
would have sent 20 messages under normal circumstances, all 20 messages would be saved and will be retried when the
5
Enable HTTP logging to save data on the SD card; this is the factory default. See SETTINGS -> LOGGING in the DXM Configuration
Tool.
38www.bannerengineering.com - Tel: 763.544.3164
Page 39
DXM100 Controller Instruction Manual
antenna is reconnected. If the signal quality was good, but the cellular network was not responding, the DXM Controller
archives the register data packets after 10 failed attempts.
5.11 Event/Action Rule or Log Files
Event-based pushes caused by Action rules and locally stored log files sent using email follow the same process when
failures occur, based on the network connection. The failed Event-based messages are resent with the next cyclical
schedule or the next event message that triggers a push message.
5.11 Email and SMS Messages
There are no retries for emails or SMS messages that fail to be sent from the
DXM Controller.
5.12 Accessing the DXM Using SMS
The DXM Controller with a cellular modem can be remotely accessed using SMS messages. Simple text messages can:
Force a push to the cloud
•
• Reboot the controller
• Read/write local registers
The incoming firewall provides security; only defined phone numbers are permitted to access the controller. Use the DXM
Configuration Tool to configure the SMS commanding feature. This feature requires firmware version 3.51 or later.
SMS command messages sent to the DXM Controller cause the DXM to respond if they come from approved phone
numbers. See the examples below for SMS responses. Responses may take 20 seconds or more, depending upon the
network.
A DXM Controller requires a few minutes after powering up before it can accept SMS messages. Initial cellular connection
times vary based on the wireless network. A SMS message sent to the controller while a push session is active delays any
response or the SMS message may be dropped based on the length of the push session.
5.12 HTTP Push
Push triggers a http push to a webserver. The DXM Controller accepts the message, executes the action, and sends an
acknowledgement text message back to the user.
Example: Texting push forces defined local registers to be sent to a webserver
push <send>
DXM Controller acknowledgement text message: Register push requested
5.12 Reboot
Reboot triggers the DXM Controller to reboot. The processor reloads the XML configuration file and zeroes all local register
data. This does not affect the other components of the DXM Controller (ISM radio, I/O board, cellular modem). The DXM
Controller accepts the message, executes the action, and sends an acknowledgement text message back to the user.
Example: Texting reboot forces the processor to reboot.
reboot <send>
DXM Controller acknowledgement text message: rebooting…
5.12 Get Register
grN gets register number N (DXM Local Register) and sends a text with the value back to the user. The response text
message shows the value in floating point format regardless of register number.
Example: Texting gr1 retrieves the value for register 1
gr1 <send>
DXM Controller acknowledgement text message: Register 1 is 0
www.bannerengineering.com - Tel: 763.544.316439
Page 40
DXM100 Controller Instruction Manual
5.12 Set Register
srN,X sets a register value, where N is the register number and X is the value. The
DXM Controller responds with a SMS
message indicating the register was set.
Example: Texting sr1,10 sets register 1 to value of 10
sr1,10 <send>
DXM Controller acknowledgement text message: Register 1 has been set to 10
5.12 Configuring the DXM Controller for SMS Controlling
Configure the DXM Controller for SMS messaging capability using the DXM Configuration Tool.
1. On the Settings > Cloud Services screen, set the network interface to Cell.
2. On the Settings > Network screen, enter the phone numbers that are allowed access to the DXM Controller.
3. Save the configuration file (File > Save.
4. Load the XML file to the DXM Controller.
5. After the device has been running for a few minutes, the cellular network should be operational. The phone number
(MDN) is visible on the DXM LCD menu (System Info > Cell).
6. Send a text message to the DXM Controller from an approved phone number.
5.13 Using the Display LEDs
Turn on the DXM Controller LEDs by writing to the LEDs' Modbus registers.
The DXM display uses Modbus slave ID 201 and has four individual
registers for each of the four LEDs on the display.
Turn on an LED by writing a 1 value to the register. Turn off the LED by
writing a 0 to the register.
Display Modbus
Register
1102: bit 0LED 1 (Green)
1103: bit 0LED 2 (Red)
1104: bit 0LED 3 (Yellow)
1105: bit 0LED 4 (Red)
Display LED
DXM Controller Display Example
This example shows setting up the
DXM Controller using the DXM Configuration Tool to read four universal inputs and
write the state values to the display LEDs.
