Atec Fluke-1555, Fluke-1550C User Manual

Fluke 1555 and 1550C Insulation Resistance Testers
Digital insulation testing up to 10 kV
The new Fluke 1555 and redesigned Fluke 1550C insulation resistance testers, offer digital insulation testing up to 10 kV, making them ideal for testing a wide range of high voltage equipment including switchgear, motors, generators and cables.
Fluke insulation testers can now conduct the entire range of test voltages specified in IEEE 43-2000 with a best in class, 3 year warranty and CAT IV 600 V safety rating. With measurement storage and PC interface, the 1555 and 1550C are perfect tools for pre­ventative or predictive maintenance programs designed to identify potential equipment failures before they occur.
Features include:
Test voltages to up 10 kV provides solutions for all applications
CAT III 1000 V, CAT IV 600 V safety rating
Warning function alerts the user that line voltage is present and
gives the voltage reading up to 600 V ac or dc for increased user safety
Selectable test voltages in 50 V steps from 250 V to 1000 V, and
100 V steps above 1000 V
Measurements can be stored in up to 99 memory locations, with
each location assigned a unique, user defined, label for easy recall
Long battery life gives the user over 750 tests between charges
Automatic calculation of Dielectric Absorption (DAR) and
Polarization Index (PI) with no additional setup
Guard system eliminates the effect of surface leakage current
on high-resistance measurements
Large digital/analog LCD for easy viewing
Capacitance and leakage current measurement
Ramp function for breakdown testing
Resistance measurements up to 2TΩ
Timer settings up to 99 minutes for timed tests
3-year warranty
Technical Data
Specifications
Electrical specifications
The tester’s accuracy is specified for one year after calibration at operating temperatures of 0 °C to 35 °C. For operating temperatures outside the range (-20 °C to 0 °C and 35°C to 50 °C), add ± .25 % per °C, except on the 20 % bands add ± 1 % per °C.
Insulation resistance measurement
Test voltage (dc) Range Accuracy (± reading)
250 V < 200 kΩ
500 V < 200 kΩ
1000 V < 200 kΩ
2500 V < 200 kΩ
5000 V < 200 kΩ
10000 V (1555 Only) < 200 kΩ
Bar graph range 0 to 1 TΩ Insulation test voltage accuracy -0 %, +10 % at 1 mA load current Induced ac mains current rejection 2 mA maximum Charging rate for capacitive load 5 seconds per μF Discharge rate for capacitive load 1.5 s/μF
Leakage current measurement
Capacitance measurement 0.01 uF to 15.00 μF ± (15 % rdg + 0.03 μF)
Timer Range Resolution
Live circuit warning Warning range Voltage accuracy
200 kΩ to 5 GΩ 5 GΩ to 50 GΩ > 50 GΩ
200 kΩ to 10 GΩ 10 GΩ to 100 GΩ > 100 GΩ
200 kΩ to 20 GΩ 20 GΩ to 200 GΩ > 200 GΩ
200 kΩ to 50 GΩ 50 GΩ to 500 GΩ > 500 GΩ
200 kΩ to 100 GΩ 100 GΩ to 1 TΩ > 1 TΩ
200 kΩ to 200 GΩ 200 GΩ to 2 TΩ > 2 TΩ
Range Accuracy
1 nA to 2 mA ± (5 % + 2 n A)
0 to 99 minutes Setting: 1 minute
30 V to 660 V ac/dc, 50/60 Hz ± (15 % + 2 V)
unspecified 5 % 20 % unspecified
unspecified 5 % 20 % unspecified
unspecified 5 % 20 % unspecified
unspecified 5 % 20 % unspecified
unspecified 5 % 20 % unspecified
unspecified 5 % 20 % unspecified
Indication: 1 second
Software specifications
Fluke ViewForms basic software requires a PC running Windows 2000, Windows XP and Windows Vista.
Included accessories
Test Cables with Alligator Clips (red, black, green)
Infrared adapter with interface cable FlukeView Forms Basic CD-ROM AC Power Cord Soft Carrying Case (base models only) English Manual Users Manual on CD-ROM Quick Reference Card Software License Agreement Registration Card FlukeView Forms Installation Guide USB-IR Cable Installation Guide IP67 Hard Case (kit only) Certificate of Calibration (kit only) Ruggedized Alligator Clips
(kit and 1555 only)
Ordering information
1550C 5 kV Insulation Tester 1555 10 kV Insulation Tester 1550C/Kit 5 kV Insulation Tester Kit 1555/Kit 10 kV Insulation Tester Kit
Optional accessories
TL1550EXT 25 foot extended
test lead set
General specifications
Display 75 mm x 105 mm Power 12 V lead-acid rechargeable battery, Yuasa NP2.8-12 Charger Input (AC) 85 V to 250 V ac 50/60 Hz 20 VA
This Class II (dou ble in sulated) instrument is supplie d with a Class 1 (grounded) power cord. The protec tive earth term inal (ground pin) i s not connected inter nally. The extra pin is for added plug retention only.
Dimensions 269 mm x 277 mm x 160 mm (10.6 in x 10.9 in x 6.3 in) Weight 3.7 kg (8.2 lb) Temperature (operating) -20 ºC to 50 ºC (-4 ºF to 122 ºF) Temperature (storage) -20 ºC to 65 ºC (-4 ºF to 149 ºF) Humidity 80 % to 31 ºC decreasing linearly to 50% at 50 ºC Altitude 2000 m Enclosure sealing IP40 Input overload protection 1000 V ac Electromagnetic compatibility EN 61326 Certifications
Safety compliance EN 61010, EN 61557 Parts 1 and 2, IEC 61010-1,
Polution degree 2
2 Fluke Corporation Fluke 1555 and 1550C Insulation Resistance Testers
CAT III 1000 V, CAT IV 600 V
Fluke. Keeping your world up and running.
Fluke Corporation
PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V.
PO Box 1186, 5602 BD Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or Fax (425) 446-5116 In Europe/M-East/Africa +31 (0) 40 2675 200 or Fax +31 (0) 40 2675 222 In Canada (800)-36-FLUKE or Fax (905) 890-6866 From other countries +1 (425) 446-5500 or Fax +1 (425) 446-5116 Web access: http://www.fluke.com
©2005-2010 Fluke Corporation. Specifications subject to change without notice. Printed in U.S.A. 10/2010 1629685G D-EN-N
Modification of this document is not permitted without written permission from Fluke Corporation.
Loading...