6.2 Calibrating values related to the rest position of proportional outputs
(oset)
1. Start up the radio remote control.
2. Press the TEACH pushbutton in the receiving unit and do not release it until the SETUP
LED illuminates.
3. Enable and release the TEACH + command of the corresponding switch on the transmitting
unit and press and release the START pushbutton within one second.
4. Repeat actions described in the previous point until the SETUP LED on the receiving
unit starts blinking three times.
5. Set the desired values as follows:
- Move the joystick out of the rest position of the axis to be calibrated. Maintain the
position and use the TEACH selector on the transmitting unit to set the desired value.
- After calibrating one joystick, press the STOP pushbutton to save calibrations.
Calibrations are saved in the data memory on the DTK connector.
6. To set other values, unlock the STOP pushbutton, press the START pushbutton and
repeat actions described in the previous point.
7. To leave the procedure, press the TEACH pushbutton on the receiving unit and do not
release it until the SETUP LED switches o.
If the proportional outputs are activated by actuators that are not joysticks (i.e.
potentiometer, switch), calibrate values related to the rest position according to
the above mentioned procedure.
6.3 Inversion of movement direction of the joystick's axis
1. Start up the radio remote control.
2. Press the TEACH pushbutton in the receiving unit and do not release it until the SETUP
LED illuminates.
3. Enable and release the TEACH + command of the corresponding switch on the transmitting
unit and press and release the START pushbutton within one second.
4. Repeat actions described in the previous point until the SETUP LED on the receiving
unit starts blinking four times.
5. Set the desired values as follows:
- Move the joystick out of the rest position of the axis to be calibrated. Maintain this
position and activate once the TEACH + command related to the corresponding switch
on the transmitting unit.
- After calibrating one joystick, press the STOP pushbutton to save calibrations. All
calibrations are saved in the memory board.
6. To invert other directions, unlock the STOP pushbutton, press the START pushbutton
and repeat actions described in the previous point.
7. To leave the procedure, press the TEACH pushbutton on the receiving unit and do not
release it until the SETUP LED switches o.
8
LIARXE00-00
Values of proportional outputs
AUTEC - Dynamic Series