Bally Refrigerated Boxes BE-Line Installation Manual

Installation and Maintenance
Instructions
for
Condensing Units
Bally Refrigerated Boxes Inc.,
General Sales, Manufacturing and Engineering 135 Little Nine Drive, Morehead City, NC 28557
Phone: 800-24BALLY, 252-240-2829 Fax: 252-240-0384
Service and Warranty
Phone: 800-344-9302, 610-337-8600 Fax: 610-337-0431
Visit our web site at www.ballyrefboxes.com
B40-CU-IM-13
1068157
Table of Contents
Pages
General Safety, Inspection & General Warranty Policy 3 Handling, Placement & Installation 4 – 6 Electrical Information & Wiring Diagrams 7 – 14 Refrigerant Piping 15 – 16 Water-Cooled Condensers, Piping & Flow Rates 17 – 18 System Accessories 19 Leak Testing, Evacuation & Dehydration 20 Line Insulation 21 Refrigerant Charging 21 – 23 Compressor Oils 24 – 25 System Start-up Check List 26 – 27 Low Temperature Room Pull-Down 27 Checking Compressor & Evaporator Superheat 28 System Operational Check List 29 System Troubleshooting 30 – 32 Customer Instructions 33 Maintenance Program 33
Service Parts Availability 33
Finished Goods Warranty & Service Log 34 Warranty Activation Certificate 35 Service Parts List Back Cover
2

General Safety

IMPORTANT SAFETY NOTE
Only a qualified refrigeration mechanic who is familiar with refrigeration systems and components, including all controls should perform the installation and start-up of the system. To avoid potential injury, use care when working around coil should be installed in accordance with all applicable codes, ordinances and local by-laws.
surfaces (if applicable) or sharp edges of metal cabinets. All piping and electrical wiring
WARNING
Always disconnect and lock off the main power supply on any system that will be worked on to avoid accidental start up of the equipment.

Inspection

Inspect all equipment before unpacking for visible signs of damage or loss. Check shipping list against material received to ensure shipment is complete.
IMPORTANT: Remember, you, the consignee, must make any claim necessary against the transportation company. Shipping damage or missing parts, when discovered at the outset, will prevent later unnecessary and costly delays. If damage or loss during transport is evident, make claim to carrier, as this will be their
responsibility, not that of the manufacturer.
Should carton be damaged, but damage to equipment is not obvious, a claim should be filed for “concealed damage” with the carrier.
IMPORTANT: Check the electrical ratings on the unit to make sure they correspond to those ordered and to electrical power available at the job site. Save all shipping papers, tags, and instruction sheets for reference by installer and owner.
General Warranty Policy
Please refer to the “Finished Goods Warranty” on page 34.
3
g
g

Handling, Placement and Installation

IMPORTANT: When selecting a location for the condensing unit, consideration should be given to some of the
following: (a) Loading capacity of the floor or roof. Check building codes for weight distribution requirements. (b) Distance to suitable electrical supply. (c) Distance to the evaporator. (d) Adequate air circulation and ventilation. (e) Close proximity to water source and floor drains (water-cooled units) (f) Accessibility for maintenance. (g) Local building codes. (h) Adjacent buildings relative to noise levels. (i) Wishes of the end user / owner.
When all of the above points have been considered and a specific location chosen, it is advisable to obtain written approval of this location from the building and/or condensing unit owner. This may be a means of avoiding disagreement and expense at a later date.
A fully qualified and properly equipped crew with the necessary tackle and rigging should be engaged to locate the condensing unit in position. When lifting the unit, spreader bars and chafing gear should be used to prevent damage.
The unit should be placed on a base, which is level and even. Units should be lagged to sleepers or support base. Place unit where it will not be subject to damage by traffic or flooding. On critical installations where noise is liable to be transmitted through the floor structure, vibration isolators should be installed. Isolators should be installed under mounting base and may be rubber or cork or equal.
DO NOT
The condensing unit should be positioned to allow adequate space for performing service work.
Indoor and outdoor air-cooled condensing units should be positioned using the guidelines shown below.
USE THE SHIPPING SKID AS A PERMANENT BASE.
Air Cooled Condensing Unit Minimum Clearance (for Horizontal Air Flow Units)
48" (1.2 m)
Minimum
Air FlowAir Flow
Condensing UnitCondensing Unit
*
Width of
Condensin
Minimum
* No closer than 24" (.62 m)
Unit
*
Width of
Condensin
Minimum
Unit
* Height of
Condensing Unit
Minimum
Walls
4
p
SPECIAL NOTE FOR LARGE AIR COOLED CONDENSING UNITS: Vertical flow air cooled condensing units are large and heavy pieces of mechanical equipment and must be handled as such. A fully qualified and properly equipped crew with the necessary tackle and rigging should be engaged to locate the condensing unit into location. The unit can be lifted by means of lifting holes located in the base frame of the unit. Spreader bars should be used to prevent damage to the sides of the unit. Do not sling directly around the base of unit. The unit should be placed on a base which is level and even.
Air Cooled Condensing Unit Minimum Clearance (For Vertical Air Flow Units)
WALLS OR OBSTRUCTIONS
All sides of the unit must be a minimum of 4 feet (1.25 m) away from the wall or obstruction. Overhead obstructions are not permitted. If enclosed by three walls, the unit must be installed as indicated for units in a
it.
MULTIPLE UNITS
A minimum of 8 feet (2.5 m) is required between multiple units placed side by side. If placed end to end, the minimum distance between units is 4 feet (1.25 m)
4 ft
(1.25 m)
min.
8 ft
(2.5 m)
min.
UNITS IN PITS:
The top of the unit must be level
the top of the pit. In addition, a
above
with, or
minimum of 8 feet (2.5 m) is required between the unit and the pit walls.
LOUVERS / FENCES:
Louvers/fences must have a minimum of 80% free area and 4 feet (1.25 m) minimum clearance between the unit and the louver/fence. Height of louver/fence must not exceed
top of unit.
8 ft
(2.5 m)
min.
8 ft
(2.5 m)
min.
4 ft
(1.25 m)
min.
4 ft
(1.25 m)
min.
Units equipped with spring-mounted compressors have shipping spacers that are designed to hold the compressor rigidly during transit to prevent possible damage. Before operating the unit, it is necessary to remove these spacers. To remove the shipping spacers, follow these steps:
(a) Remove the upper nuts / washers. (b) Discard the shipping spacers. (c) Install the rubber cone washers (located in the electrical box). (d) Replace the upper mounting nuts / washers. (e) Allow 1/16 inch space between the mounting nuts / washers and the compressor foot.
On units equipped with rigid mounted compressors, check the compressor mounting bolts to insure they have not vibrated loose during shipping.
5

