Athena Technologies 6050 User Manual

Instruction
Manual
Athena 6050
Temperature Controllers
-THENIL
Inputs:
INSTRUCTION MANUAL
ATHENA 6050
Automatic Tuning
Temperature Controller
Line Voltage Sensor Power Consumption Ranges Available
Accuracy:
Temperature Stability Cold end tracking Operating ambient for
rated accuracy
Maximum T/C lead
resistance for rated accuracy
Series mode noise
rejection:
Common mode noise rejection
T/C break protection: Dual display:
120/240 Vac
Thermocouple Less than 6 VA (Instrument)
J Couple
K Couple
0.2% of full scale 5m V/°C
0.05°C/°C
0 to
100 Ohm
80
dB
120
dB Upscale standard Process temperature displayed
continuously; set point or other parameters updated on lower display.
+lO%,
0-1400°F (O-760°C) 0-2500°F (O-137O°C)
Max 3m
55°C
V/°C
ambient
-15%,
typ.
50, 60
Hz
1
Display update rate:
5 times per second
Filtering:
°F/°C:
output:
-B Relay (time proportioning)
-F Current proportional
-S
Pulsed voltage
-T Triac proportional
Filtered LED display:
T/C linearization:
Connections:
time
Analog and digital filtering techniques increase stability of process and display.
Internal switch selection--
process, set point. Heating only SPST relay 7 Amps resistive at
120
Vac,
50 VA inductive.
4-20mADC SCR
20 Vdc pulsed time proportioning
signal for driving solid state relays.
Solid state plug-in Rated 1 Amp holding & 10 amps inrush.
4 digits for process, 4 digits for parameters.
Continuously calculated and updated using rom based algorithm.
Inputs and outputs via barrier strips
with U.L. approved locking terminals.
5 amp resistive at 240
into 500 Ohm max. For driving
power controllers.
triac
output.
Vac,
Dimensions:
Mounting: Weight:
Front panel: 96mm X 96mm X Case: 92mm X Depth behind panel: minus panel thickness)
Channel slides and screws 2 lb
92mm
X
118mm
96mm (approx.
22mm
2
3
FRONT PANEL AOJUSTMENTS Touch Key 1 Index: Allows the following adjustments to be selected.
1)
Set point temperature
2)
Heat cycle time
3)
Prop. Band (indicated
as
gain)
O-14OO'F (760°C) O-2500°F (O-137O°C)
*1 to 120 seconds
0.25-25%
of span
4)
Rate with tracking reset
5)
Auto Tune
Up/Down keys: increases/decreases values of above adjustments.
Tune/Cancel: permit set-up
E Enter: writes selected value to nonvolatile memory NOTES: *setting to zero initiates 60
for ultra fast cycling. Use state relays or SCR Power Controllers.
**Setting to zero disables reset and rate action
for proportional only control. Reset is six times higher than rate
FOR OPTIMUM RESULTS WITH THE AUTO-TUNE MODEL 6050
(AT)
"cancel" puts output on stand-by to
"tune" triggers automatic tuning procedure
**4-255 seconds
millisecond timebase
with
external solid
1.
Set point must be a minimum of 100°F above ambient for
proper start-up.
2. Multi-zone applications require auto-tune units on each zone and simultaneous warm-up.
4
3.4.Loss of power or turn-off during warm-up requires a re-start from ambient.
Change of state processes, liquid to gas, may introduce erroneous tuning parameters during process warm-up.
GENERAL
Accurately measures, linearizes and displays temperature
1. in °F and
Automatically calculates and displays parameters-heat
2. gain, and rate/reset time.
Can be field converted from relay output
3. state relay a 4-20 MA output SCR driver
4.
Will remember its "entered" settings after power failure or shut-off and not "Go To Sleep".
CAUTION: HIGH VOLTAGE AN0 HIGH TEMPERATURES CAN CAUSE INJURY AN0 ARE A FIRE HAZARO. PLEASE REAO ALL INSTRUCTIONS, HAVE ONLY SKILLED PROFESSIONALS WIRE THE UNIT, AND USE APPROVED TEMPERATURE AND/OR PRESSURE SAFETY CONTROL. EVEN THE BEST
COMPONENTS CAN BE DAMAGED OR MAY NOT FAIL SAFE. CONFIGURATION Depending on the model number of the unit you have ordered,
vou will find one of four basic modules installed. The fifth digit of the code indicate the output module type.
°C.
