Atlantic Aurea M, Aurea M 5, Aurea M 10, AEYC-1039U-AT2, AEYC-1639U-AT, Aurea M 16, Aurea M 023227, AEYC-0639U-AT, Aurea M 8, AEYC-1039U-AT1 Installation Manual
Air/water heat pump single service Monobloc system
EN
Outdoor unit
AEYC-0639U-AT
AEYC-1039U-AT1
AEYC-1039U-AT2
AEYC-1639U-AT
Hydraulic unit
023227
U0618930_1883_EN_5
22/02/2019
For professionals
To be kept by the user for future reference
Page 2
■ Installation and maintenance rules
■ Hydraulic connections
The appliance must be installed and maintained by
an approved professional in accordance with the
prevailing regulations and code of practice.
■ Handling
The outdoor unit must not be in a horizontal position
during transport.
Transport in a horizontal position may damage the
appliance by moving the refrigerant and damaging
the compressor's suspensions.
Damage caused by transportation in a horizontal
position is not covered by the warranty.
If necessary, the outdoor unit may be tilted during
manual handling (to go through a door or use a
staircase). This operation must be conducted very
carefully and the appliance must be immediately
restored to the upright position.
The connection must comply with good engineering
practices according to the regulations in force.
Reminder: Make the assembly seals according to
good engineering practices in force for plumbing
work:
- Use suitable seals or gaskets (bre seals, O rings).
- Use Teon or hemp tape.
- Use sealant (synthetic as required).
Use glycol water if the min starting temperature set
is lower than 10°C.
Use glycol water if the outdoor hydraulic links are
subject to a frost risk.
For the outdoor hydraulic links, use an insulator
which is suitable for outdoor use and is UV-resistant
(usage temperature -20 to +70 °C).
If glycol water is used, carry out an annual check of
the quality of the glycol. Use monopropylene glycol
only. The recommended concentration is 30%
minimum. Never use monoethylene glycol.
• In certain installations, the presence of dierent
metals can cause corrosion problems; in this
case, the formation of metal particles and
sludge in the hydraulic circuit is seen.
• Use a corrosion inhibitor in the proportions
recommended by its manufacturer.
• It is also necessary to ensure that the treated
water does not become aggressive.
Page 3
■ Electrical connections
2
1
3
• Always check that the electric power supply is
switched o before works.
• Characteristics of the electrical power supply
The electrical installation must be conducted in
accordance with the regulations in eect:
For installations with no neutral, a galvanic insulation
transformer earthed to the secondary must be used.
The electrical connections will only be made when
all of the other assembly operations (attachment,
assembly, etc.) have been carried out.
Warning!
The contract taken out with the energy supplier
must be sucient to cover the power of the heat
pump as well as the sum of the power requirements
of all of the appliances likely to be operated at the
same time. If the power supply is insucient, check
with your energy supplier the value of the power
supply dened in your contract.
Never use a socket for the power supply.
The heat pump must be directly powered (without
external switch) by dedicated lines that are protected
from the electrical housing by bipolar circuit breakers
dedicated to the heat pump, curve D for the outdoor
unit, curve C for the electrical DHW back-ups
(see “Specications”, page 7).
The electrical installation must be equipped with a
dierential protection of 30 mA.
This appliance is designed to operate under a
nominal voltage of 230 V +/- 10%, 50 Hz.
• General remarks on electrical connections
It is essential to maintain the phase-neutral polarity
when making the electrical connections.
Rigid wire is always preferable for xed installations,
especially in buildings.
Clamp the cables with stung glands to avoid any
accidental disconnection of the conductive wires.
Connection to earth and earth bonding continuity
are essential.
• Connecting to screw terminals
Use of ring terminals or tips is prohibited.
- Always choose a wire that complies with current
standards.
- Strip the end of the wire over a length of around
25 mm.
- With round nosed pliers, make a loop with a
diameter that corresponds to the terminal's
tightening screws.
- Tighten the terminal screw on the loop very rmly.
Insucient tightening can cause overheating,
leading to breakdown or even a re.
Rigid wires
25 mm
Loop
Lug on
exible wires
prohibited
Special screw and
washer
Terminal
block
• Connecting to regulation boards
- Remove the corresponding connector and make
the connection.
Precabled wiring connector and/or screw connector
• Connecting to spring terminals
- Strip the end of the wire over a length of around
10 mm.
- Push the spring with a screwdriver so that the wire
enters the cage.
- Slide the wire into the opening provided for this
purpose.
- Remove the screwdriver and then check that the
wire is jammed in the cage by pulling on it.
Page 4
Contents
Presentation of the equipment 6
Packing list ..............................6
Unpacking and reservations .................6
Optional equipment ........................6
Scope ..................................6
Specications ............................7
Operating principle .......................12
Location 14
Installing the outdoor unit ..................14the hydraulic unit .........................16
Hydraulic connection 18
Rinsing the installation ....................18
Hydraulic connection of the outdoor unit .......18
Hydraulically connecting the heating circuit ....18
Heating installation volume .................19
Filling and draining the installation ...........19
Electrical connection 20
Cable section and protection rating ...........21Electrical connections on the outdoor unit side ..22
Electrical connections on the hydraulic unit side ..24
Start-up 28
Conguration of the ambient sensor ..........28
Conguration of the room control unit .........28
Heating circulation pump speed settings .......29
Minimum ow settings of the installation .......29
Cleaning the lter valve ....................29
Regulation interface 30
The user interface, the central ambient unit (option)
and the ambient sensor (option) .............30
Description of the display ..................32
Weather-dependent control .................32
Regulation menu 34
List of function lines .......................35
- 4 -
Aurea M / Installation / 1883 - EN
Page 5
Fault diagnostic 50
Faults displayed on the hydraulic unit .........50
Faults displayed on the outdoor unit ..........51
Information display .......................54
Maintenance 55
Hydraulic checks .........................55Checking the electrical circuit ...............55
Maintenance 55
Draining the hydraulic unit ..................55Directional valve .........................55
- 1 package: Hydraulic unit and outdoor temperature
sensor.
Heat pumpOutdoor unitHydraulic unit
ModelReferenceModelReferenceCodeReferenceCode
Aurea M 5526900Aurea 5AEYC-0639U-AT700125
Aurea M 8526901Aurea 8AEYC-1039U-AT2700126
Aurea M 10526902Aurea 10AEYC-1039U-AT1700127
Aurea M 16526903Aurea 16AEYC-1639U-AT700129
Aurea M023227
Unpacking and reservations
►
In the presence of the carrier, carefully inspect the
general appearance of the appliances and check that
the outdoor unit has not been placed in a horizontal
position.
In the event of disagreement, write to the carrier within
48 hours mentioning all reserves and send a copy of
Weight of hydraulic unit (empty/full of water)kg40 / 62
Hydraulic module water capacityl22
Noise level at 1 m 1 (Hydraulic unit)dB (A)39
(4)
Sound power level as per EN 12102-1 Annex A 2 (Hydraulic unit)dB (A)46
Heating system operating limits
Min /max outdoor temperature°C-20 / +43
Initial max. heating water temperature °C Under-oor heating°C45
(4)
Max. water temperature for start of heating LT radiator°C55
Initial min. water temperature°C8
(4)
Refrigerant circuit
Factory charge of refrigerating uid R410A 3 g1050172017202990
Maximum operating pressureMPa (bar)4.1 (41)
1
Sound pressure level at (x) m from the appliance, 1.5m from the ground, free eld, directivity 2.
2
The acoustic power is a measurement made in the laboratory of the power of the noise emitted but contrary to the noise level, it does not correspond to the measurement of what is felt.
3
Refrigerant R410A in compliance with standard NF EN 378.1.
4
Temporary values.
Page 8
■ Outdoor unit Aurea 5
Circulating water
Circulating water
return port
return port
Circulating water
Circulating water
outgoing port
outgoing port
■ Outdoor unit Aurea 8 & Aurea 10
825
580
57
122.5122.5
75 70
43
327
73
675
357
30015.342
R3/4(20A)
54
388
■ Outdoor unit Aurea 16
Circulating water
Circulating water
outgoing port
outgoing port
Circulating water
Circulating water
outgoing port
outgoing port
Circulating water
Circulating water
return port
return port
155540155
85024
8080
2533038
882
357
2410003637330
R1(25A)
480173
R1(25A)
Circulating water
Circulating water
return port
return port
g. 6 - Outdoor unit dimensions (in mm)
- 8 -
R1 1/4(32A)
1418
680185
R1 1/4(32A)
205590205
Aurea M / Installation / 1883 - EN
Page 9
■ Hydraulic unit Aurea M
1*
3**
2*
4
803
845
450
97
g. 7 - Hydraulic unit dimensions in mm
98
84
457
479
23
45
1
1Elbow
g. 8 - Accessories supplied with the outdoor unitg. 9 - Accessories provided with the hydraulic module.
g. 12 - Ohmic value of the sensors (hydraulic unit)
Aurea M / Installation / 1883 - EN
- 11 -
Page 12
Operating principle
►
The hydraulic unit has a regulator that controls the
indoor temperature based on the measurement of the
outdoor temperature, known as weather-dependent
control. The room thermostat (optional) corrects the
weather-dependent setpoint.
The hydraulic unit may be equipped with an electrical
back-up system*, which is designed to provide additional
heat during the coldest periods.
■ Regulation functions
- The initial temperature of the heating circuit is
controlled by the weather-dependent setpoint.
- The power of the heat pump is modulated according to
ow heating temperature via the "inverter" compressor.
- Control of the electrical back-up*.
- The daily timer programme enables you to dene
the periods for comfortable or reduced ambient
temperature.
- Switching between summer/winter operation is
automatic.
- Room thermostat*: The room thermostat corrects the
weather-dependent setpoint.
