Bally Refrigerated Boxes BCHC02D Installation Manual

Page 1
BCH Air Cooled Condensers
PRODUCT DATA & INSTALLATION
Bulletin B50-BCH-PDI-12 1064626
Refrigerants - R12, R22 and R502 Electrical Power: 208-230/1/60, 460/1/60
& 575/1/60
• CSA approved for outdoor and indoor applications
• T o tally enclosed, ball bearing 1500 RPM, PSC High Efficiency Motors.
• Coils fabricated with 3/8 O.D. copper tube mechanically expanded to corrugated aluminum fins.
• Rugged heavy gauge galvanized steel construction.

NOMENCLATURE

BCH C 02 D
MODEL BALLY CONDENSER, HORIZONTAL AIR FLOW
SERIES OR GENERATION C = 3RD GENERATION
NOMINAL TONS 2, 3, 5, 8 OR 10
ELECTRICAL DESIGNA TION D = 208-230/1/60 R = 460/1/60 Q = 575/1/60
• Vinyl coated fan grille and motor mount for improved appearance and durability .
CONTENTS PAGE
Nomenclature.........................................
Capacity Data..........................................
Electrical/Physical Data.........................
Dimensional Data...................................
Inspection...............................................
Piping.......................................................
Electrical.................................................
Wiring Diagram.......................................
Maintenance...........................................
Low Ambient Operation........................
Service Parts List..................................
Cover
Back Back
2 2 2 3 3 3 3 3 3
Page 2
SPECIFICATIONS
* CAP ACITY DA T A - (TOT AL HEA T OF REJECTION - BTUH)
LEDOMF°01 F°51F°02F°52F°03
D20CHCB D30CHCB D50CHCB D80CHCB D01CHCB
* Above capacity using R22. For R12 multiply R22 capacity by X .95. For R502 multiply R22 capacity by X .98.

ELECTRICAL / PHYSICAL DATA

005,01 767,51 336,52 004,83 338,05
057,51 056,32 054,83 006,75 052,67
000,12 335,13 762,15 008,67
766,101
052,62 714,93 380,46 000,69
380,721
)TNEIBMA-.PMET.DNOC(ECNEREFFIDERUTAREPMET-.D.T
005,13
003,74
009,67
002,511 005,251
LEDOM
D20CHCB D30CHCB D50CHCB D80CHCB D01CHCB
REWOP
06-1-032/802 06-1-032/802 06-1-032/802 06-1-032/802 06-1-032/802
** Dual element type fuse.
DIMENSIONAL DA T A
LACIRTCELE
(INCHES)
SROTOM
PH-YTQ
5/1-1 5/1-1 5/1-1 5/1-2 5/1-2
ALF
HCAE
3.2
3.2
3.2
3.2
3.2
.CRIC.NIM
YTICAPMA
9.2
9.2
9.2
2.5
2.5
**.XAM
)A(ESUF
51 51 51 51 51
SNAF
"81-1 "81-1 "81-1 "81-2 "81-2
RIA
.AID-YTQ
WOLF
MFC
0043 0833 0523 0666 0246
.GIRFER
EGRAHC
)sbl(22R
38.
19.1
43.3
52.5
47.6
TINU
)sbl(THGIEW
).XORPPA(
041 041 002 072 053
BCHC02D - BCHC05D
BCHC08D - BCHC10D
.DNOC
HTDIW
LEDOM
ABCDEF
D20CHCB 23/11442/10261/1238/78/58/3
D30CHCB 23/11442/10261/1238/78/58/5
D50CHCB 23/11442/10261/1238/78/58/5
D80CHCB 23/11562/10261/1838/78/78/7
D01CHCB 23/11562/10261/1838/78/78/7
.DNOC
HTPED
.DNOC THGIEH
TELNI
.TCELE
)SAG(
.NNOC
NNOC
TELTUO
)DIUQIL(
.NNOC
Page 3

