This manualprovides
Installation&Operatinginstructionsfor
PAWSVENTILATOR
CONTROLS
For Models:
P30, P31, P32, P33, P34,
P35, P36, P37, P44, P46 and P47
NOTIFY CARRIER OF DAMAGE AT ONCE.
It is the responsibility of the consignee to inspect the
container upon receipt of same and to determine
the possibility of any damage, including concealed
damage. Avtec suggests that if you are suspicious of
damage to make a notation on the delivery receipt.
It will be the responsibility of the consignee to file a
claim with the carrier. We recommend that you do so
at once.
Manufacture Service/Questions 888-994-7636.
Information contained in this document is known to be
and accurate at the time of printing/creation. Unified Brands
recommends referencing our product line websites,
unifiedbrands.net, for the most updated product information and
specifications.
current
1055 Mendell Davis Drive
Jackson, MS 39272
888-994-7636, fax 888-864-7636
P/N PP MNL0805 Revised 10/08
unifiedbrands.net
Page 2
TABLEOFCONTENTS
I. GENERALDESCRIPTION..........................................................................................................1-2
A. ModelNumberGuide.......................................................................................................1
VI. MAINTAINENCE ..................................................................................................................................22-23
A. Detergent Dispensing System .......................................................................................... 22
B. Plumbing.....................................................................................................................
VII WARRANTEE .................................................................................................................................... 23
Onepanelwillcontroloneormorefansif
operatedsimultaneously.
operateupto50linearfeetofventilatorwitha
singlewashoutput.Sequentialwashmodels
includeupto8washoutputsandcanoperate
up to400linearfeetofventilator.
Fanandwashoperationmaybeinitiated
manually or programmed to occur at a user
specified time. The operation of the wash
output(s) may be set to a value from 2 to 10
minutes.
The PAWS panel may be provided as a wall
mounted unit or integrated into an AVTEC
Energy Distribution System (EDS).
Underwriters Laboratories Inc. (UL) list the
PAWS panel as:
“SUBASSEMBLY FOR EXHAUST HOOD
WITH EXHAUST DAMPER, for USE ONLY
WITH AVTEC LABELED HOOD
ASSEMBLY FOR EXHAUST HOOD WITH
EXHAUST DAMPER”
“SUBASSEMBLY FOR EXHAUST HOOD
WITHOUT DAMPER, for USE ONLY WITH
AVTEC LABELED HOOD ASSEMBLY
FOR EXHAUST HOOD WITHOUT
EXHAUST DAMPER”
All support plumbing and electrical components
for the PAWS panel are located within the panel
or the EDS. Peripheral plumbing components
may be shipped loose for installation in the field
by appropriate trades.
A. Model Number Guide
The PAWS control panels are available with
a wide variety of options specific to each
model number.
To determine the model number of your
panel, press and hold the (UP) (DOWN)
arrows at the same time. The top display
line will read:
All items listed for model P30.
Fuel Reset with 120-second delay
for latching Gas Solenoid output.
120vac, 600va, Battery Back Up.
Provides 120 seconds of operating
power for the gas solenoid output
and, 4-1/2 hours of power for the
operation of the PAWS panel.
P32—Single Wash Output
P36—2 to 3 Wash Outputs
P46—4 to 8 Wash Outputs
4. Models P33, P37 and P47
Features Include:
All items listed for model P30.
120vac, 600va, Battery Back Up.
Provides 5 hours of power for the
operation of the PAWS panel.
P33—Single Wash Output
P37—2 to 3 Wash Outputs
Wash Output Quantity
1
Page 5
II. Installation
P47—4to8WashOutputs
For specific operationofthefeatureslisted
above refer tothe“SequenceofOperation”
section of thismanual.
Control panel dimensionsandconnectiondetails
are shown on theenclosedshopdrawing.
Panels may be surfacemounted,partially
recessed or fullyrecessed.Typicallythebottom
edge of the panelismounted36”abovethe
floor.
A. Wall Attachment
1. SurfaceMounted
Drill four
panel plumbing compartment.
mounting holes should be near each
corner of the box to provide adequate
support. Be careful not to damage any
components.
electrical compartment since component
damage will result. Bolt to wall with
anchor bolts or other acceptable means.
Weight of control panel varies from 90
lbs. to 200 lbs. See Figure II.A.1
[4]mountingholesinPAWS
The
Do not drill in the
Figure II.A.2
3. Energy Distribution System
The PAWS panel may be provided as
an integral part of an AVTEC EDS
(Energy Distribution System). All
components are pre-mounted.
B. Electrical Interconnection
Project specific wiring schematics are
provided in the project installation package.
General Internal Wiring Diagrams
model) and a Field Interconnection
schematic are included in the Appendix of
this manual.
connections are listed below.
1. Control Panel Power Supply
Provide 120vac, 15amps, single-phase
power. Connect the hot (L1) to terminal
“H”, the neutral (L2) to terminal “N”, and
the ground to terminal “G”.
See Figure II.B.1
Individual field inter-
(by
Figure II.A.1
2. Recessed
Cut hole in wall 1/2" greater than overall
dimensions of control box
shop drawing]. Spacers or support
angles may be necessary to provide
proper support. It is recommended that
panel be bolted to wall as described for
surface mounted above. A stainless
steel trim angle is provided and may be
set in place with construction adhesive.
See Figure. II.A.2
[shown on
Figure II.B.1
2. Vent Light Switch Power Supply
(optional feature)
Provide 120vac, 20 amps, single-phase
circuit. Connect the hot (L1) to line side
of the switch. Connect the load side of
the switch to the black wire in the hood
connection box. Connect the neutral and
ground wires to the corresponding
2
Page 6
connectionsinthehoodconnectionbox.SeeFigureII.B.2
FigureII.B.2
3.FanStarter(s)
ThecontrolvoltageforthefanstartersmaybeprovidedfromthePAWSpanel
(120vac) or the outputs may be
configured as volt free normally open
contacts.
a) If the fan starters are not pre-wired
and require 120vac for the control
coils connect as shown in Figure
II.B.3.a,
PAWS PANEL TO FAN
STARTERS”.
b) If the fan starter package is pre-
wired and requires connection to
normally open volt-free
contacts connect as shown in
Figure II.B.3.b “FAN STARTER
CONTROL VOLTAGE THROUGH
VOLT FREE N.O. CONTACTS”.
