Utility Distribution System
Available for Electrical and
Gas Usage
Utility Raceways
Description:
The M-series Raceway is a Utility Distribution System
comprised of a stainless steel sheet metal housings enclosing
cable bus electrical system and plumbing services that
provide connections for individual appliances. Raceways with
plumbing services are Listed by Underwriters Laboratories (UL)
as Commercial Appliance Outlet Centers. Raceways with only
electrical services are Listed by UL as Multi-outlet Assemblies.
These raceways are intended primarily for use with cooking
batteries, or cooking appliance line-ups, on both sides of the
Raceway, or with appliances along one side and an aisle on
the other side. Individual Point-of-use connection plates are
located near the top along the length of the raceway.
Specifications:
Dimensions: Horizontal Chase Width: 6” [generally for plumbing services less than 2” NPT] or 8” [generally for plumbing services 2” NPT or greater], Height: 18” – 30” plus 3-6” peaked top, Length: as required. Service Towers Width: 6-12” Height:
Finished Floor to Exhaust Hood or Finished Ceiling, Length: 18” Nominal to 42” Nominal. Intermediate Pedestals Width: 5-8”
Height: Finished Floor to bottom of Horizontal Chase, Length: 5-8”. Construction: 300-series Stainless Steel. Removable panels
held in place with threaded fasteners. Electrical Data: 30 to 150 amperes. 120/208-240 volts. Single- or three-phase. Water:
150 psig & 140° F (60° C) maximum. Gas (Natural gas or LP): 1.25 psig
M Series
model MID
Flat Top Shown
Standard Features: Optional Accessories:
• Point-of-use branch circuit protection
with receptacle or exible liquid tight
metal conduit (pigtail) mounted
adjacent to Point-of-use branch
circuit protection on 4.5x12”
connection plate. NOTE: For other
voltage congurations, consult
factory.
• Ground fault circuit interrupter for
15 & 20 amp, 120/1, straight blade
receptacles
• Cable bus
• Copper hot and cold water supply
lines, if required
1055 Mendell Davis Drive, Jackson, MS 39272
888-994-7636, unifiedbrands.net
Please reference our website for the most
updated product information and specifications.
• Black iron gas supply line, if required
• Black iron steam supply and
condensate return lines, if required
• Quarter-turn shut-off valves on
all individual connections
• Quarter-turn shut-off valves on
main supply valves
• 2” High collar at top of service
tower allows ±1/2” vertical
adjustment to compensate for oor
and/or exhaust hood mounting
irregularities
Avtec Utility Raceways, Page 1
PP SPEC1045 Rev. A
Revised 11/07
Optional Accessories:
Model MID
Main electrical service circuit
breaker with shunt trip
Quick-disconnect ttings for individual
gas connections in addition to quarter-turn shut-off valves for movable
appliances
Quick-disconnect ttings for individual
water connections in addition to quarter-turn shut-off valves for movable
appliances
Vent light switch in service tower
Vent light switch with circuit breaker
Front, Top & Side Views
in service tower
Duplex convenience outlet in service
tower(s)
Gas delay reset (GDRI)
120V AC re-fuel shut-off solenoid
valve(s) for gas supply. 1 1/2” And
smaller located in service tower(s)
(2” and larger are remotely located)
Temperature/pressure gauge at water
incoming service location
Security package (includes):
• exposed fasteners to be tamper-re-
sistant, pin-in-head torx-head, shipped
loose and installed in eld
• hinged doors equipped with eye for
customer-supplied padlock
Panel mounted faucet or pot ller
Flat top in lieu of peaked top on
horizontal chase
Ventilation control panel mounted in
tower
Filtered water system
Front,Top & Side Views
Flat Top Shown
1055 Mendell Davis Drive, Jackson, MS 39272, 888-994-7636, unifiedbrands.net
Utility Distribution System
Available for Electrical and
Gas Usage
Utility Raceways
Description:
The M-series Raceway is a Utility Distribution System
comprised of a stainless steel sheet metal housings enclosing
cable bus electrical system and plumbing services that
provide connections for individual appliances. Raceways with
plumbing services are Listed by Underwriters Laboratories
(UL) as Commercial Appliance Outlet Centers. Raceways
with only electrical services are Listed by UL as Multi-outlet
Assemblies. These raceways are intended primarily for
use behind a cooking battery, or cooking appliance line-up.
Individual Point-of-use connection plates are located near the
top along the length of the raceway.
Specifications:
Dimensions: Horizontal Chase Width: 6” [generally for plumbing services less than 2” NPT] or 8” [generally for plumbing services 2” NPT or greater], Height: 18” – 30” plus 3-6” peaked top, Length: as required. Service Towers Width: 6-12” Height:
Finished Floor to Exhaust Hood or Finished Ceiling, Length: 18” Nominal to 42” Nominal. Intermediate Pedestals Width: 5-8”
Height: Finished Floor to bottom of Horizontal Chase, Length: 5-8”. Construction: 300-series Stainless Steel. Removable panels
held in place with threaded fasteners. Electrical Data: 30 to 150 amperes. 120/208-240 volts. Single- or three-phase. Water:
150 psig & 140° F (60° C) maximum. Gas (Natural gas or LP): 1.25 psig
M Series
model MWD
Peaked Top Shown
Standard Features: Optional Accessories:
• Point-of-use branch circuit protection
with receptacle or exible liquid tight
metal conduit (pigtail) mounted
adjacent to Point-of-use branch
circuit protection on 4.5x12”
connection plate. NOTE: For other
voltage congurations, consult
factory.
• Ground fault circuit interrupter for
15 & 20 amp, 120/1, straight blade
receptacles
• Cable bus
• Copper hot and cold water supply
lines, if required
1055 Mendell Davis Drive, Jackson, MS 39272
888-994-7636, unifiedbrands.net
Please reference our website for the most
updated product information and specifications.
• Black iron gas supply line, if required
• Black iron steam supply and
condensate return lines, if required
• Quarter-turn shut-off valves on
all individual connections
• Quarter-turn shut-off valves on
main supply valves
• 2” High collar at top of service
tower allows ±1/2” vertical
adjustment to compensate for oor
and/or exhaust hood mounting
irregularities
Avtec Utility Raceways, Page 2
PP SPEC1046 Rev. A
Revised 11/07
Optional Accessories:
Model MWD
Main electrical service circuit
breaker with shunt trip
Quick-disconnect ttings for individual
gas connections in addition to quarter-turn shut-off valves for movable
appliances
Quick-disconnect ttings for individual
water connections in addition to quarter-turn shut-off valves for movable
appliances
Vent light switch in service tower
Vent light switch with circuit breaker
Front, Top & Side Views
in service tower
Duplex convenience outlet in service
tower(s)
Gas delay reset (GDRI)
120V AC re-fuel shut-off solenoid
valve(s) for gas supply. 1 1/2” And
smaller located in service tower(s)
(2” and larger are remotely located)
Temperature/pressure gauge at water
incoming service location
Security package (includes):
• exposed fasteners to be tamper-re-
sistant, pin-in-head torx-head, shipped
loose and installed in eld
• hinged doors equipped with eye for
customer-supplied padlock
Panel mounted faucet or pot ller
Flat top in lieu of peaked top on
horizontal chase
Ventilation control panel mounted in
tower
Filtered water system
Front,Top & Side Views
Peaked Top Shown
1055 Mendell Davis Drive, Jackson, MS 39272, 888-994-7636, unifiedbrands.net