Athena Technologies 16C User Manual

SERIES
16C
TEMPERATURE/PROCESS CONTROLLER
Instruction Manual
(Basic Operations)
1
3
Precautions
Features
Congratulations on your purchase of an Athena Series 16C Temperature/Process Controller. It is designed for ease of use and reliability wherever accurate control is required.
After following the instructions for installation, simply step through and set your operating parameters using the controller’s easy menu system. The instrument may then be automatically or manually tuned to your process for optimum setpoint control. A Quick Setup Reference Card is on page 5 and also attached as a tear-off card to the back of the instruction manual for experienced users of PID controllers.
As you look through this manual, you will notice blue italicized text appearing in the margins and adjacent to operating information. These notes impart important informa­tion about the controller and may answer questions you may have about its setup or operation. If you still have questions or require any assistance, please contact your Athena repre­sentative or call technical support at 1-800-782-6776. Outside the USA, please call 610-828-2490.
After unpacking, inspect the instrument for any physical damage that may have occurred in shipping. Save all packing materials and report any damage to the carrier immediately.
Field-Selectable Thermocouple, RTD, Current or Voltage Input On/Off Through Full PID Operation Autotuning - Heat or Cool Eight-Segment Ramp/Soak On/Off Output with Adjustable Hysteresis and Deadband Dual Output Capability Field-Configurable Process or Deviation Alarms Bumpless, Auto-Manual Transfer NEMA 4X Front Panel, “Watertight” Dual 4-Digit (0.36”), 7-Segment Alphanumeric Display Selectable Ramp to Setpoint Alarm Inhibit Loop Break Alarm Capability Available Options Include Serial Communications, Contact/
Digital Input, Remote Analog Setpoint, Transducer Excitation, Auxiliary Output, Dual Alarms, or Electromechanical Relay Alarm.
Approvals: UL, cUL, CE
© Copyright 2004, Athena Controls, Inc.
Safety Warning
®
U
L
C
®
U
L
In addition to presenting a potential fire hazard, high voltage and high temperature can damage equipment and cause severe injury or death. When installing or using this instrument, follow all instructions carefully and use approved safety controls. Electrical connections and wiring should be performed only by suitably trained personnel.
Do not locate this instrument where it is subject to excessive shock, vibration, dirt, moisture, oil, or other liquids. The safe operating temperature range for this unit is 32°F to 140°F (0°C to 60°C).
This unit has been tested and found to be compliant with “NEMA Type 4X Enclosure - For Indoor Use Only.” When properly installed, this controller will maintain the integrity of a NEMA enclosure and remain “Watertight.” This rating is only applicable when the controller is properly installed into a
suitably rated NEMA Type 4X housing.
3
1
Table of Contents
For information and operating instructions related to installed options and digital communications, refer to the Series C Options and Digital Communications manual supplied with your controller.
4
Installation 1
Dimensions and Mounting 2 Wiring 3 Output Types 5
Operation 6
Front Panel Controls 6 Power On 7 Security Levels 8 Operating Modes 9 Menu System Overview 10 Initial Setup Sequence 12 Parameter/Menu Descriptions 14 Input Menu 15 Temperature Input 16 Process (Linear) Input 16 Display Menu 17 Output Menu 17 PID Output and Control Menus 18 On/Off Output and Control Menus 19 Alarm Outputs 20 Autotune Damping 22 Ramp and Soak Menu 23 Supervisor Menu 24 Calibration Menu 25 Options Menu 25
AutoTuning 26 Manual Tuning 28 Error Codes 29 Technical Specifications 30 Ordering Codes 32 Recalibration Procedures 33 Quick–Helps 34 Warranty/Repairs 36 Glossary 39
Installation
Measurements between centerlines of panel cut­outs are the minimum recommended.
Unpacking and Inspection
1. Inspect shipping carton for obvious signs of mishandling.
2. After removing the controller from the shipping carton, inspect it carefully for damage. Never attempt to install and use a damaged unit.
3. Verify that the ordering code number indicated on the side of the controller matches what was ordered.
Figure 1. Recommended Panel Layout for Multiple Controllers
C
L
2.850” (72.4 mm)
C
L
C
L
2.150” (54.6 mm)
C
L
1
3
Dimensions
2.100"
(53.3m m)
O1 O2 A1 A2 F1 F2
PV
SV
2.100"
(53.3m m)
4.654"
(118.21mm )
3.937"
(100 m m)
0.717"
(8.21 mm)
1.750"
(44.5 mm)
Figure 2. Case Dimensions
Prior to mounting the Series C in your panel, make sure that the cutout opening is of the right size, 1.771” x 1.771” (45 mm x 45 mm), and deburred to enable a smooth fit. A mini­mum of 4” (100 mm) of depth behind the panel is required.
Mounting
When properly installed through a NEMA enclosure, the integrity of the enclosure will be maintained and will remain “Watertight.”
2
Figure 3. Series C Mechanical Components
Insert the Series C through the front panel cutout and slide the mounting collar back onto the unit from behind the panel. Push the mounting collar up tight to the back of the mounting panel.
Bezel
Grips
Gasket
Case Clip
Customer Panel
Wiring
1
2
3
4
5
6
7
8
9
10
13
14
11
12
N.O.
C
N.C.
N.O.
C
SENSOR
INPUT
T/C
OUTPUT 1
OUTPUT 2
RT
D
L1 L2
100 - 250 V 50/60 Hz 100 - 250 Vdc (Auto Polarity) 24 Vac/Vdc (Auto Polarity)
A2
232/485
GND
ALARM
&
COMM.
COM
N.O.
N.O. RCV B (-)
COM XMT A (+)
A1 RS 232 RS 485
ALARM & COMM.
IMPORTANT: All electrical wiring connections should be made only by trained personnel, and in strict accordance with the National Electrical Code and local regulations.
The Series C controller has built-in circuitry to reduce the effects of electrical noise (RFI) from various sources. However, power and signal wires should always be kept separate. We recommend separating connecting wires into bundles: power; signal; alarms; and outputs. These bundles should then be routed through individual conduits. Shielded sensor cables should always be terminated at one end only.
If additional RFI attenuation is required, noise suppression devices such as an R.C. snubber at the external noise source may be used. If you wish, you may order this suppressor directly from Athena, part number 235Z005U01.
Figure 4. Contact Identification
3
Wiring
8
9
10
RTD
8
9
10
T/C
3
4
5
8
9
10
11
12
L1 L2
Thermocouple circuit resistance should not exceed 100 ohms for rated accuracy; errors will occur at higher resistance values. If shielded thermo­couple wire is used, terminate the shield only at one end.