INSTALLATION INSTRUCTIONS

INSPECTION
Careful inspection of all parts when received for loss or damage in transit is very important ­Remember, you, the consignee, must make any claim necessary against the transportation company. Shipping damage or missing parts, when discovered at the outset, will prevent later unecessary and costly delays.
Electrical characteristics should also be checked at this time to ensure that they are as ordered.
LOCATION
BALLY BCH Air Cooled Condensers are designed for outdoor installation. A number of factors must be taken into consideration when selecting a loca­tion. Most important is the provision for a supply of ambient air to the condenser, and removal of heated air from the condenser area. Failure to do so will result in higher condensing temperatures, decreased performance, plus the possibility of equipment failure.
ELECTRICAL
Wire system in accordance with governing standards and local codes. Electrical wiring is to be sized in accordance with minimum ampacity rating.
For ease of identifying the proper wiring terminals, unit wiring is color coded and terminal block connections are identified. Electrical connections are made at an external junction box.
NOTE: FAN MOTOR 2 USED
ON MODELS BCHC08D AND BCHC10 ONLY
Other considerations include:
1. Distance to suitable electrical supply.
2. Accessibility for maintenance.
3. Local building codes.
4. Adjacent building relative to noise levels.
5. Wishes of the purchaser.
6. Minimum of 2 ft. between units side by side and 4 ft. from wall (front & back).
REFRIGERANT PIPING
The importance of correct refrigerant pipe sizing and layout cannot be over-emphasized. Failure to observe proper refrigerant piping practices can result in equipment failure which may not be covered under warranty.
BALLY Air Cooled Condensers are supplied complete with headers and refrigerant connections sized for connecting to standard refrigeration tubing.
MAINTENANCE
A semi annual inspection should be carried out by a qualified refrigeration service mechanic. The main power supply must be disconnected.
1. Check electrical components. Tighten any loose connections.
2. Check tighteness of all fans and motor mounts. Remove any deposits which could affect fan balance.
3. Clean the condenser coil using a soft brush or by flushing with cool water or commercially available coil cleaners.
Page 4

LOW AMBIENT - WINTER OPERATION

US
C
11/10/06
When selecting a BALLY “BCH” AIr Cooled Condenser that will operate during the winter, some method of controlling the head pressure must be considered. At temperatures lower than 50 °F the condenser will be oversized, resulting in low head pressure. This in turn will cause poor expansion valve operation and unstable evaporator performance. This may result in unsatisfactory system performance and potential compressor failure. BALLY recommends the “Flooded - Condenser” method of head pressure control.
LEDOM21R22R205R
D20CHCB D30CHCB D50CHCB D80CHCB D01CHCB
6
21
9.32
5.23
3.34
* Based on temperatures (density) of refrigerant at 0 °F
T o calculate the partially flooded refrigerant charge for specific ambient temps and application follow the recommended charging instructions supplied by the valve manufacturer.
Since additional liquid refrigerant is required, the system must be designed to allow enough refrigerant to fill the condenser as well as the receiver in order to maintain a liquid seal. The receiver must also be sized accordingly to contain this extra refrigerant during a pump-down or when operating at higher ambient conditions (summer). Depending on the actual low ambient temp (0 °F to -40 °F) and application (High, Med, Low) the flooded condenser pressure control will flood the condenser anywhere from 70 to 97% full of liquid.
)sbl(-*)LLUF%001(EGRAHCDIUQILLATOT
6.5
1.
11
3.22
3.03
3.04
8.5
6.11
1.32
4.13
8.14
NOITPIRCSED.ONTRAP
PH5/1V032/802-ROTOMNAF
V073-DFM5-ROTICAPAC
4-2281B-EDALBNAF
TNUOMROTOM/DRAUGNAF
IMRET
General Sales, PGeneral Sales, P
General Sales, P
General Sales, PGeneral Sales, P
135 Little Nine Drive, Morehead City135 Little Nine Drive, Morehead City
135 Little Nine Drive, Morehead City
135 Little Nine Drive, Morehead City135 Little Nine Drive, Morehead City 252-240-2829 • 1-800-24-BALL252-240-2829 • 1-800-24-BALL
252-240-2829 • 1-800-24-BALL
252-240-2829 • 1-800-24-BALL252-240-2829 • 1-800-24-BALL e-mail: ballysales@ballyrefboe-mail: ballysales@ballyrefbo
e-mail: ballysales@ballyrefbo
e-mail: ballysales@ballyrefboe-mail: ballysales@ballyrefbo
KCOLBLAN
arar
ts & Serts & Ser
ar
ts & Ser
arar
ts & Serts & Ser
vice Manufacturing & Engineeringvice Manufacturing & Engineering
vice Manufacturing & Engineering
vice Manufacturing & Engineeringvice Manufacturing & Engineering
Y • FY • F
Y • F
Y • FY • F
xx
es.com • wwwes.com • www
x
es.com • www
xx
es.com • wwwes.com • www

SERVICE PARTS LIST

0031401
650-125171 9312401 3131401
xx
es.comes.com
x
es.com
xx
es.comes.com
C
9821401
, NC 28557, NC 28557
, NC 28557
, NC 28557, NC 28557
AX: 252-240-0384AX: 252-240-0384
AX: 252-240-0384
AX: 252-240-0384AX: 252-240-0384
.ballyrefbo.ballyrefbo
.ballyrefbo
.ballyrefbo.ballyrefbo
NOITPIRCSED.ONTRAP
)20(LIOCRESNEDNOC )30(LIOCRESNEDNOC )50(LIOCRESNEDNOC )80(LIOCRESNEDNOC )01(LIOCRESNEDNO
DISTRIBUTED BY:
1442401 9122401 8412401 0222401 1222401
Due to Manufacturer’s policy of continuous product improvement, the Manufacturer reserves the right to make changes without notice.
Loading...