Avaya EA401 User Manual

Avaya Inc.
211 Mt. Airy Road
Basking Ridge NJ 07920
Explosive Atmosphere Telephone
Installation & Operation
AVAYA
TELEPHONE FOR USE IN HAZARDOUS LOCATIONS
CLASS I GROUPS B, C, & D
[Exia]
Associated equipment
CLASS I ZONE 1, GROUPS IIB+ H2
Appareillage Connexe
LR65547
HANDSET WITH THIS T ELEPHONE
RELAY CONTACTS
FUSE: 0.25A 48VDC - TYPE 2AG, FAST-ACTING
COMCODE: 700302045 SER. NO.
REFER TO USER GUIDE FOR INSTALLATION
CLASS II GROUPS E, F, & G
ENCLOSURE TYPE 4
RECEPTACLE PROVIDES
INTRINSICALLY SAFE OUTPUT
USE ONLY MODEL EA10H
10A 1/3HP 240V AC 10A 1/3HP 120V AC 10A 30V DC
MADE IN CANADA
LISTED
13X8
MOD. NO.: EA401
WARNING
FIELD REPAIR NOT POSSIBLE. FOR SERVICE RETURN TO FACTORY. TO PREVENT
IGNITION OF HAZARDOUS ATMOSPHERE, DISCONNECT FROM THE SUPPLY CIRCUIT
BEFORE OPENING OR REPLACING FUSE . KE E P TIGHTLY CLOSED WHEN CIRCUITS ARE ALIVE. ALL CONDUIT RUNS MUST BE SEALED WITHIN 18 INCHES (450 mm) OF
THIS ENCLOSURE. BREAKING OF REAR BOLT SEALS VOIDS MANUFACTURER'S WARRANTY. SUBSTITUTION OF COM PONENTS MAY IMPAIR INTRINSIC SAFETY.
ATTENTION
CET APPAREIL NE PEUT ETRE REPARE A PIED D'OEUVRE. NE PAS L'OUVRIR.
LES BOULONS DOIVENT ETRE BIEN SERRES DEBRANCHE LE TELEP HONE
AVANT LE REMPLACEMENT DU FUSIBLE. RETOURNER L'APPAREIL A L'USINE
POUR LE DEPANNAGE. LE FAIT DE BRISER L E SCEAU DU FABRICANT A
L'ARRIERE DE L'APPAREIL ANNUELE LA GUARANTIE DU FABRICANT.
Industry Canada Industrie Canada
1012 4339 A
P005975 Rev. A 11/13/2003 5:24 PM
Avaya Inc. Installation and Operation
Model EA401
Table of Contents
Package Contents.............................................................................................2
Overview...........................................................................................................2
Features............................................................................................................2
Warnings...........................................................................................................2
General Requirements......................................................................................2
Installing the EA401..........................................................................................2
Wiring For Tip & Ring........................................................................................2
Fuse Replacement............................................................................................2
Replacement Of EA10H Telephone Handset Assembly...................................2
Operating Instructions.......................................................................................2
Engineering Specifications................................................................................2
Warranty............................................................................................................2
Disclaimer .........................................................................................................2
Warning.............................................................................................................2
Service Telephone Number ..............................................................................2
Avaya Product Return.......................................................................................2
APPENDIX A - Hazardous Location Classification...........................................2
APPENDIX B - Applications..............................................................................2
APPENDIX C - EA401 Models and Options .....................................................2
Table of Figures
Figure 1 - Features............................................................................................2
Figure 2 - Dimensions.......................................................................................2
Figure 3 - Typical Installation............................................................................2
Figure 4 - Lower Junction Box Wiring...............................................................2
Figure 5 - Fuse Replacement............................................................................2
Figure 6 - Handset Replacement......................................................................2
Figure 7 - I.D. and Compliance.........................................................................2
Package Contents
(1) EA401 Telephone (1) Installation & Operation Manual
Page 2
Avaya Inc. Installation and Operation
Model EA401
Overview
Model EA401 Explosive Atmosphere Telephone
This Explosive Atmosphere telephone provides safe and reliable communication in hazardous locations, up to and including Class I Division 1. Only standard wiring and fittings are required to connect the telephone to the system; no barrier is necessary. Since the heavy duty cast aluminum enclosure is basically soundproof, an external device to signal incoming calls is required.