- Domestic hot water* Heating time program, control of
the operation of the DHW circulation pump.
- Managing the cooling.
■ Fan coil units with integrated regulation
Do not use a room thermostat in the zone concerned.
■ Protection functions
- Legionella cycle for domestic hot water.
- Frost protection: Frost protection cuts in if the lowtemperature point of the heating circuit falls below 5 °C.
■ Domestic hot water (DHW) operating principle*
Two domestic hot water (DHW) temperatures may
be set: comfort temperature (line 1610 at 55 °C)
and reduced temperature (line 1612 at 40 °C).
The DHW programme (line 560, 561 and 562) is set by
default to a comfort temperature from 0:00 to 5:00 and
from 14:30 to 17:00 and a reduced temperature for the
rest of the day, which optimises electricity consumption
while ensuring comfortable levels of hot water and
heating.
Setting for reduced temperature can be useful to prevent
the DHW from switching on too often and for too long
during the day.
The production of domestic hot water (DHW) is triggered
when the temperature in the tank falls 7 °C below the
temperature setpoint.
The heat pump produces domestic hot water (DHW),
which is then heated further, if required, by the electrical
back-up system inside the tank.
To ensure a DHW setting over 45 °C, the electrical
back-up heating must be left on.
Depending on how the parameter (1620) is set, nominal
temperature can be reached 24h/day or only at night or
depending on the heat pump program.
If the contract concluded with the energy provider
includes a subscription to day/night tari, the electrical
back-up is subordinate to the supplier's power tari and
the comfort temperature may only be reached at night.
If no particular contract is concluded, the comfort
temperature can be reached at any time, including
during the day
DHW production takes priority over heating;
nevertheless the production of DHW is controlled by
cycles that control the times assigned to the heating
and the production of DHW in the event of simultaneous
demand.
A switching function of "reduced" to "comfort" is available
on the front panel of the user interface (see item g. 27,
page 30).
Legionella cycles can be programmed.
*: These options require the use of additional kits (see § “Optional equipment”, page 6).
- 12 -
Aurea M / Installation / 1883 - EN
Page 13
Page 14
Location
Installing the outdoor unit
►
Installation precautions
▼
The outdoor unit must only be installed
outdoors. If a shelter is required, it must have
broad openings on all 4 walls and comply with
the installation clearances.
• Choose the installation site after talks with the
customer.
• Prefer a sunny location, sheltered from strong and
cold dominant winds.
• The unit must be easily accessible for future installation
and maintenance work.
• Ensure that the connectors can be easily connected to
the hydraulic unit.
• The outdoor unit can be exposed to bad weather,
however avoid installing it in places where it will
become dirty or have excessive water dripping onto it
(for example under a leaky drainpipe).
• When operating water may escape from the outdoor
unit. Do not install the appliance on a terrace; install
it in a well-drained location (bed of gravel or sand).
If installed in a region where the temperature may
drop below 0 °C for a long period of time, check
that the ice does not cause any danger. A drainage
pipe can also be connected to the outdoor unit
(see g. 14, page 15).
• Nothing should obstruct the air from circulating through
the evaporator and out of the fan.
• Keep the outdoor unit away from sources of heat or
inammable products.
• Ensure that the appliance does not disturb neighbours or
users (noise level, draughts caused, low temperature of
the air blown causing a risk of freezing plants in its path).
• The surface on which the outdoor unit is mounted must:
- Be permeable (earth, gravel bed...),
- Support the weight comfortably,
- Permit it to be solidly attached,
- Not transmit any vibration to housing.
Anti-vibration pads are available as an optional extra.
• The wall bracket cannot be used in conditions likely to
transmit vibrations, where installation on the ground is
preferred.
■ Outdoor unit Aurea 5
>300 mm
> 100 mm
> 600 mm
■ Outdoor unit Aurea 8 & Aurea 10
>300 mm
> 100 mm
> 600 mm
■ Outdoor unit Aurea 16
>300 mm
> 100 mm
> 600 mm
>100 mm
> 600 mm
>100 mm
> 600 mm
>100 mm
> 600 mm
- 14 -
g. 13 - Minimum installation clearances
around the outdoor unit
Aurea M / Installation / 1883 - EN
Page 15
Positioning the outdoor unit
▼
The outdoor unit must be raised by at least 50 mm
from the ground. In snowy regions, this height must be
increased but must not exceed 1.5 m.
Fasten the outdoor unit using screws and elastic
tightening or toothed lock washers to prevent them from
coming loose.
In regions with heavy snowfall, if the outdoor
unit's entrance and exit are blocked by snow
it may be dicult to heat up and may probably
cause a breakdown.
Build a canopy or position the unit on a high stand (local
conguration).
- Put the appliance on a solid support to minimise
impact and vibration.
- Do not set the unit directly on the ground as this may
generate disruptions.
Connecting the condensate evacuation
▼
pipe
The outdoor unit may generate a large volume
of water (called consensates).
If the use of a drain hose is imperative:
- Use the elbow provided (C) and connect a hose of
16 mm diameter to discharge the condensates.
- Provide for the gravitational discharge of the
condensates (waste water, rainwater, gravel bed).
H
C
* In regions subject to frequent snow,
(H) must be greater than the average snow layer.
If the appliance is installed in a region where
the temperature may fall below 0 °C for long
periods, t the drain hose with a trace heater
to prevent it from icing over. The trace heater
must not only heat the drain hose but also the
bottom of the appliance's condensate drain
pan.
H
C
Aurea M / Installation / 1883 - EN
g. 14 - Positioning the outdoor unit,
Discharging condensates
- 15 -
Page 16
the hydraulic unit
►
Installation precautions
▼
The choice of the position for installation is
particularly important insofar as any later
movement is a delicate operation requiring the
intervention of a qualied person.
350 mm
mini
300 mm
mini
1000 mm
Positioning the hydraulic unit
▼
- Secure the support (4 screws and plugs) to a at,
sturdy wall (not a light-weight partition) ensuring that
it is correctly levelled.
- Hook the appliance onto its support.
350 mm
mini
538 mm
mini
300 mm
mini
118 mm
188 mm
418 mm
mini
• Choose the site of the heat pump and the hydraulic
unit after discussion with the customer.
• The room where the appliance operates must comply
with the regulations in force.
• To ease maintenance operations and provide access
to the various parts, sucient space should be left
around the hydraulic unit.
• Be careful to keep the heat pump away from
inammable gas during installation, in particular when
it requires brazing. The appliances are not reproof
and should therefore not be installed in a potentially
explosive atmosphere.
(S)
g. 15 - Mounting bracket
- 16 -
Aurea M / Installation / 1883 - EN
Page 17
A
3
(S)
4
5
1
2
A
1
g. 16 - Remove the panel
Aurea M / Installation / 1883 - EN
7
6
B
B
6
- 17 -
Page 18
Hydraulic connection
Rinsing the installation
►
Before connecting the hydraulic unit to the installation,
rinse the heating system correctly to eliminate the
particles that could compromise the correct operation
of the appliance.
Do not use solvents or aromatic hydrocarbons (petrol,
paran, etc.).
For older installations, t a decanting pot of adequate
capacity on the boiler return circuit and at the lowest
point equipped with a drain, in order to collect and
evacuate the impurities.
Add an alkaline product to the water and a dispersant.
Rinse the installation several times before nal lling.
Hydraulic connection of the
►
outdoor unit
Connect the pipe of the outdoor unit to the hydraulic unit
respecting the direction of ow.
Install the valve lter on the heating return circuit in the
manner suggested.
Use union connectors to facilitate removal.
Hydraulically connecting the
►
heating circuit
Connect the pipe of the central heating to the hydraulic
unit respecting the direction of ow.
The diameter of the pipe between the hydraulic unit and
the heating manifold must be at least equal to 1 inch
(26x34 mm).
Use union connectors to facilitate removal.
Prioritise connector hoses to avoid transmitting noise
and vibrations to the building.
Calculate the diameter of the pipes according to the
ow rates and the lengths of the hydraulic systems.
Tightening torque: 15 to 35 Nm.
Connect the drains from the drain valve and the safety
valve to the main sewer system.
Check that the expansion system is operating correctly.
Control the vessel pressure (precharge 1 bar) and the
safety valve setting.
The installation ow rate must be at least equal to
the min. value noted in the table “Specications”,
page 7. Installing a regulation mechanism (other
than those present in our congurations) which reduces
or stops the ow through the hydraulic unit is prohibited.
g. 17 - Installing the lter valve
- 18 -
Tightening torque: 15 to 35 Nm
Couple : 15 à 35 Nm
g. 18 - Hydraulic connections
Aurea M / Installation / 1883 - EN
Page 19
Heating installation volume
►
The installation's min. water volume must be respected.
Install a buer tank on the heating circuit return if the
volume is lower than this value. In the case of an
installation equipped with thermostat valves, you must
ensure that this min. water volume can circulate.
Theoretical volume in litres PER CIRCUIT (excl. HP)
Equipment
Aurea M 523122
Aurea M 823122
Aurea M 10363315
Aurea M 16494422
Filling and draining the installation
►
- Check the attachment of the pipes, that the connectors
are tight and that the hydraulic unit is stable.
- Check the water ow direction and that all of the valves
are open.
- Fill the installation.
Do not operate the circulating pump while lling. Open all
the drain valves in the installation and the bleeder valve
(P) for the hydraulic unit to remove the air contained in
the conduits.
- Close the drains and add water until the pressure of
the hydraulic circuit reaches 1 bar.
- Check that the hydraulic circuit is drained correctly.
- Check that there are no leaks.
After the “ Start-up”, page 28 stage, once the
machine has started, purge the hydraulic unit again.
Obligation
Fan convector
Recommendation
Radiators
Recommendation
Floor heating-cooling system
Precise lling pressure is determined by the
manometric head of the installation.