“120VAC OUTPUT FROM
Figure II.B.3.a
Figure II.B.3.b
(dry)
3
4.VentExhaustDamper Switch
(optionalfeature)Thehoodsconnected to the panel may
includeexhaustdampers with switching
devicesthatindicate when the damper
hascloseddue to an extreme
temperaturerise.There are three types
ofexhaustdamperthat may connect to
thePAWSpanel,Resetable ElectroMechanical,Fusible Link with Thermoswitch,andFusible Link with damper
switch.
a)ResetableElectro-Mechanical
Damper
Theconnection is from the PAWS
panel to the hood connection box.
Terminal #7 provides power to the
common terminal on the relay.
PAWS model series P3** provide
120vac to the common terminal on
the relay. PAWS model series P4**
provide
terminal on the relay.
Terminal #8
relay normally open contact. The
source voltage coming from terminal
#7
through this contact.
Terminal #9 provides 120vac to the
Thermo-switch. When the Thermoswitch closes 120vac is passed to
the damper solenoid and relay coil.
Terminal
neutral terminals on the damper
solenoid and relay coil. See Figure
II.B.4.a.
Figure II.B.4.a
b) Fusible Link Damper with
Thermo-switch
The connection is from the PAWS
panel to the hood connection box.
24vdc to the common
is connected to the
dictates the switched power
“N” is connected to the
Page 7
Terminal#7providespowertothe
commonterminalontherelay.
PAWSmodelseriesP3**provide
120vactothecommonterminalon
the relay.PAWSmodelseriesP4**
provide
terminalontherelay.
Terminal#9provides120vactothe
Thermo-switch.WhentheThermo-
switch closes 120vac is passed to
the relay coil.
Terminal “N” is connected to the
neutral terminal on the relay coil.
See Figure II.B.4.b.
Figure II.B.4.b
isconnectedtothe
FigureII.B.4.c
5.WaterSolenoid
Thewaterwashsolenoidisinstalled and
pre-wired in panels that have a single
wash output.
Water wash solenoids for multiple wash
output panels are pre-mounted on the
hood. The installing electrician must
provide a (2) wire circuit from the panel
terminal strip to the each solenoid valve.
Terminals #22 through #29 are provided
for each wash output
Figure II.B.5.
(1 to
8). See
c) Fusible Link Damper with Damper
Switch
The connection is from the PAWS
panel to the hood connection box.
Terminal #7 provides power to the
normally open contact on the
damper switch. PAWS model series
P3** provide 120vac to the normally
open contact. PAWS model series
P4** provide 24vdc to the normally
open contact.
Terminal #8
common terminal on the damper
switch. The source voltage coming
from terminal
switched power through this
contact. See Figure II.B.4.c
is connected to the
#7
dictates the
4
Figure II.B.5
6. Fire Pull Switch (optional feature)
The Fire Pull Switch is an optional
feature that allows the user to activate
the PAWS Fire Condition manually. The
pull switch may be panel mounted and
pre-wired, or installed in a remote
location (typically at the egress of the
kitchen). The normally closed switch is
connected to Terminals # 2 and 3. The
panel is shipped with a jumper between
these terminals. The jumper is removed
and discarded once the Fire Pull Switch
is connected. Terminal
power to the common terminal on the
The Detergent Pump is installed and
pre-wired in panels that have an integral
Detergent Tank.
Some applications use a remote
Detergent dispensing cabinet with a
large volume tank (5 gallons) or drum.
In these applications the pump is
provided in a stainless steel cabinet.
The installing electrician must provide a
(3) wire circuit from the panel terminal
strip to the Detergent Pump. Terminal
#9 is connected to the normally open
contact on the pump prime switch,
terminal 21 is connected to the normally
closed contact on the prime switch. The
neutral lead from the pump motor is
connected to the “N” terminal strip. See
Figure II.B.7.
120vactothecommon
Figure II.B.6
Figure II.B.7
8.DetergentProbe
TheDetergentProbe is installed and
pre-wiredinpanelsthat have an integral
DetergentTank.
Someapplications use a remote
Detergentdispensing cabinet with a
largevolumetank(5 gallons) or drum.
Intheseapplications the probe is
connectedtoaterminal strip in the
DetergentPumpsteel cabinet. The
installingelectricianmust provide a (2)
wirecircuitfromthepanel terminal strip
totheDetergentProbe. See Figure
II.B.8.
Figure II.B.8
The probe should be installed in the
detergent container so that it does not
protrude below the top of the detergent
pump inlet strainer. This is intended to
prevent the pump from losing its prime
and will advise when the tank needs to
be refilled. The probe rods may be cut
to facilitate a neat and effective
installation. See Figure II.B.8.a.
Figure II.B.8.a
5
Page 9
9. Gas ShutOffSolenoid(optional
feature)
An outputmaybeprovidedtopowera
normallyclosedGasSolenoidValve.
The installingelectricianmustprovidea
(2) wirecircuitfromthepanelterminal
strip to theGasSolenoid.Terminal#14
(120vachot)andterminal“N”are
connectedtothesolenoidcoil.
Additionalvalvesmaybewiredin
parallel.SeeFigureII.B.9.
Figure II.B.9
11.KillSwitch(optionalfeature)
TheKillSwitchisanoptional feature
thatallowstheusertostopthe flow of
gas
(forunitssuppliedwitha gas
solenoidoutput)andelectricity to the
cookinglineservedbythepanel. Hood
operationeffected.TheKillswitchmaybe panel
mountedandpre-wired,orinstalled in a
remotelocation.TheKillSwitch is a
momentary,normallyopencontact set
andisconnectedtoTerminals# 1 and
6.Terminal#6providespowertothe Kill
Switch.PAWSmodelseries P3**
provide120vacatTerminal#6,PAWS
model series P4** provide 24vdc at
Terminal #6. If more than one Kill Switch
is required additional switches are wired
in parallel. See Figure II.B.11.
(fanand/orwash)is not
10. Electric Shunt Trip Output (optional
connection)
The PAWS panel includes an output
that will energize (120vac) when the
PAWS panel is in a Fire Condition. This
output may be connected to a shunt trip
coil on the main breaker serving the
cooking line.
