ASSA ABLOY 681001025C1 User Manual

DRAFT
User Manual
RFID Encoder
ASSA ABLOY Hospitality
1
66 1001 001-7
Copyrights
The information in this document is subject to change at the sole discretion of ASSA ABLOY without notice.
Any use, operation or repair in contravention of this document is at your own risk. ASSA ABLOY does not assume any responsibility for incidental or consequential damages arising from the use of this manual.
All information and drawings in this document are the property of ASSA ABLOY. Unauthorized use and reproduction is prohibited.
VingCard and Elsafe are registered trademarks of ASSA ABLOY.
ASSA ABLOY Hospitality
2
66 1001 001-7
Table of contents
.................................................................................................5 FCC and IC statements
........................................................................................................................ 5FCC statements
........................................................................................................................ 5Industry Canada statements
.................................................................................................6 1. Introduction
.................................................................................................7 2. To mount the encoder
........................................................................................................................ 72.1 Dimensions
........................................................................................................................ 82.2 Mounting kit
........................................................................................................................ 82.3 To mount on the wall
........................................................................................................................ 92.4 Card holder
.................................................................................................10 3. Electrical specification
........................................................................................................................ 103.1 Connectors
.................................................................................................11 4. To connect to Visionline or VingCard Vision
........................................................................................................................ 114.1 To connect to the Visionline server
................................................................................................................................................ 114.1.1 To connect via TCP/IP
................................................................................................................................................ 114.1.2 To connect via USB
................................................................................................................................................ 134.1.3 RFID encoder in SysMon
....................................................................................................................................... 134.1.3.1 To rename the encoder
........................................................................................................................ 144.2 To connect to VingCard Vision server or workstation
................................................................................................................................................ 144.2.1 To connect via TCP/IP
.................................................................................................15 5. Configuration utility
........................................................................................................................ 165.1 To configure for use with Visionline
........................................................................................................................ 185.2 To configure for use with VingCard Vision
.................................................................................................20 6. To factory reset the encoder
........................................................................................................................ 216.1 Default parameter values
.................................................................................................22 7. Web interface (Visionline only)
........................................................................................................................ 227.1 To modify the encoder parameters
.................................................................................................23 Appendix A: Quick reference of technical data
.................................................................................................24 Appendix B: To install the USBXpress driver
.................................................................................................25 Appendix C: To upgrade firmware
........................................................................................................................ 25To upgrade firmware via RFID Encoder Configuration Utility
........................................................................................................................ 26To upgrade firmware via SysMon
ASSA ABLOY Hospitality
3
66 1001 001-7
.................................................................................................27 Appendix D: Boot-up procedure
Appendix E: More about how the encoder finds the
.................................................................................................29
server (Visionline only)
........................................................................................................................ 30To commission encoders with DNS
................................................................................................................................................ 30Single server
................................................................................................................................................ 30Multiple servers
................................................................................................................................................ 31To commission encoders without DNS
........................................................................................................................ 31To switch to backup server
................................................................................................................................................ 31Single server - to switch to backup server with DNS
................................................................................................................................................ 31Multiple servers - to switch to backup server with DNS
................................................................................................................................................ 31To switch to backup server without DNS
.................................................................................................32 Revision history
ASSA ABLOY Hospitality
4
66 1001 001-7

FCC and IC statements

FCC statements

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a
Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference; in which case, correction of the interference is at the user's expense.
Important: Changes or modifications to an intentional or unintentional radiator not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
The end product must be labeled to say 'FCC ID: Y7V-681001025C1'.

Industry Canada statements

This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes: (1) l'appareil ne doit pas produire de brouillage, et (2) l’utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en compromettre le fonctionnement.
The end product is labeled 'IC:9514A-681001025C1'.
The term "IC" before the equipment certification number only signifies that the Industry Canada technical specifications were met.
Le terme "IC" devant le numéro de certification signifie seulement que les specifications techniques Industrie Canada ont été respectées.
ASSA ABLOY Hospitality
5
66 1001 001-7

1. Introduction

Figure 1: RFID encoder
The RFID encoder is used for encoding and verifying RFID cards. It can be used together with the below systems:
Visionline VingCard Vision
Unless anything else is stated, the information in this document is valid for both systems.
Note: For upgrade of firmware in the RFID encoder, see Appendix C.
ASSA ABLOY Hospitality
6
66 1001 001-7

2. To mount the encoder

Figure 2: Encoder dimensions
The RFID encoder can either be mounted on a wall or be placed on a table etc; dimensions in Figure 2 below in mm (inches).