Wiring
Figure 5. Thermocouple Input Wiring
Make sure that you are using the appropriate thermocouple and extension wire. Connect the negative lead (generally colored red in ISA-type thermocouples) to contact #9; connect the positive lead to contact #10. Extension wires must be the same polarity as the thermo­couple.
Figure 6. RTD Wiring
The Series C accepts input from 2- or 3-wire, 100 ohm platinum resistance temperature detectors (RTDs). Connect 2-wire RTDs to contacts #9 and #10, with a jumper across contacts #8 and #10. Keep leads short and use heavy gauge copper extension wire, if necessary, to minimize
Note: For 2-Wire RTD
lead resistance. For long runs, 3-wire RTDs should be used.
Figure 7. Process and Linear Input Wiring
Voltage Inputs: Connect the positive voltage input to contact #10; the negative input to contact #9.
Current Inputs: Connect the positive current input to contact #10; the negative input to contact #9.
Jumper 8 & 10
The Series C power supply accepts 100 to 250 Vac and 100 to 250 Vdc line power without any switch settings or polarity considerations. All connections should be made in accordance with the National Electrical Code and local regulations, using only NEC Class 1 wiring for all power terminals.
It is advisable, but not necessary, to fuse one leg of the incoming power line, contact #11, with a 2AG, 0.5 amp rated fuse. It is recommended that instrument power and load
power be fused independently.
Figure 8. Power Wiring Connection
4
100 - 250 V 50/60 Hz 100 - 250 Vdc (Auto Polarity)
Output Types
The Type “B” output is a mechanical device and subject to wear. To extend the life of the relay, set the Cycle Time for the relay output to the longest duration that still affords good control.
When you ordered your Series C controller specific output types were specified, designated as “B”, “E”, “F”, “G”, “S”, “T” or “Y”. You also had the option of configuring your con­troller with either one or two output actions. The numbers below are suggested for most typical applications.
For Control Output Type — Select Cycle Time
(in seconds)
B >15
E 0.2
F 0.2
G 0.2
S 0.2
T 15*
Y >15
* “T” outputs directly driving non-inductive loads (small heaters) can have
cycle times as low as 0.2 seconds.
Output Type Description
B 5 A (120/240 Vac) relay, normally open, used
for switching resistive loads. If relays or sole­noids are to be driven, select the “T” output. If a “B” output is selected, order snubber network 235Z005U01.
E 0-20 mA
F 4-20 mA, full output to load with 500 ohm impedance max. (suppressed).
G High impedance ‘F’ (800 ohms).
S 20 Vdc pulsed output for solid-state relays.
T 1 A @ 120/240 Vac, solid-state relay, zero volt-
age-switched and optically isolated from drive signal. Only resistive loads to 1A may be con­trolled directly. Larger loads may be controlled using an external contactor.
Y 5 A (120/240 Vac) relay, but normally closed (output 2 only).
5
7
Operation
Figure 9. Front Panel Controls and Indicators
Mode/Enter Key
Used to enter Parameter selections, access operating modes, release latched alarms, and index through menu items.
Lower Key
Used to decrease values. (Hold for fast-step progression)
Raise Key
Used to increase values. (Hold for fast-step progression)
Menu Access Key
Used to enter or exit the menu system, index to the next menu, and enter the Security Level menu.
6
Power On
The Series C controller’s functional hierarchy is organized into three distinct user-program­mable groupings: Security Level, Menu System, and Operating Mode.
When power is first applied to the Series C, all segments of the LED displays will be momentarily illuminated while the instrument goes through a series of diagnostic checks to verify proper operation. A software version number will then
appear in the lower display, followed by a configuration code (upper display) and the communications protocol which is supported (lower display).
Please provide the software version number, communications protocol, and the controller’s full model number, when contacting us regarding your controller.
IMPORTANT: On initial startup, there is a possibility that outputs may be activated. We recommend placing the unit in Standby mode until you have configured the controller according to your application requirements. To place the controller in Standby, follow this procedure:
1) Press and hold Mode/Enter key until a menu label appears in upper display (approximately three seconds).
2) Press Raise or Lower key until appears in the lower display.
3) Press Mode/Enter key. (The upper display will alternate between and process value.)
Operations Overview
The user interface of the Series C allows you to use menus to set up the instrument, set the desired security level, change the setpoint, and conveniently change operating modes. Figure 9 on page 15 provides a functional representation of the user interface and the key presses necessary to perform
the basic functions.
7
Security Levels
The controller’s initial security level, set at the factory, is Configuration
. When you have completed configuring the instrument, we recommend the security level be set to the most restrictive level suitable for your application.
The security level feature allows you to limit access to the menus, setpoint, and operating mode selection according to the needs of your application. The security levels provided are Key Lockout, Setpoint, Setpoint plus Mode, User, Configuration, and Factory. To view or change security level from the Process Variable display, press and hold the Menu Access key for approximately 10 seconds. (Ignore the menu label that will appear in the upper display after approximately three seconds.) The controller will display
(Access Level) and the current security level label, e.g., . Use the Raise or Lower keys to index through the security levels. Press the Mode/Enter key once to select the new security level desired and return to the Process Value display.
Security Levels and Access Restrictions
Key Lockout Highest security level. No access to any
Setpoint No access to menus. Only allows setpoint
Setpoint
plus Mode No access to menus. Only allows setpoint
User All “Setpoint” level privileges as well as
Configuration All “User” level privileges as well as Input,
Factory All “Configuration” level privileges as well
controller functions. To escape, follow instructions above for changing security levels.
value or output percentage (manual mode) to be changed.
value, output percentage (manual mode), or operating mode to be changed.
access to Operating Mode, Autotune, and Control menus.
Output, Display, and Supervisor menus
as access to Calibration menu.
JMPØ3
NOTE: Removing this jumper on the microcontroller board disables the keypad, thus preventing any operator access.
8
Operating Modes
Remember to press the Mode/Enter key after making your selection.
If both outputs are set to or , the Series C will func­tion as a non-control­ling indicator. Control outputs will be disabled and the Operating Modes will not be displayed.
The Series C’s operating modes are: Manual, Standby, Normal, Autotune, Ramp/Soak Recipe, Run and Hold. To select a different
operating mode, press the Mode/Enter key for three seconds. The operating mode that the controller is currently in will be dis­played. To index through the available operating modes, press the Raise or Lower keys. When the desired mode is displayed, press the Mode/Enter key once to select the mode.
Manual
Standby
Normal
Autotune
(Only available when unit is placed in Standby mode and one output is PID.)
Start Ramp/Soak Recipe
(Only when programmed.)
Run
(Only available when recipe is active.)
Hold
(Only available when recipe is active.)
Operating Modes
Manual operating mode overrides auto­matic control, allowing you to control the outputs using a fixed percentage of output power, regardless of the process variable or setpoint.
