Autonics TX4S Operating Manual

LCD Display PID Temperature Controller
TX4S SERIES
I N S T R U C T I O N M A N U A L
Please read the following safety considerations before use.

Safety Considerations

Please observe all safety considerations for safe and proper product operation to avoid hazards.
Safety considerations are categorized as follows.
Warning Failure to follow these instructions may result in serious injury or death. Caution
The symbols used on the product and instruction manual represent the following
symbol represents caution due to special circumstances in which hazards may occur.
Warning
1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)
Failure to follow this instruction may result in personal injury, re, or economic loss.
2. The unit must be installed on a device panel before use.
Failure to follow this instruction may result in electric shock.
3. Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in electric shock.
4. Check the terminal numbers before connecting the power source.
Failure to follow this instruction may result in re.
5. Do not disassemble or modify the unit. Please contact us if necessary.
Failure to follow this instruction may result in electric shock or re.
Caution
1. Do not use the unit outdoors.
Failure to follow this instruction may result in shortening the life cycle of the unit, or electric shock.
2. When connecting the power input and relay output cables, use AWG20 (0.05mm sure to tighten the terminal screw bolt above 0.74N.m to 0.90N.m.
Failure to follow this instruction may result in re due to contact failure.
3. Use the unit within the rated specications.
Failure to follow this instruction may result in shortening the life cycle of the unit, or re.
4. Do not use loads beyond the rated switching capacity of the relay contact.
Failure to follow this instruction may result in insulation failure, contact melt, contact failure, relay broken, or re.
5. Do not use water or oil-based detergent when cleaning the unit. Use dry cloth to clean the unit.
Failure to follow this instruction may result in electric shock or re.
6. Do not use the unit where ammable or explosive gas, humidity, direct sunlight, radiant heat,
vibration, or impact may be present.
Failure to follow this instruction may result in re or explosion.
7. Keep dust and wire residue from owing into the unit.
Failure to follow this instruction may result in re or product damage.
8. Check the polarity of the measurement input contact before wiring the temperature sensor.
Failure to follow this instruction may result in re or explosion.
9. For installing the unit with reinforced insulation, use the power supply unit which basic level is
ensured.

Ordering Information

TX 4 S 1 4 R
Item

Installation

The above specications are subject to change and some models may be discontinued
without notice.
Thank you for choosing our Autonics product.
Failure to follow these instructions may result in personal injury or product damage.
2
) cables and make
Control output
Power supply
Option output
Size
Digit
R Relay output
S SSR drive output
C Selectable current output or SSR drive output
4 100-240VAC 50/60Hz
1 Alarm output 1
2 Alarm output 1+Alarm output 2
A Alarm output 1+Alarm output 2+Trans. output
B Alarm output 1+Alarm output 2+RS485 com. output
S DIN W48×H48mm
4 9999(4 digit)
TX LCD display standard PID temperature controller
Mount the unit on the panel. Push the bracket with tools to fix the unit as the figure.
Specications
Series TX4S Power supply 100-240VAC 50/60Hz Allowable voltage range 90 to 110% of rated voltage Power consumption Max. 8VA Display method 11 segments (PV: white, SV: green), other display (yellow) with LCD method
PV(W×H) 6.9×15.3mm
Character size
SV(W×H) 4.1×9.2mm RTD DPt100Ω, Cu50Ω (permissible line resistance max. 5Ω)
Input type
TC K(CA), J(IC), L(IC), T(CC), R(PR), S(PR) RTD
Display
2
accuracy
TC Relay 250VAC 3A 1a
Control
SSR Max. 12VDC ± 2V 20mA
output
Current DC4-20mA or DC0-20mA (load resistance max. 500Ω) Alarm output AL1, AL2 Relay: 250VAC 3A 1a
Option
Trans. output DC4-20mA (load resistance max. 500Ω, output accuracy: ±0.3%F.S.)
output
Com. output RS485 Communication output (Modbus RTU method) Control method ON/OFF control, P, PI, PD, PID control Hysteresis 1 to 100℃/℉ (0.1 to 50.0℃/℉) variable Proportional band(P) 0.1 to 999.9℃/ Integral time(I) 0 to 9999 sec. Derivative time(D) 0 to 9999 sec. Control period(T) 0.5 to 120.0 sec. Manual reset 0.0 to 100.0% Sampling period 50ms Dielectric strength 3,000VAC 50/60Hz for 1 min. (between all terminals and case) Vibration 0.75mm amplitude at frequency 5 to 55Hz (for 1 min.)in each X, Y, Z direction for 2 hours
Mechanical OUT, AL1/2: Min. 5,000,000 operations
Relay life cycle
Electrical OUT, AL1/2: Min. 200,000 (250VAC 3A resistance load) Insulation resistance Min. 100MΩ (at 500VDC megger) Noise resistance Square shaped noise by noise simulator (pulse width 1㎲) ±2kV R-phase, S-phase Memory retention Approx. 10 years (non-volatile semiconductor memory type)
Ambient temp. -10 to 50℃, storage: -20 to 60
Environ­ment
Ambient humi. 35 to 85%RH, storage: 35 to 85%RH Protection structure IP50 (front panel, IEC standards) Insulation type Double insulation (mark: Approval
3
Weight
1: When using the unit at low temperature (below 0
Control output operates normally.
At room temperature(23
2:
TC R(PR), S(PR) , below 200
TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±2
Out of room temperature range
TC R(PR), S(PR): (PV ±1.0% or ±5
TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±3
3: The weight includes packaging. The weight in parentheses is for unit only.
Environment resistance is rated at no freezing or condensation.