P
g. 19 - hydraulic unit manual bleeder valve
Aurea M / Installation / 1883 - EN
- 19 -
Page 20
Electrical connection
Ensure that the general electrical power supply has been cut o
before starting any repair work.
The electrical installation must be conducted in accordance with
the prevailing regulations.
The electrical diagram of the hydraulic unit is detailed in g. 34, page 62.
Outdoor sensor
cable 2 x 0.75 mm²
the heat pump and the hydraulic unit
Phase, Neutral, Earth, Communication bus
Interconnection between
4 x 1.5mm² cable
OK
ESC
2
3
1
4
0
bar
Electrical back-up power supply
(see table below)
General electrical power supply
(see table below)
Radio central ambient unit (option)
Radio room thermostat UA55
(optional)
Central ambient unit (option)
cable 3 x 0.5 mm²
Room thermostat (optional)
cable 2 x 0.5 mm²
Electrical
panel
or
or
or
g. 20 - Overall layout of the electrical connections for a single installation
- 20 -
Aurea M / Installation / 1883 - EN
Page 21
Cable section and protection rating
►
The cross sections of the cables are provided for information only and do not dispense the electrician from checking
that these cross sections correspond to the requirements and satisfy the standards in force.
■ Power supply to outdoor unit
Heat pump (HP)230 V - 50 Hz electric power supply
ModelMax. power absorbed
Aurea M 52500 W3 x 1.5 mm²16 A
Aurea M 83500 W3 x 2.5 mm²20 A
Aurea M 104025 W3 x 2.5 mm²20 A
Aurea M 165820 W3 x 4 mm²32 A
Connector cable
(phase, neutral, earth)
Curve C
circuit breaker size
■ Interconnection between the heat pump and the hydraulic unit
The hydraulic unit is powered by the heat pump, via a cable 4 x 1.5 mm² (phase, neutral, earth, communication bus).
■ Power supply for electrical back-up (optional)
The hydraulic unit contains two stages of electrical back-ups installed in a heat exchange tank.
Electrical back-upsPower supply to the electrical back-ups
Model
Aurea M2x3 kW26.1 A3 x 6 mm²32 A
PowerNominal current
(phase, neutral, earth)
Cable
Curve C
circuit breaker size
Aurea M / Installation / 1883 - EN
- 21 -
Page 22
Electrical connections on the outdoor unit side
►
Access to the connection terminals
▼
■ Outdoor unit Aurea 5
- Remove the cover.
Cable clamp
Unscrew the
cover
(1 screw)
Cables
■ Outdoor unit Aurea 8 & Aurea 10
& Outdoor unit Aurea 16
- Remove the cover.
Cable clamp
Unscrew the
cover
(3 screw)
Cables
Cable clampCable clamp
- 22 -
Unscrew the
cover
(3 screw)
Cables
Use cable clamps to prevent the conductors
from being disconnected accidentally.
Obstruct the space at the cable inlet in the
outdoor unit with the insulating plate.
Aurea M / Installation / 1883 - EN
Page 23
Heating cable (optional)
▼
- Locate the heating part (see g. 21).
- Place the thermostat at the bottom of the tank.
- Run the bottom of the tank with the heating part of the
cable (make sure that the drain hole is covered by the
heating part).
- Fix the heating part on the bottom of the tank with the
aluminum tape supplied.
- Route the cable to the terminal block away from the
propeller blades (use the attachment points with clamps).
Thermostat
Thermostat
Repère
mark
Avoid metal edges that could damage the
insulation.
- Connect the heating cable to the terminal block
(terminals L and N).
Heating part
Partie chauffante
1 m
1 m
Cold part
Partie froide
Supply
Alimentation
1.5 m
1.5 m
Aurea M / Installation / 1883 - EN
L N
LN
POWER
Main electricity
supply
Heating cable
g. 21 - Heating cable mounting
1
Interconnection
between outdoor unit
and hydraulic unit
23
- 23 -
Page 24
Electrical connections on the hydraulic unit side
L
N
►
Access to the connection terminals
▼
- Remove the front panel (2 screws) (g. 16, page 17).
- Open the power control box.
- Make the connections according to the diagram
g. 22, page 24.
Do not t the sensor wires and the power supply wires
in parallel in order to avoid interferences due to the
voltage surges in the power supply.
Ensure that all of the electrical cables are housed in the
spaces provided.
Interconnection between the heat pump
▼
and the hydraulic unit
Comply with the correspondence between the markings
on the hydraulic unit's terminals and those on the heat
pump when connecting the interconnection cables.
An incorrect connection can cause the destruction of
one of the units.
1 2 3
5
4
to outdoor element
contact *
6
green/yellow
brown
blue
red
Outdoor unitHydraulic unit
LN
POWER
Single phase 230 V
electric power supply
1
Interconnection between
the heat pump
and the hydraulic unit
23
g. 22 - Connection to the terminal blocks
- 24 -
Aurea M / Installation / 1883 - EN
Page 25
Electrical backup (optional)
▼
- Connect the electrical supplies of electrical back-up to
the electrical panel ( see g. 22, page 24).
- Select the electrical back-up power
Electrical back-up power
Shunt A + shunt B
Adjust :
- 5891 = Electric
immersion heater 1
ow K25
shunt B
shunt A
Second heating circuit (optional)
▼
- 5892 = Electric
immersion heater 2
ow K26
Shunt A only
Adjust :
- 5891 = Electric
immersion heater 1
ow K25
- 5892 = None
= 6 Kw
= 3 Kw
- Please refer to the instructions supplied with the
second circuit kit.
- Set the parameter 5715 - Heating circuit 2 to On.
Domestic hot water tank (optional)
▼
If the installation is equipped with a DHW tank (with
electrical back-up):
- Please refer to the instructions supplied with the DHW kit.
- Please refer to the instructions supplied with the DHW tank.
Contract with the power supplier.
▼
It is possible to control the HP's operation with
specic peak/o-peak and day / night contracts.
In particular, domestic hot water (DHW) at Nominal
temperature will be produced during the o-peak hours
when electricity is cheaper.
- Connect the "Power Provider" contact to input EX2.
- Set the parameter 1620 to "O peak tari".
- 230V on input EX2 = "Peak hours" information
activated.
Load shedding or peak shaving
▼
The purpose of load shedding is to reduce the electrical
consumption when it is too high compared to the
contract with the energy supplier.
- Connect the power limiting device to input EX1,
the back-ups for the heat pump and the DHW stop in
the event of over-consumption by the dwelling.
- 230 V on input EX1 = power limitation in progress
Faults outside the heat pump
▼
All information devices (thermostat, pressure switch,
etc.) may indicate an external problem and stop the
heat pump.
- Connect the external device to input EX3.
- 230 V on input EX3 = heat pump shutdown (the system
displays error 369).
For under-oor heating, insert the under-oor heating
thermal safety into the under-oor heating circulator
link.
Aurea M / Installation / 1883 - EN
- 25 -
Page 26
Outdoor sensor
▼
The Outdoor sensor is required for the correct operation
of the heat pump.
Consult the assembly instructions on the packaging of
the sensor.
Place the sensor on the coldest part, generally the
northern or north-eastern side.
In any case, it must not be exposed to the morning sun.
It must be installed so that it is easily accessible but at
least 2.5 m from the ground.
Avoid sources of heat such as chimneys, the tops of
doors or windows, nearby extraction ducts, underneath
balconies and porches, that would insulate the sensor
from the variations in the temperature of the air outdoors.
Connect the outdoor sensor to the X84 connector
(M and B9 terminals on the hydraulic unit regulation board).
Ambient sensor and/or central ambient
▼
unit (option)
The ambient sensor (the central ambient unit) is
optional.
Consult the assembly instructions on the packaging of
the sensor.
The sensor must be installed in the living room area on
a very uncluttered wall. It must be installed so as to be
easily accessible.
Avoid sources of direct heat (chimney, television, cooker,
sunlight) and areas exposed to draughts (ventilation,
doors).
Draughts due to the building usually cause cold air
to enter via the electrical ducts. Seal the electrical
ducts if there is a cold draught at the back of the room
thermostat.
Installing an ambient sensor
• Ambient sensor T55
Connect the sensor to the X86 connector of the
RVS regulation board using the connector provided
(terminals 1, 2).
• Radio room thermostat T58
Connect the wireless room thermostat to the connector X60.
Installing a central ambient unit
• T75 central ambient unit
Connect the sensor to the X86 connector of the
RVS regulation board using the connector provided
(terminals 1, 2 and 3).
• T78 radio room control unit
Connect the radio central ambient unit to the connector X60.
Fan convector zone
If the installation is equipped with fan-coils / dynamic
radiators, do not use a room thermostat.
- 26 -
Aurea M / Installation / 1883 - EN
Page 27
Hydraulic unit regulator
Cable grommet
Electricity supply terminal strip
g. 23 - Hydraulic module's electrical cabinet
Shedding or EJP
Délestage ou EJP
(Peak Day Clear)
(Effacement Jour de Pointe)
Tarifds, day/night, peak/o-peak
Tarifs, jour/nuit, HP/HC
External fault
Défaut externe
Contact d'organe
External component
externe*
contact *
(défauts, délesteur,
(faults, shedder energy meter)
compteur d'énergie)
EX1
EX2
EX3
X11
X86
15
Interface board
X84
M B9
L
7
6
ou
** Sonde
** T55
d'ambiance
room
T55
thermostat
* If the command does not supply a potential free contact, the contact must be relayed to obtain equivalent wiring.
In all cases, refer to the instructions for the external parts (load shedder, energy meters…) for the wiring.
** Option
Terminal 3 of the central ambient unit does not need to be connected (central ambient unit lighting).