If current automatic control is PID, transfer to Manual mode is “bumpless.”
Manual Used to set control output percentage
(Fixed Output Percentage) independent of Process Value. To set percentage, use the Menu Access key to select
and the Raise or Lower keys to set the value. Output 1 is a control output.
is displayed if Output 2 is a control
.
output
Standby Used to disable control outputs.
Normal Normal automatic control.
Autotune Used to initiate the autotuning
sequence (from Standby only).
Ramp/Soak Used to start ramp/soak recipe mode.
Recipe
Run Used to enable Run function
Hold Used to enable Hold function
is displayed if
9
11
Menu System Overview
If a key press is not sensed within five minutes, the control­ler automatically exits the Menu System and reverts to the Process Value display.
The Parameter Menu System is organized into ten basic menus: Input, Display, Output, Control, Alarm, Tune, Recipe, Supervisor, Calibration, and Option. To access the Menus, press and hold the Menu Access key for approxi­mately 3 seconds until a menu label appears in the upper dis­play. There are additional menus presented when an option is selected under the Option menu; however, the options are non-functional unless the appropriate option board has been installed. Pressing the Menu Access key indexes from menu to menu. Pressing the Mode/Enter key indexes through the parameters in a particular menu. The Raise and Lower
keys are used to modify the visible
menu parameter.
Each menu contains a logical group of parameters related to one another. Furthermore, the sequence of the menus has been carefully chosen to put the most important setup menus first.
10
Menu System Overview
To return to Process Value at any time, press and hold Menu Access key for three seconds
System
Menu
Figure 10. Series C Functional Diagram
for 3 seconds
once
for 3 seconds
Variable
Display
Process
for 3 seconds
for 10 seconds
once
Security
Levels
Selection
Mode
11
Menu System Overview
Notes: 1. It is recommended you start with the input menu.
Menu
Access
2. Parameter labels displayed will vary, depending upon the controller’s configuration.
Key
Figure 11. Chart of Series 16C Menu System
and Security Levels
(Continued on Next Page)
Mode/
Enter Key
(number)
(number)
(number)
(number)
(number)
12
Figure 11. Chart of Series 16C Menu System
and Security Levels
(Continued from Previous Page)
Functional When Option Card Installed
* See options manual for parameter selections.
Mode/
Enter Key
Raise/
Lower Key
(three seconds)
Security Levels
(Key Lockout) = No Access
(Setpoint) = Setpoint Value or Output
Percentage (Manual Mode)
(Setpoint plus Mode) = Plus
(User) = Plus
(Configuration) = Plus
(Factory) = Plus
13
Menus and Parameter Descriptions
Menus and Parameters
Input
Display
Used to select sensor-related parameters, such as input type, limits, and scaling.
Used to set or change decimal position and display units.
Output Used to specify output usage, control methods, and alarms.
Note: This menu is also functional for controllers not
equipped with alarm hardware; however, alarm indication will be only visual via the A1 and A2 LEDs on the front panel.
Control Alarm
Tune Recipe Supervisor Calibration Option Communications Contact/Digital
Input
Remote Analog
Setpoint
Auxiliary Output
Used to select parameters associated with the control methods. Used to select alarm parameters .
Used to set the autotune damping parameter.
Used to set ramp and soak parameters.
Used to set fail-safe and supervisory parameters.
Used to recalibrate input.
Used to select installed option.
(Option) Used to set serial communications parameters.
(Option) Used to select switch input functions.
(Option) Used to enter remote analog setpoint parameters.
(Option) Used to set auxiliary output parameters.
14
Input Menu
NOTE: FOR A MORE DETAILED DESCRIPTION OF MENU PARAMETERS, REFER TO THE GLOSSARY WHICH BEGINS ON PAGE 64.
The first parameter that needs to be set is Input Type. The remaining Input Menu parameters will change, depending upon whether a linear input type or a temperature input type is selected. Other menu param­eters related to the sensor range may also change. After selecting your Input Type, refer to the corresponding section on page 16 for the remainder of the Input Menu parameters.
Input Menu
Display Parameter Selection
Input Type Type J thermocouple
Type B thermocouple Type C thermocouple Type E thermocouple Type K thermocouple Type N thermocouple Type NIC thermocouple Type NNM thermocouple Type R thermocouple Type S thermocouple Type T thermocouple Platinel II thermocouple
100 ohm platinum RTD
15
17
Input Menu
Input Menu (continued)
Display Parameter Selection
Input Type 100 ohm
compressed RTD 0-20 mA 4-20 mA 0-10 mV 0-50 mV 0-100 mV 10-50 mV 0-1 V 0-5 V 0-10 V
JMPØ2
1-5 V
Note: When you ordered your controller, an input type was specified and the controller was set up accordingly and calibrated for that input type at the factory. If you decide to change input type from thermocouple to RTD or vice-versa, you will need to recalibrate the controller unless you ordered the “Calibrate All” option. (Refer to page 56 for information on recalibration.) If you are changing from a temperature input type to a linear input type, you MUST recalibrate and change the jumper settings as indicated in the above table.
JMPØ1
Input Jumper Settings
Input Type JMPØ1 JMPØ2
Thermocouple Out Out RTD Out Out Voltage <100 mV Out Out Voltage >100 mV In Out Current Process In In
Input Menu
Temperature Input Type
Display Parameter Selection
Bias (Display offset) -100 to 100 Lower Setpoint Limit Span of Sensor Upper Setpoint Limit Span of Sensor Filtering 0.1-10.0 sec.
Linear Input Type
Display Parameter Selection
Bias (Display offset) -100 to 100 Low Scale -1999 to 9999 High Scale -1999 to 9999 Lower Setpoint Limit Span of Sensor Upper Setpoint Limit Span of Sensor Filtering 0.1-10.0 sec.
16
Display Menu
Display Parameter Selection
Decimal Position 0-3 Linear Inputs
0-1 TC/RTD
Filter 0.1-10.0 sec
Units* Fahrenheit Celsius Kelvin
*NOTE: Does not appear for linear inputs.
Output Menu
Blanking (Time selected before setpoint diplay turns off.)
The first parameter that needs to be set in the Output Menu is the Output Type. There are three possible Output Type configurations: PID, On/Off, Alarm, or Off. (If you are not sure which Output Type
is best for your particular application, refer to the Glossary for an explanation of Output Types.) The remaining menu parameters in the
Output Menu will change, depending on the Output Type selected. The Control Menu will also change, depending on the Output Type selected. If you ordered two outputs, you can select two different Output Types. After setting your Output Type, refer to the correspond­ing sections below for the remaining Output Menu parameters. For simplification purposes, the following sections assume the same Output Type for both outputs. If you selected different Output Types, refer to both of those sections.