Features
Enclosure
cast copper free aluminum with powder coat finish
Internal Sealed Cavities
completely seal the unit
Keypad
standard configuration with an additional row of buttons for Last Number Redial, Link/Flash to access PABX features and Line Release to duplicate hanging up the handset
one inch diameter buttons for gloves-on operation
Circuitry Coating
circuit boards have a UV cured epoxy coating which provides protection from corrosive agents such as H with high humidity
Magnetic Reed Hook Switch
no moving parts, activates when the handset is removed from or placed in the telephone cradle
Tone (DTMF) Operation
selectable in the field; factory set to operate to tone (DTMF) exchanges
Intrinsically Safe Handset Operation
the output from the telephone to the handset passes through an intrinsically safe barrier ensuring a high degree of safety
Field Replaceable Handset
the 10’ handset cord is designed for industrial applications and is attached to the telephone by a connector for ease of replacement
Field Replaceable Fuse
a fitting in the bottom of the enclosure provides access to the fuse
Hearing-Aid Compatibility
the handset is compatible with inductively coupled hearing-aid devices
S, SO2, and NH
2
and environments
3,
Page 3
Avaya Inc. Installation and Operation
Model EA401
MAGNETIC REED
HOOK SWITCH
TELEPHONE FOR USE IN HAZARDOUS LOCATIONS
[Exia]
Associated equipment
CLASS I ZONE 1, GROUPS IIB+H2
Appareillage Connexe
LR65547
HANDSET WITH THIS TELEPHONE
RELAY CONTACTS
FUSE: 0.25A 48VDC - TYPE 2AG, FAST-ACTING
COMCODE: 700302045 SER. NO.
REFER TO USER GUIDE FOR INSTALLATION
AVAYA
CLASS I GROUPS B, C, & D
CLASS II GROUPS E, F, & G
ENCLOSURE TYPE 4
RECEPTACLE PROVIDES
INTRINSICALLY SAFE OUTPUT
USE ONLY MODEL EA10H
MADE IN CANADA
10A 1/3HP 240V AC 10A 1/3HP 120V AC 10A 30V DC
LISTED
13X8
MOD. NO.: EA401
INTRINSICALLY SAFE HANDSET
PRODUCTION IDENTIFICATION LABEL
HANDSET CORD
LINK
KEYPAD
REDIAL
(PBX TRANSFER)
WARNING
FIELD REPAIR NOT POSSIBLE. FOR SERVICE RETURN TO FACTORY. TO PREVENT IGNITION OF HAZARDOUS ATMOSPHERE, DISCONNECT FROM THE SUPPLY CIRCUIT BEFORE OPENING OR REPLACING FUSE. KEEP TIGHTLY CLOSED WHEN CIRCUITS ARE ALIVE. ALL CONDUIT RUNS MUST BE SEALED WITHIN 18 INCHES (450 mm) OF
THIS ENCLOSURE. BREAKING OF REAR BOLT SEALS VOIDS MANUFACTURER'S WARRANTY. SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY.
ATTENTION
CET APPAREIL NE PEUT ETRE REPARE A PIED D'OEUVRE. NE PAS L'OUVRIR.
LES BOULONS DOIVENT ETRE BIEN SERRES DEBRANCHE LE TELEPHONE
AVANT LE REMPLACEMENT DU FUSIBLE. RETOURNER L'APPAREIL A L'USINE
POUR LE DEPANNAGE. LE FAIT DE BRISER LE SCEAU DU FABRICANT A
L'ARRIERE DE L'APPAREIL ANNUELE LA GUARANTIE DU FABRICANT.