The installing electrician must provide a
(2) wire circuit from the panel terminal
strip (terminal #15
terminal “N”) to the Electric Shunt Trip
coil. See Figure II.B.10.
Figure II.B.10
(120vac hot) and
Figure II.B.11
12. Hood Fire System Inter-Connection
The Hood Fire Suppression system (for
example, ANSUL R102) must be
electrically connected to the PAWS
panel. When the hood fire system
discharges the PAWS panel will
respond with a Fire Condition (Exhaust
Fan “ON”, Supply Fan “OFF”, Wash
“ON”, Detergent Pump “OFF” Fuel to the
Cooking Equipment “OFF”).
The installing electrician must provide a
(2) wire circuit from the panel terminal
strip (terminal #4 and terminal #5) to a
normally closed (when armed—opens
on discharge) contact set on the hood
Fire Suppression system.
Terminal #5 provides power to the Fire
System Switch. PAWS model series
P3** provide 120vac at Terminal #5,
PAWS model series P4** provide 24vdc
at Terminal #5. See Figure II.B.12.
6
Page 10
FigureII.B.12
C. PlumbingInterconnection
Aprojectspecificdrawingisprovidedintheprojectinstallationpackagethatlistsspecificconnectionsrequired,andcomponentsthat
are supplied by AVTEC.
Individual field interconnections are listed
below.
1. Hot Water Supply
140οF (minimum) hot water, 20-40 psig
is needed to properly clean the extractor
chamber. The Hot Water Supply is
connected to the control panel inlet. A
pressure reducing valve may be
required if water pressure exceeds 60
psig. Refer to your project drawing for
the pipe size required. Typical water
consumption at 30 psig is 1.2 gallons
per minute per linear foot of hood. For
example a
require 12 gallons per minute. Refer to
Figure II.C.1.
2. Hot Water from Panel to Hood Inlets
Hot water piping is required from the
panel outlet to a vacuum breaker-check
valve-detergent injection tee assembly.
NOTE:
Panels with a single wash output
(water solenoid mounted in the
panel) require an atmospheric
vacuum breaker, mounted at least
6” above the hood inlet.
Panels with multiple wash outputs
(water solenoids mounted on hood
sections) require a pressure type
vacuum breaker, mounted at least
18” above the hood inlet.
10’-0” long hood would
Additionalpipingis required from the
vacuumbreaker, check valve, and
detergentinjection tee assembly to the
Hoodwaterinlet(s). AVTEC will prepipemultiplehoods to a single inlet
whenspecified. Refer to your project
drawingforhood inlet connection
requirements.Referto Figure II.C.1.
3.ColdWaterMistSupply (optional
feature)
Whenspecified,the Cold Water Mist
featureisprovidedto add an additional
levelofgreaseextraction. The Cold
watermistoperates whenever the
ExhaustFanisrunning.
The cold water supply (20-30 psig) is
connected to the control panel inlet. A
pressure reducing valve may be
required if water pressure exceeds 30
psig. Refer to your project drawing for
the pipe size required. Typical water
consumption at 30 psig is 0.6 gallons
per minute per linear foot of hood. For
example, a 10’-0” long hood would
require 6 gallons per minute. The Cold
Water Mist manifold is constructed the
same as a single wash Hot Water
manifold. Refer to Figure II.C.1.
4. Cold Water from Panel to Hood Inlet
Cold water piping is required from the
panel outlet to a vacuum breaker-check
valve assembly.
NOTE:
An atmospheric vacuum breaker,
mounted at least 6” above the hood
cold water inlet is required.
The vacuum breaker-check valve
assembly is provided by AVTEC when
specified. Refer to your project drawing.
Additional piping is required from the
vacuum breaker-check valve assembly
to the Hood water inlet(s). AVTEC will
pre-pipe multiple hoods to a single inlet
when specified. Refer to your project
drawing for hood inlet connection
requirements. Refer to Figure II.C.1.
The vacuum breaker-check valve
assembly is provided by AVTEC
when specified. Refer to your
project drawing.
7
Page 11
5. Detergent Pump Pick-up Tube
The pump pick-up tube is provided and
installed by AVTEC when the Detergent
Tank is provided. Some applications use
a remote Detergent dispensing cabinet
with a large volume tank (5 gallons) or
drum. In these applications the pump is
provided with a 5’-0” length of clear PVC
suction tube and a pick-up strainer
screen. The Pick-up tube may not
exceed 5 feet in length. Install as shown
in Figure II.C.1.
6. Detergent Pump to Injection Tee
The output side of the pump (pressure
side) is provided with a pre-piped check
valve. Provide 3/8” O.D. tubing (copper,
or stainless steel) from the detergent
check valve outlet to the injection tee
located between the vacuum breakercheck valve assembly and the ventilator
Figure II.C.1
inlet. Normally the detergent pump and
tank are located in the control panel,
and tubing from the detergent pump to
the detergent tank is factory connected.
Refer to Figure II.C.1.
output tubing on the pump. Once a
solid column of fluid is present press
the “Fan Off/Wash Off” button. The
pump is primed.
e) Open the PAWS water supply valve.
The Panel is ready for normal
operation.
Figure III
8. Detergent Pump Settings
The pump includes a volume
adjustment. Refer to Figure II.C.1 for the
9
propersettingbased on the maximum
hoodlengthwashed. To adjust the
pumpoutput:
a)Turnoffpowerto the PAWS panel
byopeningDIN rail mounted
fuseddisconnect.
b)Removethepump mechanism
cover.Itisattached with (1) screw
ontherightside. Refer to Figure
II.C.1.
c)LoosentheAdjustment Lock nut
(wingnut).
d)TurntheGraduated Adjustment
Disc so the desired number is in
alignment with the Setting Pointer.
e) While holding the Graduated
Adjustment Disc tighten the
Adjustment Lock nut (wing nut).
f)
Replace the pump mechanism
cover and attachment screw.
g) Restore power to the PAWS panel
by closing the DIN rail mounted
fused disconnect.
III.
Sequence of Operation
A. Manual Inputs
Manual Inputs refer to the operator interface
on the front of the control panel. The five
lower buttons are used for manual operation
of the fans, and to initiate the wash cycle(s).
The five upper buttons are used to program
the PAWS control panel for automatic
operation. See Figure III and III.A.