“T",
to solid state driver
i.e.
solid to liquid or
"B",
"S"
"F".
or to
to solid
B- Relay F- 4-20 mA (Proportional) T-
Triac S- 20 VDC Pulsed for driving solid state relays Example:
Note: If you have not received your controller from the
factory direct, check to confirm that the correct module for your application is installed. Since the modules plug-in, and since controller plug into cases as well, previous users may have changed modules, controller damage.
7A/5A @ 120/240 Vac
1 Amp @ 240
6050-F
has proportional 4 to 20 mA heat
output.
Vac
which can result in severe
5
Output
Modules
The Athena 6050 offers users field interchangeable output modules. This unique feature makes it possible to fill
output requirements for a variety of applications with
a single controller model.
Module Type B: This
NOTE: Do not use this output module with mechanical
contactors field which can interfere the 6050's microprocessor.
Instead we
application.
Module Type F: This 4-20 mA output module can deliver
Module Type T: This solid state relay is capable of 1 AM?
7A/5A
driving resistive heaters.
because they generate an excessive EM1
recommend "T"
full output to loads having an input impedance of 500 Ohms or less. The cycle time setting must be ZERO for smooth
A push-on terminal is utilized as a return for ground currents of the milliamp source. It is connected internally to the
mating lug on the heat sink. To avoid ground loops, drive floating (ungrounded)
loads or use isolated thermocouples.
at
120/240 Vac. and optically isolated from the drive signal. With
it, resistive loads up to 120 watts at at 120 controlled directly. Using direct control
there is no lower limit on the cycle time setting (down to 60 milliseconds). Larger
loads may be controlled utilizing an external contactor. In this case, it is advisable to use cycle settings of ten seconds or greater to minimize contactor wear. External suppression of the contactor is mandatory.
relay
Vac
and 240 watts at 240
(at 120/240 Vac)
output modules for this
It is zero voltage switched
is used for
Vac
may be
Module Type S: Similar to F, but pulsed
for driving solid state relays. Up to 6 (input series connected) solid state relays
can be used. Cycle time can be set to optimize
the load response time requirements without sacrificing S.S.R. life.
2OV/2OmA
7
DC output
INTERNAL SWITCHES
Damping tuning for processes with varying heating characteristics and with varying heating capabilities, the 6050 offers three damping choices:
Keypad Security -Switch 2 in the open position locks the operator out of access to all parameters except set point.
CELSIUS/FAHRENHEIT DISPLAY SECTION Switch 1 allows both displays to read in degrees Celsius or
Fahrenheit, and is indicated on front panel
Control -To allow the controller to provide automatic
High damping: for over-powered heating systems, systems with multiple heat lags, and/or poor coupling between the heater and the temperature
sensor.
Normal: for most standard processes where the heater is properly sized for the system and there is good coupling between the heater and the temperature sensor.
Low damping: for adequately powered systems with excellent coupling between the heater and the temperature sensor where quick response and the tightest possible temperature control are desired.
LED's.
WIRING THERMOCOUPLE CIRCUITS Before wiring, check thermocouple and extension wire to make
sure that they conform to the appropriate thermocouple type specified on the serial number tag. In thermocouple circuits, the negative lead is colored red. Extension wires
must
be the same alloy and polarity as the couple. The thermocouple circuit resistance should not exceed 100 OHMS. Do not run thermocouple leads in the same conduit as the power lines. If shielded thermocouple is used, terminate the shield only at the controller end using the corner screw provided for that purpose.
STANDARD THERMOCOUPLES
I.S.A.
TYPE J K
MATERIALS Iron Constantan Chrome1 Alumel
(C/A)
(I/C)
COLOR CODE White(+) Red(-) Yellow(+) Red(-)
8
THERMOCOUPLE PLACEMENT Proper thermocouple placement can eliminate many problems in
the system. The probe should be placed so that it can detect any temperature change with minimal thermal lag. In a process
that requires fairly constant heat output, the probe should be placed close to the heater. In processes where the heat demand is variable, the probe should be close to the work area. Some experimenting with probe location is often needed to find its optimum position.
In a bath process, addition of a stirrer will help to eliminate thermal a point measuring device, putting more than one in parallel will provide an average temperature produce better results in air heated processes.
lags.
Since the thermocouple is basically
thermocouple reading and
will
result,
loads with an isolated input and
24OV)
NOTE: If controls with grounded or hot input terminals thermocouple must be used. Otherwise, when both output are grounded, ground loop currents causing errors and controller damage.
Standard thermocouple limits of error are 4°F or 0.75% of sensed temperature (half that for special) plus drift caused by improper protection or overtemperature. This is far greater than controller error, and can not be corrected at the sensor except by selection and replacement.
