Bacharach IAM-100 Quick Start Guide

INTEGRATED AREA MONITOR
and CONTROLLER
INSTALLATION GUIDE
P/N: 6209-9002
Revision 0
January 13, 2016
IAM-100
Controller
CAUTION: DO NOT MOUNT the
IAM-100 or controller in an area
that may contain flammable liquids or vapors. Operaon of electrical equipment in such an area cons-
tutes a safety hazard.
WARNING: Strictly follow the instrucons in the User Manuals (part number 6209-9000 and 6709-
9000) available at www.MyBacharach.com.
The IAM-100 is an ideal soluon for gas detecon in the following occupied spaces with variable refrigerant flow (VRF) or variable refrigerant volume (VRV)
systems:
hotel rooms
• storage facilies
conference rooms
theaters
apartment blocks
airports
• office buildings
light industrial spaces
• air condioned spaces
large systems requiring many sensors.
The instrument is powered by 110 VAC/60 HZ or 220 VAC/50 Hz; 11 W Max.
2: SAFETY INSTRUCTIONS
USER MANUAL: Before using this equipment,
carefully read and strictly follow the User Manuals (part numbers 6209-9000 and 6709-9000). The user
must fully understand and strictly observe the
instrucons. Use the equipment only for the purposes listed and under the condions specified in
that document.
CODE COMPLIANCE: Comply with all local and naonal laws, rules and regulaons associated with
this equipment.
GENUINE PARTS: Use only genuine Bacharach spare parts and accessories, otherwise proper funconing
of the equipment may be impaired. TECHNICIAN USE ONLY: This unit must be installed
by a suitably qualified technician who will install this unit in accordance with these instrucons and the standards in their parcular industry/country. Opera­tors of the unit should be aware of the regulaons and standards in their industry/country for the operaon of this unit. These notes are only intended
as a guide and the manufacturer bears no responsi-
bility for the installaon or operaon of this unit.
Failure to install and operate the unit in accordance
with these instrucons and with industry guidelines
may cause serious injury including death and the
manufacturer will not be held responsible in this
regard. SAFE MOUNTING: This monitor must be connected
by a marked, suitably located and easily reached
switch or circuit-breaker as means of disconnecon.
IMPORTANT: For compliance with EN378, at least one detector shall
be installed in each occupied space
being considered and the locaon
of detectors shall be chosen in
relaon to the refrigerant and they shall be located where the refriger­ant from the leak will collect. In
this case refrigerants are heavier than air and detectors should have
their sensors mounted low, e.g., at
less than bed height in the case of a hotel or other similar Category Class A space. Ceiling voids or other voids if not sealed are part of the occupied space.
CAUTION: Monitoring ceiling voids
in a hotel room would not strictly comply with EN378.
IMPORTANT: Mount in-room sen­sors at less than the normal heights of the occupants. E.g., in a hotel room this is less than bed height
(between 100 and 300 mm [4 and 12 inches] off the floor). Avoid dras and heat sources (liek radia­tors), and avoid sources of steam.
WARNING: Strictly follow the instrucons in the User Manuals (part number 6209-9000 and 6709-
9000).
3: WEIGHTS AND DIMENSIONS
IAM-100 Housings Specifications
Standard Size: 147x88x62 mm [5.8x3.5x2.4 in]
Weight: 633 g [1.4 lbs]
Faceplate (Brushed Steel)
Size: 86x86 mm [3.4x3.4 in] Weight: 86 g [0.2 lbs]
4: MOUNTING
ENVIRONMENTAL CONSIDERATIONS: Carefully
consider the full range of environmental condions to which the instruments will be exposed.
TARGET GAS CONSIDERATIONS: The physical data of the gas or vapor to be detected must be observed.
APPLICATION CONSIDERATIONS: The specifics of the applicaon (for example, possible leaks, air movement/dra, etc.) must be observed.
ACCESSIBILITY CONSIDERATIONS: The degree of accessibility required for maintenance purposes must be granted.
ACCESSORY CONSIDERATIONS: The types of oponal and accessory equipment that will be used with the
system must be kept in mind. ELECTRONIC CONSIDERATIONS: The system contains
sensive electronic components that can be easily
damaged. Do not touch nor disturb any of these components.
Mount the IAM-100 and Controller according to the
above consideraons, product dimensions (see Secon
3), maximum wiring lengths (see Secon 5), and the corresponding mounng dimensions shown in the illustraons that follow.
IAM-100
120.6 ± 0.8 mm [4.75 ± 0.03 in]
11.1 mm [0.4 in]
[1.3 in]
33.4 mm
20.3 mm
[0.8 in]
63.5 mm [2.5 in ]
D = 11.1 mm
[0.4 in]
2 places
130.250 mm [5.1 in]
12.1 mm
[0.5 in]
11.1 mm [0.4 in]
12.1 mm
[0.5 in]
12.1 mm
[0.5 in]
11.1 mm [0.4 in]
11.1 mm [0.4 in]
63.5 mm [2.5 in ]
12.1 mm [0.5 in]
22.9 mm x 11.1 mm
13 mm x 7.6 mm
[0.5 in x 0.3 in]
2 places
16.5 mm x 11.1 mm [0.7 in x 0.4 in]
2 places
[0.9 in x 0.4 in]
20.3 mm
[0.8 in]
260.50 mm [10.3 in]
86.9 mm [3.4 in]
1: OPERATING AREA AND CONDITIONS
The IAM-100 is a system that combines sensor and monitoring features in an integrated unit. It is a stand-alone system used to detect gases in an area,
room, zone, airspace or airflow. The IAM-100 can be expanded into large gas detecon systems using the oponal IAM controller. Up to 16 IAM-100s can connect to an IAM controller. The controller shows
each other enabling the construcon of large gas
detector systems.
