OWTS M 28
Benefi ts
PD Measurement by means of DAC similar to
nominal net frequency
Online processing for complex PD-Diagnosis
Portable test system, compact design and
low weight
Integrated tan δ - measurement
Description
The oscillating wave test system OWTS is used to identify, evaluate and locate partial discharge (PD) faults in a cable insulation and accessories in all types of medium voltage cables.
The system consists of a notebook as a WLAN control unit and a HV unit. The HV unit contains a HV source and a resonance inductor with an integrated electronic switch to generate the AC test voltage. The HV divider and an embed­ded controller for the digital data acquisition and PD signal processing is integrated. The storage, analysis and evaluation of the PD signals takes place in the notebook and can be done either on site or in the offi ce. The PD fault location is based on the time domain refl ection method.
For the PD diagnosis the test object is charged to the pre­selected peak value by a HV source within a couple of seconds and afterwards shorted with an electronic switch via a resonance coil. Thus a sinusoidal oscillating AC voltage with low damping is created (DAC). The frequency is fi xed in a range from 50 Hz to several 100 Hz, depending on the capacitance of the test object.
Since the frequency of the test voltage is close to nominal service conditions, all measured PD activities can be effec­tively evaluated.
The oscillating voltage energizes the test object only for a few 100 ms and therefore cause no long-term infl uences.
The PD extinction voltage and the tan δ-value can be easily determined due to the decaying amplitude of the test voltage. Critical PD levels responsible for the future status of the cable insulation are an important criteria in the evaluation.
The analysis and evaluation of the typical PD parameter as well as the PD fault location supports the Asset Management for reliable decision criteria for maintenance- or replacement activities.
Features
PD diagnosis by means of damped AC voltage (DAC) PD level measurement according to IEC 60270 Automatic adjustment of the bandwidth of the
measurement circuit for optimised signal detection
Automatic calibration mode with joint location feature PC with WIN XP and WLAN for system control Statistical PD fault acquisition, online processing Menu-driven unit to operate the test sequence Portable design, low weight, easy set-up on-site
Scope of delivery
HV unit Notebook with WLAN connection to the HV unit Safety-Box with HV ON/OFF; Emergency push button and
key switch Accessory bag Operating manual 5 m HV test lead; power supply- and grounding cable OWTS Explorer package, 2 Dongle CD-ROM Calibrator
Technical Data
Max. DAC output­voltage
28 kVpeak / 20 kVrms
DAC frequency range 50 Hz … 800 Hz Capacitance range 0,025 µF … 2 µF HV charging current 10 mA
PD measuring range 1 pC … 100 nC
PD level detection acc. to IEC 60270 Bandwidth for PD-
localisation
150 kHz … 45 MHz
Dissipation factor tan δ 0,1 % … 10 % Power supply 110 … 240 V-AC, 50 … 60 Hz Operating temperature -10 °C … +40 °C Weight app. 55 kg Components Unit 1 Ø: 600 mm, H: 650 mm Unit 2 Notebook app. 2 kg