765
12 13 2
ou
** Centrale
** T75
ambiance
room
T75
control unit
765
13 2
** Centrale
** T78
ambiance
radio room
radio T78
control unit
Oudoor
Sonde
Sensor
extérieure
ou
**Sonde
** T58
d'ambiance
radio room
radio T58
thermostat
g. 24 - Connections to the Hydraulic module regulator (accessories and options)
Aurea M / Installation / 1883 - EN
- 27 -
Page 28
Start-up
- Engage the main isolator switch of the installation.
When rst put into service (or in winter), to preheat
the compressor, engage the main isolator switch
of the installation (heat pump power supply) for
several hours before the tests.
- Switch on the Start/Stop button of the heat pump.
To guarantee the correct operation of inputs EX1,
EX2, EX3: Check that the phase-neutral polarity
of the electrical power supply is respected.
When the power is switched on and every time that the
ON/OFF button is switched o and then switched on
again, the heat pump will take approximately 4 minutes
to start up, even if the setting is requesting heating.
The display can show error 370 when
the appliance (re)starts. Do not worry,
the communication will be reestablished between
the heat pump and the hydraulic module after a
few minutes.
During the initialisation phase of the regulator, all of
the symbols are displayed, then the "Data, update",
then"Heat pump status" is displayed.
- Make all of the specic settings for the regulation
(conguration of the installation in particular):
- Press OK.
Conguration of the ambient
►
sensor
To congure the ambient sensor and associate it to the
adequate heating zone:
Hold down the presence button for over 3s.
The ambient sensor displays RU and a gure ashes.
- Press the presence button, the ambient
sensor displays P1 and a gure ashes.
1: Automatic storing; a correction of the value with
the knob is adopted without any specic validation
(timeout) or by pressing the operation button.
2: Save with conrmation; a correction of the value with
the knob is only adopted after pressing the operation
button.
- Press the presence button again, the ambient sensor
displays P2 and a gure ashes.
0: OFF; all of the operating elements are available.
1: ON; the following operating elements are locked:
- Switching the operation mode of the heating
circuit.
- Adjusting the comfort value.
- Changing the operating level.
The ambient sensor displays OFF for 3s when a locked
button is pressed.
- Hold the button for 3s and select the access level
"Putting into service" using the knob .
- Conrm with the OK button.
- Parameter the heat pump's setting (consult the “List of
function lines”, page 35).
On commissioning (or the case of error 10), the electrical
back-up heaters are liable to start up even if the outdoor
temperature at the time is above the back-up trigger
temperature.
The regulating system uses an average initial outdoor
temperature of 0 °C and requires some time to update
this temperature.
To counter this situation, with the outdoor sensor correctly
connected, reset the parameter 8703 (commissioning
level, consumer diagnosis menu).
Conguration of the room control
►
unit
When putting into service, after a reset of around
3 minutes, the user language needs to be set:
- Press OK.
- Select the "User interface" menu.
- Select the language.
Select the language (English, Deutsch, Français,
Italiano, Nederlands, Español,
- 28 -
Aurea M / Installation / 1883 - EN
Page 29
Heating circulation pump speed settings
AEYC-0639U
AEYC-1039U
AEYC-1639U
Fermeture
►
Main water pump in the heat pump has 3 levels of speed. Factory default value is Level 3.
Select dip switch of DIP SW. on PCB(Terminal) to change the setting.
■ Outdoor unit Aurea 5, 8 & 10■ Outdoor unit Aurea 16
PCB (Display)
PCB(Display)
SW5 position
ON
1 2
OFF
1 2
ON
OFF
1 2
ON
OFF
■ Outdoor unit Aurea 5
(m)
12
11
10
9
8
7
6
5
4
3
2
1
051015
Level 3
Vitesse 3
Level 2
Vitesse 2
Vitesse 1
Level 1
Level 3
Level 3
(Maximum)
Level 2
Level 2
(Medium)
Level 1
Level 1
(Minimum)
20(L/min)
PCB(Display)
Level 3 Level 2 Level 1
Level 3
(Maximum)
■ Outdoor unit Aurea 16
(m)
14
12
10
8
6
4
2
0
10203040
MODE SW
ON
1 2 3 4
OFF
Turn ON the dip switch 3
1 - Turn ON the SW3
2 - Press SW-Pump
PUMP SW
Level 2
(Medium)
3 - Turn OFF the SW3
Vitesse 2
Level 2
Level 1
Vitesse 1
1 2 3 4
ON
OFF
Level 1
(Minimum)
Level 3
Vitesse 3
50(L/min)
The quantity should not be less than 5L/min.
■ Outdoor unit Aurea 8 & Aurea 10
(m)
8
7
6
5
4
3
2
1
010520
Vitesse 1
Level 1
15253035
Vitesse 2
Level 2
Level 3
Vitesse 3
The quantity should not be less than 10L/min.
Aurea M / Installation / 1883 - EN
40(L/min)
The quantity should not be less than 15L/min.
Minimum ow settings of the
►
installation
Adjust parameter 2899 (page 43) according
to the heat pump installed.
Cleaning the lter valve
►
Immediately after commissioning, clean the lter of the
lter valve (remove waste generated by the installation:
seals, oakum, lings, etc.).
- Close the valve.
- Unscrew the cap.
- Remove the clip
using pliers.
- Clean the lter.
Closure
- 29 -
Plug
Bouchon
Clips
Clips
Filtre
Filter
Page 30
Regulation interface
The user interface, the central ambient unit (option)
►
and the ambient sensor (option)
1
2
3
4
g. 27 - User interface
5
6
7
8
9
1
Auto
2
3
0 4 8 12 16 20 24
ESC
4
g. 25 - Central ambient unit T75/T78
5
Auto
5
7
OK
11
2
°C
10
11
8
6
g. 26 - Radio room thermostat T55/T58
- 30 -
Aurea M / Installation / 1883 - EN
Page 31
Ref.Functions- Denition of the functions
Arrêt
Auto
1Selecting the DHW operation
On
Marche
- Start: Production of DHW in function of the timer programme.
- Stop: Production of the DHW stopped with antifreeze function of the
domestic water active.
- Manual start button: Press the DHW button for 3 s (switches from
O
"reduced" to "comfort" until the DHW timer programme is switched again).
2Digital display - Check the operation, read the current temperature of the heating
operation, or a possible fault.
- View the settings.
3"ESC" output - Exit the menu.
4Navigation and setting - Setting the comfort temperature value.
- Menu selection
- Setting the parameters.
5Selecting the heating operation
-
Service heating according to the heating programme
(automatic summer/winter switching).
- Permanent comfort temperature.
- Permanent reduced temperature.
- "Stand-by" operation with antifreeze protection (provided that the
electrical power supply of the heat pump is not interrupted).
6Displaying information - Miscellaneous information (see “Information display”, page 54).
-Reading the error codes (see “ Fault diagnostic”, page 50).
-Information on maintenance, special operation.
7Validation "OK" - Enter the selected menu.
- Validate the parameter settings.
- Validate the comfort temperature value setting.
8Selection of the refresh mode
-Service cooling according to the heating programme
(automatic summer/winter switching).
9Reset
(Press and relief)
- Reset the parameters and cancel the error messages.
Do not use during normal operation
10Setting button - Setting the comfort temperature value.
562U 1st Out of service phase (end)00:00... --:--10 min05:00
563U 2
nd
In service phase (start)00:00... --:--10 min14:30
564U 2nd Out of service phase (end)00:00... --:--10 min17:00
565U 3
nd
In service phase (start)00:00... --:--10 min--:--
566U 3rd Out of service phase (end)00:00... --:--10 min--:--
576U Standard valuesNo, YesNo
Yes + OK: The default values memorised in the regulator replace and cancel the customised heating programs.
Your personal settings are therefore lost.
- 36 -
Aurea M / Installation / 1883 - EN
Page 37
LineFunctionSetting range or display
Holiday programs, Circuit 1 (the heating mode must be on "AUTO")
641U PreselectionPeriod 1 to 8Period 1
642U Date of start of holidays (day/month)01:01... 31.121--.--
643U Date of end of holidays (Day/Month)01:01... 31.121--.--
Setting
increment
Basic
setting
648U Heating rate during the holidaysAntifreeze protection, ReducedAntifreeze
Holiday programs, Circuit 2 (the heating mode should be on “AUTO”).
If the installation consists of 2 heating circuits (Only with the 2nd circuit kit option).
651U PreselectionPeriod 1 to 8Period 1
652U Date of start of holidays (day/month)01.01... 31.121
653U Date of end of holidays (Day/Month)01.01... 31.121
658U Heating rate during the holidaysAntifreeze protection, ReducedFrost protection
Heating, Circuit 1
710U Ambient comfort temperature valueReduced temperature…
712U Reduced ambient temperature valueAntifreeze temperature...
714U Ambient "antifreeze" temperature value4 °C… Reduced temperature0.5 °C8 °C
716S Maximum comfort valueComfort temperature... 35 °C1 °C28 °C
720IHeating curve slope
(see g. 29, page 33)
721ITranslation of the heating curve
(see g. 30, page 33)
Comfort value
Comfort temperature
0.1... 400:020.5
-4.5... 4.5 °C0.5 °C0 °C
0.5 °C20 °C
0.5 °C19 °C
protection
730ISummer/winter heating limit8... 30 °C0.5 °C18 °C
When the mean of the external temperatures over the last 24 hours reaches 18 °C the regulator stops the heating (economy).
In summer operation, the display shows "Eco". This function is only active in automatic operation.
740IMin. start value8 °C... Max. start value1 °C17 °C
(with dynamic radiator, set from 30 to 35 °C)
741IMax. start valueMin. start value 70 °C1 °C55 °C
Under-oor heating = 50 °C / Radiators = 65 °C.
Important remark: The maximum limit is not a safety function as that required for under-oor heating.