AIR CONDITIONER
AIR CONDITIONER
240.50 mm [9.5 in]
224.70 mm [8.8 in]
O5.10mm
[0.20 in]
CONTROLLER
242.50 mm [9.5 in]
O4.60mm [0.18 in]
Mounng Holes
5: WIRING
NOTE: To make wiring connecons,
you must first open the the IAM-100 by removing the two front cover screws. Remove the metal faceplate and locate the connecon termi-
nals.
Refer to the User Manuals (part numbers 6209-
9000 and 6709-9000)
www.MyBacharach.com for detailed wiring
instrucons.
NOTE: The maximum wire size into terminal blocks is 1.5 mm2 [16 AWG].
WARNING: The main power supply
cable should be of an approved type
based on local regulaons. Connecon to the main power supply must be made
via an approved, readily-accessible,
switched and fused plug and socket (or as per local wiring regulaons) wihch should be within 10 feet (3 meters) of
the control unit.
SHIELD WIRE WARNING: Connect
the shield of the power wires to the
earth ground of the central control system (e.g., chassis, ground bus bar,
etc.).
1: Strip 0.2 to 0.25 inches (5 to 7 mm) of wiring insulaon. 2: Connect the wires as indicated.
NOTE: Aer wiring is completed,
carefully re-assemble the enclosure and
its components, nong the keyed
ribbon cable and sensor connectors.
Aer installaon is complete, be sure to refer to the User Manual (part number
6109-9000)
www.MyBacharach.com for detailed
instrucons on registering the sensors and configuring the IAM-100 for proper operaon.
World Headquarters
621 Hunt Valley Circle
New Kensington, PA 15068 USA
Phone: 724-334-5000 • Fax: 724-334-5001
Toll Free: 1-800-736-4666
Website: www.MyBacharach.com
E-mail: help@MyBacharach.com
114A Georges Street Lower
Dun Laoghaire • Co Dublin • Ireland
Phone: +353 1 284 6388 • Fax: +353 1 284 6389
available at
available at
No Volt Contacts
5VDC, 10mA Min.
24VDC, 1A Max.
Remote
on o
5: Remote Reset from Panel On: Enabled Off: Disabled 1: Delay Seng 1 (See Chart) 2: Delay Seng 2 (See Chart) 3: Latch Seng On: Manual Reset Off: Automac Reset 4: Horn Seng On: Enabled Off: Disabled
Reset Buon Access Hole
Access
Screw
Sample
Label
Relay#1Relay
N/C
N/O
Relay Contacts
0V
To
Panel
Jumper Sengs
N/O
COM
5 1 2 3 4
CN6
0.21 mm2 [24 AWG ] Cable 500 m [1640  ] Max (110 V System) 300 m [984 ] Max (220 V System)
#2
COM
Panel Output
P1 P2
N/C
120/230 VAC
L E N
Main Power
Connectors
VS VREF
for Audible Alarm and Relays
Vent Holes
(Not Shown)
Vent Holes
Serial Number: T012345B 27/04/2012
Gas: R410A Range: 1000 PPM
Standby Voltage: 0.3V
MODEL:
Alarm Voltage: 3.05V
IAM
Voltage: 110V AC 50/60Hz
IAM Printed Circuit Board
(Rear View)
Delay Jumpers 1 and 2
1
2
1
2
1
2
1
2
0 Minutes
(No Delay)
5 Minute
Delay
10 Minute
Delay
15 Minute
Delay
Power
Alarm LED
LED
15
Access
Screw
Mute
Buon
Panel Interconnect Output
0.21 mm
2
[24 AWG] Cable 500 m [1640 ] Max (110 V System) 300 m [984 ] Max (220 V System)
Enclosure
Push Buon
Mutes
Switch
Horn
Deacvates Horn
B
Key Switch
e
r
i
W
k
c
a
l
Red Wire
Horn (9 VDC, 100 mA Max)
Main Power Note that the cable should
have strain relief fied. Main power should be externally switched and fused. 5A rang is recommended
Key Switch Not Shown (Deacvates Horn)
Power
LED
Jumper Sengs
HD1: Not Used (Do Not Remove Link) HD2: Not Used HD3: Remote Reset:
Enabled
(Link Fied)
(Link Removed)
Disabled
NOTE: Remote Reset MUST be disabled on Master Panel.
N/O
COM
N/C
N/O
COM
N/C
Relay Contacts
REMOTE
PANEL
LD16 LD15
LD14 LD13
LD12
SW1
LD11 LD10
HD3 HD2 HD1
-
+
CN19
CN17
L
+
E
N
LD9
LD8
LD7 LD6 LD5
LD4 LD3
LD2
LD1
LD17
Transformer
Fuse
16 Channel
IAM Controller
Cable Glands (12 Places)
CN7 CN8 CN9 CN10 CN11 CN12 CN13 CN14 CN15 CN16
CN6
Input Connectors CN1 through CN16
CN1 CN2 CN3 CN4 CN5
Push Buon Not Shown (Mutes Horn)
Alarm
LEDs (16 Channels)
Acess
Screws (2 Places)
HD3 HD2 HD1
Unconnected inputs should
be disabled by shorng with
a 2.2 K resistor.
2.2 K
[24 AWG] Cable
2
500 m [1640 ] Max (110 V System)
To IAM-100 Sensors or Panel
Interconnect Outputs using
300 m [984 ] Max (220 V System)
0.21 mm
Loading...