INTEGRATED AREA MONITOR
and CONTROLLER
INSTALLATION GUIDE
P/N: 6209-9002
Revision 0
January 13, 2016
IAM-100
Controller
CAUTION: DO NOT MOUNT the
IAM-100 or controller in an area
that may contain flammable liquids
or vapors. Operaon of electrical
equipment in such an area cons-
tutes a safety hazard.
WARNING: Strictly follow the
instrucons in the User Manuals
(part number 6209-9000 and 6709-
9000) available at
www.MyBacharach.com.
The IAM-100 is an ideal soluon for gas detecon in
the following occupied spaces with variable refrigerant
flow (VRF) or variable refrigerant volume (VRV)
systems:
• hotel rooms
• storage facilies
• conference rooms
• theaters
• apartment blocks
• airports
• office buildings
• light industrial spaces
• air condioned spaces
• large systems requiring many sensors.
The instrument is powered by 110 VAC/60 HZ or
220 VAC/50 Hz; 11 W Max.
2: SAFETY INSTRUCTIONS
USER MANUAL: Before using this equipment,
carefully read and strictly follow the User Manuals
(part numbers 6209-9000 and 6709-9000). The user
must fully understand and strictly observe the
instrucons. Use the equipment only for the
purposes listed and under the condions specified in
that document.
CODE COMPLIANCE: Comply with all local and
naonal laws, rules and regulaons associated with
this equipment.
GENUINE PARTS: Use only genuine Bacharach spare
parts and accessories, otherwise proper funconing
of the equipment may be impaired.
TECHNICIAN USE ONLY: This unit must be installed
by a suitably qualified technician who will install this
unit in accordance with these instrucons and the
standards in their parcular industry/country. Operators of the unit should be aware of the regulaons
and standards in their industry/country for the
operaon of this unit. These notes are only intended
as a guide and the manufacturer bears no responsi-
bility for the installaon or operaon of this unit.
Failure to install and operate the unit in accordance
with these instrucons and with industry guidelines
may cause serious injury including death and the
manufacturer will not be held responsible in this
regard.
SAFE MOUNTING: This monitor must be connected
by a marked, suitably located and easily reached
switch or circuit-breaker as means of disconnecon.
IMPORTANT: For compliance with
EN378, at least one detector shall
be installed in each occupied space
being considered and the locaon
of detectors shall be chosen in
relaon to the refrigerant and they
shall be located where the refrigerant from the leak will collect. In
this case refrigerants are heavier
than air and detectors should have
their sensors mounted low, e.g., at
less than bed height in the case of
a hotel or other similar Category
Class A space. Ceiling voids or
other voids if not sealed are part of
the occupied space.
CAUTION: Monitoring ceiling voids
in a hotel room would not strictly
comply with EN378.
IMPORTANT: Mount in-room sensors at less than the normal heights
of the occupants. E.g., in a hotel
room this is less than bed height
(between 100 and 300 mm [4 and
12 inches] off the floor). Avoid
dras and heat sources (liek radiators), and avoid sources of steam.
WARNING: Strictly follow the
instrucons in the User Manuals
(part number 6209-9000 and 6709-
9000).
3: WEIGHTS AND DIMENSIONS
IAM-100 Housings Specifications
Standard Size: 147x88x62 mm [5.8x3.5x2.4 in]
Weight: 633 g [1.4 lbs]
Faceplate
(Brushed Steel)
Size: 86x86 mm [3.4x3.4 in]
Weight: 86 g [0.2 lbs]
4: MOUNTING
ENVIRONMENTAL CONSIDERATIONS: Carefully
consider the full range of environmental condions to
which the instruments will be exposed.
TARGET GAS CONSIDERATIONS: The physical data of
the gas or vapor to be detected must be observed.
APPLICATION CONSIDERATIONS: The specifics of the
applicaon (for example, possible leaks, air
movement/dra, etc.) must be observed.
ACCESSIBILITY CONSIDERATIONS: The degree of
accessibility required for maintenance purposes must
be granted.
ACCESSORY CONSIDERATIONS: The types of oponal
and accessory equipment that will be used with the
system must be kept in mind.
ELECTRONIC CONSIDERATIONS: The system contains
sensive electronic components that can be easily
damaged. Do not touch nor disturb any of these
components.
Mount the IAM-100 and Controller according to the
above consideraons, product dimensions (see Secon
3), maximum wiring lengths (see Secon 5), and the
corresponding mounng dimensions shown in the
illustraons that follow.
IAM-100
120.6 ± 0.8 mm [4.75 ± 0.03 in]
11.1 mm
[0.4 in]
[1.3 in]
33.4 mm
20.3 mm
[0.8 in]
63.5 mm [2.5 in ]
D = 11.1 mm
[0.4 in]
2 places
130.250 mm [5.1 in]
12.1 mm
[0.5 in]
11.1 mm
[0.4 in]
12.1 mm
[0.5 in]
12.1 mm
[0.5 in]
11.1 mm
[0.4 in]
11.1 mm
[0.4 in]
63.5 mm [2.5 in ]
12.1 mm
[0.5 in]
22.9 mm x 11.1 mm
13 mm x 7.6 mm
[0.5 in x 0.3 in]
2 places
16.5 mm x 11.1 mm
[0.7 in x 0.4 in]
2 places
[0.9 in x 0.4 in]
20.3 mm
[0.8 in]
260.50 mm [10.3 in]
86.9 mm [3.4 in]
1: OPERATING AREA AND CONDITIONS
The IAM-100 is a system that combines sensor and
monitoring features in an integrated unit. It is a
stand-alone system used to detect gases in an area,
room, zone, airspace or airflow. The IAM-100 can be
expanded into large gas detecon systems using the
oponal IAM controller. Up to 16 IAM-100s can
connect to an IAM controller. The controller shows
any sensor in alarm and has relays for control
purposes. These controllers can be connected to
each other enabling the construcon of large gas
detector systems.