Unit Description

4 5 6
7 8
10

Connection

OUT SSR 12VDC
± Current DC0/4-20mA Load 500 Relay 250VAC 3A 1a RESISTIVE LOAD
SOURCE 100-240VAC 50/60Hz 8VA
●At room temperature (23℃±5℃): (PV ±0.3% or ±1℃, select the higher one) ±1digit Out of room temperature: (PV ±0.5% or ±2℃, select the higher one) ±1digit
: ,
dielectric strength between all terminals and case: 3kV)
Approx. 135.2g (approx. 85.2g)
)
℃±5℃
: (PV ±0.5% or ±3℃, select the higher one) ±1 digit
, over 200℃: (PV ±0.5% or ±2℃, select the higher one) ±1 digit
1. Measured value (PV) component:
2. Setting value (SV) display component:
1
3. Temperature unit(℃/℉) indicator:
3 2
4. Control output (OUT1) indicator: Turns ON while control output is ON.
9
5. Alarm output (AL1, AL2) indicator:
6. Auto-tuning indicator:
7. key: Enters parameter group, returns to RUN mode, moves parameters,
and saves the setting value.
8. Setting value adjutment key: Enters SV setting mode and move digits.
9. Digital input key: Press the
functions which is set at digital input key[ clear alarm output, auto-tuning).
10. PC loader port: It is for serial communication to set parameter and monitoring by
DAQMaster installed in PC. Use this for connection EXT-US (converter cable, sold separately) + SCM-US (USB to Serial converter, sold separately).
2V 20mA Max.
1
Max.
2
3
+-+
mA
-
4
5
6
℃), display cycle is slow.
, select the higher one) ±1 digit
, select the higher one) ±1 digit
, select the higher one) ±1 digit
RUN mode: Displays current measured value (PV). SETTING mode: Displays parameters.
RUN mode: Displays setting value(SV). SETTING mode: Displays setting value of parameter.
Displays the set temperature unit as temperature unit [ parameter 2 group.
Turns ON when MV is over 3.0% at cycle/phase control of SSR drive
output method.
Turns ON when the corresponding alarm output turns ON.
Flashes during auto-tuning every 1 sec.
+
RS485(A+)
mA
­RS485(B-)
Communication Output Transfer Output DC4-20mA
+ keys for 3 sec. to execute the digital input key
13
14
15
16
17
18
]of parameter 2 group (RUN/STOP,
DI-K
Shaded terminals is standard model.
7
8
9
10
11
12
AL1 OUT: 250VAC 3A 1a RESISTIVE LOAD
AL2 OUT: 250VAC 3A 1a RESISTIVE LOAD
A
B
B'
SENSOR
1
] of
UNIT
+
-
TCRTD

Input Type And Range

Input type Decimal point Display Input range(℃) Input range(℉)
Thermocouple
RTD
K(CA)
J(IC)
L(IC)
T(CC)
R(PR) 1 S(PR) 1
DPt 100Ω
CU50Ω
1
0.1 1
0.1 1
0.1 1
0.1
1
0.1 1
0.1
-50 to 1200 -58 to 2192
KCaH
-50.0 to 999.9 -58.0 to 999.9
KCaL
-30 to 800 -22 to 1472
JIcH
-30.0 to 800.0 -22.0 to 999.9
JIcL
-40 to 800 -40 to 1472
LIcH
-40.0 to 800.0 -40.0 to 999.9
LIcL
-50 to 400 -58 to 752
TCcH
-50.0 to 400.0 -58.0 to 752.0
TCcL
0 to 1700 32 to 3092
RPR
0 to 1700 32 to 3092
SPR
-100 to 400 -148 to 752
DPtH
-100.0 to 400.0 -148.0 to 752.0
DPtL
-50 to 200 -58 to 392
CUsH
`-50.0 to 200.0 -58.0 to 392.0
CUsL

Parameter Groups

RUN mode
Press any key among
, , , once.
SV setting Parameter 1 group[
Order of parameter setup
All parameters are related one another. Set the parameters as above order.
If there is no key input for 30 sec. while setting SV or the parameters, the new settings are ignored, and
the unit will return to RUN mode with previous settings. When returning to RUN mode by holding the
re-enter the first parameter of previous parameter group. Hold the
● SV setting
Check SV
+ + keys for 5 sec. in RUN mode, to enter re-set parameter menu. Select '
parameters are reset as factory default.
To change set temperature from 210℃ to 250
RUN mode
SV setting mode
● Parameter 1 group
RUN mode
3 sec.
PAR1
AL1 temperature
AL1
AL2 temperature
AL2
Auto-tuning
Parameter 2 group
Press any key among
Change SV
, ,
key
: Press any key among , , .
1: 2: Press the
value and move to the next parameter Hold the key for 3 sec. to save the setting value and return to RUN mode after changing the setting value. Dotted parameters may not appear by model type or other parameter settings.
Setting range: Deviation alarm(-[F.S] to [F.S]),
1250
2
1250
2 sec.
by
※ ※
1
AT
Proportional band
P
Integral time
I
Derivative time
D
Manual reset
REST
Hysteresis
Setting range: 0.1 to 999.9℃/
1)0
Setting range: 0 to 9999 sec.
Integral operation will be OFF
0
when the setting value is '0.
Setting range: 0 to 9999 sec.
Derivative operation will be OFF
0
when the setting value is '0.
Setting range: 0.0 to 100.0%
Only appears in P, PD control.
5)0
Setting range: 1 to 100℃/℉ (0.1 to 50.0℃/℉)
Only appears when control method [
2HYS
set as