0-9999 sec
,
Output Type
Display Parameter Selection
Output 1 Type
Output 2 Type
JMPØ1
17
19
Output Menu
Control Menu
Setting Derivative (Rate) or Integral (Reset) to disables that aspect of PID control.
If BOTH outputs are set to direct-acting or BOTH outputs are set to reverse-acting, then only one proportional band selection will be displayed.
18
PID Output Type
Output 1 Action Reverse-acting (Heating)
Direct-acting (Cooling)
Output 1 Cycle Time* 0.2; 1 to 120 seconds Output 1 Low Limit 1-100% Output 1 High Limit 1-100%
Output 2 Action Reverse-acting (Heating)
Direct-acting (Cooling)
Output 2 Cycle Time* 0.2; 1 to 120 seconds Output 2 Low Limit 1-100% Output 2 High Limit 1-100%
*Recommended Cycle Time Settings
Output Type Recommended Setting (seconds)
B (5A/3A) 15 to 120 E (0-20 mA) 0.2 F (4-20 mA) MUST be set to 0.2 G (4-20 mA) MUST be set 0.2 S (pulsed 20 Vdc) 0.2 T (S.S. relay) 15 to 120** Y (5A/3A) N.C. 15 to 120 (Output 2 only)
** “T” outputs directly driving non-inductive loads (small heaters) can have
cycle times as low as 0.2 seconds.
PID Output Type
As with the Output Menu, the Control Menu will change, depending upon the Output Type selected. Note: These parameters are auto-
matically set during the autotune procedure. We do not recommend altering the value of these control parameters unless your process requires manual tuning.
Display Parameter Selection
Proportional Band 1 1...to span of sensor
Proportional Band 2 1...to span of sensor
Derivative Action (Rate) 0 to 2400 seconds
Manual Reset OFF, -100% to 100%
NOTE: The Integral Action (Auto Reset) parameter appears only if OFF is selected in the Manual Reset parameter.
Integral Action (Auto Reset) 0 to 9600 seconds
Output Menu
On/Off Output Type
Display Parameter Selection
Output 1 Action Reverse-acting (Heating)
Direct-acting (Cooling)
Output 2 Action Reverse-acting (Heating)
Direct-acting (Cooling)
Control Menu
On/Off Output Type
If both outputs are set to in the Output Type Menu, the controller will function as a non-controlling indicator. Control outputs will be disabled and the Operating Modes will not be displayed.
Display Parameter Selection
Deadband 1 Negative span of sensor to
positive span of sensor
Hysteresis Output 1 1...to span of sensor
Deadband 2 Negative span of sensor to
positive span of sensor
Hysteresis Output 2 1...to span of sensor
19
21
Notes On Alarms
Deviation, Inverse Band, and Normal Band Alarms track with setpoint.
When a latching alarm has been activated and the alarm condition has been removed, the Mode/Enter key must be pressed to unlatch the alarm.
Outputs can be set up as an alarm, similar to the standard alarm format. Four types of alarms are available: Process, Deviation, Inverse Band, and Normal Band. All alarms may be configured to be inhibited on power-up for a configurable time duration.
Process Alarm: Activates at preset value, independent
of setpoint. “High” process alarm activates at and above alarm setting. “Low” process alarm activates at and below alarm setting.
Deviation Alarm: Activates at a preset deviation value
from setpoint. “High” or “Low” deviation alarm activates above or below setpoint according to the preset deviation value.
Inverse Band Alarm: Activates when the process is within
a specified band centered around the setpoint.
Normal Band Alarm: Activates when the process exceeds
a specified band centered around the setpoint.
Latching Alarms
The Series C’s alarms may also be configured as latching alarms by selecting in the Alarm Action parameter selection.
20
Output Menu
Note: The Control Menu does not apply to an Alarm Output Type; therefore, the Control Menu does not appear.
Alarms A1 & A2 can be set up using this same information in the menu.
Alarm Output Type
Display Parameter Selection
Output 1 Alarm Action (Latching) (Normal)
Output 1 Alarm Operation (Process Low) (Process High) (Inverse Band) (Normal Band) (Deviation Low) (Deviation High)
Output 1 Alarm Delay 0-9999 sec
Output 1 Alarm Inhibit 0-9999 sec
Output 1 Alarm Setpoint Span of Sensor
Output 2 Alarm Action (Latching) (Normal)
Output 2 Alarm Operation (Process Low) (Process High) (Inverse Band) (Normal Band) (Deviation Low) (Deviation High)
Output 2 Alarm Delay* 0-9999 sec
Output 2 Alarm Inhibit** 0-9999 sec
Output 2 Alarm Setpoint Span of Sensor
*Alarm Delay - the time delay between the detection of the alarm condition and the initiation and indication of the output action. **Alarm Inhibit - prevents low setpoint alarm activation during cold startup applications.
21
Autotune Damping Menu
Recipe (Ramp/ Soak) Menu
22
Display Parameter Selection
Damping Low
Normal
High
Note: The damping parameter specifies how aggressively the controller performs its autotuning. The “Normal” setting is a compromise between the fast recovery and overshoot. The “Low” setting provides faster recovery, but with the possibil­ity of overshoot; the “High” setting a slower recovery, but with minimum or no overshoot.
Single Setpoint Ramp Time
This selection will cause the controller to ‘ramp’ the process from the starting point (current process value) to the setpoint in the time specified. This ramp will take place at startup when selected from the Ramp/Soak menu. The setpoint must be at least ±0.2% of sensor span for the ramp to be employed.
Multi-Step Ramp
This selection will enable the programming of a recipe (make all ramp/soak recipe variables visible). Recipes can be resumed on startup if interrupted by a power failure or initiated, held, and terminated from the front panel via the Mode Menu or with the logic input option (initiate and held/resumed only).
Holdback Band
Specifies the maximum number of degrees above or below setpoint that the process can be for the segment timer to keep going. The timer will hold while the process settles back into the band and then continue. If this feature is not desired, this param­eter should be set to which will disable it.
Termination State
This parameter determines what the control will do at the completion of a recipe. Last Setpoint refers to the last temperature specified in the ramp/soak recipe. Default Setpoint refers to the standard setpoint which was in effect prior to recipe initiation.
Recycle Number
Specifies the number of times after the first time that the recipe is run before the program terminates.
Recipe (Ramp/ Soak) Menu
If a ramp/soak error condition occurs, the upper display will toggle between and the numeric error code for three seconds before the recipe terminates. Possible error codes are: 02 = Recipe Empty (i.e. no non-zero ramp times) 05 = Insufficient Setpoint-Process Value Deviation
Power Fail Resume
Setting this parameter to On will cause the control to resume a recipe which was active when a power failure occurred. The recipe will resume at the start of the last active ramp or soak segment.