Start-Up Before line voltage is applied, double-check the following:
Make sure the thermocouple type is correct, and
properly connected (see section on thermocouples) to terminals 1 and 2 (red on
Make sure there is no AC or DC voltage leading or arcing to T/C.
Make sure the proper terminals are selected for
line voltage. (8 & 9 for
Check to assure there are no heater shorts, or
shorts to ground, and no bare wires or frayed insulation.
Make sure correct plug-in module is used.
"F"
or
"S"
outputs drive
(not
floating),
2).
12OV,
8 & 10 for
9
OPERATING INSTRUCTIONS
How to Start the automatic tuning procedure
STEP 1: Energize the unit and proceed immediately to step 2. STEP 2: Place the unit on standby by holding the "Index"
The unit is now ready for set point and cycle time entry. STEP 3: To enter a set point:
STEP 4: Set cycle time by advancing "Index" to "HC" and
STEP
button until the the Cancel button.
the SP LED lights and B) Use the appropriate touch key, either up or down to enter set point.
When
you've entered the desired set point, simply press the enter key. NOTE: Set point must be at least 100°F above ambient.
select desired value using up or down keys. Cycle
time is shown in seconds, from 1-120. Setting zero
initiates a 60 millisecond cycle time for ultra fast
cycling for use with
mechanical relays or
When you've found the desired cycle time press the enter key.
5: To start warm up and calculate all PID parameters
advance Index to auto tune again and press the
"tune" button.
The "AT" L.E.D. will light and light. You may now index to any parameter for viewing as process heats. Upon completion of
tuning, the "AT" L.E.D. will be off.
"Autotune"
LED lights then press
A) Hold "Index" button until
"F"
or
"S"
contactors
output modules. For
use
l0-120
seconds.
"HT"
L.E.D. will
NOTE: The parameters that the 6050 calculates automatically
can be entered on the Athena 6000/6200 to achieve the
same smooth and precise temperature control on your
process.
10
How to override automatic tuning parameters
It is possible to set or fine tune three mode parameters
manually on the 6050. To manually enter parameters:
1)
Press "Index" button until the LED for the desired
parameter lights.
2)
Enter the new parameter using the up or down key.
3)
Press the "enter" button.
The new parameters will now take control of the process. To calculate the PID parameters without using the automatic tuning mode, consult the Athena
6000/6200
instruction manual.
Reading automatically calculated Press the "index" key. The LED‘s in the "Index" display will
light in sequence, and as they change, the lower digital display will show each parameter.
PID
parameters
11
TROUBLE SHOOTING
no
Front dark
instrument power.
-
Process display terminals 1 and 2. Process display should indicate
temperature at back of case. Repair or replace thermocouple.
About Half or Twice Expected Reading - Check position of °C/°F
switch. Short 1 and 2 to read room temperature. 22-30
is
°C, 70-85
About
30% Disconnect above 2500°F.
No Heat Heat Stays On -Welded relay contacts, shorted output module,
or shorted power handler. Process Display Shows OOOO Or Initially Displays Room
Temperature Then Counts Down Scale As Process for reversed thermocouple.
Display blinks, entered values change - Caused by electromagnetic
interference eliminate high voltage spikes, power wiring from "dirty" power lines. Ground heated devices.
Unit Repairs
It is recommended that units requiring service be returned
to an authorized service center. When a controller is
returned for service, a note stating the problem should
accompany the unit.
Error- Wrong thermocouple type.
couple.
-
No heater power, heater wiring, wrong output module.
is
(EMI).
shows
CCCC - Open thermcouple. Short
°F.
"J"
units over range above
Supress arcing contacts in system to
seperate sensor and controller
14OO°F, "K"
Warns -
Check
NOTE: Warranty is void when units are modified by the customer or other non-authorized parties.
A spare parts list can be supplied upon request if complete model number, serial number and temperature range is supplied.
12
WARRANTY
This equipment is warranted to be free from defects of
material and workmanship. It is sold subject to our mutual
agreement that the liability of Athena Controls, Inc. is to replace and/or repair at its factory, provided the equipment
is returned, transportation prepaid within
purchase. The purchaser agrees that Athena Controls, Inc. shall assume no liability for consequential damages resulting use or packaging of shipments returned to the factory. Components which wear or which are damaged by misuses are not warranted. These include contact points, fuses, and modules. Units which have been modified by customer are not warranted.
Specifications are subject to change without notice.
(2)
years of its
from
triacs,
its
13
dTHENd
Controls, Inc., 5145 Campus Drive
Plymouth
Meeting,
PA 19462
(215) 828-2490
Loading...