Dimensions

5
45
31
20
5
36
15
21
Bracket
44.9
48
48.6 45
55
56
] Parameter 2 group[
PAR1
3 sec.
Parameter 1 group SV setting
key for over
3 sec., press the
,
, ,
once.
key once after changing the setting value, to save the setting
Absolute value alarm(temperature range) Does not appear when AL1/AL2 alarm operation[ of parameter 2 group is set as Only alarm output 2 models have [
When setting as
completing,
ONOFF
During auto-tuning, the auto-tuning indicator
ashes (every 1 sec.).
.
ONOF
AM)_/SBa
ON
is automatically set.
OFF
Panel cut-out dimensions
44.8 Min. 65
Terminal cover(sold separately)
RSA-COVER(48×48mm)
48.4
16
9.8
22.5
4 sec. 2 sec.
PAR2
3 sec.
key within
1 sec. to
' and all
YES
Completes SV
setting
AL-1, AL-2
.
/
LBa
].
AL2
, the unit starts auto-tuning. After
Only appears when control
method [ 2 group is set as
C-MD
] of parameter
C-MD
PID
] of parameter 2 group is
(unit:mm)
Min. 65
+0.6
45
0
41.5
22
18
● Parameter 2 group
3 sec.
]
Input sensor
Temp. unit
correction
Input digital
SV low-limit
SV high-limit
output mode
Control method
selection
SSR drive
operation
]
operation
hysteresis
monitoring
.
+0.6
detection
output low-
limit value
output high-
limit value
address
parity-bit
0
45
stop-bit
response
waiting time
input key
output MV for
input break
: Press any key among , , .
1:
2: Press the
1
RUN mode
4 sec.
PAR2
IN-T KCaH
value and move to the next parameter
Hold the key for 3 sec. to save the setting value and return to RUN mode
after changing the setting value. Dotted parameters may not appear by model type or other parameter
settings.
UNIT ?F?C
Input
IN-B 0
MAvF )1
lter
L-SV -50
value
H-SV 1200
value
Control
O-FT HEAT COOL
Setting range: -999 to 999
Setting range: 0.1 to 120.0 sec.
Setting range: Within temperature range of each sensor[
Setting range: Within temperature range of each sensor [
C-MD PID ONOF
Control
output
OUT CURR SSR
output
SSrM STND CYCL PHAS
method
Current
output
oMA 4-20 0-20
range
Control
cycle
AL1
AL2
Alarm output
LBA
time
LBA
band
Trans.
Trans.
Comm.
Comm.
speed
Comm.
Comm.
Comm.
Comm.
write
Digital
Control
Lock
T 2)0
AL-1
AL-2 AM@A
AHYS 1
LBaT 0
LBaB 2
FS-L -50
FS-H 1200
ADRS 1
BPS 96
PRTY
STP 2 1
RSwT 20
COMW EnA DIsA
DI-K
ErMV )0
LOC LOC1 LOC2 LOC3OFF
Setting range: 0.5 to 120.0 sec.
※ ※
Alarm operation
Press the key to switch 'Alarm operation'
'Alarm option' setting.
Setting range: 1 to 100℃/℉(0.1 to 100.0℃/℉)
Setting range: 0 to 9999 sec.(automatically set during auto-tuning)
Setting range: 0 to 999
Setting range: 1 to 127
Setting range: 24, 48, 96, 192, 384 bps Multiply 100 to read the setting value.
NONE EVEN ODD
Setting range: 5 to 99ms
Setting range: 0.0 to 100.0%
key once after changing the setting value, to save the setting
Setting range: Refer to '
When changing the setting value, SV, [
AL1, AL2, LBaB, AHYS
2
reset.
When changing the setting value, SV, [
L-SV, AL1, AL2, LBaB, AHYS
parameter 2 group are reset.
When changing the setting value, and SV
When changing the setting value, and SV
When changing the setting value, [
[
DI-K
Appears only in selectable current output or SSR drive
output model(TX4S- 4C).
Appears only when control output[
Appears only when control method[ Does not appear when SSR drive output is set as
LBaAAM!A
Set method is same as AL1 alarm operation[
AL-1
Appears only in alarm output 2 models.
Does not appear when AL1/AL2 alarm operation[ as
AM)_/SBa
Appears only when alarm operation[
(automatically set during auto-tuning) Appears only when alarm operation [ and [
] is not set as 0.
LBaT
Setting range: Refer to ' Input Type And Range'.
Appears only in transmission output model(TX4S-A4
Input Type And Range'.
] parameters of parameter 2 group are
(-199.9 to 999.9℃/℉)
℃/℉
L-SV
H-SV
] is reset as
.
OFF
Appears only in SSR drive output model
(TX4S- 4S).
] is
C-MD
AM!A AM!B
Alarm option
].
.
/
LBa
AL-1, AL-2
(0.0 to 999.9℃/℉)
℃/℉
AL-1, AL-2
Appears in RS485
communication output model(TX4S-B4 ).
IN-B, H-SV/L-SV
] parameters of
PID
AlRE OFFATSTOP
does not appear when control method [
AT
is set as
(OFF)/
Only
)0
] is set as
10)0
Setting range:
10)0 ONOF
LOC1 LOC2 LOC3
[
C-MD
When control method [ value is below
(ON) appear when control method
, it is reset as )0.
OFF
.
ONOF
.
] is changing
C-MD
Unlock Parameter 2 group lock Parameter 1,2 group lock Parameter 1,2 group, SV setting lock
PID↔ONOF
IN-B, H-SV
L-SV≤(H-SV
, SV is reset as
H-SV≥(L-SV
, SV is reset as
] is reset as )0,
ErMV
] is set as
OUT
.
, or
CYCL
When changing the
setting value, [
AL1, AL2
parameter of parameter 1 group is reset.
AL-1, AL-2
] is set as
] is set as
).
and the setting
PHAS
LBa
LBa
,
/
-1digit)]
L-SV
+1digit)]
H-SV.
CURR
]
] is set
.
C-MD
.
.
.
]
Alarm[