Industry Canada Industrie Canada
1012 4339 A
RELEASE WARNING LABEL
MOUNTING LUG TIP/RING/GROUND WIRES
ENTRY POINT FUSE
HANDSET CORD
CONNECTOR
Figure 1 - Features
10.1" [257mm]
8.5" [216mm]
AVAYA
TELEPHONE FOR USE IN HAZARDOUS LOCATIONS
CLASS I GROUPS B, C, & D
[Exia]
Associated equipment
CLASS I ZONE 1, GROUPS IIB+H2
Appareillage Connexe
CLASS II GROUPS E, F, & G
ENCLOSURE TYPE 4
RECEPTACLE PROVIDES
INTRINSICA LLY SAFE OUTPUT
USE ONLY MODEL 301SC OR 301SCPB
LR65547
HANDSET WITH THIS TELEPHONE
10A 1/3HP 240V AC
RELAY CONTACTS
10A 1/3HP 120V AC 10A 30V DC
FUSE: 0.25A 48VDC - TYPE 2AG, FAST-ACTING
SER. NO.
REFER TO USER GUIDE FOR INSTALLATION
MADE IN CANADA
LISTED
13X8
CAT. NO.: 401
Ø0.4" [Ø10mm]
2 PLCS.
TELEPHONE FOR USE IN HAZARDOUS LOCATIONS
[Exia] Associated equipment Appareillage Connexe
LR65547
FUSE: 0.25A 48VDC - TYPE 2AG, FAST-ACTING
SER. NO.
REFER TO USER GUIDE FO R INSTALLATION
AVAYA
CLASS I GROUPS B, C, & D
CLASS I ZONE 1, GROUPS IIB+H2
CLASS II GROUPS E, F, & G
ENCLOSURE TYPE 4
RECEPTACLE PROVIDES
INTRINSIC ALLY SAFE OUTPUT
USE ONLY MODEL 301SC OR 301SCPB
HANDSET WITH THIS TELEPHONE
RELAY CONTACTS
MADE IN CANADA
4.9" [124mm]4.4" [111mm]
LISTED
13X8
10A 1/3HP 240V AC 10A 1/3HP 120V AC 10A 30V DC
CAT. NO.: 401
WARNING
FIELD REPAI R N O T POSSIBLE. FOR SE R V ICE RETURN TO FACTORY. TO PREVENT IGNITION OF H A Z ARDOUS ATMOSPHE R E , DISCONNECT FROM THE SUPPLY CIRCUIT BEFORE OPENING OR REPLACING FUSE. K EEP TIGHTLY CLOSED WHEN CIRCUITS ARE ALIVE. ALL CONDUIT RUNS MUST BE SEALED WITHIN 18 INCHES (450 mm) OF
THIS ENCLOSURE. BREAKING OF REAR BOLT SEALS VOIDS MANUFACTURER'S
WARRANTY. SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY.
ATTENTION
CET APPAREIL NE PEUT ETRE REPARE A PIED D'OEUVRE. NE PAS L'OUVRIR.
LES BOULONS DOIVENT ETRE BIEN SERRES DEBRANCHE LE TELEPHONE
AVANT LE REMPLACEMENT DU FUSIBLE. RETOURNER L'APPAREIL A L'USINE
POUR LE DEPANNAGE. LE FAIT DE BRISER LE SCEAU DU FABRICANT A
L'ARRIERE DE L'APPAREIL ANNUELE LA GUARANTIE DU FABRICANT.
Industry Canada Industrie Canada
1012 4339 A
13.5" [342mm]
WARNING
FIELD REPAIR NOT POSSIBLE. FOR SERVICE RETURN TO FACTORY. TO PREVENT
IGNITION OF HAZARDOUS ATMOSPHERE, DISCONNECT FROM THE SUPPLY CIRCUIT
BEFORE OPENING OR REPLACING FUSE. KEEP TIGHTLY CLOSED WHEN CIRCUITS ARE ALIVE. ALL CONDUIT RUNS MUST BE SEALED WITHIN 18 INCHES (450 mm) OF THIS ENCLOSURE. BREAKING OF REAR BOLT SEALS VOIDS MANUFACTURER'S WARRANTY. SUBSTITUTION OF COMPO NE NT S MAY IMPAIR INTRINSIC SAFETY.
