Atec Agilent-6690A, Agilent-6692A User Manual

Agilent Models 6690A-6692A System dc Power Supply
Data Sheet
Minimize your testing downtime with this reliable, high power dc supply
• Low ripple & noise
• Fast up-and-down programming
• High accuracy current programming and read back
• Analog programming
• Analog monitoring
• Parallel connection for more current output
• Full protection from overcurrent, overvoltage overtemperature
• Remote sense
• Electronic calibration
• Standard 1-year warranty
Agilent Technologies
The 6690A Series is dc power you can depend on.
At the 6600 watt power level, it’s not easy to design a reliable dc power supply. Agilent Technologies builds in ruggedness and durability, to meet even the grueling needs of continuous stress testing in harsh environ­ments. During the development phase, Agilent power supplies undergo a battery of environ­mental tests such as 8-days temperature profile. Other tests include humidity, altitude, shock and vibration, ESD, ac line tests, EMC and RFI. The power sup­plies are designed with built-in margin so that they can meet their specifications over time, under all conditions, and with­stand peak stress.
Protect your DUT
At these high power levels, you want to protect your expensive DUT. Whether your DUT is a rack of data storage control units, or a base station ready for deployment, it is quite valuable and well worth recovery. The 6690 Series has a wide range of protection features available to protect your DUT from damaging conditions.
Overvoltage protection
Overcurrent protection
Overtemperature protection
Programmable shut-down
Error status reporting
DFI-RI
External TTL shut-down input
Linked power supply shutdown
Easy GPIB Programming
All Agilent system power sup­plies have SCPI (Standard Commands for Programmable Instruments) based command sets. This means that the same function would have the same command for any instrument. For example, to program the output voltage on two power supplies, the command would be the same, and to measure the output voltage the command would be the same for the Agilent system power supply as any SCPI voltmeter. Using SCPI instruments makes your software simpler and quicker to design.
Easy System Configuration and Enhancement
The 6600 watt dc power supplies of the Agilent 6690 Series are the same size as the 5000 watt power supplies of the Agilent 6680 Series. This means that system power can be upgraded without needing more rack space. All programming commands and
features are 100% compatible between both series. Also, up to three same model 6690 Series power supplies can be connected in parallel, to provide additional power as your needs expand.
Manual Power Supply Control
Non-automated testing in R&D, or power for the repair bench in manufacturing, are no problem for the 6690 Series. The front panel has everything that is needed to control both the power supply output and the associated protection features. Both the out­put voltage and current can be easily monitored on the front panel meters.
Analog Programming and Monitoring
Analog signals can be used to program the output voltage and current. This allows custom waveforms to be generated, and is also useful for process control applications. The output current and voltage can be monitored via analog signals on the rear panel, for custom interface applications, and process control implementations.
You have better things to worry about than dc power.
Will failure of your dc power supply delay your testing?
Will failure of your dc power supply damage your DUT?
Will failure of your dc power supply keep you from meeting your customers’ needs?
Parameter Agilent Model Number
6690A 6691A 6692A
Output Ratings
Voltage: 0-15 V 0-30 V 0-60 V
Current:* 0-440 A 0-220 A 0-110 A *Derated linearly 1%/°C from
40°C to 55°C
Programming Accuracy (@ 25 ±5°C)
Voltage: 0.04% + 15 mV 30 mV 60 mV
Current: 0. l % + 230 mA 125 mA 65 mA
Ripple & Noise
(from 20 Hz to 20 MHz with outputs ungrounded, or with either output terminal grounded)
Constant Voltage: rms 2.5 mV 2.5 mV 1.5 mV
Constant Voltage: p-p 15 mV 25 mV 25 mV
Constant Current:** rms 200 mA 50 mA 30 mA **With load inductance >5 µH.
Readback Accuracy
(from front panel or over GPIB with respect to actual output @ 25 ±5°C)
Voltage: 0.05% + 22.5 mV 45 mV 90 mV
±Current: 0.1% + 300 mA 165 mA 80 mA
Load Regulation
(change in output voltage or current for any load change within ratings)
Voltage 0.002% + 650 µV 1.1 mV 2.2 mV
Current: 0.005% + 40 mA 17 mA 9 mA
Line Regulation
(change in output voltage or current for any line change within ratings)
Voltage: 0.002% + 650 µV 650 µV 650 µV
Current: 0.005% + 40 mA 17 mA 9 mA
Transient Response Time
(for the output voltage to recover to within 150 mV following any step change from 100% to 50% or 50% to 100% of the rated output current): <900 µs
Specifications
Agilent Technologies’ Test and Measurement Support, Services, and Assistance
Agilent Technologies aims to maximize the value you receive, while minimizing your risk and prob­lems. We strive to ensure that you get the test and measurement capabilities you paid for and obtain the support you need. Our extensive sup­port resources and services can help you choose the right Agilent products for your applications and apply them successfully. Every instrument and system we sell has a global warranty. Support is available for at least five years beyond the production life of the product. Two concepts underlie Agilent’s overall support policy: “Our Promise” and “Your Advantage.”
Our Promise
Our Promise means your Agilent test and mea­surement equipment will meet its advertised performance and functionality. When you are choosing new equipment, we will help you with product information, including realistic perfor­mance specifications and practical recommenda­tions from experienced test engineers. When you receive your new Agilent equipment, we can help verify that it works properly and help with initial product operation.
Your Advantage
Your Advantage means that Agilent offers a wide range of additional expert test and measurement services, which you can purchase according to your unique technical and business needs. Solve problems efficiently and gain a competitive edge by contracting with us for calibration, extra-cost upgrades, out-of-warranty repairs, and onsite education and training, as well as design, system integration, project management, and other professional engineering services. Experienced Agilent engineers and technicians worldwide can help you maximize your productivity, optimize the return on investment of your Agilent instruments and systems, and obtain dependable measurement accuracy for the life of those products.
For more information on Agilent Technologies’ products, applications or services, please contact your local Agilent office. The complete list is available at:
www.agilent.com/find/contactus
Phone or Fax
United States:
(tel) 800 829 4444 (fax) 800 829 4433
Canada:
(tel) 877 894 4414 (fax) 905 282 6495
China:
(tel) 800 810 0189 (fax) 800 820 2816
Europe:
(tel) 31 20 547 2111
Japan:
(tel) (81) 426 56 7832 (fax) (81) 426 56 7840
Korea:
(tel) (080) 769 0800 (fax) (080)769 0900
Latin America:
(tel) (305) 269 7500
Taiwan: (tel) 0800 047 866 (fax) 0800 286 331
Other Asia Pacific Countries:
(tel) (65) 6375 8100 (fax) (65) 6755 0042 Email: tm_ap@agilent.com
Agilent Email Updates
www.agilent.com/find/emailupdates
Get the latest information on the products and applications you select.
For more assistance with your test and measure­ment needs or to find your local Agilent office
go to: www.agilent.com/find/assist
Product specifications and descriptions in this document subject to change without notice.
Windows is a U.S. registered trademark of Microsoft Corporation.
MATLAB is a U.S. registered trademark of The Math Works, Inc.
© Agilent Technologies, Inc. 2005 Printed in USA, March 8, 2005 5988-3149EN
Loading...