Where available use the HFESC series valve which includes sweat fittings with a removable/cleanable inlet screen.
Note: Above Selections are based on 100 oF Entering Liquid Temperature.
VENTURI - FLO distributor does not require the selection or use of distributor nozzles.
* Valve part numbers are coded for R404A (also may be used on R502 or R507) and R134a (also may be used on R12)
Note: Above Selections are based on 100 oF Entering Liquid Temperature.
VENTURI - FLO distributor does not require the selection or use of distributor nozzles.
- 8 -
SJE 3-C
EBSJE 7-C
Page 9
ELECTRICAL VIEW
DEFROST
ADJUSTABLE DEFROST
TERMINATION
CONTROL
ENTERING
SERVICE
KNOCK-OUTS
TERMINAL BLOCKS
DEFROST CONTROL (TOP)
HEATERS (MIDDLE)
FAN MOTORS (BOTTOM)
THERMOSTAT
BULB
FRONT HEATER
SLOT COVER PLATE
(REMOVE 5 SCREWS)
REAR HEATER SLOT
COVER PLATE
(REMOVE 5 SCREWS)
DEFROST HEATER
(4 0N AIR-ENTERING SIDE,
2 ON LEAVING AIR-SIDE)
ELEMENTS (6)
HEATER
SPRING
CLIPS
DRAIN PAN
HEATER
ELEMENT(1)
APPLICATION
These Unit Coolers are designed for use with R12,
R22, R134a, R404A, R407A/B/C, R507 or R502
refrigerants.
At room temperatures above 34°F and evaporating
temps no lower than 27°F the air flowing through the
coil will accomplish the defrost. Temperatures of 34°F
and below (to -40°F) require positive defrosting.
(either Electric or Hot Gas).These models require the
use of (1) Time Clock (to initiate and terminate the
defrost cycle). (2) Fan-Delay thermostat (to prevent
evaporator fans from starting up right after defrost and
blowing water on to fan blades, guards and floor) (3)
Defrost Termination Control (to prevent unnecessary
prolonged heating and steaming of the coil once all
the ice and frost has melted).
The coil must not be exposed to any abnormal atmospheric or acidic environments. This may result in
corrosion to the cabinet and possible coil failure
(leaks). (Consult manufacturer for optional baked on
phenolic protective coatings).
INSTALLATION
The installation and start-up of Unit Coolers should
only be performed by qualified refrigeration mechanics.
This equipment should be installed in accordance
with all applicable codes, ordinances and local bylaws.
INSPECTION
Inspect all equipment before unpacking for visible
signs of damage or loss. Check shipping list against
material received to ensure shipment is complete.
PIPING VIEW
SUCTION
CONNECTION
EXTERNAL
EQUALIZER
CONNECTION
IMPORTANT: Remember, you, the consignee, must
make any claim necessary against the transportation
company. Shipping damage or missing parts, when
discovered at the outset, will prevent later unnecessary and costly delays.
If damage or loss during transport is evident,
make claim to carrier, as this will be their responsibility, not the manufacturer’s.
Should carton be damaged, but damage to equipment is not obvious, a claim should be filed for “concealed damage” with the carrier.
IMPORTANT: The electrical characteristics of the unit
should be checked at this time to make sure they
correspond to those ordered and to electrical power
available at the job site.
Save all shipping papers, tags and instruction sheets
for reference by installer and owner.
LOCATION
The unit location in the room should be selected to
ensure uniform air distribution throughout the entire
space to be refrigerated. Be sure that the unit does
not draw air in, or blow directly out, through an
opened door and that the product does not obstruct
the free circulation of air. Allow a minimum of 24”
clearance at each end and behind the unit.
The Unit Coolers draw air through the coil and discharge air from the fan side.
Consideration should be given to the coil location in
order to minimize the piping run length to the condensing unit and floor drain.
TX VALVE
CONNECTION
- 9 -
Page 10
MOUNTING
Mounting brackets with 7/16” dia holes are provided
for flush mounting to the ceiling. For details refer to
dimensional data on page 6. Ensure adequate clearance (at least 24”) is provided behind the coil as well
as each side (to enable access to the electrical and
refrig. compartments).
Ensure that the ceiling is level since the drain pan
has been sloped for drainage during the defrost
cycle.
DRAIN LINE
The drain line should be run from the drain connection, sloping at least 4” per foot. A trap outside the
room will prevent warm air from entering through the
tubing. Connection should be made to proper drainage
facilities that comply with local regulations.