Ventilation

If the compressors or condensing units are to be located in machine rooms, adequate ventilation air must be provided in order to avoid an excessive temperature rise in the room. Air requirements vary with ambient air temperatures and the refrigeration load, however the following rule of thumb may be used to approximate ventilating air quantities:
Model Type Air Quantity
Air-cooled condensing units (for horizontal air flow units) 1,000 cfm (472 L/s) per Hp
Air-cooled compressors (with remote condensers) 250 cfm (118 L/s) per Hp
Suction cooled or water-cooled compressors 200 cfm (94 L/s) per Hp (with remote or water cooled condensers)
All of the above mentioned air quantities are based on relatively short discharge line runs within the machine rooms. If using long uninsulated discharge line runs are unavoidable in the machine room, additional ventilation air is required to offset the heat added to the room by the discharge gas.
6

Electrical Information

WARNING
All wiring and connections to the unit must be made in accordance with national as well as local electrical codes and by-laws.
Electrical wiring should be sized in accordance with the minimum circuit ampacities shown on the unit nameplate and applicable electrical codes. The unit power connections are approved for copper wire only.
Connect the field power supply through a fused branch circuit disconnect switch. The entering service fuse must not exceed the maximum overcurrent protection (MOP) value on the unit data plate.
Field connected control circuit wires are terminated directly at the control circuit terminal block in accordance with the appropriate wiring diagram.
Voltage at the unit terminals must not vary more than the allowable variation during start-up and while under full load. If the voltage is normal at the supply with the compressor not running and drops considerably when the switch is closed and the motor is trying to start, there is a high resistance due to undersized wires or faulty connections. Voltage drop between inoperative and full load must not exceed 3% of line voltage. In addition, the phase imbalance at the motor terminals should be within 2% on three phase units.
60 Hz Supply 50 Hz Supply
Power Allowable Variation Power Allowable Variation
115-1-60 103-127 V 100-1-50 90-110 V
208/230-1-60 197-254 V 200/220-1-50 190-242 V
208/230-3-60 187-254 V 200/220-3-50 180-242 V 460-3-60 414-506 V 380/400-3-50 342-440 V 575-3-60 518-632 V
All systems should use a liquid line solenoid valve (installed at the evaporator) and should be energized by the room or fixture thermostat. For systems with a defrost time clock, the liquid line solenoid and thermostat should be energized by the time clock. Initially set the defrost time clock (model 8145) as follows:
Air defrost evaporators; 3 per day (every 8 hours) with the time termination at 45 minutes.
Electric defrost evaporators; 4 per day (every 6 hours) with time termination set (Fail Safe) at 30 minutes.
Check that the wiring from the defrost termination thermostat is wired to terminal “X” on the clock and terminates the defrost cycle when the evaporator coil reaches approximately 55 also be checked for proper operation. This ensures that all water droplets have been refrozen to the coil before the evaporator fan starts back up.
Note: The above settings are guidelines only and must be re-adjusted to suit local field conditions and actual evaporator equipment specifications.
Refer to the evaporator installation manual for further information.
An evaporator airflow interlock is recommended on some installations so that the compressor will pump down and shut off in the event that the evaporator fan is off for any reason. This is wired into the control circuit in series with the thermostat and solenoid valve.
Refer to the following wiring diagrams for typical air defrost and electric defrost wiring arrangements.
o
F. The fan delay thermostat wiring should
WARNING
Any deviation or change to the electrical components or wiring as supplied on the original equipment, or noncompliance with the voltage and phase balance requirements without written authorization will void the warranty.
7
Electrical Wiring Diagram – Horizontal Air Flow Condensing Units (RP-Line)
8
Electrical Wiring Diagram – Horizontal Air Flow Condensing Units (RP-Line)
9
Electrical Wiring Diagram – Horizontal Air Flow Condensing Units (BE-Line)
10
Electrical Wiring Diagram – Horizontal Air Flow Condensing Units (BE-Line)
11
Loading...
+ 25 hidden pages