Bacharach Portable Manometer Owner's Manual

Page 1
INSTRUCTIONS 0017-9003
MANOMETER
GAS PRESSURE GAUGE
Operation/Maintenance
Rev. 10 - May 2010
Part # 0017-7000 (Filled) Part # 0017-7008 (Unfi lled) Range: 0-15 inches of water and 38 cm. water. (Reversible Scale)
Part # 0017-7002 (Filled) Range: 0-15 in. of water and 8.5 oz./sq. in. water. (Reversible Scale)
Part # 0017-7013 (Filled). Part # 0017-7016 (Unfi lled) Range: 0-7 inches of water and 18 cm. water. (Reversible Scale)
WARRANTY
Bacharach, Inc. war rants to Buyer that at the time of deliv ery this Product will be free from defects in material and manufac ture and will conform substan­tially to Bacharach Inc.’s applica ble specifi cations. Bacharach’s liability and Buyer’s remedy under this warranty are limited to the repair or replace ment, at Bacharach’s option, of this Product or parts thereof returned to Seller at the factory of manu facture and shown to Bacharach Inc.’s reason able satisfaction to have been defective; provided that written notice of the defect shall have been given by Buyer to Bacharach Inc. within one (1) year after the date of delivery of this Product by Bacharach, Inc. For full details concerning this warranty, contact Bacharach Inc.
621 Hunt Valley Circle, New Kensington, PA 15068
Ph: 724-334-5000 • Fax: 724-334-5001 • Toll Free: 1-800-736-4666
Website: www.mybachrach.com • E-mail: help@mybacharach.com
Bacharach, Inc.
Page 2
OPERATING INSTRUCTIONS
Supporting Gauge: (Optional - Not Supplied by Bacharach) Clamp Bracket mounts on ¼ to 1-½ inch horizontal or vertical pipe. Where
Clamp Bracket is not available, Gauge can be supported by hand or propped against vertical support while reading. In all cases, Gauge should be vertical while reading for maximum accuracy (estimation by eye is suffi cient).
CONNECTING TO GAS LINE (Figure 1) Turn OFF Main Gas Cock (6) to appliance. Remove Pipe Plug (7) from control
valve or gas line between regulator and burner. (Bush Plug opening larger than ¼ inch N.P.T. to ¼ inch.) Press tapered rubber Plug (8) with projecting metal Tube (9) rmly into Plug hole with slight twisting motion. Open both Valves (10-11) one full turn. Press tapered Plug (12) over right hand (facing front) Valve (11). Open main Gas Cock (6) to appliance. Check pilot fl ame.
Where standard rubber sampling tube with tapered Plugs is not available, con­nect ¼ inch I. D. rubber tubing to gas line with hose nipple in pipe plug opening and other end of hose to Valve (11).
READING-ADJUSTING MANIFOLD PRESSURE (Figure 2) Turn burner on (after checking pilot fl ame) either by advancing thermostat 5-10°
F, or by manual turn on at control valve. Slide Scale (14) up with Scale Knob (15) until Zero Scale Arrow (16) is opposite top of low (right hand) liquid column. Read gas manifold pressure on Scale opposite top of higher (left hand) liquid col­umn (17). This is direct reading of pressure. Do not multiply this reading by 2.
To adjust pressure, remove Regulator Cap (18- Figure 1). Turn exposed screw head clockwise to increase pressure, counterclockwise to reduce pressure. Adjust manifold pressure to value recommended by local utility (service engineer) or manufacturer of burner.
2
Page 3
10
6
TO VENT
FIGURE 1
12
15
14
11
13
12
BACHARACH, INC. PITTSBURGH, PA U.S.A.
9
8
FILL LINE
TO BURNER
18
9
8
7
15
14
13
BACHARACH, INC. PITTSBURGH, PA U.S.A.
12
9
8
FILL LINE
7
6
5
4
3
INCHES WATER
2
1
0
0
5
17
4
3
INCHES WATER
2
16
1
14
0
22
15
FIGURE 2
3
Page 4
APPLICATION INSTRUCTIONS
With a given size orifi ce spud (or orifi ce setting where adjustable) the gas mani- fold pressure determines the fi ring rate in cubic feet of gas per hour. For quick, con- venient calculation of fi ring rate or orifi ce size, use BACHARACH GAS SERVICE CALCULATOR. This is a simple type of slide rule designed specifi cally for gas service personnel or installer with simple, easy to follow instructions on the face of the calculator. For every type or mixture of combustible gases, it is necessary to operate burner in a given manifold pressure range for proper burner operation. Consult local gas utility, service engineer or burner manufacturer for recommended limits of gas manifold pressure.