1. Fan Off/Wash Off button
This button Cancels either fan or wash
operation. A Fire Condition initiated by
the hood Fire System, optional Fire Pull
Switch, or the exhaust damper switch
will override this input. This button will
Figure III.A
Page 13
also canceltheFireDelayCyclethat
occursafteraFireConditionhas
cleared.
2. Fan On/WashOffbutton
This buttonturnsthefans
cancelsthewashoperation.AFire
Conditionwilloverridethisinput.
3. Fan Off/WashOnbutton
This buttoncancelsthefanoperation
and initiatesthehoodwashcycle.The
PAWS panelwillwashthehoodforan
adjustableperiodoftime(2-10minutes)
and automaticallyshutoff.Thisbutton
is typicallyusedattheendofthedayto
shut off the fans and clean the hood.
PAWS models P30* through P33* have
a single wash output. This single output
will control up to a 1-1/2” solenoid valve
that will provide sufficient water flow for
up to 50 linear feet of hood.
PAWS models P34* through P47* have
multiple wash sequences that range
from 2 to 8 outputs, depending on the
model. When a wash cycle is initiated
the outputs operate sequentially, one
after the next. The total time required to
complete all wash sequences is equal to
the length of the wash (adjustable 2-10
minutes) times the number of wash
outputs. For example if you have a 4output PAWS panel and have adjusted
the wash duration for
Wash cycle will operate for 16 minutes
(4 minutes for each output).
4. Fuel Reset button (optional feature)
This button will restore power to the gas
solenoids that control the flow of gas to
the cooking equipment, served by the
hood that is controlled by the panel.
The electrical power to the cooking
equipment may also be restored after
pressing the fuel reset button. A main
service breaker that is equipped with a
shut off device
controls the electrical power.
The fuel-reset feature is provided to
integrate the PAWS panel with the Hood
Fire Suppression system to shut off fuel
to the cooking equipment during a
kitchen fire. There are two types of fuel
reset, one with battery back-up and one
without.
(shunt trip) typically
“ON”,and
4 minutes, the
Intheeventofapoweroutagethe fuel
resetwill:
Unitswithoutbatteryback-up; the
solenoidlatchingcircuitwillhold for
1-½seconds,eliminatingthe need
toresetthesolenoids.
Unitswithbatteryback-up;the Gas
Solenoidswillremainonfor
seconds.
5.AlarmSilencebutton
Thisbuttonwillsilencethehorn that
soundsintermittentlywhenthePAWS
panelisinaTROUBLEmode.
A TROUBLE mode may be initiated by a
LOW DETEGENT condition, PAWS
Water Supply Valve Closed (optional),
or, PAWS Water Pressure Low
condition (optional).
If additional trouble conditions occur
after the horn silence button is used; the
horn will not re-sound until all trouble
conditions are cleared and another
trouble condition is initiated.
B. Programmed Events
The PAWS panel can automatically control
the Fan and Wash operation by a user
defined operation schedule. This feature
may or may not be used. It is not required
for the panel to function. There are three
programmable functions:
FAN ON {FAN ON #1 & #2}
FAN OFF {FAN OFF #1 & #2}
WASH ON {WASH ON #1 & #2}
Each of the three functions may be set to
occur twice on a given day (example FAN ON #1 and FAN ON #2).
Whether a function is initiated manually or
by a programmed event, the last event to
occur takes precedence, with exception to
Fire Conditions. Fire Conditions always
take precedence
1. Fan Off Event
{Fan Off #1 & #2}
This event cancels fan operation. The
Fan Off function is programmed when
the user wishes to cancel fan operation
without initiating a wash, typically used
for daytime fan shut down.
A Fire Condition initiated by the hood
Fire System, optional Fire Pull Switch,
TheWashOnfunctionisprogrammedwhentheuserwishestocancelfanoperationandinitiatethehoodwashcycle.Itisbesttowashthehood
immediately after the cooking equipment
is shut down, the grease in the hood is
still warm and more easily cleaned. If
the hood is washed after cool down, an
extended wash period may be required.
Typically the user will program this
event as the last function of the work
day, since the fans are shut down and
one wash cycle per day is usually
adequate.
The user may elect to program this
function to occur in the middle of the
night when hot water demand is low.
The fan does not have to be on in order
to program this event.
Please refer to the Programming section
of this manual to ensure the Wash event
does not conflict with other programmed
events.
C. Device Inputs
There are peripheral devices that are
connected to the PAWS panel for purposes
of monitoring operation and causing
variances in panel operation due to external
events. The following is a list of devices and
their effect on panel operation.
Closure of the duct switch indicates that
the exhaust damper on the connected
hood has closed.
Both exhaust and supply fans are turned
“OFF”. The wash spray in the exhaust
plenum is turned
interior of the hood and prevent flame
spread.
“ON” to cool the
Inordertoreturnthe panel to Normal
operationtheDuct Switch must be
open.
WhentheDuctSwitch opens a Fire
DelayCyclewillmaintain the plenum
washsprayandfan off condition for a
periodofDelaymaybecancelled by pushing the
FanOff/WashOffbutton.
A pulsed tone will emanate from the
Alarm Horn while the fire condition is
active.
Following Actions apply to MODELS
P31*, P32*, P35*, P36*, P45* and P46*
ONLY.
Power to the Gas Solenoid output is
turned “Off “
After the Duct Fire Condition and Fire
Delay Cycle are cleared: press the Fuel
Reset button to reset the Gas Solenoid
and Electric Shunt trip outputs.
After the fire condition is cleared the
horn sounds a constant tone until the
Fuel Reset Button is activated.
2. Hood Fire Suppression System
Switch (N.C.) (optional connection)
Normally Closed dry contacts on the
Hood Fire Suppression System (Ansul
R-102, for example) are connected to
the PAWS panel. Upon discharge of the
Fire Suppression system:
The exhaust fan is turned “ON” and the
supply fan is turned “OFF”. The wash
spray in the exhaust plenum is turned
“ON” to cool the interior of the hood and
prevent flame spread.
Power to the Electric Shunt trip Output
is turned “ON”.
In order to return the panel to Normal
operation the Fire Suppression System
must be reset.
When the Fire Suppression System is
reset a Fire Delay Cycle will maintain
the plenum wash spray and fan
condition for a period of 5 minutes. The
5minutes. The Fire Cycle
11
Page 15
Fire CycleDelaymaybecancelledby
pushingtheFanOff/WashOffbutton.
