Atec T-R-200A-3PH-ED User Manual

200A
-
3PH/ED
3 phase Current
Injection System
Features
0-200A 3 phase output
Accurate true RMS digital
metering
All outputs fully isolated
Multi-function 1ms resolution
timing system
Auxiliary AC output
Electronic over-current
protection
Compact and portable
T&R Test Equipment is a market leader in the field of current injection equipment. The range includes single phase units with 100A-6000A output capability and three phase systems up to 200A. All have true RMS metering, a flexible timing system, and an easy to understand user interface.
The 200A-3PH/ED test system provides commissioning and maintenance engineers with a compact, portable and flexible system for the testing and timing of protective relays, circuit breakers and thermal overloads. The unit is equally at home testing solid state or electro-magnetic relays, and has a rating suitable for testing thermal trips.
The 200A-3PH/ED has independent true rms digital metering for each output with independently selectable ranges.
The outputs are isolated and independently variable and allow the injection of currents up to 200A. The outputs are protected by electronic over-current trips and fuses.
The timing system on the 200A-3PH/ED is flexible and exceptionally easy to use, allowing trip times to be measured to a high degree of accuracy. Units with auxiliary contacts may be timed using the NC or NO timer modes, and devices with no auxiliary contacts may be timed using the current operated mode.
The unit is ideal for testing the following devices:
Over and under current relays
IDMT relays
Thermal overloads
Magnetic circuit breakers
The unit may also be used in conjunction with the DVS3 digital voltage source to test protection systems requiring three voltages and three currents. Protection that may be tested in conjunction with the DVS3 includes:
Directional relays
Distance protection
Power relays and transducers
DVS3 Digital voltage source
13
200A-3PH/ED Specification
Main Output
The units have three independently controlled outputs, one for each phase. The output is switched on and off by illuminated pushbuttons, and the current is set using the three control knobs on the front panel. All ranges are continuously variable from zero.
Range Continuous 5 minutes 1 minute
5V 50A 100A 200A The above intermittent on times must be followed by an off time of 15 minutes, and are based on an ambient temperature of 25°C.
Auxiliary AC Outputs
A switched, isolated auxiliary 240V 50mA AC supply is available to power auxiliary control circuits. The output is protected by a fuse.
Metering
The output on the 200A-3PH/ED is metered by a digital true RMS system with a 3.5 digit LED display. The range for each channel is independently selected for each channel by a switch on the front panel.
Range Resolution Trip Current Accuracy
10A 0.01A 11.5A ±0.6% rdg+6d 20A 0.01A 23A ±0.6% rdg+6d 100A 0.1A 115A ±0.6% rdg+6d 200A 0.1A 230A ±0.6% rdg+6d
An electronic current trip is automatically set to 115% of full scale of the selected metering range to protect the device under test.
Supply Requirements
400V+14%-6% 50/60Hz 3ph 4 wire 3300VA max A delta-star transformer is available as an optional accessory for operation from a 3 wire supply.
Temperature Range
Storage -20°C to 60°C Operating 0°C to 45°C
Dimensions Weight
200A-3PH/ED 315mm x 550mm x 300mm 35kg
Accessories Supplied With Unit
Operating manual, mains lead, spare fuse set, 5m 200AL/3PH output lead set.
Lead Set specifications
The 200AL/3PH lead set includes the following items: 6 x 5m 25mm 1 x 5m 2 core auxiliary lead terminated in 4mm plugs 1 x 5m 2 core auxiliary lead terminated bare ends The lead set is supplied in a reinforced plastic wallet.
2
200A leads terminated in M10 fork crimps
Timing System
The timing system on the 200A-3PH/ED is very flexible, allowing a wide range of protective devices to be timed.
Range 0-999.999s Resolution 1ms Accuracy 0.01% rdg +1d (all except current operated mode)
0.01% rdg +3d (current operated mode) The contact circuit has an open circuit voltage of 24Vdc and a
short circuit current of 300mA. The contacts may be connected to volt-free contacts or contacts connected to a DC voltage system (220Vdc maximum).
The following functions are provided:
Mode Timer Start Timer Stop
Normally Open Press ‘ON’ Contact closes Normally Closed Press ‘ON’ Contact opens Current operated Current > 20% Current < 20% of range of range Off Timer inoperative Timer inoperative
The output is automatically switched off at the end of the test to safeguard the relay under test.
Protection and Safety
The 200A-3PH/ED is protected by electronic over current trips on the outputs, fuses on the contact input, the mains input and regulators.
The auxiliary AC output is fuse protected. An earth terminal is provided for connection to a local earth.
The unit is designed to comply with BSEN61010, and is CE marked.
Optional Delta-Star Supply Transformer
The optional delta-star supply transformer allows operation from 115V, 230V, 400V, and 440V 3 wire (delta) supplies. The input voltage is selected by a switch on the unit. An auxiliary single phase output is also provided to supply power to a DVS3 voltage source.
Input: 115V, 230V, 400V, 440V ±10% 3 wire, 4000VA max
3φ output: 400V 4 wire 3300VA 1 min on/15 min off 1100VA continuous
1φ output: 230V 300VA 5 min on/15 min off 150VA continuous
Optional Accessories
200A-3PH delta-star transformer.
Note: Due to the company’s continuous research programme, the information above may change at any time without prior notificatio n. Please check that you have the most recent data on the product.