2.1 Dimensions

Note: The RFID encoder can be mounted either horizontally or vertically.
ASSA ABLOY Hospitality
7
66 1001 001-7

2.2 Mounting kit

Description
Quantity
Usage
Screws 2,9x25mm
2
For mounting the RFID encoder on a wall
Collar screw 3,5x25mm
1
For mounting the RFID encoder on a wall
Screws 2,5x6,4mm
4
For mounting the card holder and mounting brackets
Expand plugs 6x30
3
Mounting brackets
2
Adhesive Velcro strips
2
If the RFID encoder should be mounted without using screws
Figure 3: Exploded view of RFID encoder,
card holder and mounting details
The RFID encoder is delivered with a mounting kit containing the following items:
Table 1: Mounting kit

2.3 To mount on the wall

The encoder can be mounted on the wall either with the enclosed screws or with the enclosed Velcro strips.
If the encoder should be mounted with screws:
fasten the mounting brackets at the bottom of the encoder with the two mounting bracket screws fasten the encoder on the wall with the collar screw at the suspension and two screws at the mounting brackets
Note: When mounting the encoder on the wall, the parameter 'Wall mounted' must be enabled; this can be done via the RFID Encoder Configuration Utility (see chapter 5). If Visionline is applicable, it can also be done via the web interface (see chapter 7).
ASSA ABLOY Hospitality
8
66 1001 001-7

2.4 Card holder

If the RFID encoder is mounted on the wall, a card holder should be mounted on the encoder. The card holder, including two screws for fixation, are enclosed with the encoder at delivery.
Figure 4: The card holder is snapped onto the RFID encoder and also fastened with two screws.
ASSA ABLOY Hospitality
9
66 1001 001-7

3. Electrical specification

Figure 5: Rear panel of encoder
There are several possibilities for powering:
Power via PoE; power over Ethernet External power via adapter of 5VDC regulated voltage Power via USB (only applicable for Visionline)

3.1 Connectors

ASSA ABLOY Hospitality
10
66 1001 001-7

4. To connect to Visionline or VingCard Vision

4.1 To connect to the Visionline server

4.1.1 To connect via TCP/IP

If the encoder connects to the server via TCP/IP, it automatically adjusts to 10 or 100Mbit/s networks. The encoder starts by retrieving an IP address via DHCP; Dynamic Host Configuration Protocol. The encoder then automatically finds the server.
Note: When the encoder has been detected by the server, the display shows the date and time. An encoder device will automatically be added to the server.
If no DHCP server is available:
1. The display will show 'offline' and the encoder IP address (default 192.168.0.100, or another IP address if the encoder has already been connected to a network).
2. Shortly after, the IP address on the encoder display will change to an IP address in the range 169.254.1.0 – 169.254.254.255; this range is based on the zero config standard.
Note: When the RFID encoder has got an IP address, either via DHCP or via zero config, it makes an announcement broadcast which either the Visionline server or
a connected ZigBee gateway should answer to. For more information about how the RFID encoder finds the server, see Appendix E.