AIR CONDITIONER
AIR CONDITIONER
240.50 mm [9.5 in]
224.70 mm [8.8 in]
O5.10mm
[0.20 in]
CONTROLLER
242.50 mm [9.5 in]
O4.60mm [0.18 in]
Mounng
Holes
5: WIRING
NOTE: To make wiring connecons,
you must first open the the IAM-100
by removing the two front cover
screws. Remove the metal faceplate
and locate the connecon termi-
nals.
Refer to the User Manuals (part numbers 6209-
9000 and 6709-9000)
www.MyBacharach.com for detailed wiring
instrucons.
NOTE: The maximum wire size into
terminal blocks is 1.5 mm2 [16
AWG].
WARNING: The main power supply
cable should be of an approved type
based on local regulaons. Connecon
to the main power supply must be made
via an approved, readily-accessible,
switched and fused plug and socket (or
as per local wiring regulaons) wihch
should be within 10 feet (3 meters) of
the control unit.
SHIELD WIRE WARNING: Connect
the shield of the power wires to the
earth ground of the central control
system (e.g., chassis, ground bus bar,
etc.).
1: Strip 0.2 to 0.25 inches (5 to 7 mm)
of wiring insulaon.
2: Connect the wires as indicated.
NOTE: Aer wiring is completed,
carefully re-assemble the enclosure and
its components, nong the keyed
ribbon cable and sensor connectors.
Aer installaon is complete, be sure to
refer to the User Manual (part number
6109-9000)
www.MyBacharach.com for detailed
instrucons on registering the sensors
and configuring the IAM-100 for proper
operaon.
World Headquarters
621 Hunt Valley Circle
New Kensington, PA 15068 USA
Phone: 724-334-5000 • Fax: 724-334-5001
Toll Free: 1-800-736-4666
Website: www.MyBacharach.com
E-mail: help@MyBacharach.com
114A Georges Street Lower
Dun Laoghaire • Co Dublin • Ireland
Phone: +353 1 284 6388 • Fax: +353 1 284 6389
available at
available at
No Volt Contacts
5VDC, 10mA Min.
24VDC, 1A Max.
Remote
on off
5: Remote Reset from Panel
On: Enabled
Off: Disabled
1: Delay Seng 1 (See Chart)
2: Delay Seng 2 (See Chart)
3: Latch Seng
On: Manual Reset
Off: Automac Reset
4: Horn Seng
On: Enabled
Off: Disabled
Reset Buon
Access Hole
Access
Screw
Sample
Label
Relay#1Relay
N/C
N/O
Relay Contacts
0V
To
Panel
Jumper Sengs
N/O
COM
5
1
2
3
4
CN6
0.21 mm2 [24 AWG ] Cable
500 m [1640 ] Max (110 V System)
300 m [984 ] Max (220 V System)
#2
COM
Panel
Output
P1 P2
N/C
120/230 VAC
L E N
Main Power
Connectors
VS VREF
for Audible Alarm and Relays
Vent Holes
(Not Shown)
Vent Holes
Serial Number: T012345B 27/04/2012
Gas: R410A Range: 1000 PPM
Standby Voltage: 0.3V
MODEL:
Alarm Voltage: 3.05V
IAM
Voltage: 110V AC 50/60Hz
IAM Printed Circuit Board
(Rear View)
Delay Jumpers 1 and 2
1
2
1
2
1
2
1
2
0 Minutes
(No Delay)
5 Minute
Delay
10 Minute
Delay
15 Minute
Delay
Power
Alarm
LED
LED
15
Access
Screw
Mute
Buon
Panel Interconnect Output
0.21 mm
2
[24 AWG] Cable
500 m [1640 ] Max
(110 V System)
300 m [984 ] Max
(220 V System)
Enclosure
Push
Buon
Mutes
Switch
Horn
Deacvates
Horn
B
Key
Switch
e
r
i
W
k
c
a
l
Red Wire
Horn
(9 VDC, 100 mA Max)
Main Power
Note that the cable should
have strain relief fied.
Main power should be
externally switched and fused.
5A rang is recommended
Key Switch Not Shown
(Deacvates Horn)
Power
LED
Jumper Sengs
HD1: Not Used (Do Not Remove Link)
HD2: Not Used
HD3: Remote Reset:
Enabled
(Link Fied)
(Link Removed)
Disabled
NOTE: Remote Reset MUST be
disabled on Master Panel.
N/O
COM
N/C
N/O
COM
N/C
Relay Contacts
REMOTE
PANEL
LD16
LD15
LD14
LD13
LD12
SW1
LD11
LD10
HD3
HD2
HD1
-
+
CN19
CN17
L
+
E
N
LD9
LD8
LD7
LD6
LD5
LD4
LD3
LD2
LD1
LD17
Transformer
Fuse
16 Channel
IAM Controller
Cable Glands (12 Places)
CN7 CN8 CN9 CN10 CN11 CN12 CN13 CN14 CN15 CN16
CN6
Input Connectors CN1 through CN16
CN1 CN2 CN3 CN4 CN5
Push Buon
Not Shown
(Mutes Horn)
Alarm
LEDs (16
Channels)
Acess
Screws
(2 Places)
HD3
HD2
HD1
�
Unconnected inputs should
be disabled by shorng with
a 2.2 K resistor.
2.2 K�
[24 AWG] Cable
2
500 m [1640 ] Max (110 V System)
To IAM-100 Sensors or Panel
Interconnect Outputs using
300 m [984 ] Max (220 V System)
0.21 mm