Alarm

operation
Alarm operation
AL-1/ AL-2
AM!A

] Functions

Set both alarm operation and alarm option by combining. Each alarm operates individually in two alarm output models. When the current temperature is out of alarm range, alarm
Alarm option
clears automatically. If alarm option is alarm latch or alarm latch and standby sequence 1/2, press digital input key( digital input key[ turn OFF the power and turn ON to clear alarm.
] of parameter 2 group set as
DI-K
+ 3 sec.,
AlRE
Mode Name Alarm operation Description
- -
AM)_
Deviation high-limit
AM!
alarm
Deviation low-limit
AM@
alarm
Deviation high/low-
AM#
limit alarm
Deviation high/low­limit
AM$
reserve alarm
Absolute value high
AM%
limit alarm
Absolute value low
AM^
limit alarm
Sensor
SBa
break alarm
Loop break
LBa
alarm
H: Alarm output hysteresis [
Alarm option
Option Name Description
Standard
AM
.A
alarm
Alarm latch
AM
.B
Standby
AM
.C
sequence 1
Alarm latch and standby
AM
.D
sequence 1
Standby
AM
.E
sequence 2
Alarm latch and standby
AM
.F
sequence 2
Condition of re-applied standby sequence for standby sequence 1, alarm latch and standby sequence 1: Power ON
Condition of re-applied standby sequence for standby sequence 2, alarm latch and standby sequence 2: Power ON, changing set temperature, alarm temperature [ to RUN mode.
Sensor break alarm
The function that alarm output will be ON when sensor is not connected or when sensor's disconnection is detected during temperature controlling. You can check whether the sensor is connected with buzzer or other units using alarm output contact. It is selectable between standard alarm [
Loop break alarm
It checks control loop and outputs alarm by temperature change of the subject. For heating control(cooling control), when control output MV is 100%(0% for cooling control) and PV is not increased over than LBA detection band [ control) and PV is not decreased below than LBA detection band [ alarm output turns ON.
Start control to
to
to
to
to
to
to
to
When executing auto-tuning, LBA detection band[
on auto tuning value. When alarm operation mode [ detection band [
OFF ONH
SV
100PV110
High-limit deviation: Set as 10High-limit deviation: Set as -10
PV
90SV100
Low-limit deviation: Set as 10℃ Low-limit deviation: Set as -10
PV
90
High, Low-limit deviation: Set as 10
OFF OFFONH H
PV
90
High, Low-limit deviation: Set as 10
OFF ONH
PV
90SV100
Alarm absolute-value: Set as 90Alarm absolute-value: Set as 110
PV
90
Alarm absolute-value: Set as 90 Alarm absolute-value: Set as 110
100
-
-
AHYS
If it is an alarm condition, alarm output is ON. If it is a clear alarm condition, alarm output is OFF.
If it is an alarm condition, alarm output is ON and maintains ON status. (Alarm output HOLD)
First alarm condition is ignored and from second alarm condition, standard alarm operates. When power is supplied and it is an alarm condition, this rst alarm condition is ignored and from the second alarm condition, standard alarm operates.
If it is an alarm condition, it operates both alarm latch and standby sequence. When power is supplied and it is an alarm condition, this rst alarm condition is ignored and from the second alarm condition, alarm latch operates.
First alarm condition is ignored and from second alarm condition, standard alarm operates. When re-applied standby sequence and if it is alarm condition, alarm output does not turn ON. After clearing alarm condition, standard alarm operates.
Basic operation is same as alarm latch and standby sequence1. It operates not only by power ON/OFF, but also alarm setting value, or alarm option changing. When re-applied standby sequence and if it is alarm condition, alarm output does not turn ON. After clearing alarm condition, alarm latch operates.
(LBA)
] during LBA monitoring time [
LBaB
When control output MV is 100%, PV is increased over than LBA detection band [ LBA monitoring time [
The status of changing control output MV (LBA monitoring time is reset.)
When control output MV is 0% and PV is not decreased below than LBA detection band [ during LBA monitoring time [
Control output MV is 0% and loop break alarm (LBA) turns and maintains ON.
The status of changing control output MV (LBA monitoring time is reset.)
When control output MV is 100% and PV is not increased over than LBA detection band [ during LBA monitoring time [
When control output MV is 100% and PV is increased over than LBA detection band [ during LBA monitoring time [
The status of changing control output MV (LBA monitoring time is reset.)
LBaB
LBaT
] and LBA monitoring time [
OFF ONH
PV
90SV100
OFFON H
SV
100PV110
OFFON ONH H
SV
100
SV
100
OFFON H
SV
PV
110
PV
110
OFF ONH
SV
100PV110
SV
100PV110
]
] or alarm operation [
AL1, AL2
], or when control output MV is 0%(100% for cooling
LBaT
].
], loop break alarm (LBA) turns ON after LBA monitoring time.
LBaT
], loop break alarm (LBA) turns ON after LBA monitoring time.
LBaT
], loop break alarm (LBA) turns OFF after LBA monitoring time.
LBaT
] and LBA monitoring time are automatically set based
LBaB
AL-1, AL-2
] parameter is displayed.
LBaT
No alarm output
If deviation between PV and SV as high-limit is higher than set value of deviation temperature, the alarm output will be ON.
OFFON H
If deviation between PV and SV as low-limit is higher than set value of deviation temperature, the alarm output will be ON.
If deviation between PV and SV as high/low-limit is higher than set value of deviation temperature, the alarm output will be ON.
If deviation between PV and SV as high/low-limit is higher than set value of deviation temperature, the alarm output will be OFF.
If PV is higher than the absolute value, the output will be ON.
OFFON H
If PV is lower than the absolute value, the output will be ON.
It will be ON when it detects sensor disconnection.
It will be ON when it detects loop break.
], switching STOP mode
AL-1, AL-2
] or alarm latch [
SBaA