Ramp/Soak Events (1-8) (If alarms are configured as ramp/soak events.)
Ramp/Soak events occur at the beginning of their designated segment. All events are terminated once the recipe has been completed or terminated. This can be used as an alarm when a segment is reached.
Display Parameter Selection
Recipe Option Single-Setpoint Ramp Multi-Step Ramp Disabled
Single-Setpoint 1-9999 mins. Ramp Time*
*NOTE: Only available when single-setpoint ramp is selected.
Holdback Band Off-100 degrees
Termination State Last Setpoint Default Setpoint Recipe to Standby
23
25
Recipe (Ramp/ Soak) Menu
For Ramp Events and Soak Events to be employed, Alarm 1 or Alarm 2 must be set for event usage in the Alarm Menu.
Supervisor Menu
The Failsafe State is only enforced when a problem is detected with the process input. It is not reli­ably enforceable in instances of internal circuitry failure such as EEPROM problems.
NOTE: The following seven parameters are only available when multi-step ramp is selected.
Display Parameter Selection
Recycle Number 0-99,
(Recipe Executions)
Power Fail Resume Off
On
Ramp Times 1-8 0-9999 mins.
Ramp Events 1-8 Alarm 1 On Alarm 1 Off Alarm 2 On Alarm 2 Off Disabled
Soak Levels 1-8 Display Units, FS
Soak Times 1-8 0-9999 mins.
Soak Events 1-8 Alarm 1 On Alarm 1 Off Alarm 2 On Alarm 2 Off Disabled
Display Parameter Selection
Output 1 0 to 100%
Failsafe State of output
Output 2 0 to 100%
Failsafe State of output
Loop Break Time Off, 4-9600 sec Highest Reading n/a Lowest Reading n/a Load Default
Parameters
Choosing “Yes” to Load Default Parameters resets all menu parameters to factory settings.
Output % High Limits are ignored when the unit enters a Failsafe State.
24
Calibration Menu
Toggles with the temperature value that should be input to
perform the low calibration operation.
The low calibration operation is triggered by pressing the up
arrow key.
Toggles with the temperature value that should be input to
perform the high calibration operation.
The high calibration operation is triggered by pressing the
up arrow key.
Options Menu
Display Parameter Selection
Installed Card Serial Communications Serial Communications with Switch Input Remote Analog Setpoint Auxiliary Output Alarm Switch Input with Alarm
Note: See options manual for parameter selections.
25
27
Autotuning
In order for the controller to autotune properly, the setpoint value must be at least 1% of span above or below the initial process value. Make sure that the Setpoint Target Time parameter is set to OFF.
Tuning accuracy increas­es as the spread between ambient and setpoint value increases.
Tuning should be performed with system in equilibrium (no latent energy remaining).
To place the controller in Autotune mode:
1) Configure the controller by following the directions for
Initial Setup Sequence through Step 3 on page 7. Set damping parameter. (See page 22.)
2) If the controller is not already in Standby mode, place it in Standby now as follows. Press and hold the
Mode/Enter
key for three seconds. Display will indicate your current operating mode. Press the Raise key or Lower key to select Standby. Press Mode key again and the display will alternate between and the pro­cess value. This will deactivate all outputs.
3) If Setpoint Value has not been entered, adjust setpoint
now by using the Raise or Lower key to set the desired setpoint.
4) Wait for process to stabilize before proceeding, e.g., in the
case of a heating and cooling process, return to ambient temperature.
5) Initiate Autotuning. Press and hold the Mode/Enter key
again for three seconds, then press the Raise or Lower key repeatedly until appears. Finally, press the Mode/Enter key again. The display will alternately indicate
and process value as the controller “learns” the proper proportional band, derivative, and integral values for the process. If unacceptable overshoot occurs on restart, shut down the process and increase the damping setting. If sluggish response is observed, shut down the process and decrease the damping setting.
26
Autotuning
If a tune error condition occurs, the upper display will toggle between and a numeric error code for three seconds before the tune process terminates. The controller will then automatically go into Standby mode when a tuning error occurs. Possible error codes are: 02 = No PID Device Configured 03 = Incorrect Output Action 05 = Insufficient Setpoint-Process Value Deviation 08 = Invalid Tune Results 09 = Tune Timeout
Autotuning Procedure Diagram
Note: Keep in mind that the setpoint value must be at least 1% of span above or below the initial setpoint, and that the process value must be stable prior to initiating the tune.
Hold for
three
seconds
Hold for
three
seconds
Current
Mode
Standby
Mode
Press
Press until
appears
Standby
Mode
Autotune
Mode
Press
Once
Press
Once
Flashes
Flashes
Controller is
now autotuning
27
Manual Tuning
T
While some processes other than heat or cool applications may respond successfully to autotuning procedures, the controller may need to be manually tuned for non-temperature processes.
Manual Tuning Procedure (Zeigler-Nichols PID Method)
This tuning method may be used for non-temperature control processes or if the spread between ambient temperature and process operating temperature is small. For best results, the use of a recording device is required when tuning with this method.
1) For temperature control processes, disable any cooling
device used.
2) With the power off and the controller NOT in the Key
Lockout security level, apply power and immediately put the controller in Standby mode by pressing the Mode/ Enter key for three seconds, the Raise key until
appears and press the Mode/Enter key again.
3) If you have a direct-acting output, it must be disabled
before proceeding further = .
4) Under the Control menu, make sure that the derivative
term , the offset term , and the integral term are all set to zero, and the proportional band or is set to the maximum setting.
5) Adjust setpoint to the desired value with the Raise/Lower
keys.
6) Press the Mode/Enter key for four seconds, the Raise
key twice
return the controller to normal operation.
7) While monitoring the recording device, decrease the
proportional band value by repeatedly halving the value until a small, sustained temperature oscillation is observed. Measure the period of one cycle of oscillation (“T” on the diagram below).
, and the Mode/Enter key again to
8) Divide the period of oscillation (T) by eight. The resulting
number is the correct Derivative time in seconds. Multiply this number by four. This is the correct Integral time in seconds.
28
9) Multiply the bandwidth value obtained in Step 7 by 1.66
and enter this as the new proportional band value.
Error Codes
If an error code cannot be cleared by using the actions provided, contact factory.
Display Problem Actions
Open Sensor Check sensor,
wiring, and Input.
Reversed Sensor Check the type selection in the Input menu, and check sensor polarity.
Loop Break Correct problem and reset controller.
Checksum Error Press any key
RAM Error to perform a
Defaults Loaded soft reset and
EEPROM Write Failure reinitialize controller.
Power Fail Resume No further resume Feature Disabled actions available.