A FireSystemConditiontakes
precedenceoveralleventsotherthana
Duct SwitchEvent.
FollowingActionsapplytoMODELS
P31*,P32*,P35*,P36*,P45*and P46*
ONLY
PowertotheGasSolenoidoutput is
turned“Off“.
A pulsedtonewillsoundfromtheAlarm
Horn whilethefireconditionisactive.
The followingactionsapplyto
MODELSP31*,P32*,P35*,P36*,P45*
and P46*ONLY
Power totheGasSolenoidoutputis
turned “Off“.
After theFireSystemConditionandFire
Delay Cycle are cleared, pressing the
Fuel Reset button will reset the Gas
Solenoid and Electric Shunt trip outputs.
After the fire condition is cleared a
constant tone is delivered until the Fuel
Reset Button is activated.
3. Fire Pull Switch (N.C.) (Panel option)
The optional Fire Pull switch may be
mounted on the PAWS panel or in a
remote location, such as at the point of
egress. When the Fire Pull Switch is
activated:
The exhaust fan is turned “ON” and the
supply fan is turned “OFF”. The wash
spray in the exhaust plenum is turned
“ON” to cool the interior of the hood and
prevent flame spread.
Power to the Electric Shunt trip Output
is turned “ON”.
In order to return the panel to Normal
operation the Fire Pull Switch must be
reset.
When the Fire Pull Switch is reset a Fire
Delay Cycle will maintain the plenum
wash spray and fan condition for a
period of 5 minutes. The Fire Cycle
Delay may be cancelled by pushing the
Fan Off/ Wash Off button.
A Fire Pull Switch Condition is equal to
a Fire System Condition and takes
precedence over all events other than a
Duct Switch Event.
A pulsed tone will emanate from the
Alarm Horn while the fire condition is
active.
AftertheFirePullSwitchcondition and
FireDelayCyclearecleared,theGas
SolenoidandElectricShunttripoutputs
canberesetbypushingtheFuel reset
button.
Afterthefireconditioniscleared a
constanttoneisdelivereduntil the Fuel
ResetButtonisactivated.
4. AC Power Loss (N.C.) (Panel option)
Loss of AC power will disable the
outputs of the panel with exception of
the Gas Solenoid circuit (when
provided).
The Fire Pull Switch, Fire System
Switch, Duct Switch, or Kill Switch will
override the AC power loss condition
and cause the actions listed for each
input.
Models P32*, P36*, and P46 ONLY!
After a 2-minute delay, power to the Gas
Solenoid output is turned “OFF”. When
AC Power is restored the “Fuel Reset”
button must be pushed to close the
circuit to the gas solenoid valve output
and open the circuit to the shunt trip
output.
5. Detergent Probe (N.C.)
The detergent probe is provided with the
PAWS panel detergent tank. When the
detergent in the tank is low, the probe
initiates a Low Detergent Condition
(PAWS Trouble Condition).
The Detergent Pump Output is turned
“OFF”.
The Probe is set to disable the pump
prior to losing fluid in the pump body.
The pump will not need to be primed
once the detergent supply is
replenished.
The horn will sound intermittently and
may be silenced with the Alarm Silence
button.
ThePAWSpanelmaybeequippedwithapressureswitchtomonitoradequatewatersupply.Ifthepressureswitchisactivatedduetolowwaterpressurea
PAWS Trouble Condition is initiated.
The horn will sound intermittently and
may be silenced with the Alarm Silence
button.
IV. Programming Instructions
A. HOLIDAY MODE (Intermittent use)
The
HOLIDAY MODE
suspend programmed Fan/Wash operation.
Set this feature “ON” when normal operation
is suspended during a holiday or shut down
period. Manual operation of the panel is still
active when in Holiday Mode.
When the panel is in “HOLIDAY MODE” the
bottom display line message will alternate
between Fan/Wash status and “
MODE ON”.
To Set HOLIDAY MODE
1. Press the MENU key. Display
Reads: ”SET CLOCK”.
2. Use the (DOWN) arrow key until
the display reads “SET HOLIDAY”.
3. Press the ENTER key. Display
Reads: “SET HOLIDAY MODE”
4. Press the ENTER key. The bottom
display line reads: “SET MODE X ENTER”.
5. Use the (UP) (DOWN) arrow
keys to adjust the HOLIDAY MODE
ON--OFF
[0=OFF, 1=ON].
key. To return to the MENU tree
press the MENU key.
is provided to
HOLIDAY
13
B.SettheWASHDURATION
TheWASHDURATION is the length of time
eachventwashcyclewill run. When a
sequentialwashoutput)panelisprovided each wash will
operateforthesetwash duration. The
minimumoperationalsetting is 2 minutes.
Themaximumsettingis10 minutes. Typical
settingis4to5minutes. Under heavy loads
avalueof7to10minutes may be required.
TosettheWASHDURATION
1.PresstheMENUkey. Display
Reads:”SETCLOCK”.
2.Usethe(UP)arrow key until the
displayreads“SET WASH
DURATION”.
3. Press the ENTER key. Display
Reads: “SET WASH TIME”
4. Press the ENTER key. The bottom
display line reads: “SET WASH XX MINUTES”.
5. Use the (UP) (DOWN) arrow
keys to adjust the Wash Time value.
6. Press the ENTER key to accept the
adjusted value. Display Reads:
“SET WASH TIME”.
7. To EXIT press the CLEAR/ABORT
key. To return to the MENU tree
press the MENU key.
C. Set the Programmed Events Schedule
(Automatic Fan On-Off and Wash Cycle)
The PAWS panel can automatically control
the Fan and Wash operation by a user
defined operation schedule.
This feature may or may not be used. It is
not required for the panel to function. There
are three programmable functions:
1. FAN ON {FAN ON #1 & FAN
2. FAN OFF {FAN OFF #1 & FAN
3. WASH ON {WASH ON #1 &
Each of the three functions may be set to
occur twice on a given day (example FAN ON #1 and FAN ON #2).
Please refer to the PAWS Programmed
Events Worksheet included in the Appendix
of this manual for an outline of the Event
Schedule.
When planningtheeventscheduleyoumust
account forthetimerequiredbythewash
cycle.