1. Using the DXM Configuration Tool, go to the Local Registers > Local Register Configuration screen.
2. Define the local registers by assigning names to the first four registers and setting the LCD permissions parameter
to read/write. The LCD permissions show the register contents on the LCD menu under the REGISTER menu. You
can also set the value from the LCD menu.
40www.bannerengineering.com - Tel: 763.544.3164
Page 41
DXM100 Controller Instruction Manual
3. Create a Read Rule to read the four universal inputs from the I/O board (Modbus slave 200) and write the values in
local registers 1 through 4.
4. Create a Write Rule to write the four local register values to the DXM display registers 1102 through 1105 (Modbus
Slave 201). Define the Write Rule to only write the display registers when the inputs change.
5. Save the XML configuration from the File > Save As
menu.
6. Connect to the DXM Controller using a USB cable and select Device > Connection Settings from the menu bar.
7. Upload the XML configuration file to the DXM Controller by selecting Device > Upload Configuration to Device
from the menu bar.
After a configuration file is uploaded, the DXM Controller reboots. The new configuration is now running.
Turning on any one of the universal inputs 1 through 4 on the I/O base board of the DXM Controller now turns on an LED
on the display.
On the DXM Controller's LCD menu, the arrow on the left side of the register line indicates this local register can be written
to. Try changing the configuration to delete the Read Rule then turn on/off the LEDs by changing the register value
through the LCD display.
www.bannerengineering.com - Tel: 763.544.316441
Page 42
DXM100 Controller Instruction Manual
6 File System and Archive Process
The DXM file system consists of two physical components: the serial EEPROM that stores non-volatile configuration
information and a removable micro SD card that stores file backup data and user created files.
6 EEPROM Files
The serial EEPROM stores basic data that is required to be non-volatile, including network configuration data, IP address,
MAC address, network masks, firewall settings, and authentication information. The controller XML configuration file
created by the
in EEPROM.
6 Micro SD Card Files
The micro SD card contains most files at the root level. The archive directory contains files kept by the system for history
backup. Archive files are stored in the directory _sxi and are only accessible by removing the SD card.
• Data Log Files
• HTTP Push Files
• User created ScriptBasic file
• ScriptBasic program file
• CmVMon file
• _sxi Archive directory
Data Log files. Users may create up to four data log files using the DXM Configuration Tool. The log files are stored in the
root directory on the SD card. When the file size limit is reached, the filename is changed to include the date and time and
the file is moved into the archive directory _sxi. If a finished log file is to be e-mailed, it will be done at this time and then
moved into the archive directory. Archived log files are deleted based on the Clear Logs parameter.
DXM Configuration Tool is stored in EEPROM. The small section of non-volatile local registers is also stored
HTTP Push File. If the DXM Controller is configured to send data to a webserver or host system, the device creates an
HTTP.LOG file on the SD card. The HTTP log is created only if the Logging Interval is non-zero and the HTTP enable log is
set. An entry is placed in the HTTP log file at the Logging Interval specified by the user. At the Push Interval time, the
HTTP log file is sent to the webserver or host system. If the transmission is successful, the HTTP log file is time stamped
and placed into the archive directory (_sxi). If the transmission fails, the file remains in the root directory and subsequent
Logging Intervals are appended to the file and are sent at the next Push Interval. For more information on the
communications retry mechanism, refer to the technicel note on system retries. (DXM Ethernet and Cellular PushRetries.docx)
ScriptBasic Created Files. Users may use ScriptBasic to create files on the SD card by using the FILEOUT function. The
filenames are fixed and up to five files can be created in the root directory.
ScriptBasic Program File. The main ScriptBasic program that runs at boot time is stored on the SD card in the root
directory.
System Voltage Monitor File. The CmVMon.txt file (Cellular milli-Volt Monitor) is created by the system and is used to
track power events. Every power-up cycle is date/time stamped with the voltage read from the I/O board. The value
24487 is equal to 24.487 volts. If the voltage drops below 11.2 V, another entry is put in the log file indicating the cellular
modem will shut down.