] during LBA monitoring time [
LBaB
LBaB
] is set as loop break alarm(LBA)[
SBaB
].
LBaT
] during
LBaB
LBaB
LBaB
LBa
1. Input correction[
Controller itself does not have errors but there may be error by external input temperature sensor. This function is for correcting this error. Ex) If actual temperature is 80℃ but controller displays 78℃, set input correction value [ controller displays 80
), or
As the result of input correction, if current temperature value (PV) is over each temperature range of input
sensor, it displays
2. Input digital lter[
If current temperature (PV) is uctuating repeatedly by rapid change of input signal, it reects to MV and stable control is impossible. Therefore, digital lter function stabilizes current temperature value. For example, set input digital lter value as 0.4 sec, and it applies digital lter to input values during 0.4 sec and displays these values. Current temperature may be different by actual input value.
3. SSR drive output method (SSRP function)[
SSRP function is selectable one of standard ON/OFF control, cycle control, phase control by utilizing standard SSR drive output.
This function parameter appears only in SSR drive output model (TX4S- 4S).
Realizing high accuracy and cost effective temperature control with both current output (4-20mA) and linear output(cycle control and phase control)
Select one of standard ON/OFF control [ parameter of parameter 2 group. For cycle control, connect a zero cross turn-on SSR or random turn-on SSR. For phase control, connect random turn-on SSR.
Temperature controller
(TX4S Series)
100-240VAC
When selecting cycle or phase control mode, the power supply for a load and a temperature controller must be the same.
Control cycle[T] is able to set only when control method[
drive output method [ In case of selectable current output or SSR drive output model(TX4S- 4C), this parameter does not appear.
Standard ON/OFF control by SSR is only available.
1)Standard ON/OFF control [ Controls ON (100% output)/OFF (0% output) as same as standard relay output.
2)Cycle control [ Controls the load by repeating output ON / OFF according to the rate of output within setting cycle based on certain period (50-cycle). Control accuracy is almost the same with phase control’s. This control has improved ON/ OFF noise than phase control’s due to zero cross type which turns ON/OFF at zero point of AC.
3)Phase control [
Controls the load by controlling the phase within AC half cycle. Serial control is available. Must use random turn-on SSR for this mode.
4. Current output range[
In case of selectable current output or SSR drive output model(TX4S- 4C), when control output [ parameter 2 group is set as [ current output.
5. Hysteresis[
Set interval between ON and OFF of control output for ON/OFF control.
If hysteresis is too narrow, hunting(oscillation, chattering) could
occur due to external noise. In case of ON / OFF control mode, even if PV reaches stable
status, there still occurs hunting. It could be due to hysteresis [
HYS
location. In order to reduce hunting to a minimum, it is required to take into following factors consideration when designing temp. controlling; proper Hysteresis [ characteristics, sensor’s response and location.
6. Manual reset[
],
When selecting P/PD control mode, certain temperature difference exists even after PV reaches stable status because heater's rising and falling time is inconsistent due to thermal characteristics of controlled objects, such as heat capacity, heater capacity. This temperature difference is called offset and manual reset [ correct offset. When PV and SV are equal, reset value is 50.0%. After control is stable, PV is lower than SV, reset value is over 50.0% or PV is higher than SV, reset value is below 50.0%.
CYCL
HYS
] setting value, load’s response characteristics or sensor’s
7. Digital input key( + 3 sec.)[
Parameter
Time
]
OFF
RUN/STOP
]
Clear alarm
]
Auto-tuning
8. Control output MV for input break[
When input sensor is break, set control output MV.
], LBA
When control method[ or
10)0
STOP
AlRE
(ON). When control method[
]
IN-B
℃.
or
HHHH
Power
50/60Hz
PHAS
]
]
.
LLLL
]
MAvF
SSrM
], cycle control [
STND
SSR voltage output
(12VDC)
SSrM
] is set as
STND
]
oMA
CURR
.
STND
]
AC
OUT
ON ONOFF OFF
AC
OUT
AC
OUT
], you can select high/low-limit range, 4-20mA [
]
] , phase control [
CYCL
SSR module
]of parameter group 2 is set as
C-MD
50 Cycle 50 Cycle
50% 80%
10% 50%
4-20
]
Control output
], heater’s capacity, thermal
HYS
]
REST
] function is to set/
REST
]
Operation
It does not use digital input key function.
OFF
Pauses control output. Auxiliary output (except loop break alarm, sensor break alarm) except Control output operates as setting. Hold the digital input keys for 3 sec. to restart.
DI-K
ON OFF
●Manual reset [
Set below 50.0 as reset value
SV
Set over 50.0 as reset value
t t tt
RUN RUN
STOP STOP RUN
Clears alarm output by force. (only when alarm option is alarm latch, or alarm latch and standby sequence 1/2 .)
This function is applied when present value is out of alarm operation range but alarm output is ON. Alarm operates normally right after clearing alarm.
Starts/Stops auto-tuning. This function is same as auto-tuning[AT] of parameter 1 group. (You can start auto-tuning [AT] of parameter 1 group and stop it by digital input key.)
AT
This parameter AT appears only when control method [
is set as parameter is changed as
. When control method [
PID
ErMV
] of parameter 2 group is set as
C-MD
C-MD
] is set as
C-MD
.
OFF
]
, set control output MV as )0(OFF)
ONOF
, setting range for control output MV is )0 to
PID
C-MD
] parameter 2 group is set as
] as '2' and
IN-B
PHAS
Load
PID
OUT
] or 0-20mA [
Heating operation
Hysteresis
[
]
HYS
SV
] by control result
REST
Offset
Offset
Digital input key
(t: over 3 sec.)
] parameter 2 group
] at
SSrM
and SSR
]
] of
0-20
Temp.
, this
ONOF
.
10)0