In the previoussection
Duration” thelengthofthewashcyclewas
determined.Donotschedulefanoperation
until sufficienttimehaspassedforthewash
cycle to run tocompletion.
If your panelincludessequentialwash
operation determinethewashoutput
quantity.
(
DOWN)
bottom display line will read “PROGRAM
WASH QTY. X
the “X” is shown, is the wash quantity value.
Multiply the quantity of wash outputs by the
wash duration to determine the total wash
time required.
EXAMPLE: If
DURATION
output quantity is 4, total wash time is 16
minutes (4 min. wash duration x 4 wash
outputs = 16 minutes).
To stop the operation of the fans a “
OFF” event OR a “WASH ON” event may be
scheduled. While both functions turn the
fans off, the WASH ON function will also run
the hood(s) through a wash cycle.
You may schedule any function independent
of relative functions. For example, if you
normally operate the fans manually, but
want to ensure that the fans are shut off
each night, you could program a “FAN OFF”
event at the end of the day.
operations cook past midnight, so you may
want to program a “
start of the cooking operation, and schedule
a “
FAN OFF”
following day.
1. To Program an Event
a) Press the
b) Use the (UP)
c) Press the
(copyincludedintheproject
Press and hold the
arrows at the same time. The
for 4 minutes, and the wash
Reads: ”SET CLOCK”.
display reads “SET PROGRAM”.
Reads: “SELECT DAY”
(orfacsimile)ofthe
“SettingWash
”. The value placed where
or “
WASH ON”
MENU
ENTER
you set the
FAN ON
key. Display
arrow key until the
key. Display
WASH
FAN
Some
” event at the
event for the
(UP)
14
d)PresstheENTERkey.Thebottom
displaylinereads:“SETDAYXENTER”.
e)
Usethe
keystoadjusttheDayvalue to the
dayyouwishtoprogram
[1=Sunday,2=Monday,3=Tuesday,
4=Wednesday,5=Thursday,
6=Friday,7=Saturday].
f)PresstheENTERkeytoaccept the
adjustedvalue.Display Reads:
“SELECTDAY”.
g)
Usethe(
displayreads“SELECTPROGRAM
EVENT”.
h)
Press the
Reads: “FAN ON #1”.
i)
Use the
keys until the display shows the
function you wish to program. In the
following example the “FAN ON #1”
function is used to demonstrate the
programming process.
j)
Press the
Reads:
“FAN ON #1 HOUR X”
k)
Use the
keys to adjust the hour value. If you
wish to clear this programmed
event, adjust the hour value to “0”.
l) Press the ENTER key to accept the
adjusted value. If you accepted a
value other than “0”. Display reads:
“FAN ON #1 MIN. XX”
m)
Use the
keys to adjust the minute value. n)
Press the ENTER key to accept the
adjusted value. Display Reads:
“FAN ON #1 AM/PM. X”
o)
Use the
keys to adjust the AM/PM value
[1=AM, 2=PM].
p) Press the ENTER key to accept the
adjusted value. Display Reads:
“FAN ON #1”.
q) To continue programming
additional events for the same
day:
Use the
arrow keys until the display shows
the function you wish to program.
Repeat steps j to q. Each function
may be scheduled to occur twice
onlyprogrammedvaluesthatwillbesavedarethosethatwere
confirmed with an ENTER key.
D. Setting the Clock
The clock does not continue to keep time
when the MENU mode is active. Therefore
the time of day is the last item that should
be set.
1. To Set Day of Week
(a) Press the MENU key. Display
Reads: ”SET CLOCK”.
(b) Press the ENTER key. Display
Reads: “SET MINUTES”
(c) Use the (UP) arrow key until the
display reads “SET DAY OF WEEK”.
(d) Press the ENTER key. The bottom
display line reads: “SET DAY X ENTER”.
(e) Use the (UP) (DOWN) arrow
keys to adjust the Day value to the
current day [1=Sunday, 2=Monday,
3=Tuesday, 4=Wednesday,
5=Thursday, 6=Friday, 7=Saturday].
(f) Press the ENTER key. The bottom
display line reads: “SET DAY OF WEEK”.
MENU
”.Pressthe
key.Display
atanytime.The
(DOWN)
3.ToSetHour
(a)Usethe(UP)arrow key until the
displayreads“SET HOUR”.
(b)PresstheENTER key. Display
Reads:“SETHOUR X
Enter”.
(c)Usethe(UP) (DOWN) arrow
keystoadjustthe Hour value to the
currenttime.
(d)PresstheENTER key to accept the
adjustedvalue.Display Reads:
“SETHOUR
4.ToSetMinutes
(a)Usethe(UP)arrow key until the
display reads “SET MINUTES”.
(b) Press the ENTER key. Display
Reads: “SET MIN. XX Enter”.
(c) Use the (UP) (DOWN) arrow
keys to adjust the Minute value to
the current time.
(d) Press the ENTER key to accept the
adjusted value. Display Reads:
“SET MINUTES.
(e) To back up one level in the menu
tree press the MENU key.
(f) To EXIT and return to the default
Display Messages press
CLEAR/ABORT at any time.
2. To Set AM/PM
(a) Use the (UP) arrow key until the
display reads “SET AM/PM”.
(b) Press the ENTER key. Display
Reads: “SET AM/PM X Enter”.
(c) Use the (UP) (DOWN) arrow
keys to adjust the AM/PM value to
the current time [1=AM, 2=PM].
(d) Press the ENTER key to accept the
adjusted value. Display Reads:
“SET AM/PM”.
15
Page 19
V. Engineering Data
A. Component Layout/Part Numbers
All PAWS panels share a common chassis
and base components. Following is a list of
components, AVTEC part number,
description, and additional drawings when
necessary. Refer to Figure V.A as a general
reference.
1. Panel Faceplate
A stainless steel faceplate is provided
as an integral part of the PAWS control
panel.
2. AVTEC PAWS Overlay P/N PP LBL0342
An adhesive backed polycarbonate
colorfast label. All printing is printed
second surface. The label is die-cut to
index with # 3 (operator interface”).
