Atec Fluke-1550 User Manual

Manufacturers > Fluke
Categories > Electrical & High Voltage Test Equipment >
Meggers-Megohmmeters
Fluke 1550B
MegOhmMeter
Digital insulation testing
up to 5000 Volts
How-To Video
The Fluke 1550B is a digital megohmmeter capable of test­ing switchgear, motors, genera­tors and cables at up to 5000 V dc. It can be used for a wide range of tests: from simple spot checks to timed tests and breakdown tests. Measurement storage and PC interface soft­ware make it ideal for preven­tive maintenance. Heavy-duty leads, probes and alligator clips fit in the custom carrying case, for a rugged field testing kit.
Standard test voltages of
250 V, 500 V, 1000 V, 2500 V and 5000 V Additional test voltages
available in 50 volt steps from 250 to 1000 volts, 100 volt steps from 1000 to 5000 volts Measures up to 1 Tera-Ohm
Warning voltage function
alerts the user that line volt­age is present and gives the voltage reading up to 600 V ac or dc Automatic calculation of
Dielectric Absorption and Polarization Index with no setup Guard system eliminates
the effect of surface leakage current on high-resistance measurements Large digital/analog LCD
delivers detailed measure­ment data
Measures cable or insulation
capacitance Measures leakage current
Ramp function (0-5000 V
dc) for breakdown testing 99 minute timer for timed
tests Automatically stores test
data in up to 99 locations that user can name for quick recall later High-capacity rechargeable
batteries
Includes FlukeView®Forms
Basic 1550B Software and Optical Interface cable for downloading to a Windows®PC Custom soft case for tester
and accessories Includes heavy-duty leads,
probes and alligator clips Two-year warranty
Specifications
Electrical specifications
The meter’s ac after calibration at operating temperatures of 0 °C to 35 °C. For operating temperatures outside the range (-20 °C to 0 °C and 35 °C to 50 °C), add +/- .25 % per °C, except on the 20 % bands add +/- 1 % per °C.
Insulation resistance measurement
est Voltage Range Accuracy
T (dc) (± reading)
250 V 200 kto 5 G 5 %
500 V 200 kto 10 G 5 %
000 V 200 kto 20 G 5 %
1
2500 V 200 kto 50 G 5 %
5000 V 200 kto 100 G 5 %
Short circuit current greater than 1 mA and less than 2 mA Bar graph range 0 to 1 T Insulation test voltage -0 % to +10 % at 1 mA load current
accuracy Induced ac mains 2 mA maximum
current rejection Charging rate for 5 seconds per µF
capacitive load
Leakage current 1 nA to 2 mA ± (5 % + 2 nA) Capacitance 0.01 uF to 15.00 µF ± (15 % rdg + 0.03 µF)
measurement Live circuit 30 V to 600 V ± (5 % + 2 V)
indicator
Timer 0 to 99 minutes; settable in 1 minute increments;
Ramp 0 % to 100 % of selected test voltage, or until
curacy is specified for one year
5 Gto 50 G 20 %
0 GΩ to 100 G 20 %
1
to 200 G 20 %
20 G
50 Gto 500 G 20 %
00 Gto 1 T 20 %
1
Range Accuracy
ac/dc, 50/6
indicated to w
breakdown
0 Hz
ithin 1 sec
ond
Environmental specifications
Operating temperature -20 °C to 50 °C (-4 °F to 122 °F) Storage temperature Relative humidity
Operating altitude Enclosure sealing
ibration MIL-PRF-28800F, CLASS II
Shock, v EMI immunity EN 61326 Safety EN 61010-1, CAT III, 600 V,
Input overload protection
-20 °C to 65 °C (-4 °F to 149 °F) 80 % at 31°C decreasing linearly
to 50 % at 50 0 to 2000 meters IP-40
EN61557, PARTS 1 & 2 600 V ac continuous
°C
Software specifications
FlukeView®Forms Basic 1550B Software requires a PC running Windows 2000, NT4.0 Two-year warranty
®
95, 98, Me,
Included accessories
Test leads and low leakage probes Alligator clips Interface adapter and cable FlukeView®Forms Basic 1550B PC software Line cord Soft carrying case with waterproof bottom User’s manual CD with 12 languages Getting Started Guide
Optional accessories
FVF-UG FlukeView®Forms Upgrade to Version 3.0 TL1550EXT 25 foot extension leads
Mechanical specifications
0 mm x 242 mm x 330 mm
7
Dimensions (L x W x H)
Weight (with battery) 4 kg (8.8 lbs)
1 (6.7 in x 9.5 in x 13.0 in)
Power
y type 12 volt, lead-acid, rechargeable
Batter
Charger input (AC) 85 to 250 V ac 50/60 Hz 50 VA
est voltages Number of tests
y life (typical)
Batter Note: At higher temperatures, 250 V 4138 the battery requires more 500 V 3913 frequent charging. 1 kV 3462
T
2.5 kV 2043 5 kV
1
000
Fluke. Keeping your world
up and running.
Fluke Corporation
O Box 9
P
Fluke Europe B.V.
PO Box 1186, 5602 BD Eindhoven, The N
For more information call:
In the U
ax (425) 446-5
F In Europe/ Fax (31 40) 2 675 222 In Canada (800)-36-FLUKE or
ax (9
F From other countries +1 (425) 446-5500 or Fax +1 (425) 446-5116 Web access: http://www.fluke.com/
©2005 Fluke Corporation Trademarks are the property of their respective owners. Printed in U
0, Everett, W
9
0
.A. (800) 443-5853 or
.S
East/
-
M
0-6866
05) 89
.A. 7/2005 1629685 D-ENG-N Rev E
.S
A USA 98206
etherlands
6
1
1
Africa (3
. All rights reserved.
1 40) 2 6
5 200 or
7
Loading...