4.1.2 To connect via USB

If the encoder should connect via USB, the following steps must be taken:
The USBXpress driver must be installed; see Appendix B for details. An encoder device must be added to the Visionline device list; see details here.
Note: Power via USB is not always enough for the encoder. If this is the case, use the enclosed external power supply of 5VDC.
ASSA ABLOY Hospitality
11
66 1001 001-7
To add an encoder device in the Visionline device list:
Figure 6
1. When the USBXpress driver has been installed according to
Appendix B, open the Visionline
device list by double clicking on Devices under the Lists tab in the navigation window.
2. In the Devices dialog, click Add; the Device details dialog will be shown.
3. Enter a Name for the encoder.
4. If desired, enter a Description for the encoder.
5. At Type, choose 'Network RFID encoder (USB)' in the drop-down-menu.
Figure 7
6. At S/N, click the button. All network RFID encoders that are connected via USB will be shown in the drop-down list; see Figure 7.
7. In the Device details dialog, mark the applicable radio button under
Location. For Server and Computer, the field PMS address will be available;
fill in this if applicable.
8. Click Save and Close.
Figure 8
9. Double click on RFIDEncoderConfig.exe which is available on the Visionline CD under Drivers/RFID Encoder/
RFID Encoder Configuration Utility; if the encoder is correctly
connected to the PC and uses the USBXpress driver, the serial number of the encoder should be shown in the upper left window at USB; see example in Figure 8.
10.Follow the steps in section 5.1 to make the settings in RFID Encoder Configuration Utility.
ASSA ABLOY Hospitality
12
66 1001 001-7

4.1.3 RFID encoder in SysMon

Figure 9
1. Double click on SysMon.exe in
the Visionline installation folder.
2. Go to View/RFID Encoders;
encoders that have been connected via TCP/IP will be shown. Note: When hovering over an RFID encoder in the RFID Encoders window of SysMon, information about Mac address, IP address, firmware version and last ping will be shown.
Note: For upgrade of firmware via SysMon, see Appendix C.
4.1.3.1 To rename the encoder
Figure 10
1. To rename an encoder, right click on it in SysMon and choose Edit Name.
Figure 11
2. The dialog in Figure 11 will be shown; enter a name for the encoder and click OK.
ASSA ABLOY Hospitality
13
66 1001 001-7
4.2 To connect to the VingCard Vision server or workstation
Figure 12
1. Install the USBXpress driver according to Appendix B.
2. Double click on RFIDEncoderConfig.exe; if the encoder is correctly connected to the PC and uses the USBXpress driver, the serial number of the encoder should be shown in the upper left window at USB; see example in Figure 12.
3. Follow the steps in section 5.2 to make the settings in RFID
Encoder Configuration Utility.

4.2.1 To connect via TCP/IP

To make the RFID encoder accessible for VingCard Vision, the encoder must be assigned with four parameters:
IP address IP port number gateway address subnet mask
Before setting the above parameters in RFID Encoder Configuration Utility, the USBXpress driver must be available for the RFID encoder to be able to connect and perform the setup. When the RFID encoder has been configured with the four parameters above, the encoder becomes backward compatible with the KDE encoder which connects via TCP/IP only and has a static IP address.
ASSA ABLOY Hospitality
14
66 1001 001-7