Plus other Unexpected or Reset 2-Digit Invalid Interrupt controllers Code
Autotune Errors
If a tune error condition occurs, the upper display will toggle between and a numeric error code for three seconds before the tune process terminates. The controller will then automatically go into Standby mode when a tuning error occurs. Possible error codes are: 02 = No PID Device Configured 03 = Incorrect Output Action 05 = Insufficient Setpoint-Process Value Deviation 08 = Invalid Tune Results 09 = Tune Timeout
Ramp/Soak Errors
Possible error codes are: 02 = Recipe Empty (i.e. no non-zero ramp times)
05 = Insufficient Setpoint-Process Value Deviation
29
Technical Specifications
30
Operating Limits
Ambient Temperature 32°F to 140°F (0°C to 60°C) Relative Humidity Tolerance 90%, Non-Condensing Power 100 to 250 V 50/60 Hz (Single-Phase) 100 to 250 Vdc 24 Vac/dc Power Consumption Less than 6 VA
Performance
Accuracy ±0.20% of Full Scale (±0.10% Typical), ±1 Digit Setpoint Resolution 1 Count / 0.1 Count Repeatability ±1 Count Temperature Stability 5 µV /°C (Maximum) TC Cold-End Tracking 0.05°C /°C Ambient Noise Rejection >100 dB Common Mode, >70 dB Series Mode Process Sampling 10 Hz (100 ms)
Control Characteristics
Setpoint Limits Automatically Adjust to Selected TC/RTD Alarms Adjustable for High/Low; Selectable Process, Deviation, or Band Alarms Proportional Band 1 to Span of Sensor Integral 0 to 9600 Seconds Derivative 0 to 2400 Seconds Cycle Time 200 ms; 1 to 120 sec Control Hysteresis 1 to Span of Sensor Autotune Operator Initiated from Front Panel Manual Control Operator Initiated from Front Panel
Mechanical Characteristics
Display Dual, 4-digit 0.36” (9.2 mm) LED display Process Value: Orange Setpoint Value/Menu: Green Numeric Range -1999 to 9999 Front-Panel Cutout 1.771” x 1.771” (45 mm x 45 mm) Depth Behind Panel 3.937” (100 mm) Front Panel Rating NEMA 4X Operating Temperature 32 to 140° F (0 to 60° C) Humidity Conditions 90% R.H. max., non-condensing Parameter Retention Solid-state, non-volatile memory Connections Input and output via barrier strip with locking terminals Contacts Twin bifurcated
Technical Specifications
Input Type
Thermocouple B, C, E, J, K, N, NIC, NNM, R, S, T, Platinel II Maximum lead resistance 100 ohms for rated accuracy
RTD Platinum 2- and 3-wire, 100 ohms at 0° C, DIN curve standard (0.00385) 1000 ohms available
Linear 0-50 mV/10-50 mV, 0-5 V/1-5 V 0-20 mA/4-20 mA, 0-100 mV, 0-10 V
Output Device B 5 A (120/240 Vac) relay, normally
open, used for switching resistive loads. If relays or solenoids are to be driven, select the “T” output. If a “B” output is selected, order snubber network 235Z005U01.
E 0-20 mA
F 4-20 mA, full output to load with 500 ohm impedance max.
G High impedance ‘F’ (800 ohms max.)
S 20 Vdc pulsed output for solid-state relays.
T 1 A @ 120/240 Vac , solid-state relay, zero voltage-switched and optically isolated from drive signal. Only resistive loads to 1A may be controlled directly. Larger loads may be controlled using an external contactor.
Y 5 A (120/240 Vac) relay, but normally closed (output 2 only).
Alarm Type
See ordering code on page 55.
31
33
Ordering Codes
Model
16
Code Input Type CT Thermocouple CR RTD CS Compressed RTD CM Millivolt Linear CV Volt Linear CC Current Linear CA All CB TD & T/C
Input
Calibration Type
C
Output
1
Code Output 1
0 None B Relay (N.O.) E 0 to 20 mA F 4 to 20 mA G High Impedance ‘F’ P 20 Vdc @ 35 mA S Pulsed 20 Vdc T Solid-State Relay X 0 to 10 Vdc
Code Output 2
0 None B Relay (N.O.) E 0 to 20 mA F 4 to 20 mA G High Impedance ‘F’ P 20 Vdc @ 35 mA S Pulsed 20 Vdc T Solid-State Relay Y T.C. Relay
Output
2
Standard
Options
Code Option
00 None Alarms 10 Dual SSR, N.O. 20 Dual Open Collector 21 Dual 24 Vdc 22 Dual SSR, N.C. 23 Relay, N.O. Communications 30 RS-232/Athena+ RS-485, Athena+ with Contact/Digital Input 31 No Switch 36 Switch Close 37 Switch Open 38 5V Input Contact/Digital Input (with Alarm) 40 Switch Closed 41 Switch Open 42 5 V Input RS-485, Modbus with Contact/Digital Input 45 No Switch 46 Switch Close 47 Switch Open 48 5V Input Transducer Excitation 50 10 Vdc 51 12 Vdc 52 15 Vdc 53 5 Vdc Auxiliary Output 60 4 to 20 mA 61 1 to 5 V 62 0 to 20 mA 63 0 to 5 V
Special Options
Code Option
AB Back Cover: Screw Mount AD No-Name Overlay, Standard Athena Patterns and Colors AZ 24 Vac/Vdc Supply EO SPI Communications Protocol EP Engel/Arburg Communications Protocol
32
Recalibration Procedures
The Series C controller is precalibrated at the factory. Under normal circumstances, the factory calibration should be valid for the life of the instrument. If recalibration should be required, allow the controller to warm up for 15 minutes and follow these steps carefully.
1) Remove power from the controller and disconnect all output devices. Disconnect input. Attach an appropriate calibrator to the input terminals.
2) Apply power to the calibrator, making sure that the dis­played value is not outside the range of the controller. Then, apply power to the controller.
3) Index to the Calibration Low menu item in the Calibration Menu.
(You must have Security Level set to “Factory” to access this menu.)
4) Dial Calibrator to prompted value on the controller’s dis­play. See chart below for RTD resistance vs. temperature values.
5) Allow the controller to settle for at least one minute.
6) Press Raise Key.
7) Repeat Steps 4, 5, and 6 for the Calibration High setting.
8) Press the Menu Access key for three seconds to return to the Process Value display.
RTD Calibration Values
RTD Cal Lo 0° C 32° F 100
RTD Cal Hi 768° C 1414° F 366
RT.D Mid-range 328° C 622.4° F 222
33
Quick-Helps
1. To return the unit to last operating mode (Normal, Standby, FOP, or Tune):
Action Display
From Menu System: Press and hold PV + SV + Mode
From Security Level Menu: Press PV+ SV + Mode
2. To enter Standby
operating mode:
From Normal Press and hold
operating mode:
Press
From FOP (Manual) Press and hold
operating mode:
Press Press + PV + SV
From Menu System: Press and hold
Press
for 3 sec.