3. Operator Interface - P/N EL MOD0303
Includes 2-line by 20 character LCD
display, 5
control keys.
programming keys and
5
Figure
V.A
4. Vent Light Switch - P/N EL SWTO318
5. Fire Pull Switch - P/N EL STA0301
Optional feature, Yellow pull switch with
replaceable glass rod, (1) normally open
contact and (1) normally closed contact.
6. PAWS PLC Chassis
Pre-punched stainless steel chassis with
integral threaded fasteners for
component mounting. Provided as an
integral part of the PAWS control panel.
Suitable for all PAWS models.
120vac PLC as provided includes 8
DC inputs,
integral 24vdc power supply.
8. Din Rail (typical)
9. Relay (Exhaust Fan) - EL RLY0334,
SPDT Relay with 120/1 coil, 7.5a @
120vac contacts and ELRLY 0327 relay
socket
10. Relay (Supply Fan) - EL RLY0334, SPDT
Relay with 120/1 coil, 7.5a @ 120vac
contacts and EL RLY0327 relay socket
11. Relay (Fuel Shut Off) - EL RLY0334,
SPDT Relay with 120/1 coil, 7.5a @
120vac contacts and EL RLY0327 relay
socket
Relay (AC Power Loss, not shown) EL RLY0334, SPDT Relay with 120/1 coil,
7.5a @ 120vac contacts and EL RLY0327
relay socket
12. Liquid Level Control - EL SEN0401, and
135664 (8-pin socket)
relayoutputs,and
CPU - P/N EL CPU0301
CPU battery P/N EL BAT 0302
4-slot i/o base P/N EL BSE 0301
DC Input Module P/N EL MOD0302
AC Relay Output Module P/N EL RLY0316
ϖRefertothejobspecificwiringdiagramforelectricalinterconnections.ϖApplyexternalpoweronlytothoseterminalscodedwithashadedbox.Appliedpower may not
exceedspecifiedelectricalratings.
ϖDonotexceedthespecifiedoutputterminalcurrentratings.ϖIfyouareunsureorrequireassistance,contactAVTECProductService(800-621-8560) before
proceedingwithinstallation.
AVTECwillnothonorwarrantyclaimsresultfromofimproperelectricalinterconnection or abuse.
TERMINAL
NUMBER
1
2
3
4
5, 6, 7
8
9
10
11
12
13
14
15
16
N
H
G
FUNCTION
OUTPUT,KILLSWITCH(OPTIONAL):SWITCHED
CURRENTFROMTERMINAL5,6,or7OUTPUT, FIRE PULL SWITCH (OPTIONAL):
NORMALLY CLOSED, SWITCHED CURRENT FROM
TERMINAL 5, 6, or 7
OUTPUT, FIRE PULL SWITCH (OPTIONAL):
COMMON, SWITCHED CURRENT FROM TERMINAL
5, 6, or 7
OUTPUT, HOOD FIRE SYSYTEM SWITCH:
SWITCHED CURRENT FROM TERMINAL 5, 6, or 7
OUTPUT: SOURCE VOLTAGE FOR INPUT
DEVICES. 120VAC FOR MODELS P30 TO P37,
24VDC + FOR MODELS P44 TO P47.
OUTPUT, HOOD EXHAUST DUCT SWITCH:
SWITCHED CURRENT FROM TERMINAL 5, 6, or 7
OUTPUT EXHAUST DAMPER HOT, 120VAC, 15A
OUTPUT: 20VDC, 2ma, DETERGENT PROBE
OUTPUT: 20VDC, 2ma, DETERGENT PROBE
OUTPUT, SUPERVISED WATER SUPPLY VALVE
(OPTIONAL): SWITCHED CURRENT FROM
TERMINAL 5, 6, or 7
OUTPUT, WATER SUPPLY PRESSURE SWITCH
(OPTIONAL): SWITCHED CURRENT FROM
TERMINAL 5, 6, or 7
OUTPUT, (OPTIONAL): 120VAC GAS SOLENOID,
HOT
OUTPUT, (OPTIONAL): 120VAC ELECTRIC SHUNT
TRIP, HOT
AVTEC USE ONLY, (OPTIONAL UPS POWER
INPUT)
POWER INPUT, 120VAC, 15 AMPS, NEUTRAL BUS.
COMPOSED OF 9 JUMPERED TERMINALS POWER
INPUT, 120VAC, 15 AMPS, HOT
GROUND TERMINAL (CHASSIS GROUND)
TERMINAL
NUMBER
17 NOT USED IN THIS APPLICATION.
18 OUTPUT, 120VAC SWITCHED HOT TO EXHAUST
19 NOT USED IN THIS APPLICATION.
20 OUTPUT, 120VAC SWITCHED HOT TO SUPPLY FAN
ALTERNATE FAN STARTER WIRING, N.O. DRY CONTACTS
(HOA STARTERS OR CONTROL VOLTAGE FROM STARTERS)
NOTE: PRE-WIRED JUMPER FROM TERMINAL H TO 17 AND 19
MUST BE REMOVED PRIOR TO APPLICATION OF POWER
The ProgrammableLogicControllerthatisexceptP31,P35)
provided withthePAWSpanelincludes
diagnostic lightsthatwillilluminatewhenanP35)
input or outputisactive.
The PLC andOperatorInterfacealso
include switchesthatmustbeconfiguredin
order for thepaneltooperate.Detailsare
shown below.
1. Model P30toP37PLC
Refer toFigureV.C.1forterminal
locations.ThediagnosticLED'sare
shown in Figure V.C.1 with their
identifying labels. Input and Output
assignments are as follows:
INPUTS
120vac is applied through switch
devices to the terminals outlined below.
The associated COMMON is connected to
120vac neutral. When an input is
“ON” the associated diagnostic LED will
light. Some inputs will have a lit LED in
normal operation while others will
illuminate only when the device is “ON”.
Normal status is listed below as M to
indicate a lit LED, and L to indicate the
LED is “OFF”.
L
Y5=Ex.FanRelay
L
Y6=Wash#3Solenoid(all
L
Y6=GDRReset(modelsP31,
L
Y7=SupplyFanRelay
Figure V.C.1
L X0 = Exhaust Duct Switch
M X1 = Fire System Switch
L X2 = Kill Switch
L X3 = Spare
L X4 = Water Valve
L X5 = Water Pressure Switch
L X6 = Detergent Probe
L X7 = Spare
L X10 = Spare
M X11 = AC Power Loss
OUTPUTS
120vac, “hot”, is applied to the common
terminal for all outputs. When an output is
“ON” the associated diagnostic LED will
light. Normal status for each Input is listed
below as M to indicate a lit LED, and L to
indicate the LED is “OFF”.