CM2015-09-22 18:52:43VMonPower entered normal range 24487
CM2015-10-13 20:49:47VMonPower entered normal range 24004
CM2015-10-16 15:00:20VMonPower entered normal range 24014
CM2015-10-19 19:12:26VMonPower entered normal range 12845
Archive Directory. Only two types of files are moved into the archive directory: data log files and HTTP log files. Data log
files are date/time stamped and placed into the archive directory when the size limit is reached. HTTP log files are date/
time stamped then placed into the archive directory when they are successfully sent to the webserver or host system. If
the HTTP log files were not successfully sent after the retries have been exhausted, the files are placed into a root
directory called sav.
42www.bannerengineering.com - Tel: 763.544.3164
Page 43
DXM100 Controller Instruction Manual
7 DXM Modbus Registers
DXM100 Controller may have up to four internal Modbus slave devices:
The
DXM Internal Modbus Slave IDs (factory default)
Modbus Slave IDDevice
1Gateway (PE5) or MultiHop (HE5) ISM Radio—MultiHop wireless devices connected to the internal MultiHop radio should
199Local Registers—Internal storage registers of the DXM Controller
200I/O Base Board—All data and parameters for each input or output of the DXM Controller.
201LCD Display—The user has access to the LED indicators on the DXM Controller.
All Modbus registers are defined as 16-bit Modbus Holding Registers. When connecting external Modbus slave devices, only
use Modbus slave IDs 2 through 198. The local registers, the I/O base, and the LCD slave IDs are fixed, but the internal
radio slave ID can be changed if needed.
7.1 Gateway Performance 1 Watt Radio
The DX80 Gateway (PE5) is a star-based architecture device that contains all the Modbus registers for the wireless
network within the Gateway. To access any input or output values within the entire wireless network, read the appropriate
Modbus register from Gateway.
There are 16 Modbus registers allocated for each device in the wireless network. The first 16 registers (1–16) are allocated
for the Gateway, the next 16 (17–32) are allocated for Node 1, the next 16 (33–48) are allocated for Node 2 and so forth.
There are no inputs or outputs on the DXM embedded Gateway but the Modbus registers are still allocated for them.
be assigned Modbus Slave addresses starting at 11.
Although only seven Nodes are listed in the table, the Modbus register numbering continues for as many Nodes as are in
the network. For example, the register number for Node 10, I/O point 15 , is 175. Calculate the Modbus register number
for each device using the equation:
Access all wireless network registers by reading Modbus slave ID 1.
www.bannerengineering.com - Tel: 763.544.316443
Page 44
DXM100 Controller Instruction Manual
DX80 DeviceSlave IDModbus Registers
DXM Gateway radio1Modbus registers 1–8 are inputs, 9–16 are outputs
Node 1-Modbus registers 17–25 are inputs, 26–32 are outputs
Node 2-Modbus registers 33–40 are inputs, 41–48 are outputs
Node 3-Modbus registers 49–56 are inputs, 57–64 are outputs
7.2 MultiHop 1 Watt Radio
The DX80 MultiHop master radio (HE5) is a tree-based architecture device that allows for repeater radios to extend the
wireless network. Each device in a MultiHop network is a Modbus device with a unique Modbus ID. Modbus registers in a
MultiHop network are contained within each individual radio device. To get Modbus register data from a MultiHop device,
configure the
Example: MultiHop Modbus Register Table
Example MultiHop Modbus registers with generic devices.
MulitHop DeviceSlave IDModbus Registers
DXM Master radio1none
Slave device11Modbus register 1–16 are inputs, 501–516 are outputs
Repeater device12Modbus register 1–16 are inputs, 501–516 are outputs
Slave device15Modbus register 1–16 are inputs, 501–516 are outputs
DXM Controller to access each device across the wireless network as an individual Modbus slave device.
7.3 Modbus Registers - Internal Local Registers (Modbus Slave 199)
The main storage elements for the DXM Controller are its Local Registers, which can store 4-byte values that result from
register mapping, action rules, or ScriptBasic commands.
Local Registers 1 through 450 are standard 32-bit signed registers.
•
• Local Registers 451 through 500 are non-volatile registers that are limited to 100,000 write cycles.