Action Display
for 3 sec.
Press
for 3 sec.
for 3 sec.
Press and hold
for 3 sec.
+ PV + SV
Press + PV + SV
From Security Level Menu: Press PV + SV
for 3 sec. Press
Press and hold
Press + PV + SV
3. To escape from Standby Action Display operating mode:
for 3 sec.
Press
Press and hold
Press PV + SV
4. To initiate Autotuning: Action Display Enter Standby operating mode (See Quick-Help #2)
Press
Press
34
Press + PV + SV
Quick-Helps
5. To abort Autotuning Action Display
and return to normal Press and hold
operation:
Press
for 3 sec.
Press PV + SV
6. To enter FOP (Manual) Action Display
operating mode:
Press + PV +
% of Power Value
Press
Press and hold
for 3 sec.
to set new
% of Power Value
Press to + PV + set % of Power % of Power
for Output 2 Value if desired.
7. To escape from FOP Action Display
(Manual) operating mode:
Press
Press and hold
for 3 sec.
Press PV + SV
35
Warranty/ Repairs
36
Two-Year Limited Warranty
THIS EQUIPMENT IS WARRANTED TO BE FREE FROM DEFECTS OF MATERIAL AND WORKMANSHIP. IT IS SOLD SUBJECT TO OUR MUTUAL AGREEMENT THAT THE LIABILITY OF ATHENA CONTROLS, INCORPORATED IS TO REPLACE OR REPAIR THIS EQUIPMENT AT ITS FACTORY, PROVIDED THAT IT IS RETURNED WITH TRANSPORTATION PREPAID WITHIN TWO (2) YEARS OF ITS PURCHASE.
THE PURCHASER AGREES THAT ATHENA CONTROLS, INCORPORATED ASSUMES NO LIABILITY UNDER ANY CIRCUMSTANCES FOR CONSEQUENTIAL DAMAGES RESULTING FROM ITS USE OR FROM IMPROPER HANDLING OR PACKAGING OF SHIPMENTS RETURNED TO THE FACTORY.
COMPONENTS WHICH WEAR OR WHICH ARE DAMAGED BY MISUSE ARE NOT WARRANTED. THESE INCLUDE CONTACT POINTS, FUSES, ELECTROMECHANICAL RELAYS, AND TRIACS. UNITS WHICH HAVE BEEN MODIFIED BY A CUSTOMER IN ANY WAY ARE NOT WARRANTED.
Other than those expressly stated herein, THERE ARE NO OTHER WARRANTIES OF ANY KIND, EXPRESS OR IMPLIED, AND SPECIFICALLY EXCLUDED BUT NOT BY WAY OF LIMITATION, ARE THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY.
IT IS UNDERSTOOD AND AGREED THE SELLER’S LIABILITY WHETHER IN CONTRACT, IN TORT, UNDER ANY WARRANTY, IN NEGLIGENCE OR OTHERWISE SHALL NOT EXCEED THE RETURN OF THE AMOUNT OF THE PURCHASE PRICE PAID BY THE PURCHASER AND UNDER NO CIRCUMSTANCES SHALL SELLER BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES. THE PRICE STATED FOR THE EQUIPMENT IS A CONSIDERATION IN LIMITING SELLER’S LIABILITY. NO ACTION, REGARDLESS OF FORM, ARISING OUT OF THE TRANSACTIONS OF THIS AGREEMENT MAY BE BROUGHT BY PURCHASER MORE THAN ONE YEAR AFTER THE CAUSE OF ACTION HAS ACCRUED.
SELLER’S MAXIMUM LIABILITY SHALL NOT EXCEED AND BUYER’S REMEDY IS LIMITED TO EITHER (i) REPAIR OR REPLACEMENT OF THE DEFECTIVE PART OR PRODUCT, OR AT SELLER’S OPTION (ii) RETURN OF THE PRODUCT AND REFUND OF THE PURCHASE PRICE, AND SUCH REMEDY SHALL BE BUYER’S ENTIRE AND EXCLUSIVE REMEDY. THE SPECIFICATIONS PUT FORTH IN THIS MANUAL ARE SUBJECT TO CHANGE WITHOUT NOTICE.
Warranty/ Repairs
Unit Repairs
It is recommended that units requiring service be returned to an authorized service center. Before a controller is returned for service, please consult the service center nearest you. In many cases, the problem can be cleared up over the telephone. When the unit needs to be returned, the service center will ask for a detailed explanation of problems encountered and a Purchase Order to cover any charge. This information should also be put in the box with the unit. This should expedite return of the unit to you.
This document is based on information available at the time of its publication. While efforts have been made to render accuracy to its content, the information contained herein does not purport to cover all details or variations in hardware, nor to provide for every possible contingency in connection with the installation and maintenance. Features may be described herein which are not present in all hardware. Athena Controls assumes no obligation of notice to holders of this document with respect to changes subsequently made.
Proprietary information of Athena Controls, Inc. is furnished for customer use only. No other use is authorized without the written permission of Athena Controls, Inc.
37
39
IEC Requirements
USE OF THIS EQUIPMENT IN A MANNER NOT SPECIFIED BY THE MANUFACTURER MAY IMPAIR PROTECTION PROVIDED BY THE EQUIPMENT!
The maximum supply current is line voltage dependent:
230 mA for a 24 Vac/dc input fuse rating=700 mA 60 mA for an 85-250 Vac input fuse rating=100 mA
Output Specifications
Output Type Max current Voltage Leakage B 5 A 250 Vac 1000 M ohms T 1 A 250 Vpk 1 mA S 20 mA 5 V NA
CLEANING INSTRUCTIONS
1. Remove power from the unit prior to any cleaning operation.
2. Use a cotton cloth to gently and sparingly apply isopropyl
alcohol only. Do not use cleaners or other solvents as they may damage the unit.
3. Allow the unit to dry completely prior to reapplying power.
38
Glossary
Alarm Delay - the time delay between the detection of the alarm condi-
tion and the initiation and indication of the output action.
Alarm Inhibit - prevents low setpoint alarm activation during cold startup
applications.
Bias - allows the operator to compensate for any difference between sensor
temperature and the point to be measured. The process display and set­point will be offset by the value entered in the Bias parameter in the input menu. Ex: Desired temperature is 150 degrees. Sensor is adjacent to heater and reads 50 degrees higher than the actual process temperature. Enter bias of -50. Enter setpoint of 150. Process will display 150 even though sensor will be measuring 200 degrees.