750S Room temperature inuence1 %... 100 %1 %50 %
If the installation is equipped with an ambient sensor:
This function enables you to choose the ambient temperature's inuence on the setting.
If no value is entered, the regulation is via the water logic.
If the parameter is set to 100%, the regulation is only made using the ambient temperature.
760S Room templimitation0.5... 4 °C0.5 °C0.5 °C
As soon as the room temperature = [Setpoint line 710 (ex.20 °C) + Room temperature limitation setpoint line 760
(ex.0.5 °C)] > 20.5 °C => The heat pump is stopped. It restarts when the room temperature falls below the setpoint
(in the example, Room temperature < 20.0 °C).
780S Quick setbackO, Up to reduced setpoint,
790S Maximum optimisation on trigger
(Anticipated start to reach the comfort value)
Up to protection setpoint
0... 360 min10 min180 min
O
791S Maximum optimisation on disconnection
(Anticipated stop to switch from the comfort value
to the reduced value)
Aurea M / Installation / 1883 - EN
0... 360 min10 min30 min
- 37 -
Page 38
LineFunctionSetting range or display
800S Start increasing the reduced operation-30... 10 °C1 °C--
801S End of increase in reduced operation-30... 10 °C1 °C-5 °C
830S Raising of mixing valve0... 50 °C1 °C0 °C
834S Servomotor travel time30... 873 s1 s240 s
850IControl of oor drying (g. 1)O
0: O: Advanced stoppage of the programme running, programme not active
1: Heating functional.
2: Heating ready for occupation.
3: Functional heating + heating ready.
4: Heating ready + functional heating.
5: Manual: Manual mode enables you to program your own concrete slab drying time.
The function ends automatically after 25 days.
Setting
increment
setting
Respect the standards
55
50
45
40
35
30
25
Heating start temperature°C
20
0 151018 1
X
Heating ready for occupation
1
Heating functional + Heating ready for occupation
57
Functional
heating
Day
25
and values of the building
constructor!
Correct operation of this
function is only possible with a
correct installation (hydraulic,
electricity and settings)!
The function may be interrupted
earlier by setting to "Stop".
Basic
g. 1 - Diagram of the oor drying programmes
851IManual oor drying value (if line 850 = manual)0... 95 °C1 °C25 °C
This function allows the customised oor drying temperature to be set. This temperature remains xed.
The oor drying programme stops automatically after 25 days of operation.
856ICurrent drying day0... 320
857IDrying days completed0... 320
900S Switching of operationNone, Protection mode,
Reduced, Comfort, Automatic
Operating mode at the end of oor drying.
Cooling, Circuit 1 (Only available when parameter 5711 is set to "2-pipe system")
902U Ambient comfort temperature value17... 40 °C0.5 °C24 °C
903U Reduced ambient temperature value17... 40 °C0.5 °C26 °C
Reduced
Protection
- 38 -
Aurea M / Installation / 1883 - EN
Page 39
LineFunctionSetting range or display
Setting
increment
setting
908IFlow temp setp at OT° 25°C6... 35 °C0.5 °C20 °C
Starting cooling temperature setting for an outdoor temperature of 25 °C.
909IFlow temp setp at OT° 35°C6... 35 °C0.5 °C16 °C
Starting cooling temperature setting for an outdoor temperature of 35 °C.
Flow temperature setpoint
°C
20
908
18
16
909
2535
30
Outdoor temperature
°C
g. 2 - Slope of the Cooling curve
912ICooling limit at T° ex mixed (8704)--, 8... 35 °C0.5 °C24 °C
Basic
If the mixed outside temperature is below this value, the cooling mode is disabled.
913S Lock time at end of heating/cooling--, 8... 1001 h24 h
The time delay for operating in cooling mode after having operated in heating mode and vice versa.
918S Summer comp start at OT°20... 50 °C1 °C26 °C
The comfort setting (902) is increased in line with the outdoor temperature rising above this reading.
919S Summer comp end at OT°20... 50 °C1 °C40 °C
Above this reading, the comfort setting (902) is no longer aected by an increase in the outdoor temperature.
920S Summer comp setp increase--, 1... 10 °C1 °C4 °C
Maximum increase in the comfort setting (902).
Nominal ambient temperature setpoint
°C
In summer, the comfort setting for cooling (Line 902)
92 0
902
91 9918
Outdoor temperature
is oset upwards in line with the increase in outdoor
temperature.
The saves on cooling power and prevents too great a
dierential between the ambient indoor and outdoor
temperatures.
°C
Remark: Summer compensation explains the dierence
between the value set on Line 902 (or on the setting
knob) and the reading on line 8740.
g. 3 - Compensation for the comfort setting
Aurea M / Installation / 1883 - EN
- 39 -
Page 40
LineFunctionSetting range or display
Setting
increment
setting
923S Flow temp setp min OT° 25°C6... 35 °C0.5 °C18 °C
The lowest starting temperature for cooling for an outdoor temperature of 25 °C.
924S Flow temp setp min OT° 35°C6... 35 °C0.5 °C18 °C
The lowest starting temperature for cooling for an outdoor temperature of 35 °C.
Flow temperature setpoint
°C
908
923
924
20
18
Flow temperature setpoint
(WITH minimum limit)
Basic
909
16
Flow temperature setpoint
(WITHOUT minimum limit)
2535
30
°C
Outdoor temperature
g. 4 - Limitations on the starting temperature setting
928S Room temperature inuence--, 1... 100 %1 %80 %
If the installation is equipped with an ambient sensor:
This function enables you to choose the ambient temperature's inuence on the setting.
If no value is entered, the regulation is via the water logic.
If the parameter is set to 100%, the regulation is only made using the ambient temperature.
932S Room temp limitation0... 4 °C0.5 °C0.5 °C
938S Mixing valve decrease0... 20 °C1 °C0 °C
941S Servomotor travel time30... 650 s1 s240 s
963S With prim contr/system pumpNo, YesYes*
*Basic setting: 1 circuit = No; 2 circuits = Yes.
Heating, Circuit 2
Only with the 2nd circuit kit option (If the installation consists of 2 heating circuits).
1010UComfort setpointReduced setpoint…
Comfort setpoint maximum
0.5 °C20 °C
1012UReduced setpointFrost protection setpoint…
Comfort setpoint
0.5 °C19 °C
1014UFrost protection setpoint4 °C… Reduced setpoint0.5 °C8 °C
1016S Comfort setpoint maximumComfort temp... 35 °C1 °C28 °C
1020IHeating curve slope
(see g. 29, page 33)
1021ITranslation of the heating curve
(see g. 30, page 33)
0.1... 40.020.5
-4.5... 4.5 °C0.5 °C0 °C
1030ISummer / Winter heating limits8... 30 °C0.5 °C18 °C
When the average of the outdoor temperatures over the past 24 hours reaches 18 °C, the regulator switches o the heating
(as an economy measure). During summer mode, the display shows "Eco". This function is only active in automatic mode.
1040IFlow temp setpoint min8... 70 °C1 °C17 °C
(with dynamic radiator, adjust from 30 to 35 °C)
1041IFlow temp setpoint max8... 70 °C1 °C60 °C
Under-oor heating = 50 °C / Radiators = 65 °C.
Important remark: The maximum limit is not a safety function as that required for under-oor heating.
- 40 -
Aurea M / Installation / 1883 - EN
Page 41
LineFunctionSetting range or display
1050S Room inuence1 %... 100 %1 %50 %
If the installation is tted with a room thermostat:
This function enables you to choose the ambient temperature's inuence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
1060S Room temperature limitation0.5... 4 °C0.5 °C0.5 °C
As soon as the room temperature = [Setpoint line 1010 (ex. 20 °C) + Room temperature limitation setpoint line 1060
(ex. 0.5 °C)] > 20.5 °C => The heat pump is stopped. It restarts when the room temperature falls below the setpoint
(in the example, Room temperature < 20.0 °C).
Setting
increment
Basic
setting
1080S Quick setbackO, Up to reduced setpoint,
1090S Optimum start control max0... 360 min10 min180 min
1091S Optimum stop control max0... 360 min10 min30 min
1101SReduced setpoint increase end-30... 10 °C1 °C-5 °C
1130SMixer valve increase0... 50 °C1 °C0 °C
1134SActuator running time30... 650 s1 s240 s
1150IControl of oor drying (g. 1, page 38)O
0: O: Advanced stoppage of the programme running, programme not active
1: Heating functional.
2: Heating ready for occupation.
3: Functional heating + heating ready.
4: Heating ready + functional heating.
5: Manual: Manual mode enables you to program your own concrete slab drying time.
The function ends automatically after 25 days.
1151IFloor curing setpoint manually
(if line 1150 = manual)
This function enables you to set the custom concrete slab drying temperature. This temperature remains xed.
The concrete slab-drying program stops automatically after running for 25 days.
1202UComfort cooling setpoint17... 40 °C0.5 °C24 °C
1203UReduced setpoint5... 40 °C1 °C26 °C
1208IFlow temp setp at OT° 25°C6... 35 °C0.5 °C20 °C
Starting cooling temperature setting for an outdoor temperature of 25 °C.
1209IFlow temp setp at OT° 35°C6... 35 °C0.5 °C16 °C
Starting cooling temperature setting for an outdoor temperature of 35 °C.
1212ICooling limit at T° ex mixed (8704)--, 8... 35 °C0.5 °C24 °C
If the mixed outside temperature is below this value, the cooling mode is disabled.
1213S Lock time at end of heating--, 8... 1001 h24 h
The time delay for operating in cooling mode after having operated in heating mode and vice versa.
Reduced
Protection
Aurea M / Installation / 1883 - EN
- 41 -
Page 42
LineFunctionSetting range or display
1218S Summer comp start at OT°20... 50 °C1 °C26 °C
The comfort setting (1202) is increased in line with the outdoor temperature rising above this reading.
