Sorensen SG Series
4–150 kW
Programmable Precision High Power DC Power Supply
• High Power Density: up to 15 kW in 3U, 30 kW
in a 6U chassis
• Wide Voltage Range: 0-10V up to 0-1000V,
from 4 to 30 kW
• Fast Load Transient Response: Protection from
undesired voltage excursions
• Low Ripple and Noise
• Hardware Trigger (Ethernet Option)
• Parallelable up to 150 kW
• Sequencing: Free system controller & speed up test
• Low audible noise: Temperature controlled variable
speed fans
The Sorensen SG Series (hereafter SG Series)
represents the next generation of high power
programmable DC power supplies. The SG
Series is designed for exceptional load transient
response, low noise and the highest power
density in the industry. With a full 15 kW
available down to 20VDC output in a 3U package
the SG leads the industry in power density. The
power density is enhanced by a stylish front air
intake allowing supplies to be stacked without
any required clearance between units.
At the heart of the SG series is a 5 kW power
module. Depending on the output voltage, one
to six modules can be congured in a single
chassis to deliver 5 kW to 30 kW of power.
Combinations of these chassis can then be
easily paralleled to achieve power levels up to
150 kW. Paralleled units operate like one single
supply providing total system current. Available
in two control versions, the SGA has basic analog
controls, while the SGI provides intelligent control
features.
SGI: Advanced Intelligent Control
(Sorensen General purpose Intelligent) The SGI
combines onboard intelligent controls with
the outstanding power electronics common to
all SG family supplies. These controls enable
sophisticated sequencing, constant power mode
and save/recall of instrument settings. Looping
of sequences makes the SGI ideal for repetitive
testing. An impressive vacuum uorescent
graphical display in eight languages, context
sensitive “soft” keys and front panel keyboard
simplify programming of the SGI.
SGA: Outstanding Value - Analog Control
(Sorensen General purpose Analog) The SGA,
with its industry leading performance, is available
for customers requiring simple front panel analog
controls or external control. With the same high
performance power electronics as the SGI, the
SGA provides essential features like 10- turn
potentiometers for setting voltage and current, 3
½ digit LED readout plus front panel over-voltage
protection (OVP) preview/adjustment and reset.
10–1000 V
5–6000 A
208 400 480
858.458.0223
sales@ProgrammablePower.com
AMETEK
Programmable Power
9250 Brown Deer Road
San Diego, CA 92121-2267
USA
05012013
77
SG Series : Product Specications
Common
Remote Sense Terminals are provided to sense output voltage at point of load. Maximum line drop 5% of rated voltage per line for 40-100V models,
Parallel Operation Up to 5 units may be paralleled for additional current within the power supply single-unit specications, with exception of the
Series Operation Up to 2 units (see Output Float Voltage)
Input
Nominal Voltage
3 phase, 3 wire + ground
Frequency 47 – 63Hz , 400Hz ( 400Hz @ 208VAC, for 6U units is optional modication and does not carry CE, UL or CSA markings )
Power Factor >0.9 typical for 10V - 30V, 50V, 1000V and other models with optional “PF” modication.
Protection ( typical ) ½ cycle ride-though , typical, on all three phases, 3 cycle ride through on single phase; missing phase shutdown
Programming & Read-back Specications ( with sense wires used )
Accuracy Resolution Accuracy Resolution
SGA: +/- (0.5%fs + 1 digit)
SGI (40-1000V) +/- 0.1% of
voltage at full scale
SGI (40-1000V) +/- 0.4% of
Front panel Display
Remote Analog
Interface
Remote Digital
Interface
OVP +/- 1% of full scale
User I/O Disconnect & Polarity-reversal relay control ( Only available with Ethernet Option )
Software IVI & CVI drivers available under SUPPORT at: www.ProgrammablePower.com
current at full scale
SGI (10-30V) 0.1% of set point
+0.1% of voltage rating
SGI (10-30V) 0.1% of set point
+0.4% of current rating
Voltage +/-0.25% of full scale
Current (40-1000V) 0.8% of full
scale , (10-30V) 1.0% of full
scale
Voltage: +/- 0.1% of full scale,
Current: +/- 0.4% of full scale
Physical 3U Models (10V-30V) 3U Models (40V-1000V) 6U Models (60V-600V)
Width 19.00 in (48.3 cm) 19.00 in (48.3 cm) 19.00 in (48.3 cm)
Depth 27.18 in (69.0 cm) 26.4 in (67.1 cm) 27.06 in (68.8 cm)
Height 5.25 in (13.3 cm) 5.25 in (13.3 cm) 10.5 in (26.7 cm)
Weight (4kW, 10V 15V) ≈<65 lbs (29 kg)
Shipping Weight Contact factory for more product & shipping weights
line drop 1V of rated voltage per line for 10-20V models, 1.5V for 30V models, 2% of rated voltage per line for models 160V and
greater. (Greater line drop is allowed, but output regulation specications no longer apply).
DC output current set accuracy. Additional paralleled SG units will add 0.3% inaccuracy per unit. To parallel more than 5 units,
contact factory.
208/220 VAC (operating range 187 - 242 VAC)
380/400 VAC (operating range 342 - 440 VAC)
440/480 VAC (operating range 396 - 528 VAC)
>0.75 typical for 208/220 VAC input (40V, 60V - 800V models, 0.9 available with modication “PF”)
>0.72 typical for 380/480 VAC input (40V, 60V - 800V models, 0.9 available with modication “PF”)
>0.69 typical for 440/480 VAC input (40V, 60V - 800V models, 0.9 available with modication “PF”)
( 800V model 6.4 msec on all 3 phases )
Programming Read-Back / Monitoring
SGA: +/- (0.5%fs + 1 digit)
SGI, Voltage: +/- 0.1% of full scale
SGA: 3.5 digits
SGI: 4.0 digits
NA
+/-0.002% of
full scale
+/-0.002% of
full scale
(5kW, 20V 30V) ≈<65 lbs (29 kg)
(8kW, 10V 15V) ≈<85 lbs (39 kg)
(10kW, 20V 30V) ≈<85 lbs (39 kg)
(12kW, 10V 15V) ≈<110 lbs (50 kg)
(15kW, 20V 30V) ≈<110 lbs (50 kg)
SGI, Current: +/- 0.4% of full scale
SGI (10-30V) 0.1% of actual
+0.15% voltage rating
(40-1000V) +/-1.0% of full scale
(10-30V) +/-0.5% of full scale
Voltage: +/- 0.1% of full scale
Current: +/- 0.4% of full scale
(5kW) ≈ 40 lbs (18 kg)
(10kW) ≈ 60 lbs (27 kg)
(15kW) ≈ 80 lbs (36 kg)
SGA: 3.5 digits
SGI: 4.0 digits
NA
+/-0.002% of
full scale
Knob control & Display read-back
25-pin D-sub connector (0~5 V or 0~10 V)
RS-232C (Standard on SGI), Optional
IEEE-488.2 and Optional LXI
Compliant 10/100 base-T Ethernet (see
Options)
Programming range: 5-110% Congured
from front panel, remote analog or via
optional digital inputs
Digital 10-pin Molex type connector
See www.programmablepower.com
(20kW) ≈ 120 lbs (54 kg)
(25kW) ≈ 140 lbs (64 kg)
(30kW) ≈ 160 lbs (73 kg)
78