Blanking - controls the time the setpoint value display remains on. After the
set time, the setpoint value display turns off. Pressing any button causes the setpoint value display to reappear for the selected time interval.
Cycle Time - The period of time in which the controller’s output completes
an on-off cycle (Proportional Output Type only). Example: Output type = Mechanical relay Cycle time = 10 seconds Output power = 50% Controller output = 5 seconds closed, 5 seconds open
Deadband - In On/Off temperature control, it is the band above or below
the setpoint where there is no output action. It has the effect of moving the apparent setpoint.
Derivative (rate) - Adjusts the controller gain quickly in response to load
changes.
Failsafe State - designates the percentage of power output that the con-
troller defaults to after it detects a loop break condition and after the loop break time has elapsed.
Filter (in Display menu) - changes the filtering speed for the process value
display only. It does not affect control. This parameter is mainly used to slow down the flickering of the display when the decimal position chosen is greater than zero.
Filtering (in Input menu) - sets the time period over which the process
value is averaged.
Highest Reading - records the highest process value read by the controller.
It may be reset to zero by using the Raise or Lower arrow keys.
Hysteresis - In On/Off temperature control, hysteresis represents the band
where the output changes state from deactivated to activated. It prevents chattering around the setpoint and prevents rapid output cycling.
Integral (automatic reset) - slowly adjusts the position of the Proportional
Band (range of power output) to eliminate offset error.
Loop Break - a condition where the input is not changing or responding
properly to the output action. This could be caused by a thermocouple or
39
41
Glossary
input failure, or a heater or load failure.
Loop Break Time - the time interval from when the controller detects a
loop break condition and the initiation of the failsafe state.
Lowest Reading - records the lowest process value read by the controller.
May be reset to zero by using the Raise or Lower arrow keys.
Lower Setpoint Limit - prohibits users from adjusting the setpoint lower
than the selected value.
Manual Reset - an adjustment that moves the Proportional Band up or
down by a fixed percentage so that more or less power is applied at set­point. It is used to eliminate offset error.
On/Off Output Type - In a heating application, the controller applies 100%
output power if the process temperature is below the setpoint and 0% at the setpoint. For a cooling application, the controller applies 100% output power if the process temperature is above the setpoint and 0% output power at the setpoint. There are only two output states: fully on and fully off. Applications for On/Off Control:
1. When temperature oscillation is acceptable.
2. When constant cycling of mechanical devices is
prohibited (Compressors, Blowers, etc.)
3. Under-powered processes
Output Low Limit % - Prohibits the controller’s output from going
below the specified percentage.
Output High Limit % - Prohibits the controller’s output from going above
the specified percentage.
PID Output Type (Proportional - Integral - Derivative) - The controller
modulates output power by adjusting the output power percentage within a proportional band. Power is proportionally reduced as the process temperature gets closer to the setpoint temperature. PID control helps reduce overshoot on start-up, enhances stability, and compensates for process lag. The PID parameters are automatically calculated for a par­ticular application during the autotune procedure. Applications for PID Control:
1. Where process temperature lags exist
2. When load changes are present
3. When overshoot is prohibited
4. When very accurate control is required
Proportional Band - the band (expressed in degrees of temperature) in
which the controller modulates its power percentage.
Temperature Lag - The product of thermal resistance and thermal capac-
ity. Also defined as delay of the transmission of heat from the controlled element to the sensor caused by thermal mass of the process material and/or process container, or the distance between the control element and the sensor.
Upper Setpoint Limit - prohibits users from adjusting the setpoint higher
than the selected value.
40
Quick Setup Instructions - Series 16C Temperature Controller
Experienced users, already familiar with the Series 16C, and using the controller with PID outputs, may follow these condensed instructions to autotune the controller and get started quickly once the instrument is prop-
erly mounted and wired, and the Security Level is set to . Once setup is complete, we recommend changing the Security Level back to the most restrictive level suitable for your application.
These quick setup instructions are not meant as a substitute for reading the
full instruction manual supplied with the controller. Please be sure to read through the manual for specific details of operation and, most importantly, for safety precautions. If you have any questions, or experience problems with setting up your controller, consult the full instruction manual first and, if you still need assistance, contact your Athena representative or call 1-800-782-6776.
Menu Access Raise Lower Mode/Enter
1. Apply power. After self-check display stops, place controller in Standby mode by pressing and holding the
Mode/Enter key for 3 seconds, the or key until appears, and then the key again.
will flash, alternating with the Process Value.
2. Press and hold the Menu Access key for 3 seconds until is displayed. Press key once until
appears, then use or keys to select sensor input type.
3. Press to display . Then press once to display . Use or to select .
4. Press the key until Output 1 Action is displayed. Select the desired output action using the
or keys. (Reverse = Heating)
41
43
Keep This Information in a Safe Place
Configured Parameters Reference Data
Series C Temperature Controllers
Model Number Zone Location
(Displayed when the controller is powered up after all the
segments on both lines of the display have been tested.)
Dear Customer:
Please keep this information handy – in case your controller should lose its configured initial parameter
values or for easy reference when setting up a new controller. After auto-tuning, and when your controller is controlling well, we suggest you write the displayed value for each of the menu parameters listed below. If you do not use a listed param­eter, indicate “N/A”. Using this information to document your parameter settings could reduce your downtime. If you have any questions, or need further assistance, please contact Athena Controls Technical
Support: Toll-free (in USA): 800.782.6776 Telephone: 610.828.2490 Fax: 610.828.7084 E-Mail: techsupport@athenacontrols.com Website: athenacontrols.com
Configured Parameters Reference Data
Inp
Type
BIAs
OUTP
01.tY
01.Ac
Firmware Version No.
Series C Temperature Controllers
CtrL
02.tY
02.Ac
db.1
HYS.1
ALr.
A1.AA
A1.AO
SCL.L
SCL.H
Sp.LL
Sp.HL
I.FIL
Options
42
01.cY
01.LL
01.HL
01.AA
01.AO
01.dl
01.IH
01.SP
02.cY
02.LL
02.HL
02.AA
02.AO
02.dl
02.IH
02.SP
db.2
HYS.2
Pb1
Pb2
dEr
OFFS
Int
A1.dl
A1.IH
A1.SP
A2.AA
A2.Ao
A2.dl
A2.IH
A2.SP
Notes
43
For Toll-FreeTechnical Assistance in the USA,
Call Toll Free: 1-800-782-6776
Athena Controls, Inc.
5145 Campus Drive
Plymouth Meeting, PA 19462 U.S.A.
Tel: (610) 828-2490
Fax: (610) 828-7084
Toll-Free in U.S.: 1-800-782-6776
Internet: www.athenacontrols.com
900M011U00 REVISION “B” / 09-13-2004
44
Loading...