L Y0 = Audible Alarm (Horn)
L Y1 = Detergent Pump
L Y2 = Wash #1 Solenoid
L Y3 = elec. Shunt Trip (all except
P31, P35)
M Y3 = GDR Power (models P31,
P35)
20
Page 24
2. Model P44 to P47 PLC
Refer to Figure V.C.2
locations. The diagnostic LED’s are
shown in Figure V.C.2
identifying labels. Input and Output
assignments are as follows:
INPUTS
24vdc positive is applied through switch
devices to the terminals outlined below.
The associated COMMON is connected
to 24vdc negative. When an input is
“ON” the associated diagnostic LED will
light. Some inputs will have a lit LED in
normal operation while others will
illuminate only when the device is “ON”.
Normal status is listed below as M to
indicate a lit LED, and L to indicate the
LED is “OFF”.
L X0 = Exhaust Duct Switch
M X1 = Fire System Switch
L X2 = Kill Switch
L X3 = Spare
L X4 = Water Valve
L X5 = Water Pressure Switch
L X6 = Detergent Probe
M X7 = AC Power Loss
for terminal
with their
Figure
V.C.2
OUTPUTS
120vac, “hot” is applied to the common
terminal for all outputs. When an output
is
“ON” the associated diagnostic LED
will light. Normal status for each Input is
listed below as M to indicate a lit LED,
and L to indicate the LED is “OFF”.
Relay Output Module #1, (Slot 3)
L Y0 = Audible Alarm (Horn)
L Y1 = Detergent Pump
L Y2 = Wash #1 Solenoid
L Y3 = elec. Shunt Trip (all except
P45)
M Y3 = GDR Power (model P45)
L Y4 = Spare
L Y5 = Ex. Fan Relay
L Y6 = Spare (all except P45)
L Y6 = GDR Reset (model P45)
L Y7 = Supply Fan Relay
Relay Output Module #2, (Slot 4)
Program address is shown in ( )
L Y0 (Y10) = Wash #2 Solenoid
L Y1 (Y11) = Wash #3 Solenoid
L Y2 (Y12) = Wash #4 Solenoid
L Y3 (Y13) = Wash #5 Solenoid
L Y4 (Y14) = Wash #6 Solenoid
L Y5 (Y15)= Wash #7 Solenoid
L Y6 (Y16)= Wash #8 Solenoid
L Y7 (Y17) = Spare
21
Page 25
A “Run-Terminal“switchisprovidedonVI.
the PLC.The
must beinthe“
the paneltooperate.
3. OperatorInterface
Refer toFigureV.C.3forswitchsettings
and diagnosticLEDlocations.
For the paneltooperateswitch1and2
must beinthe“OFF”position(allthe
way to theleft).
A transmit(labeled“TX”)andreceive
(labeled“RX”)LEDarelocatedonthe
back of theunit.TheLED’swilllight
when theoperatorinterfaceis
communicating with the PLC.
A serial communication port is provided
on the back of the unit. This port is
connected to the PLC with a special
cable that is supplied with the panel.
See Figure V.C.3.
Figure V.C.3
”Run-Terminal“switch
Termina
l”positionfor
Maintenance
A.DetergentDispensingSystem(pump)
1.DetergentTank
Thedetergenttankshould be
replenishedatleastweekly. The
LowDetergentProbewillmonitor
theneedformorefrequentrefills.
Afteranextendedperiodoftime the
tankmayrequirecleaning. The
probeandpickuptubemay be
removed,butensuretheyare reinstalledasshowninFigureII.C.1.
2.Detergent
AVTEC EVAC is a biodegradable
detergent specifically formulated for
use with water wash hoods.
AVTEC will provide a Lifetime
Warrantee for the PAWS Detergent
Dispensing System when AVTEC
EVAC is used exclusively.
EVAC can be obtained through
Authorized AVTEC Service Agents.
Refer to the EVAC spec sheet in the
Appendix of this manual.
3. Detergent Pump
Every six months:
Check the Foot Strainer Pick-Up
to ensure the screen is not
clogged. Refer to Figure II.C.1.
Check all tubing fittings to
ensure they are tight.
For additional information refer to
the pump manufacturer's manual
that is included in the AVTEC
Ventilator manual.
B. Plumbing
A Wye (line) strainer is included in the
PAWS water manifold to protect the
water solenoid(s) and hood spray
nozzles. If you experience a loss in
water pressure it is frequently due to a
clogged wye strainer.
Before opening the cleanout on the wye
strainer make sure the water is “OFF”
and the water manifold is not under
pressure.
A bucket should be placed under the
cleanout prior to removing the cleanout
plug. Some water spill will occur.
22
Page 26
Figure
Once the cleanout plug is removed
withdraw the strainer screen.
Thoroughly clean the strainer screen
and make sure additional debris is not
lodged in the wye strainer body. Refer to
Figure VI.B.
VII. Warranty
AVTEC INDUSTRIES INC. warrants to the original
purchaser for use of our products, that any part
thereof which proves to be defective in material or
workmanship under normal use within one year from
date of installation, will be replaced free of charge,
labor to replace such part is warranted for one year
from installation. All warranty labor to be performed
during regular working hours, with no overtime
premium.
All Warranty service must be authorized by the
factory and be performed by AVTEC's authorized
service personnel.
This Warranty is limited to the United States and
Canada.
VI.B
other products or damage to equipment or property
resulting from mechanical or electrical failure.
AVTEC neither makes nor assumes and does not
authorize any other person to assume any other
obligation or liability in connection with its products
other than that covered in this Warranty.
FOR THE NAME AND LOCATION OF THE
NEAREST
AVTEC SERVICE AGENCY, CALL OR WRITE TO:
AVTEC / Unified Brands
525 S. Coldwater Rd.
Weidman MI 48893
PH. 800/621-8560
This Warranty does not apply to any damage
resulting from shipping, improper installation,
accident, unauthorized alteration, local codes not
previously brought to the attention of AVTEC,
misuse, or abuse; and does not cover loss of food,
Rev. 10/08
23
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.