ATTENTION
CET APPAREIL NE PEUT ETRE REPARE A PIED D'OEUVRE. NE PAS L'OUVRIR. LES BOULONS DOIVENT ETRE B IEN SERRES DEBRANCHE LE TELE PHONE AVANT LE REMPLACEMENT DU FUSIBLE. RETOURNER L'APPAREIL A L'USINE
POUR LE DEPANNAGE. LE FAIT DE BRISER LE SCEAU DU FABRICANT A
L'ARRIERE DE L'APPAREIL ANNUELE LA GUARANTIE DU FABRICANT.
Industry Canada Industrie Canada
1012 4339 A
11.4" [290mm]
12.8" [326mm]
Ø0.3" [Ø9mm]
4.6" [117mm]
2 PLCS.
Figure 2 - Dimensions
Page 4
Avaya Inc. Installation and Operation
Model EA401
Warnings
In no case should this telephone apparatus or wiring be installed in a location where acetylene may be present in the atmosphere.
Two back cover retaining bolts on the model EA401 are factory sealed. Damage to the seals voids the warranty and safety approvals, and may compromise unit safety.
It is the responsibility of the installer to advise a supervisor if any telephone equipment or wiring in a hazardous location may not comply with regulations and standards applicable to that location.
Avoid creating a spark by striking tools or metal objects together, against concrete, stone, or any similar substance.
Test equipment capable of producing an electric spark must not be used in an explosive atmosphere.
All apparatus should be completely assembled and properly sealed before reconnecting power.
General Requirements
A EA401 telephone should only be installed with proper authorization. It is necessary for the customer and the telephone company to have a definite agreement regarding the location of the telephone unit, auxiliary apparatus, and protector (i.e. lightning arrestor at the demarcation block).
NOTE:
To maintain maximum protection, broken or worn parts must be replaced immediately. Any abnormal conditions should be immediately corrected. Periodic inspections are recommended.
Unless otherwise specified, the customer must provide and install explosion-proof conduit and fittings approved by the Canadian Standards Association (CSA) or listed by Underwriters Laboratories (UL). The customer is also responsible for having the system inspected and approved by the appropriate electrical inspector in accordance with local legal requirements and National Electrical Code Standards.
EA401 telephone sets and associated external bells and control relays are designed to provide security against ignition of the surrounding atmosphere. All parts of the apparatus which might produce an electrical spark are completely enclosed. All passages to the outside are made such that any spark or flame will be cooled to a temperature below the ignition threshold before reaching the outside atmosphere.
If the handset or cord is damaged, it must be replaced with part EA10H handset assembly. Handsets and cords are not covered under warranty other than to be free of defects at time of installation.
If the telephone is found to be defective or in need of repair, it must be returned to the manufacturer. No field repair is possible other than replacement of the handset and fuse.
Telephones in good condition may be moved from one location to another.
Page 5
Avaya Inc. Installation and Operation
Model EA401
Installing the EA401
Declassify the hazardous location before proceeding with any
installation or electrical wiring.
Follow all appropriate electrical codes and use only approved electrical fittings for the installation.
Choose a wall location that is free of obstructions and permits space for ½” NPT conduit runs
Ensure mounting can support 16.5lbs. (7.5kg), plus the weight of any peripheral equipment.
Ensure that none of the electrical connection circuits are live.
Use the template provided to locate and drill holes for mounting screws.
Use ¼” bolts or screws to mount the unit.
Secure the unit to the wall:
Attach lower conduit nipples to the telephone and ensure a minimum five
thread engagement.
Mount an approved explosion proof junction box within 45.7 cm (18") of the telephone’s lower sealing cavity and bring telephone wires into this box.
Caution: Installation or electrical wiring in a hazardous location could result in serious injury to personnel or damage to property.
See: Figure 3 - Typical
Installation.
See: Figure 2 ­Dimensions.
Tip: Use ¼” bolts or screws to secure the unit to the wall.
Tip: Fittings compatible with 1/2 inch NPT nipples, conduit, or 1/2 inch explosion-proof flexible couplings not exceeding 45.7 mm (18 inches) may be fitted directly.