• Local Registers 1001 through 1500 are floating point format numbers. Each register address stores half of a
floating point number. For example, registers 1001 and 1002 store the first full 32-bit floating point number.
• Local Registers 10001 through 19000 are system, read-only, registers that track DXM Controller data and
statistics.
7.3 Local Registers 1–450 (Internal Processor Memory, 32-bit, Unsigned)
The local registers are the main global pool of registers. Local registers are used as basic storage registers and as the
common data exchange mechanism.
Modbus slave ID 0 is reserved for the processor.
External Modbus device registers can be read into the local registers or written from the local registers. The DXM
Controller, as a Modbus master device or a Modbus slave device, exchanges data using the local registers.
Modbus over Ethernet (Modbus/TCP) uses the local registers as the accessible register data.
7.3 Local Registers 451–500 (Data Flash, Non-volatile, 32-bit, Unsigned)
The top 50 local registers are special non-volatile registers. The registers can store constants or calibration type data that
must be maintained when power is turned off.
This register data is stored in a data flash component that has a limited write capability of 100,000 cycles, so these
registers should not be used as common memory registers that change frequently.
7.3 Local Registers 1001–1500 (32-bit IEEE Floating Point)
These local registers are paired together to store a 32-bit IEEE floating point format number in big endian format.
44www.bannerengineering.com - Tel: 763.544.3164
Page 45
DXM100 Controller Instruction Manual
Registers 1001 [31:16], 1002 [15:0] store the first floating point value; registers 1003, 1004 store the second floating
point number. There are a total of 250 floating point values; they are addressed as two 16-bit pieces to accommodate the
Modbus protocol.
Use these registers when reading/writing external devices that require Modbus registers in floating point format. Since
Modbus transactions are 16-bits, the protocol requires two registers to form a 32-bit floating point number.
7.3 Virtual Registers
The
DXM Controller has a small pool of virtual registers that show internal variables of the main processor. Some register
values will be dependent upon the configuration settings of the DXM Controller.
RegistersDefinition
10001GPS latitude direction (N, S, E, W)GPS Coordinate Data if the DXM is configured to read an external GPS unit.
10002GPS latitude
10003GPS longitude direction (N, S, E, W)
10004GPS longitude
10011–10012Resync timerEngineering use
10013–10014Resync timer rolloverEngineering use
10015–10016Reboot cause (Restart Codes above)Reboot Type
10017–10018Watchdog reset countCounter to track how many resets have been caused by the Watchdog
10021IO Board Battery Voltage (mV)DXM Base I/O board battery / solar charger statistics.
10022IO Board Battery Charging Current (mA)
10023IO Board Incoming Supply (mV)
10024IO Board On board thermistor ( degrees C)
10025–10026Http Push SSL AcquiresStatistical counts of connections, disconnections and forced disconnects when
10027–10028Http Push SSL Releases
10029–10030Http Push SSL Forced Releases
10031–10032Http Push AttemptsStatistical counts of connections, disconnections and forced disconnects when
10033–10034Http Push Successes
10035–10036Http Push Failures
10037–10038Http Push Last StatusLast DXM Controller push status
10039–10040Cellular Strength, BERCellular signal strength. Value range: 0–31
Refer to the DXM Instruction Manual for more information.
the DXM Controller creates a connection using SSL/TLS (Encrypted
connections)
the DXM controller creates a connection using HTTP non-encrypted
10100Number of read maps in defaultRead Map statistics
10101Number of read map successes
10102Number of read map timeouts
10103Number of read map errors
10104Read map success streak
10105Number of write map successesWrite Map statistics
10106Number of write map timeouts
10107Number of write map errors
10108Write map success streak
www.bannerengineering.com - Tel: 763.544.316445
0 = –113 dBm or less
1 = –111 dBm
2–30 = –109 dBm through –53 dBm in 2 dBm steps
31 = –51 dBm or greater
99 = not known or not detectable; BER not used
Page 46
DXM100 Controller Instruction Manual
RegistersDefinition
10109Number of passthrough successesAPI message passing statistics
10110Number of passthrough timeouts
10111Number of passthrough errors
10112Passthrough success streak
10113Number of 43 buffer successesDX80 Gateway automatic messaging buffer statistics
501NMOS Output 1
502NMOS Output 2
503NMOS Output 3
504NMOS Output 4
505Switched Power 1 (5 V or 16 V)
506Switched Power 2 (5 V or 16 V)
507DAC Output 1
508DAC Output 2
7.4 Input/Output Parameter Modbus Registers
Universal Input Parameter Modbus Registers
Universal Inputs1234
Enable Full Scale3303332333433363
Temperature °C/°F3304332433443364
Input Type3306332633463366
Threshold3308332833483368
Hysteresis3309332933493369
Enable Rising4908492849484968
Enable Falling4909492949494969
High Register for Counter4910493049504970
Low Register for Counter4911493149514971
Enable Full Scale.