1219S Summer comp end at OT°20... 50 °C1 °C40 °C
Above this reading, the comfort setting (1202) is no longer aected by an increase in the outdoor temperature.
1220S Summer comp setp increase--, 1... 10 °C1 °C4 °C
Maximum increase in the comfort setting (1202).
1223S Flow temp setp min OT° 25°C6... 35 °C0.5 °C18 °C
The lowest starting temperature for cooling for an outdoor temperature of 25 °C.
1224S Flow temp setp min OT° 35°C6... 35 °C0.5 °C18 °C
The lowest starting temperature for cooling for an outdoor temperature of 35 °C.
1228S Room inuence1... 100 %1 %80 %
If the installation is tted with a room thermostat:
This function enables you to choose the ambient temperature's inuence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
24h/day: The DHW temperature is maintained permanently at the DHW comfort value.
Time programs HCs : The DHW production follows the timer programming of the ambient temperature (with start
advanced by 1 hour).
Timer programme 4/DHW : The DHW program is separate form the heating circuit program.
O peak rates tari (THC)* : The electrical back-up heating is only authorised to operate during the o-peak period.
1 °C55 °C
1 °C40 °C
Time program
4/DHW
- 42 -
Timer prog.4/DHW and THC* : The electrical back-up heating is authorised to operate during the nominal period or
o-peak.
- Connect the "Power Provider" contact to input EX2. (see g. 24, page 27). In the case of a day /night contract, the
electrical back-ups for the DHW tank are subject to the power supplier's taris. Switching on the electrical back-up for
the DHW tank is only authorised during o-peak hours.
Aurea M / Installation / 1883 - EN
Page 43
LineFunctionSetting range or display
Setting
increment
Basic
setting
1640IAnti-legionnella functionO, Periodic (according to the setting for line),
O
Fixed day of the week (according to the setting
for line 1642)
1641S Frequency of anti-legionella cycle1 to 71 day7
2899 parameter setting according to outdoor unit used
Heat pumpOutdoor Unit ModelParameter 2899
Aurea M 5Aurea 5300 (5 l/min)
Aurea M 8Aurea 8600 (10 l/min)
Aurea M 10Aurea 10600 (10 l/min)
Aurea M 16Aurea 16900 (15 l/min)
2907S Silent mode power max1... 100 %1 %80 %
2916S Heat pump DHW max temperature8... 80 °C1 °C58 °C
2920S In the event of an EJP blocking signal (EX1)Locked, ReleasedReleased
Released :
HP = On _ DHW back-up = O _ 1st HP back-up = O _ 2nd HP back-up = O _ Boiler = On.Locked :
HP = O _ DHW back-up = O _ 1st HP back-up = O _ 2nd HP back-up = O _ Boiler = On.
3026S Silent mode on00:00... 23:5010--:--
On time of the Silent mode function
3027S Silent mode o00:00... 23:5010--:--
Of time of the Silent mode function
3028S Silent mode speed incr start-50... 50 °C1 °C-5 °C
3029S Silent mode speed incr end-50... 50 °C1 °C-10 °C
g. 5 - Silent mode
Aurea M / Installation / 1883 - EN
Silent mode power max
(2907)
%
100
80
-10 (3029)
-5 (3028)
Outdoor temperature
°C
- 43 -
Page 44
LineFunctionSetting range or display
Energy meter
3113U Energy brought inKwh--
Cumulation of total consumed electrical energy.
Electrical energy consumed = Electrical energy absorbed by outdoor unit + electric energy absorbed by the heating
electrical backup and / or DHW electrical backup (if installed).
3124UEnergy brought in heating 1 (N - 1)Kwh--
3125U Energy brought in DHW 1Kwh--
3126UEnergy brought in cooling 1Kwh--
3131UEnergy brought in heating 2 (N - 2)Kwh--
3132UEnergy brought in DHW 2Kwh--
3133UEnergy brought in cooling 2Kwh--
3138UEnergy brought in heating 3 (N - 3)Kwh--
3139UEnergy brought in DHW 3Kwh--
3140UEnergy brought in cooling 3Kwh--
3145UEnergy brought in heating 4 (N - 4)Kwh--
3146UEnergy brought in DHW 4Kwh--
3147UEnergy brought in cooling 4Kwh--
Setting
increment
Basic
setting
3152UEnergy brought in heating 5 (N - 5)Kwh--
3153UEnergy brought in DHW 5Kwh--
3154UEnergy brought in cooling 5Kwh--
3159UEnergy brought in heating 6 (N - 6)Kwh--
3160UEnergy brought in DHW 6Kwh--
3161UEnergy brought in cooling 6Kwh--
3166UEnergy brought in heating 7 (N - 7)Kwh--
3167UEnergy brought in DHW 7Kwh--
3168UEnergy brought in cooling 7Kwh--
3173UEnergy brought in heating 8 (N - 8)Kwh--
3174UEnergy brought in DHW 8Kwh--
3175UEnergy brought in cooling 8Kwh--
3180UEnergy brought in heating 9 (N - 9)Kwh--
3181UEnergy brought in DHW 9Kwh--
3182UEnergy brought in cooling 9Kwh--
3187UEnergy brought in heating 10 (N - 10)Kwh--
3188UEnergy brought in DHW 10Kwh--
3189UEnergy brought in cooling 10Kwh--
3190S Reset xed day storageNo, YesNo
Reset the historical counters (1 to 10). The general counter (parameter 3113) is not reset.
Note: "Energy" Counters increment as of 1 July each year.
3197 parameter setting according to outdoor unit used
Heat pumpOutdoor Unit ModelParameter 3197
Aurea M 5Aurea 51.28
Aurea M 8Aurea 81.78
Aurea M 10Aurea 102.32
Aurea M 16Aurea 164.10
Additional generator (Boiler connection)
3692S With DHW chargingLocked, Substitute,
Complement, Instantly
Substitute
- DHW Instantly : When DHW request, the HP and the boiler are put into operation. The HP will stop when the primary
return temperature is over 55 °C.
- DHW Substitute : If the outdoor temperature is above 2 °C, the operation of the HP when DHW request last 5 minutes
at least. The HP operating time can be extended depending on the outdoor temperature. The boiler will activate then.
3700S Release below outdoor temperature-50... 50 °C1 °C2 °C
5983S Input action direction EX2Normal closed, Normal openedNormal closed
5985S Input action direction EX3Normal closed, Normal openedNormal opened
6100S Correction of outdoor temperature sensor-3... 3 °C0.1 °C0 °C
6120S Installation antifreezeO, OnOn
6201S Erase sensorNo, YesNo
6205S Reset parametersNo, YesNo
6220S Software version (RVS)0... 99--
6221S Developpement index0... 65535--
6229S Eeprom version0... 65535--
6230S Info 1 OEM--
6231S Info 2 OEM--
6258S Info 3 OEM--
reduced tari
6259S Info 4 OEM--
6375S Relay output QX35None
6420S H33 input function (= contact in X152)1... 561
1: HC+DHW 2 rate switching: HC 3 rate switching: HC1 4 rate switching: Not used, 5: HCP rate switching,
6 to 56: Not used.
6421S Contact action direction H33Normal closed, Normal openedNormal opened
Error
6700UError signal0... 255--
6711U Reset HPNo, YesNo
6800S History 1Date, Time, Error code
6802S History 2Date, Time, Error code
6804S History 3Date, Time, Error code
6806S History 4Date, Time, Error code
6808S History 5Date, Time, Error code
6810S History 6Date, Time, Error code
6812S History 7Date, Time, Error code
6814S History 8Date, Time, Error code
6816S History 9Date, Time, Error code
6818S History 10Date, Time, Error code
Maintenance/Special operation
7070S Time interval for the maintenance of the heat pump 0... 2401 month--
7071S Operating time of the heat pump since last
maintenance. Reset? (return to zero) No, Yes
7073S Mean number of compressor start up operations
per hour of operation, over the last 6 weeks.
Reset? (return to zero) No, Yes
- 46 -
0... 2401 month--
0... 12--
Aurea M / Installation / 1883 - EN
Page 47
LineFunctionSetting range or display
7141UAssist modeO, OnO
O: Heat pump functions normally (with boosters if necessary).
On: Heat pump uses the electric boost system or the boiler connection.
Use the “On” position only in Assist mode or Test mode:may result in high power bills.
7142S Backup service operating typeManually, AutomaticallyManually
Manually: The emergency operation is not activated when there is a fault (Emergency operation = Stop).
Automatically: The emergency operation is activated when there is a fault (Emergency operation = Start).
In the "Automatically" position, the energy bill may be high if the error is not detected and resolved.
7150ISimulation of outdoor temperature-50... 50 °C0.5 °C--
Inputs / outputs test
7700IRelay testNo test
This test consists of commanding the regulator relays one by one and checking the outputs. It is used to check that the
relays are operating and that the wiring is correct (for this, check that each appliance is operating on the installation).
The display shows the "key" symbol. By pressing the Info button, "error 368" is displayed.
Warning! During the test, the component tested is electrically powered.
