OWTS M 60
Partial discharge Test and Fault  
Location System
Benefi ts:
 PD Measurement by means of DAC similar 
to nominal net frequency 
 Online processing for complex PD-Diagnosis
 Portable test system, compact design and 
low weight
 Integrated tan δ - measurement
Description
The oscillating wave test system OWTS is used to identify, 
evaluate and locate partial discharge (PD) faults in a cable 
insulation and accessories in all types of medium voltage 
cables.
The system consists of a notebook as a WLAN control unit 
and a HV unit. The HV unit contains a HV source and a 
resonance inductor with an integrated electronic switch to 
generate the AC test voltage. The HV divider and an embedded controller for the digital data acquisition and PD 
signal processing is integrated. The storage, analysis and 
evaluation of the PD signals takes place in the notebook and 
can be done either on site or in the offi ce. The PD fault 
location is based on the time domain refl ection method.
For the PD diagnosis the test object is charged to the preselected peak value by a HV source within a couple of 
seconds and afterwards shorted with an electronic switch via 
a resonance coil. Thus a sinusoidal oscillating AC voltage with 
low damping is created (DAC). The frequency is fi xed in a 
range from 50 Hz to several 100 Hz, depending on the 
capacitance of the test object. 
Since the frequency of the test voltage is close to nominal service conditions, all measured PD activities can be effectively 
evaluated.
The oscillating voltage energizes the test object only for a few 
100 ms and therefore cause no long-term infl uences.
The PD extinction voltage and the tan 
determined due to the decaying amplitude of the test voltage. 
Critical PD levels responsible for the future status of the cable 
insulation are an important criteria in the evaluation. 
The analysis and evaluation of the typical PD parameter as 
well as the PD fault location supports the Asset Management 
for reliable decision criteria for maintenance- or replacement 
activities.
δ-value can be easily 
Technical Data 
Max. DAC outputvoltage
DAC frequency range 50 Hz … 800 Hz 
Capacitance range 0.025 µF … 2 µF 
HV charging current 7 mA 
PD measuring range 1 pC … 100 nC 
PD level detection acc. to IEC 60270 
Bandwidth for PD-
localisation 
Dissipation factor tan δ 0.1 % … 10 % 
Power supply 110 … 240 V-AC, 50 … 60 Hz 
Operating temperature -10 °C … +40 °C 
Weight app. 80 kg
Components
Unit 1 Ø: 650 mm, H: 970 mm 
Unit 2 Notebook app. 2 kg
Features
 PD diagnosis by means of damped AC voltage (DAC) 
 PD level measurement according to IEC 60270 
 Automatic adjustment of the bandwidth of the 
 measurement circuit for optimised signal detection
 Automatic calibration mode with joint location feature 
 PC with WIN XP and WLAN for system control 
 Statistical PD fault acquisition, online processing 
 Menu-driven unit to operate the test sequence 
 Portable design, low weight, easy set-up on-site 
Scope of delivery
 HV unit 
 Notebook with WL AN connection to the HV unit 
 Safety-Box with HV ON/OFF; Emergency push button 
and key switch 
 Accessory bag 
 Operating manual 
 5 m HV test lead; power supply- and grounding cable 
 OWTS Explorer package, 2 Dongle CD-ROM 
 Calibrator
60 kVpeak / 42 kVrms
150 kHz … 45 MHz
SebaKMT · Dr.-Herbert-Iann-Str. 6 · 96148 Baunach/Germany · Tel. +49(0) 95 44 - 6 80 
Fax +49(0) 95 44 - 22 73 · sales@sebakmt.com · www.sebakmt.com
ISO 9001:2000
 sebaKM T is a regi stered tr adema rk of the sebaKM T group
 Technical data subject to change without notice. 
LFT_OWTS M 60_eng_2007_05