Comprehensive Device Management Program[DAQMaster]

DAQMaster is a comprehensive device management software for setting parameters and monitoring processes. DAQMaster can be downloaded from our web site at www.autonics.com.
Item Minimum specications System IBM PC compatible computer with Pentium Ⅲ or above Operations Windows 98/NT/XP/Vista/7/8/10 Memory 256MB+ Hard disk 1GB+ of available hard disk space VGA Resolution: 1024×768 or higher Others RS232C serial port (9-pin), USB port

RS485 Communication Output

Applicable for models with RS485 communication output through option output(TX4S-B4 ). Please refer to ' Ordering Information'.
1. Communication Specications
Com. protocol Modbus RTU
Applied standard EIA RS485
Max. connections 31 units(address: 1 to 99) Start-bit 1-bit xed
Com. method 2-wire half duplex Data-bit 8-bit xed
Synchronization method
Com. distance Within 800m Stop-bit 1, 2Bit
Com. response time 5 to 99ms
2. Modbus Mapping Table
2-1. Read Coil Status (Func 01) / Force Single Coil (Func 05) [Func: 01/05, R/W: R/W]
No.(Address) Type Description
000001(0000) RUN/STOP 000002(0001) AT Auto-tuning run/stop 0: 000003(0003) Alarm Reset Alarm output clear 0: 000004 to 000050 Reserved
Asynchronous Parity-bit None, Even, Odd
Related coil, variable
Com. speed
Control output run/stop
2-2. Read Discrete Inputs(Func 02) [Func: 02, R/W: R]
No.(Address) Type Description
100001(0000)℃ indicator 100002(0001)℉ indicator Unit indicator 0: OFF 1: ON - ­100003(0002) OUT indicator Control output indicator 0: OFF 1: ON - ­100004(0003) AT indicator Auto-tuning indicator 0: OFF 1: ON - ­100005(0004) AL1 indicator Alarm output 1 indicator 0: OFF 1: ON - ­100006(0005) AL2 indicator Alarm output 2 indicator 0: OFF 1: ON - ­100006 to 100050 Reserved
Unit indicator 0: OFF 1: ON - -
Front indicator
2-3. Read Input Registers (Func 04) [Func:02, R/W : R]
No.(Address) Type Description
300001 to 300100 Reserved 300101(0064) - Product number H - -
300102(0065) - Product number L - -
300103(0066) - Hardware version - ­300104(0067) - Software version - ­300105(0068) - Model 1 - - "TX" 300106(0069) - Model 2 - - " 4" 300107(006A) - Model 3 - - "S " 300108(006B) - Model 4 - - "14" 300109(006C) - Model 5 - - "R " 300110(006D) - Model 6 - - " " 300111(006E) - Model 7 - - " " 300112(006F) - Model 8 - - " " 300113(0070) - Model 9 - - " " 300114(0071) - Model 10 - - " " 300115(0072) - Reserved - - ­300116(0073) - Reserved - - ­300117(0074) - Reserved - - ­300118(0075) - Coil status start address - - 0000 300119(0076) - Coil status quantity - - 0 300120(0077) - Input status start address - - 0000 300121(0078) - Input status quantity - - 0 300122(0079) - Holding register start address - - 0000 300123(007A) - Holding register quantity - - 0 300124(007B) - Input register start address - - 0000 300125(007C) - Input register quantity - - 0 300127 to 300200 Reserved 301001(03E8) PV Present value -1999 to 9999℃/
301002(03E9) DOT Decimal point location
301003(03EA) UNIT Display unit 0: ?C, 1: 301004(03EB) SV Setting value
301005(03EC)
310006 to 310050 Reserved
2-4. Read Holding Register (Func 03)/Preset Single Register (Func 06)/
Preset Multiple Registers (Func 16)[Func:03/06/16, R/W : R/W]
2-4-1. SV setting
No.(Address) Parameter Description Setting/Display range Unit Default