Set to 1 to enable a linear range from 0 to 65535 for specified input range. For a 4 to 20 mA input, a
value of 0 represents 4 mA and 65535 represents 20 mA. Set this parameter to 0 to store input readings in unit-specific
data. For example, the register data representing a 15.53 mA reading is 15530. For units of current (0 to 20 mA inputs),
values are stored as µA (micro Amps) and voltage values are stored as mV (millivolts).
Enable Rising/Falling. Use these registers to enable the universal input logic to count on a rising transition or a falling
transition. Write a one (1) to enable; write a zero (0) to disable.
High/Low Register for Counter. The low and high registers for the counter hold the 32-bit counter value. To erase the
counter, write zeroes to both registers. To preset a counter value, write that value to the appropriate register.
Hysteresis and Threshold. Threshold and hysteresis work together to establish the ON and OFF points of an analog
input. The threshold defines a trigger point or reporting threshold (ON point) for a sensor input. Setting a threshold
establishes an ON point. Hysteresis defines how far below the threshold the analog input is required to be before the input
is considered OFF. A typical hysteresis value is 10% to 20% of the unit’s range.
www.bannerengineering.com - Tel: 763.544.316447
Page 48
Threshold
ON point
Time
Input Value
Input
Hysteresis
OFF point
DXM100 Controller Instruction Manual
In the example shown graphically, the input is considered on at 15 mA.
To consider the input off at 13 mA, set the hysteresis to 2 mA. The input
will be considered off when the value is 2 mA less than the threshold.
Input Type. Program the universal inputs to accept input types NPN, PNP, 10k thermistor, 0 to 10 V, 0 to 20 mA, or
potentiometer. The default setting is 8: NPN raw fast. To set the input type, write the following values to the Input Type
Modbus registers.
0 = NPN
1 = PNP
2 = 0 to 20 mA
3 = 0 to 10 V dc
4 = 10k Thermistor
5 = Potentiometer Sense (DXM150 only)
6 = Not used
7 = Bridge
8 = NPN Raw Fast (default)
Temperature °C/°F.
Set to 1 to represent temperature units in degrees Fahrenheit, and set to 0 (default) to represent
temperature units in degrees Celsius.
Universal Input Register Ranges
Register TypesUnitMinimum ValueMaximum Value
Discrete input/output01
Universal input 0 to 10 VmV010000
Universal input 0 to 20 mAµA020000
Universal input temperature (–40 °C to +85 °C)C or F, signed, in tenths of a
Universal potentiometerunsigned065535
Analog Output Parameter Modbus Registers
Modbus RegisterAnalog OutputDescription
4008Analog Output 10 to 20 mA or 0 to 10 V dc output (I/O board jumper selectable)
4028Analog Output 2
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit
After changing the jumper position, write the appropriate value to the Modbus
registers to define your analog output to match the setting selected by the jumper.
2 = 0 to 20 mA output (default)
3 = 0 to 10 V output
degree
–400850
6
6
6
Setting Enable Full Scale to 1 sets the ranges to a linear scale of 0 to 65535.
48www.bannerengineering.com - Tel: 763.544.3164
Page 49
DXM100 Controller Instruction Manual
7.4 Power Modbus Registers
Modbus RegisterDescription
6071Battery backup charging algorithm.