5. Configuration utility

Dynamic IP address (DHCP)
Note: This parameter is only applicable for Visionline.
If this checkbox is marked, the RFID encoder retrieves an IP address via DHCP (Dynamic Host Configuration Protocol) and then automatically finds the server.
Host IP address
The IP address of the encoder
Subnet Mask
A mask used to determine what subnet an IP address belongs to
Announcement broadcast
If there is no DNS (Domain Name System), the RFID encoder will still find the server if this checkbox is marked
Emulate KDE
Emulate a KDE encoder Note for Visionline: With the 'emulate KDE' alternative marked, the web interface described in chapter 7 will not be available.
Wall mounted
This parameter changes the text orientation on the encoder display. Mark Enable if the encoder should be mounted on the wall.
Zero config
Note: This parameter is only applicable for Visionline.
If no DHCP server is available, the encoder will at startup show 'offline' and the encoder IP address. Shortly after, the IP address will change to an address in the range
169.254.1.0 – 169.254.254.255; this range is based on the zero config standard. Note: It is recommended to always have this checkbox marked.
EPHY auto negotiate
If the link speed (10 or 100 Mbit/s) has been unaltered for a certain time, a detector changes to manual speed and alternatively tests 10MBit/s and 100MBit/s until an answer is given. When this detector is activated, the parameter EPHY (Ethernet PHYsical transceiver) auto negotiate will be set to 'No' and the checkbox will be unmarked.
If the encoder parameters need to be modified to suit the network where the encoder is located, this can be done in RFID Encoder Configuration Utility. Table 2 below describes the configurable parameters.
For guidance about how to configure the RFID encoder for use together with Visionline, see section 5.1. For information about how to configure the RFID encoder for use together with VingCard Vision, see section 5.2. For default parameter values, see section 6.1. Note: For Visionline, the parameters can also be changed via a web interface; see chapter 7.
Table 2: Configurable parameters
ASSA ABLOY Hospitality
15
66 1001 001-7
5.1 To configure the encoder for use with Visionline
Figure 13
1. Make sure that the USBXpress driver is installed; see Appendix B for details.
2. Double click on RFIDEncoderConfig.exe.
3. Connect the encoder to USB power; the encoder will appear in the drop-down-menu at 'USB' in the upper left corner of the RFID Encoder Configuration Utility window.
4. Select the encoder in the drop-down-menu.
5. Click the Start button to connect.
Figure 14
6. Click the Get version button.
Figure 15
7. The firmware version of the encoder will be shown; make sure that it is the latest version, if not upgrade the encoder according to Appendix C.
ASSA ABLOY Hospitality
16
66 1001 001-7
Figure 16
8. Click the Get config button. At first configuration, the default encoder parameters will be shown; see Figure
16. Note: The default parameter values are also shown in section 6.1.
Figure 17
9. To modify one or more parameters, make the desired changes and click the Set config button.
Figure 18
10.When the new configuration has bee set in the encoder, a message as in Figure 18 will be shown.
ASSA ABLOY Hospitality
17
66 1001 001-7
5.2 To configure the encoder for use with VingCard Vision
Figure 19
1. Make sure that the USBXpress driver is installed; see Appendix B for details.
2. Double click on RFIDEncoderConfig.exe.
3. Connect the encoder to USB power; the encoder will appear in the drop-down-menu at 'USB' in the upper left corner of the RFID Encoder Configuration Utility window.
4. Select the encoder in the drop-down-menu.
5. Click the Start button to connect.
Figure 20
6. Click the Get version button.
Figure 21
7. The firmware version of the encoder will be shown; make sure that it is the latest version, if not upgrade the encoder according to Appendix C.
ASSA ABLOY Hospitality
18
66 1001 001-7
Figure 22
8. Click the Get config button. At first configuration, the default encoder parameters will be shown; see Figure
22. Note: The default parameter values are also shown in section 6.1.
Figure 23
9. Under IP Setup:
- uncheck Dynamic IP address (DHCP)
- set Host IP address; this is the encoder IP address
- set Default gateway; this is the encoder gateway address
- set Subnet mask; this is the encoder subnet mask
10.Under Connection Setup:
- uncheck Announcement broadcast
- let Server IP and Server Port be empty; these parameters are not applicable for VingCard Vision
- let KDE port be 3001
11.Under Misc Settings:
- check Emulate KDE
- uncheck the rest of the checkboxes
12.Click the Set config button.
Figure 24
13.When the new configuration has been set in the encoder, a message as in Figure 24 will be shown.
14.Disconnect the power and USB cables.
15.Connect the LAN cable to the local hub.
16.Power up the encoder.
ASSA ABLOY Hospitality
19
66 1001 001-7

6. To factory reset the encoder

Figure 25
1. Click the Defaults button.
Figure 26
2. If the default parameters should be set in the
encoder, click the Set config button. Note: If VingCard Vision is applicable, it will not be possible to connect to the encoder after the default values have been set in it. In this case, the encoder must then be reconfigured according to section 5.2; make sure that Emulate KDE is checked in RFID Encoder Configuration Utility.
There are two ways to reset the encoder parameters to default values, e.g. if an encoder should be used at a demo installation:
Press and hold the F button with a narrow instrument while powering up the encoder; see in Figure 5 where the button is located. Press Defaults and then Set config in the RFID Encoder Configuration Utility;
see below for details. The default values are also shown in Table 3.
ASSA ABLOY Hospitality
20
66 1001 001-7