MAINTENANCE INSTRUCTIONS
REVERSING SCALE (0017-7002 only) (Figure 3)
Front of Scale, as shipped from factory, reads pressure in inches of water. Rear of Scale of 0017-7002 (only) is also graduated in ounces per square inch. When only occasionally reading in ounces per square inch, reverse Scale.
Close Valves (10-11). Remove Screw (19). Press Retaining Ring (20-20) out of retaining grooves. Lift off Front Cover (21). Remove Scale Knob (15), Scale Clamp Cover (22), and Scale Clamp Screw. Reverse Scale and reassemble.
ADDING INDICATING FLUID (Figure 3)
Always use Bacharach Fluid, 0017-0025. Use of other fl uids will result in error in reading pressure.
NOTE: Water will not operate in either Manometer Part# 0017-7002 or
0007-7013 (0017-7016 unfi lled) due to action of Blow Over-Seals (23).
Remove left hand Valve (10) and open Valve (11). Slide Scale to bottom of Gauge. Add suffi cient Bacharach Fluid, 0017-0025, with dropper provided, through Valve opening to raise fl uid level in both legs to Fill Line on Scale (with Gauge in vertical position).
4
Page 5
Where Gauge contains little or no fl uid, Blow-Over Seals may, in fi lling, pre- vent fl ow of fl uid from one leg to the other. When this happens, fi ll left hand leg (through Valve (10) opening) approximately to Fill Line on Scale. Install Valve and close both Valves. Invert Gauge and rap sharply with palm of hand. Slowly turn Gauge upright and loosen both Valves. Fluid should now fl ow from one leg to the other. If not, close both Valves and repeat previous steps. Then remove Valve (10), loosen Valve (11), and add suffi cient Bacharach Fluid, 0017-0025, to raise Fluid level in both legs to Fill Line on Scale.
PARTS REPLACEMENT (Figure 3)
Valve (10-11) may be screwed out of top assembly for replacement without dis­mantling top assembly. To remove Front Back Covers (21-24) at both top and bottom of Gauge, remove Screws (19-25); press Retaining Rings (20-26) out of retaining grooves and lift off Covers. This will permit replacement of Body (27), Check Valve Balls (23-23, Manometer 0017-7013 contains only one ball at bottom of right hand liquid column) and Grommet Tube (28) assembly.
CAUTION
Be sure to close Valves fi rmly before packing or transporting Gauge.
5
Page 6
PARTS LIST
BACHARACH MANOMETER (Parts Apply to All Models Unless Noted)
Part No. Description Req’d
0001-3466 Cover Screw 2 0001-6829 Scale Screw 1 0002-2715 Retaining Ring 4 0003-6351 Hose (Flexible, Black 3/16” I.D. x l/16” wall) 4.25 ft. 0005-5108 O-Ring 2 0017-7001 Body (17-7000/17-7002) (15” Range) 1 0017-0002 Body (17-7013) (7” Range) 1 0017-0003 Valve 2 0017-0004 Cover (Rear) 2 0017-0006 Cover (Front) 2 0017-0007 Precision Plastic Ball (17-7013) 1 0017-0007 Precision Plastic Ball (17-7000/17-7002) 2 0017-0008 Grommet 2 0017-0009 Connector Tube 1 0017-0011 Knurled Nut 2 0017-0013 Scale (17-7002) (15” Range and 8.5 oz/sq. in water) 1 0017-0014 Scale (17-7000) (15” Range and 38 cm water) 1 0017-0016 Scale Knob 1 0017-0018 Scale Clamp 1 0017-0025 Fluid Rell (Not Shown) 1 0017-0030 Hose Assembly complete 1 0017-0035 Manifold Plug 2 0017-0050 Scale (17-7013) (7” Range and 18 cm. water) 1
6
Page 7
17-0035
17-0011
17-0003
17-0030 Complete Hose Assembly
[ 03-6351 (4.25 FT.), 17-0035 (2), 17-0037 (1), 11-0070 (1)]
02-2715
05-5108
03-6351 (4.25
FT.
)
SEE PARTS LIST
FIGURE 4
17-0004
17-0001
OR
17-0002
17-0011
17-0004
17-0007
17-0009
7
17-0006
01-6829
01-3466
17-0007
17-0013
OR
17-0014
OR
17-0050
17-0008
17-0035
SEE PARTS LIST
17-0018
17-0016
17-0006
01-3466
02-2715
Loading...