Setting
increment
Basic
setting
7710ITest on output UX10... 100 %1 %--
7716ITest on output UX20... 100 %1 %--
7722ICooling operation D2O, OnO
7723IHeat pump D3O, OnO
7724ITest on output U4 ("Inverter" command)0... 100 %1 %--
7725IVoltage signal U4 (Ux3)0... 10 V1 V--
7804ISensor temperature BX1 (heat pump start T°)-28... 350 °C1 °C--
7805ISensor temperature BX2 (heat pump return T°)-28... 350 °C1 °C--
7806ISensor temperature BX3 (water T°)-28... 350 °C1 °C--
7807ISensor temperature BX4 (outdoor T°)-28... 350 °C1 °C--
7845IH2 module 1 input signalWithout, Closed (ooo), open (---),
Pulses, Frequency Hz, Voltage V
7858IH3 input signalWithout, Closed (ooo), open (---),
Pulses, Frequency Hz, Voltage V
7911IInput EX1 (load shedding, EJP)0, 230 V1 V--
7912IInput EX2 (peak/o peak taris)0, 230 V1 V--
7913IInput EX3 (external fault)0, 230 V1 V--
7973ISensor temperature BX1-28... 350 °C1 °C--
Without
Without
7974ISensor temperature BX2-28... 350 °C1 °C--
7975ISensor temperature BX3-28... 350 °C1 °C--
7976ISensor temperature BX4-28... 350 °C1 °C--
7999IH33 input signalWithout, Closed (ooo), open (---),
Pulses, Frequency Hz, Voltage V
Aurea M / Installation / 1883 - EN
Without
- 47 -
Page 48
LineFunctionSetting range or display
State
8000IHeating circuit 1 status--
8001IHeating circuit 2 status--
8003IDHW status--
8004ICooling circuit 1 status--
8006IHP status--
8022IStupplementary source status
8025ICooling circuit 2 status--
Diagnostics producer
8400IState of compressor 1O, OnO
8402IElectrical resistance 1 startO, OnO
8403IElectrical resistance 2 startO, OnO
8410UReturn temp HP0... 140 °C1 °C--
Setpoint (ow) HP0... 140 °C1 °C--
8412UFlow temp HP0... 140 °C1 °C--
Setpoint (ow) HP0... 140 °C1 °C--
Setting
increment
setting
Basic
8413UCompressor modulation0... 100 %1 %--
8425S Condenser temperature dierence-50... 140 °C1 °C--
8450S Hours run compressor 11 h--:--
8454S Heat pump locking start
Reset? (return to zero) No, Yes
8455S Heat pump counter locking
Reset? (return to zero) No, Yes
8456S Hours of operation of electrical start
Reset? (return to zero) No, Yes
8457S Counter for n° of electrical starts
Reset? (return to zero) No, Yes
8458IState of smart gridLocked draught, Released draught,
8460IHeat pump rate1 l/min--
Diagnostics consumer
8700UOutdoor temperature-50... 50 °C1 °C--
8701UMinimum outdoor temperature
Reset? (return to zero) No, Yes
8702UMaximum outdoor temperature
Reset? (return to zero) No, Yes
0... 2730 h1 h--:--
0... 199999--
0... 2730 h1 h--:--
0... 199999--
Required draught, Forced draught
-50... 50 °C1 °C--
-50... 50 °C1 °C--
Released
draught
8703IAttenuated outdoor temperature
Reset? (return to zero) No, Yes
This is the average outdoor temperature over a 24 hour period.
This value is used for automatic summer / winter switching (line 730).
8704IMixed outdoor temperature-50... 50 °C1 °C--
The mixed outdoor temperature is a combination of the "current outdoor temperature" and the "mean outdoor
temperature" calculated by the regulator. This value is used to calculate the start temperature.
8773UFlow temp setpoint resulting HC 20... 140 °C1 °C--
Flow temperature ref. value 2--
8781ICooling circuit pump, circuit 2O, OnO
8782ICool circ mix valve 2 openO, OnO
8783ICool circ mix valve 2 closedO, OnO
8786UCooling ow temperature 20... 140 °C1 °C--
Cooling ow temperature setpoint 2--
8820IDHW pumpO, OnO
8821IEl imm heater DHWO, OnO
Setting
increment
Basic
setting
8830UDHW (domestic hot water) temperature0... 140 °C1 °C--
DHW temperature setpoint50 °C
8832IDHW measured temperature down (B31)0... 140 °C1 °C--
8840S Hours run DHW pump0... 2730 h1 h--:--
8841S Start counter DHW pump0... 199999--
8842S Hours run electric DHW0... 2730 h1 h--:--
8843S Start counter electric DHW0... 65535--
9031IRelay output QX1O, OnO
9032IRelay output QX2O, OnO
9033IRelay output QX3O, OnO
9034IRelay output QX4O, OnO
9035IRelay output QX5O, OnO
9071IRelay output QX31O, OnO
9072IRelay output QX32O, OnO
9073IRelay output QX33O, OnO
9074IRelay output QX34O, OnO
9075IRelay output QX35O, OnO
Aurea M / Installation / 1883 - EN
- 49 -
Page 50
Fault diagnostic
Depending on whether the fault is on the heat pump or the hydraulic module, the fault may be indicated by the
hydraulic unit's digital display or the outdoor unit's display.
Faults displayed on the hydraulic unit
►
The faults or breakdowns of the hydraulic unit are reported on the display unit of the user interface.
The display shows the symbol.
Press the button to obtain the details of the origin of the fault.
When the error has been resolved, the faults are re-initialised at zero automatically.
■ Hydraulic module: Error codes visible on the digital display
Error number Error contentsError position
-No connection.
10Outdoor sensor.B9Yes
33Heat pump start sensor temperature error.B21Yes
44Heat pump start sensor temperature error.B71Yes
50DHW temperature sensor.B3Yes
60Ambient sensor 1.Yes
65Ambient sensor 2.Yes
105Maintenance message.Yes
121Heating circuit 1 start temperature not reached.Yes
122Heating circuit 2 start temperature not reached.Yes
127Anti-legionella temperature not reached.Yes
369External fault (safety device)No
370
4412e zone sensor not congured (if 2nd circuits kit)
516Heat pump missing
Outdoor unit error
(during a start-up phase, see § "Commissioning").
The polarity of the ambient
sensor has not been respected.
see below.No
BX31; Set the parameter 5700
to 2
Loss of connection between
controller and HP.
HP operation
despite the error
No
No
No
- 50 -
Aurea M / Installation / 1883 - EN
Page 51
Faults displayed on the outdoor unit
►
The faults or breakdowns on the outdoor unit are indicated by the outdoor unit's main board display.
The display indicates the last error code.
Main board
"RESET" button
Display
Press the “RESET” button to reset the fault.
Press the “RESET” button for 10 seconds to reset the fault list.
■ Outdoor unit: Error codes visible on the outdoor unit's main board display.
Error
codes
------
A0
A1
Error contents,
Location of the error
Direct Voltage Error
“Discharge”
temperature error
VericationBreakdown maintenance
Electrical power supplyCheck the power supply.
Fuse CF1
0639U : 250V 15A
1039U : 250V 25A
1639U : 250V 30A
Fuse CF3
250V 3A
Fuse CF4
0639U : 250V 15A
1039U : 250V 25A
Main boardOther than described above Replace the main board
Fan motor
Fuse CF6
1639U : 250V 3A
Fuse CF7
1039U : 250V 3A
1639U : 250V 3A
Circulator
ReactorTest the resistance (0.1Ω to 20°C)If the reactor is defective, replace it
Main board
Electrical power supplyCheck the power supply.
Discharge temperature
sensor
Gas leak
Test the CF1 fuseIf CF1 burnt, replace the main board
Test the CF3 fuseIf CF3 burnt, replace the main board
Test the CF4 fuseIf CF4 burnt, replace the main board
If the same error code appears again, replace the main
board or the fan motor
Run the heat pump with the fan
motor disconnected
Test the fuse
Run the heat pump with the
circulator disconnected
Test the fan motor voltage
Test the circulator voltage
Test the sensorIf the sensor is defective, replace it
Check the service valve and cooling
circuit (pipes)
If another error code appears, replace the fan motor
If CF4 is burnt, replace it
If CF7 is burnt, replace it
If the same error code appears again, replace the main
board or the circulator
If another error code appears, replace the circulator
If the voltage is incorrect, replace the main board
Collect the cooling gas rst of all, then reload with the
recommended quantity of gas
Error
reset
---
Restart
Auto
Aurea M / Installation / 1883 - EN
- 51 -
Page 52
Error
codes
Protection measures
against direct
A2
current overintensity
detection
A3CT disconnectionMain board---Replace the main board
Protection measures
against direct
A4
current overintensity
detection
A5
Anormal compressor
rotation
Suction temperature
A6
sensor error.
Defrosting
A7
temperature sensor
error.
Discharge
A8
temperature sensor
error
Error contents,
Location of the error
Abnormal operation in
under/overload
Drop in power supply
voltage
Main board
Temporary interruption
in power supply (in the
event of a storm)
CompressorOther than described aboveReplace the compressor
Abnormal operation in
under/overload
Drop in power supply
voltage
Temporary interruption
in power supply (in the
event of a storm)
Abnormal operation in
under/overload
Drop in power supply
voltage
Fuse CF6
0639U : 250V 15A
1039U : 250V 25A
Circulator and/or
hydraulic circuit blocked
Drop in power supply
voltage
Temporary interruption
in power supply (in the
event of a storm)
Compressor or Main
board
Suction temperature
sensor
Defrosting temperature
sensor
Discharge temperature
sensor
VericationBreakdown maintenance
Check the installation's environment
(blockage of the air inlet and outlet)
Check the excess gas
Check the power supply voltage (230V)
Run the heat pump with the
compressor disconnected
---Restart
Check the installation's environment
(blockage of the air inlet and outlet)
Check the excess gas
Check the power supply voltage (230V)
---Restart
Check the installation's environment
(blockage of the air inlet and outlet)
Check the excess gas
Check the power supply voltage (230V)
Check the electrical continuity
Test the CF6 fuse
Check the circulator and the
hydraulic circuit
Check the power supply voltage (230V) during operation
---Restart
Other than described aboveReplace the compressor
Test the sensorIf the sensor is defective, replace it
Test the sensorIf the sensor is defective, replace it
Test the sensor (*1)If the sensor is defective, replace it
Check that the air ows freely in and out
If there is excess gas, collect the cooling gas rst of all,
then reload with the recommended quantity of gas
If the same error code appears again, replace the main
board
Check that the air ows freely in and out
If there is excess gas, collect the cooling gas rst of all,
then reload with the recommended quantity of gas
Check that the air ows freely in and out
If there is excess gas, collect the cooling gas rst of all,
then reload with the recommended quantity of gas
If CF6 is burnt, replace the main board
Remove the plug then restart
Error
reset
Manual
Manual
Auto
(*1) If a circuit is open on the discharge sensor, the error message is displayed 10 minutes after start-up.