400001(0000) Set value SV setting value Within
400002 to 400050 Reserved
2-4-2. Parameter 1 group [
No.(Address) Parameter Description Setting/Display range Unit Default
400051(0032)
400052(0033)
400053(0034)
400054(0035)
400055(0036)
400056(0037)
400057(0038)
400058(0039)
400059 to 400100 Reserved
indicator
indicator
OUT indicator AT indicator AL1 indicator AL2 indicator
AL1
AL2
AT
REST
HYS
Unit indicator 0: OFF 1: ON - ­Unit indicator 0: OFF 1: ON - ­Control output indicator 0: OFF 1: ON - -
Front indicator
Auto-tuning indicator 0: OFF 1: ON - ­Alarm output 1 indicator 0: OFF 1: ON - ­Alarm output 2 indicator 0: OFF 1: ON - -
]
PAR1
AL1 temperature
AL2 temperature
Auto-tuning 0:
Proportional band 1 to 9999: )1 to
P
Integral time 0 to 9999: 0 to
I
Derivative time 0 to 9999: 0 to
D
Manual reset 0 to 1000: )0 to
Hysteresis
Deviation temperature: -F.S. to F.S. Absolute value alarm: Temperature range
1:
OFF
ON
9999
9999
1 to 100(1 to 500):
2400, 4800, 9600, 19200, 38400 bps
Setting/Display range 0:
1:
RUN
1:
OFF
1:
OFF
Setting/Display range
Setting/Display range
0:0, 1:)0, 2:
)00
Within
to
L-SV
H-SV /℉ 0
99(9 /℉ 1)0
10)0
to
1
100()1
STOP ON ON
, 3:
L-SV
to
5)0
)000 ?F
to
)
H-SV
Unit Default
-
-
-
Unit Default
Unit Default
- -
- -
℃/℉ 0
℃/℉ 1250
-
Sec.
Sec.
%
-
STOP OFF OFF
Dedicated model number
-
OFF
5)0
2-4-3. Parameter 2 group [
No.(Address)
400101(0064)
400102(0065)
400103(0066)
400104(0067)
400105(0068)
400106(0069)
400107(006A)
400108(006B)
400109(006C)
400110(006D)
400111(006E)
400112(006F)
400113(0070)
400114(0071)
400115(0072)
400116(0073)
400117(0074)
400118(0075)
400119(0076)
400120(0077)
400121(0078)
400122(0079)
400123(007A)
400124(007B)
400125(007C)
400126(007D)
400127(007E)
400128(007F)
400129 to 400150
Parameter
IN-T
UNIT
IN-B
MAvF
L-SV
H-SV
O-FT
C-MD
OUT
SSrM
oMA
AL-1
AL-2
AHYS
LBaT
LBaB
FS-L
FS-H
ADRS
BPS
PRTY
STP
RSwT
COMW
DI-K
ErMV
LOC
Reserved
]
PAR2
Description Setting/Display range Unit Default
Input sensor Refer to ' Input Type And Range' -
Temperature unit 0: ?C, 1:
Input correction
Input digital lter 1 to 1200: )1 to
SV low-limit value
SV high-limit value
Control output mode 0:
control method 0:
Control output selection
SSR drive output method
Current output range 0:
Control cycle 5 to 1200: )5 to
T
AL1 operation
AL2 operation
Alarm output hysteresis
LBA detection time 0 to 9999: 0 to
LBA detection band
Trans. output low­limit value
Trans. output high­limit value
Com. address 1 to 127: 1 to
Com. speed 0: 24, 1: 48, 2: 96, 3:
Com. parity bit 0:
Com. stop bit 0: 1, 1:
Com. response waiting time
Com. write 0:
Digital input key 0:
Control output MV for input break
Lock 0:
?F
-999 to 999(-1999 to 9999): to
-999
Refer to ' Input Type And Range'
HEAT
, 1:
PID
0:
, 1:
SSR
0:
STND
4-20
00:
AM)_
60 to 65: 70:
SBaA
1 to 100(1 to 500): 1 to
0 to 999(0 to 9999): 0 to
Refer to ' Input Type And Range'.
NONE
5 to 99: 5 to
, 1:
EnA
, 1:
OFF
0 to 1000: )0(OFF) to
, 1:
OFF
999(`9(9
, 1:
COOL
ONOF
CURR
, 1:
CYCL
, 1:
0-20
, 10 to 15:
AM^A
, 71:
SBaB
127
, 1:
EVEN
2
99
DIsA
STOP
LOC1
to
9999
, 2:
, 2:
12)0
, 2:
12)0
AM^F
, 2:
to
PHAS
AM!A
, 80:
ODD
AlRE
LOC2
99(9
100()1
999()0
192
10)0
)
to
AM!F
,
, 81:
LBaA
to
to
99(9
, 4:
384
, 3:
AT
(ON) %
, 3:
LOC3
5)0
, ...
LBaB
) -
)