0 = Battery is recharged from a solar panel
1 = Battery is recharged from 12 to 30 V dc . (default)
6081Battery voltage (mV)
6082Battery charging current (mA)
6083Incoming supply voltage (mV) (solar or power supply)
6084On-board thermistor temperature (⁰C)
7.5 LCD Board (Modbus Slave ID 201)
Control the four user-defined LEDs using the display board's Modbus registers. Using write maps or ScriptBasic, write the
Modbus registers shown below with 0 (off) or 1 (on). The LCD display is Modbus Slave 201.
1102 : bit 0LED 11104 : bit 0LED 3
1103 : bit 0LED 21105 : bit 0LED 4
www.bannerengineering.com - Tel: 763.544.316449
Page 50
DXM100 Controller Instruction Manual
8 Restoring Factory Default Settings
To reset to factory defaults, write to two Modbus registers in the I/O board. The default slave ID for the I/O board is
To reset the DXM I/O board parameters:
1. Write a 1 to Modbus register 4152
2. Write a 10 to Modbus register 4151
To reset only the I/O board:
1. Write a 0 to Modbus register 4152
2. Write a 10 to Modbus register 4151
Modbus RegisterValuesDescription
41510–65535Reset/restore trigger. This timer is based in 100 millisecond units. Once written, the timer starts to count down to
41520–11 = Restores factory defaults for I/O parameters.
zero. After the timer expires, the restore factory defaults are applied if register 4152 = 1. If register 4152 is zero,
the I/O board is reset.
Default value: 0
1 = 100 milliseconds, 10 = 1 second.
Default value: 0
200.
50www.bannerengineering.com - Tel: 763.544.3164
Page 51
DXM100 Controller Instruction Manual
9 Contact Us
Corporate Headquarters
Address:
Banner Engineering Corporate
9714 Tenth Avenue North
Minneapolis, Minnesota 55441, USA
Europe
Address:
Banner Engineering EMEA
Park Lane Culliganlaan 2F
Diegem B-1831, Belgium
Turkey
Address:
Banner Engineering Turkey
Barbaros Mah. Uphill Court Towers A Blok D:49
34746 Batı Ataşehir Istanbul Türkiye
India
Address:
Banner Engineering India Pune Head Quarters
Office No. 1001, 10th Floor Sai Capital, Opp. ICC Senapati Bapat Road
Pune 411016, India
Banner Engineering de Mexico Monterrey Head Office
Edificio VAO Av. David Alfaro Siqueiros No.103 Col. Valle Oriente C.P.66269
San Pedro Garza Garcia, Nuevo Leon, Mexico
Brazil
Address:
Banner do Brasil
Rua Barão de Teffé nº 1000, sala 54
Campos Elíseos, Jundiaí - SP, CEP.: 13208-761, Brasil
China
Address:
Banner Engineering Shanghai Rep Office
Xinlian Scientific Research Building Level 12, Building 2
1535 Hongmei Road, Shanghai 200233, China
Japan
Address:
Banner Engineering Japan
Cent-Urban Building 305 3-23-15 Nishi-Nakajima Yodogawa-Ku
Osaka 532-0011, Japan
Antenna Installations. Install and properly ground a qualified surge suppressor when installing a remote antenna system. Remote antenna configurations
installed without surge suppressors invalidate the manufacturer's warranty. Keep the ground wire as short as possible and make all ground connections to a single-point
ground system to ensure no ground loops are created. No surge suppressor can absorb all lightning strikes; do not touch the Sure Cross®
connected to the Sure Cross device during a thunderstorm.
Exporting Sure Cross® Radios. It is our intent to fully comply with all national and regional regulations regarding radio frequency emissions. Customers who want to
re-export this product to a country other than that to which it was sold must ensure the device is approved in the destination country. A list of approved
countries appears in the Radio Certifications section of the product manual. The Sure Cross wireless products were certified for use in these countries using the antenna that
ships with the product. When using other antennas, verify you are not exceeding the transmit power levels allowed by local governing agencies. Consult with Banner
Engineering Corp. if the destination country is not on this list.
Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp.
will repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty
period. This warranty does not cover damage or liability for misuse, abuse, or the improper application or installation of the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION,
ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE
OF DEALING OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE
LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL,
CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER
ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product
previously manufactured by Banner Engineering Corp.
device or any equipment
52www.bannerengineering.com - Tel: 763.544.3164
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.