In the event of a short circuit on the discharge sensor, the error message is displayed immediately.
(*2) During a check on the fan motor and/or the circulating pump, disconnect the electricity supply completely then check its terminals and
connectors.
- 52 -
Aurea M / Installation / 1883 - EN
Page 53
Error
codes
C1
Location of the error
Upper fan motor
error
(1639U)
Error contents,
Fuse CF7
250V T3.15A
Main board
VericationBreakdown maintenance
Check the electrical continuity
Test the CF7 fuse
If CF7 is burnt, replace the fan motor and the CF7 fuse
If CF7 is not burnt, check the fan motor's power supply
voltage
If the voltage is normal, replace the fan motor
If the voltage is abnormal, replace the main board
Error
reset
Manual Fan motor (*2)
Outdoor temperature
C2
sensor error
Lower fan motor
error
(1639U)
C3
Fan motor error
(0639U, 1039U)
Main board
C4
temperature
elevation (>110°C)
Main board
C5
temperature sensor
error
C6Main board errorMain board---Replace the main boardRestart
- Check that the refrigeration circuit is lled with gas.
- Check the hydraulic circuit's pressure (1 to 2 bars), check that the heat pump is drained, along with the rest of the
installation.
- Make sure that all the DIP SW are OFF before starting up.
Commissioning check-list
►
Before start-up
▼
OKNon-compliant
• Outdoor unit visual checks (see chapter “Hydraulic connection of the outdoor unit”, page 18)
Position and attachments, condensate evacuation.
Compliance with distances from obstacles.
• Hydraulic unit hydraulic checks (see chapter “Hydraulically connecting the heating circuit”, page 18)
Connections of pipes, lter valve, aps and pumps (heating circuit, DHW).
Installation water volume (expansion tank capacity adapted?).
No leaks.
Primary and gas release network pressure.
• Outdoor unit electrical checks (see chapter “ Electrical connection”, page 20)
230 V mains power supply
Protection by calibrated circuit breaker.
Cable section.
Earth connection.
• Hydraulic unit electrical checks (see chapter “Electrical connections on the hydraulic unit side”, page 24)
Connection with outdoor unit (L, N, Earth).
Sensor connections (positioning and connections).
Connection of directional valve (DHW) and circulation pump.
Power supply and protection of electrical back-up (option).
- 64 -
Aurea M / Installation / 1883 - EN
Page 65
Start-up
▼
• Starting up (see chapter “ Start-up”, page 28 and “List of function lines”, page 35)
Push in the installation's general circuit breaker (outdoor unit power )
2 hours before the tests => Compressor pre-heating.
Push in the on/o switch => Few seconds' initialisation.
Operation of the heating circulator
The outdoor unit starts after 4 min.
Congure the Time, Date and Heating Circuit, hourly programmes if dierent from
the default values.
Congure the hydraulic circuit (parameter 5700):
Select the outdoor unit (parameter 3197).
Set the heating slope (720 / 1020).
Adjust the maximum start setting (741 / 1041).
Conguration, operations, checks.
Adjust the heating circuit setpoints if dierent than default values
(710 - 714 / 1010 - 1014).
• Outdoor unit checks
Operation of the fan(s), compressor.
Intensity measurement.
After a few minutes, measure the dierence in air T°.
Condensation and evaporation pressure / temperature check.
OKNon-compliant
• Hydraulic unit checks
After 15 minutes of operation.
Dierence in primary water T°.
Heating operation, etc.
• Usage explanations
The heat pump is ready for operation!
Aurea M / Installation / 1883 - EN
- 65 -
Page 66
Conguration le
►
Parameter
Preliminary settings
20languageinter. Use
1hour / minutestime and
2day / monthtime and
3yeartime and
5700installation cong.conguration
Heating circuit No. 1
if circuits = the least hot (e.g.: underoor)
710comfort valueHC1 adjust.
712reduced settingHC1 adjust.
720weather-dependent setpoint slopeHC1 adjust.
741max. initial setpointHC1 adjust.
750room T° inuenceHC1 adjust.
790 / 791start / stop optimis./HC1 adjust.
834Servomotor travel timeHC1 adjust.
850 / 851oor drying/HC1 adjust.
Heating circuit No. 2 (with 2nd circuit option)
= the warmest one (e.g.: radiators)
1010comfort setpointHC2 adjust.
1012reduced setpointHC2 adjust.
1020heating curve slopeHC2 adjust.
1041ow temp setpoint maxHC2 adjust.
1050room inuenceHC2 adjust.
1090 / 1091 optimis. at switch-on / offHC2 adjust.
1134servomotor travel timeHC2 adjust.
1150 / 1151oor dryingHC2 adjust.
Domestic hot water (if DHW kit)
1610comfort DHW T° valueDHW
1612reduced DHW T° valueDHW
1620Liberation of DHWDHW
1640 to 1642 Legionella cycleDHW
5024Activation diff. DHWDHW tank
5030Charging time limitationDHW tank
5061Elect. resistance releaseDHW tank
Item
Setting
Menus
date
date
date
Parameter
Boiler backup
3700OT.switch-on authoris.addit. gen.
3705swith-off delayaddit. gen.
Miscellaneous
6420H33 input function1conguration
6100ext. T° sensor correct.conguration
6120antifreeze on/offconguration
6205parameter resetconguration
6220software versionconguration
6711Heat pump reseterror
Cooling (if cooling kit)
5711cooling unit2 pipesconguration
901 to 969cooling congurationCooling
Faults (if a fault appears, press the "Info" button)
No. 10outdoor sensor
No. 33Initial T° sensor
No. 44Return T° sensor
No. 50DHW T° sensor
No. 60Ambient sensor 1
No. 65Ambient sensor 2
No. 105maintenance message
No. 121Initial T° Heating circuit 1 not reached
No. 122Initial T° Heating circuit 2 not reached
No. 127Anti-legio T° not reached
No. 369external fault (EX3)
No. 370outdoor unit connection error
6711Heat pump reseterror
Heat pump
2844Max thermodynamic oper. T°heat pump
2884OT auth. to start elec. aux.heat pump
2920 EJP (EX1) released / ver.heat pump
Item
Setting
Menus
circuit 1
- 66 -
Aurea M / Installation / 1883 - EN
Page 67
Start-up data sheet
►
WorksiteInstaller
Outdoor unit
Type of refrigerantRefrigerant charge kg
ChecksVoltages and currents in operation on the outdoor unit
Compliance with positioning distancesL/NV
Condensate evacuation OKL/TV
Electric connections / connections tightenedN/TV
Hydraulic network on hydraulic unit
Secondary network
Domestic hot water; tank type
Secondary network water volume estimateL
Options & accessories:
Location of room sensor correctT55 ambient sensor
DHW kitT58 radio room thermostat
2-circuit kitT75 central ambient unit
Electrical back-up kitT78 radio room control unit
Boiler connection kit
Serial No.
ModelModel
Underoor heatingCirculation pump brandType
LT radiators
Fan-coil heaters
Hydraulic unit
IcompA
Details
Serial No.
Regulation conguration
Type of conguration
Key parameters
ErP performance gures
Energy performance data is available in the user manuals.
Instructions for the user
Explain to the user how the installation operates, in particular the functions of the room thermostat
and the programmes accessible via the user interface.
Emphasise that a heated oor has signicant inertia and that therefore any adjustments must be made
progressively.
Also explain to the user how to check the lling of the heating circuit.
This unit is identied by this symbol. It means that all electrical and electronic products must not be included in household waste.
A specic recycling system for this type of product has been set up in European Union countries (*), Norway, Iceland and Liechtenstein.
Do not try to dismantle this product yourself. It may have damaging eects on your health or on the environment.
Reprocessing of the refrigerant, lubricant and other parts may be performed by a qualied installer in compliance with the local and national legislation in force.
This unit must be recycled by a specialised service and in no case may it be thrown away with household waste, rubble or in a landll.
Please contact your installer or local representative for more .
* Depending on the national regulations of each member state.
Aurea M / Installation / 1883 - EN
- 67 -
Page 68
012
atlantic-comfort.com
Date of commissioning:
Société Industrielle de Chauage
SATC - BP 64 - 59660 MERVILLE - FRANCE
This equipment complies with:
- Low Voltage Directive 2014/35/EC in accordance with NF EN 60335-1, NF EN 60335-2-40, NF EN 60529, NF EN 60529/A2 (IP) standards,
- Pressure Equipment Directive 2014/68/EC in accordance with NF EN 378-2 standard,
- Ecodesign Directive 2009/125/EC,
- Energy Labelling Directive 2010/30/EC.
This appliance also complies with:
- Decree No. 92-1271 (and its modications) relating to certain refrigeration uids used in refrigeration and air conditioning equipment.
- Regulation 842/2006 of the European parliament on certain uorinated greenhouse gases.
- The standards relating to the product and the testing methods used: Air-conditioners, refrigeration units and heat pumps with
compressor driven by electric motor for heating and refrigeration EN 14511-1, 14511-2, 14511-3, and 14511-4.
- Standard XP ENV 12102: Air-conditioners, heat pumps and dehumidiers with compressor driven by electric motor. Measurement of
airborne noise. Determination of acoustic power level.