Error

Display Description Troubleshooting
Flashes when input sensor is disconnected or sensor is not connected. Check input sensor status.
OPEN
Flashes when measured value is higher than input range.
HHHH
Flashes when measured value is lower than input range.
LLLL

Factory Default

SV setting
Parameter Factory default
-
0
Parameter 2 group
Parameter Factory default Parameter Factory default
Parameter 1 group
Parameter Factory default
AL1 AL2
1250
AT OFF
P 1)0 I D
0
REST 5)0
HYS 2
IN-T KCaH AHYS 1 UNIT ?C LBaT 0 IN-B 0 LBaB 2 MAvF )1 FS-L -50 L-SV -50 FS-H 1200 H-SV 1200 ADRS 1 O-FT HEAT BPS 96 C-MD PID PRTY NONE
OUT CURR STP 2
SSrM STND RSwT 20
oMA 4-20 COMW EnA
T
(Relay)
2)0 DI-K STOP
(SSR drive)
@0 ErMV )0
AL-1 AM!A LOC OFF
When input is within the rated input range, this display disappears.
AL-2 AM@A

Caution During Use

1. Please separate the unit wiring from high voltage lines or power lines to prevent inductive noise.
2. For crimp terminal, select following shaped terminal (M3).
Max. 5.8mm Max. 5.8mm
3. Install a power switch or circuit breaker to control the power supply.
4. The power switch or circuit breaker should be installed where it is easily accessible by the user.
5. The unit is for temperature controller. Do not use the unit as volt-meter or ampere-meter.
6. When using RTD temperature sensor, must wire it as 3-wire type. If cable is extended, use 3 wires which are same thickness as the line. It might cause the deviation of temperature when line resistance is different.
7. If power line and input signal line are close each other, install line lter for noise protection at power line and use shielded input signal line.
8. Keep away from the high frequency instruments.(High frequency welding machine & sewing machine, large capacity SCR controller).
9. When supplying the measured input, the unit displays Turn OFF the power to the unit and check the line. .
10. This unit may be used in the following environments.
It shall be used indoor.
Pollution degree 2.
Failure to follow these instructions may result in product damage.
Altitude up to 2,000m.
Installation category II.
HHHH
or
, the measured input may have problem.
LLLL

Major Products

Photoelectric Sensors Temperature Controllers Fiber Optic Sensors Temperature/Humidity Transducers Door Sensors SSR/Power Controllers Door Side Sensors Counters Area Sensors Timers Proximity Sensors Panel Meters Pressure Sensors Tachometer/Pulse(Rate)Meters Rotary Encoders Display Units Connector/Sockets Sensor Controllers
0
Switching Mode Power Supplies Control Switches/Lamps/Buzzers
0
I/O Terminal Blocks & Cables Stepper Motors/Drivers/Motion Controllers Graphic/Logic Panels
2
Field Network Devices Laser Marking System(Fiber, Co₂, Nd:yag) Laser Welding/Cutting System
http://www.autonics.com
Trusted Partner In Industrial Automation
HEADQUARTERS:
18, Bansong-ro 513beon-gil, Haeundae-gu, Busan, South Korea, 48002
OVERSEAS SALES:
#402-303, Bucheon Techno Park, 655, Pyeongcheon-ro, Wonmi-gu, Bucheon, Gyeonggi-do, South Korea, 14502 TEL: 82-32-610-2730 / FAX: 82-32-329-0728
E-mail: sales@autonics.com
EP-KE-03-0400B
KCaH
-
-
Sec.
-50
℃/℉
1200
-
HEAT
-
PID
-
CURR
-
STND
-
4-20
2)0
Sec.
AM!A
-
AM@A
Sec.
℃/℉ 2
-
-50
-
1200
-
-
-
NONE
-
ms
-
EnA
-
STOP
-
OFF
?C
)1
@0
96
20
)0
0
(Relay)
(SSR drive)
1
0
1
2
Loading...