6.1 Default parameter values

Parameter
Default value
Dynamic IP address (DHCP; Dynamic Host Configuration Protocol)
Enable Host IP
192.168.0.100
Default gateway
192.168.0.1
Subnet mask
255.255.255.0
Announcement broadcast
Enable
Server port
7799
KDE port
3001
Emulate KDE
Disable
Wall mounted
Disable
Zero config
Enable
EPHY auto negotiate
Enable
Note: For a description of the encoder parameters, see Table 2.
Table 3: Default parameter values for the RFID encoder
ASSA ABLOY Hospitality
21
66 1001 001-7
7. Web interface
Figure 27
1. Press the F button down to the right on
the back of the encoder (see Figure 5); use a narrow instrument.
2. In the web browser, enter http://
ipaddress; the IP address to enter is shown
on the display at startup of the encoder. See example below:
Note: If no DHCP server is available, use
the zero config IP address which is shown on the display; see section 4.1.1 for more information about zero config.
3. Make the desired changes in the RFID Encoder Setup page; see example in Figure 27.
4. If the server IP should be changed and there is no DNS (Domain Name System):
Enter the applicable Server IP, OR
mark the radio button 'Enable'
for Announcement Broadcast;
this makes the encoder find the server.
5. When all desired changes have been done in the RFID Encoder Setup page:
- Click Save.
- Click Reboot.
- Press the F button on the encoder again to close the web interface.
(only applicable for Visionline)
If the parameters for the RFID encoder need to be modified to suit the network where the encoder is located, this can be done either
via the configuration utility described in section 5.1 via the web interface described in the section To modify the encoder parameters. To open the web interface, http://ipaddress must be entered in a web browser. The encoder IP address is shown on the encoder display. Note: See Table 2 for a description of the encoder parameters.

7.1 To modify the encoder parameters

ASSA ABLOY Hospitality
22
66 1001 001-7

Appendix A: Quick reference of technical data

Dimensions, encoder (WxHxD):
83.3 x 152.0 x 42.2 mm (3 9/32" x 5 31/32" x 1 21/32")
Dimensions, card holder (WxHxD):
88.7 x 85.8 x 48.0 mm (3 1/2" x 3 3/8" x 1 57/64")
Material in encoder: ABS UL 94V-0
Automatic adjustment to 10 or 100MBit/s networks
Material in card holder: PC UL 94V-0, semitransparent
Several possibilities for powering:
- Power via PoE; power over Ethernet
Note: The RFID encoder is of PoE class 1; power range 0.44-3.84W.
- External power via adapter of 5VDC regulated voltage
- Power via USB (only applicable for Visionline)
The maximum current consumption for the RFID encoder is 400 mA continuously
Sound signals
Intended for indoor use only, temperature range +5ºC to +50ºC
Relative humidity 10-90%; non-condensing
Required version of Visionline: 1.11.1 or higher
Required version of VingCard Vision: 5.2 or higher
ASSA ABLOY Hospitality
23
66 1001 001-7

Appendix B: To install the USBXpress driver

Figure B1
1. All necessary files for the USBXpress driver are found on the Visionline CD under Drivers/USBXpress Driver; double click on USBXpressInstaller.exe and follow the instructions.
2. Connect the RFID encoder by USB cable to the computer.
3. Go to the Device Manager in Windows and click the plus sign in front of 'Universal Serial Bus controllers'; see Figure B1.
Figure B2
4. In the Device Manager, double click on the USBXpress Device and make sure that the USBXpress Device Properties dialog says 'This device is working properly' as in Figure B2.
ASSA ABLOY Hospitality
24
66 1001 001-7

Appendix C: To upgrade firmware

Figure C1
1. Double click on
RFIDEncoderConfig.exe.
2. Connect the encoder to USB power; the encoder will appear in the drop­down-menu at 'USB'.
3. Select the encoder in the drop­down-menu.
4. Click the Start button.
5. Click the Open button.
Figure C2
6. Browse to the desired firmware file and click Open.
Figure C3
7. When the firmware version has been loaded, it will be shown next to the Bootload button as shown in Figure C3.

To upgrade firmware via RFID Encoder Configuration Utility

ASSA ABLOY Hospitality
25
66 1001 001-7
Figure C4
8. Click the Bootload button.
Figure C5
9. When the bootloading has finished, a message as in Figure C5 will be shown.

