Atec Fluke-985 User Manual

Fluke 985
Particle Counter
Troubleshooting indoor air quality made easy
The particle counter is an essential tool in the facility maintenance, HVAC and IAQ professional’s toolbox. From filter testing to indoor air quality investigations, the particle counter equips the user with valuable data concerning the concentration and source of particulates in the tested environment.
The new Fluke 985 Particle Counter is ideal for troubleshooting and monitoring indoor air quality issues and verifying HVAC filter performance and critical locations for ISO Class 5–9 certification.
With the ultra-light weight ergonomic design, easy to view color screen with intuitive icons, on-screen trend graphs for easy and quick analysis, the Fluke 985 is a must for any maintenance, HVAC and IAQ professional.
Technical Data
Fluke 985 Particle Counter features:
Six channels and a particle size range of 0.3 µm to 10 µm
Ultra-lightweight and ergonomic design for easy single-hand
operation
Ten hours of standard-use battery life to last a full work day
Large 3.5 inch QVGC color display with backlight, intuitive icons,
and large font options make for easy navigation and viewing
10,000 records stored in device for easy access to historical data
Data can be viewed in traditional tabular or trend graph at the
user’s preference
Configurable display, sample methods, and alarm setting for sample
size count (raw count, per cubic feet, cubic meter, or liter)
Data export to USB memory stick or direct connection to PC via USB
cable. No special software required to view Excel compatible files
Ethernet enabled for accessing data via internet browser (Windows
Explorer, Safari, and Firefox)
USB/Ethernet charge cradle ensures the unit always ready for use
Administrator password control (optional) for added security
Meets ISO 21501, JIS B9921, and CE standards
Profile of 0.3 to 10 μm particles captured over 15 minutes window.
Specifications
Six size channels 0.3 µm, 0.5 µm, 1.0 µm, 2.0 µm, 5.0 µm, 10.0 µm Flow rate 0.1 cfm (2.83 L/min) Light source 775 nm to 795 nm, 90mW class 3B laser Count modes Raw counts, #/m3, #/ft3, #/liter in Cumulative or Differential mode Counting efficiency 50 % @ 0.3 µm; 100 % for particles > 0.45 µm (per ISO 21501) Zero count 1 count/5 minute (JIS B9921) Concentration limits 10 % at 4,000,000 particles per ft3 (per ISO 21501) Data storage 10,000 records (rotating buffer) Alarms User selected particle channels and limits Display QVGA color with backlight Delay time 0 to 24 hours Sample inlet Isokinetic probe Security Administrator password controlled (optional) Communication mode USB or Ethernet Dimensions (L x W x D) 27.2 cm x 9.9 cm x 5.3 cm (10.7 in x 3.9 in x 2.1 in) Weight 0.68 kg (1.5 lb) Power adapter 100 V ac to 240 V ac, 12 V dc, 2.5 A Rechargeable battery Li-ion 7.4 V 2600 mAh Battery duration/charge time 10 hours typical use (5 hours continuous sampling)/3.5 hours Calibration PSL particles in air (NIST traceable) Operating environment 50 °F to 104 °F (10 °C to 40 °C)/< 95 % non-condensingrelative humidity Storage environment 14 °F to 122 °F (-10 °C to 50 °C)/Up to 98 % non-condensingrelative humidity Warranty One-year Accessories included Cradle for charging and convenient USB and Ethernet communications, Ethernet cable, USB cable,
12 V dc power supply, zero count inlet-filter, filter adapter, sample inlet protective cap, hard case, getting started manual and users manual CD
Other IAQ tools from Fluke Ordering information
CO-205 Aspirator Kit for flue gas sampling using Fluke family of gas measuring devices.
CO-220 Carbon Monoxide Meter measures CO levels in industrial environments, commercial or residential buildings where accumulation of combustion gas is possible.
Fluke 922 Airflow Meter makes airflow measurements easy by combining differential pressure, airflow, and velocity into a single, rugged meter.
Fluke 971 Temperature Humidity Meter takes accurate humidity and temperature readings in the air for maintaining optimal comfort levels and good indoor air quality for facility maintenance and utility technicians, and HVAC-service contractors.
Fluke 975 AirMeter
powerful air quality tools into one for measuring essential IAQ parameters: temperature, humidity, dew point and wet bulb temperature, air volume, air velocity, CO, CO2, and % of outdoor air calculation.
2 Fluke Corporation Fluke 985 Particle Counter
combines 5
Fluke-985 Airborne Particle Counter Fluke-CO-205 Aspirator Kit Fluke-CO-220 Carbon Monoxide Meter Fluke-922 Airflow Meter Fluke-971 Temperature Humidity Meter Fluke-975 AirMeter™
Fluke. Keeping your world up and running.
Fluke Corporation PO Box 9090, Everett, WA 98206 U.S.A.
Fluke Europe B.V. PO Box 1186, 5602 BD Eindhoven, The Netherlands
For more information call: In the U.S.A. (800) 443-5853 or Fax (425) 446-5116 In Europe/M-East/Africa +31 (0) 40 2675 200 or Fax +31 (0) 40 2675 222 In Canada (800)-36-FLUKE or Fax (905) 890-6866 From other countries +1 (425) 446-5500 or Fax +1 (425) 446-5116 Web access: http://www.fluke.com
©2012 Fluke Corporation. Specifications subject to change without notice. Printed in U.S.A. 3/2012 4148253A D-EN-N
Modification of this document is not permitted without written permission from Fluke Corporation.
®