To prevent freeze-up when the temperature of the
refrigerated space is 32 oF or lower, the drain line
should be heated along its run inside the cold room.
The heated drain line should be insulated. It is recommended that the heater be energized at all times. A
heat input of 20 watts per foot in a 0 oF room and 30
watts per foot in a -20 oF room is usually satisfactory.
The drain pan may be mounted with the drain fitting at
either end (remove pan heater and relocate pan). See
page 6 for drain fitting details.
Ensure that the drain pan has sufficient slope for
proper drainage (prevention of ice build up/blockage in pan).
PIPING
Refrigerant line sizes are important and may not be
the same size as the coil connections. (depends on
the length of run) If in doubt, consult “Recommended
refrigerant line sizes” charts. (Engineering Manuals or
other recognized sources of information).
WIRING
Wire system in accordance with governing standards
and local codes. See data and wiring diagrams on
pages 2, 3, 4 and 5 for wiring arrangement. Electrical
wiring is to be sized in accordance with minimum
circuit ampacity rating.
For ease of identifying the proper wiring terminals, unit
wiring is colour coded and terminal block connections
are identified. When fan delay thermostats (combination fan delay and defrost termination) are installed,
on start-up, the fans do not operate until the coil
temperature is reduced to approximately
20 oF. It is normal for the fans to cycle a few times
until the room temperature is brought down. At higher
evaporating temperatures this control may not close
and therefore should be by-passed or replaced with an
adjustable type.
The defrost termination control is adjustable and
may be set at a minimumof 40 oF (fully CW) to a
maximum of 75 oF (fully CCW). Normal setting is
55 oF. This can be increased if the defrost heaters are terminated too soon (frost still left) or
decreased if terminated too long (steaming of
coil). Time clock should be set for a fail-safe time
termination of 30 minutes.
SYSTEM CHECK
Before Start-Up:
1. All wiring should be in accordance with local
codes.
2. Refrigerant lines should be properly sized.
3. Electric defrost systems should include a
liquid line solenoid valve.
4. Thorough evacuation and, dehydration has
been performed.
5. The suction, discharge, and receiver service
valves must be open.
6. The system should include a liquid line drier
mois ture indicator and suction filter.
7. Pour enough water into the drain pan to allow
a good check on drainage and seal the trap.
After Start-Up:
1. If necessary, temporarily by-pass fan delay
control to run fans until room temp is lowered.
(Run jumper wire from terminal N to F on
control circuit terminal block).
2. Check the compressor oil level to ensure the
correct oil charge.
3. Be sure that the expansion valve is properly
set to provide the correct amount of superheat.
(should be around 5 to 6 oF for 10 oF T.D.
operation).
4. Heavy moisture loads are usually encountered
when starting the system for the first time. If
the coil temperature is below freezing, this will
cause a rapid build-up of frost on the coil.
During the initial pull-down frost build-up
should be watched and the coil defrosted
manually, as required.
5. Check for proper evaporator fan blade rotation.
MAINTENANCE
The unit should be periodically inspected for any
dirt or build-up on the fin surface and cleaned if
necessary with a soft whisk or brush.
Also ensure coil and pan does not have any
excessive ice build-up from improper defrost
operation. When replacing heater elements first
remove heater slot covers and heater clips. (See
page 9 for detailed view).
10
Page 11
SERVICE PARTS LIST
FAN MOTORS - 60Hz
208-230/1/60
208-230/3/60
460/3/60
575/3/60
FAN MOTORS - 50Hz
200-220/1/50
200-220/3/50
380-400/3/50
FAN BLADES
20" 18o Pitch 4-Blade
20" 23o Pitch 4-Blade
FAN GUARDS
Moulded Throw Booster (standard)
Metal Wire (optional)
Acorn Nut
Motor Mount
Terminal Block - Fan Motor(s)
Terminal Block-Defrost Heaters
Terminal Block-Control
Defrost Control Thermostat
Face Heater Clip
MODELS
ALL
ALL
ALL
ALL
MODELS
ALL
ALL
ALL
MODELS
116P-ED
ALL (EXCEPT 116P-ED)
MODELS
ALL
ALL
ALL
MODELS
ALL
MODELS
ALL
ALL
ALL
ALL
ALL
PART #
1045032
1045033
1045034
1045035
PART #
1045032
1045033
1045034
PART #
1048568
1045115
PART #
1045089
1045091
1045138
PART #
1045031
PART #
1045017
1045018
1045017
1048610
1048609
COIL FACE HEATERS (6 REQUIRED)DRAIN PAN HEATER (1 REQUIRED)