To upgrade firmware via SysMon

Figure C6
1. Double click on SysMon.exe in
the Visionline installation folder.
2. Go to View/RFID Encoders;
encoders that have been connected via TCP/IP will be shown.
3. Mark the applicable encoder and click
the Set button; choose Set Firmware Files for Bootloading.
Figure C7
4. The dialog in Figure C7 will be shown.
5. Click the Browse button at the applicable one of ’RFID Encoder’ or ‘RFID Encoder w ext memory’ and select the applicable encoder firmware file.
6. Click OK in the Select Firmware Files for Bootload dialog.
(only applicable for Visionline)
ASSA ABLOY Hospitality
26
66 1001 001-7

Appendix D: Boot-up procedure

1. When an encoder comes out of reset, it reads its IP configuration from a non-volatile memory.
2. If 'Dynamic IP Address' is set to Disable (see chapter 7): the encoder sets its IP address to the address stored in the config memory. Continue at
step 13 below.
3. If 'Dynamic IP Address' is set to Enable (see chapter 7): the encoder sends a DHCP Request packet with IP destination address 255.255.255.255, i.e. IP broadcast, requesting its most recently used IP address.
4. If the network/subnet configuration has not changed, the DHCP server will most likely send a DHCP ACK packet, allowing the encoder to continue to use the same IP. The DHCP server may use either IP broadcast or unicast for this packet; broadcast is however most commonly used. Continue at step 10 below.
5. If the DHCP server is unwilling to let the encoder use the same address as before, or if the requested IP is out of scope, it sends a DHCP NAK.
6. The encoder resets its IP address to 0.0.0.0 and sends a DHCP Discover packet with IP destination address 255.255.255.255; IP broadcast.
7. If a DHCP server is available, it sends a DHCP Offer packet. Since the encoder has no valid IP address, the DHCP server must send to IP destination
255.255.255.255; IP broadcast.
8. The encoder receives the offer and sends a DHCP Request packet, as in step 3 above, but this time requests the IP address offered by the DHCP server.
9. The DHCP server sends a DHCP ACK packet, confirming that the encoder may start using the new IP address. Unlike the ACK in step 4 above, this ACK packet must be sent to IP destination address 255.255.255.255 (IP broadcast), since the encoder has not got any confirmed IP address yet.
10.The encoder performs gratuitous ARP (Address Resolution Protocol) to ensure that no other host has got the same IP.
11.If IP collision is detected, the encoder sends a DHCP Decline packet which refuses the assigned IP address and restarts the IP acquirement procedure for the encoder.
12. New functionality, RFID encoder version 2.0.0 and later: If there is no DHCP server available on the subnet, the encoder self-assigns an IP address from the IPv4 Local Link address space (169.254.0.0/16), and sends gratuitous ARP to ensure that no other host has got the same IP.
13. The encoder reads the most recently used Visionline server IP address and tries to open a TCP connection to the server.
14. If the TCP connection attempt fails, the encoder will continue to try connections to the same IP over and over again – unless it detects that the network/subnet setup has changed, e.g. the encoder may have been moved to a new location. Then it will send an application specific service discovery request (announcement broadcast) with IP destination address
255.255.255.255; IP broadcast.
14 b. New functionality, RFID encoder version 2.0.0 and later: Even if the
network/subnet setup is unchanged, but long time (one hour) has elapsed
ASSA ABLOY Hospitality
27
66 1001 001-7
without any successful TCP connection with the Visionline server, the encoder will start sending service discovery requests.
15. If a Visionline server is on the same subnet, or if another encoder with a valid TCP connection to the server is on the subnet, they will send a reply to the querying unit, letting it know the IP address and TCP port of the Visionline server. The encoder then tries TCP connection to that IP.
15 b. New functionality, RFID encoder version 2.0.0 and later: From the payload
supplied in the reply (the reply is sent with IP destination address
255.255.255.255, IP broadcast), the querying unit can determine if its own IP address properties are correct with respect to network class, default encoder IP and subnet mask. If required, it will self-assign a new IP address within the subnet specified in the reply, and then send gratuitous ARP to ensure that no other host has got the same IP. Then it goes on and tries TCP connection to the received server IP address.
16. New functionality, RFID encoder version 2.0.0 and later: Prior to sending the service discovery request, the encoder tries to contact a DNS server (Domain
Name System), with a request for resolving the most recently used server host name. If that name is unknown to the DNS, the encoder tries to resolve the
factory default server host name. If any of the two names renders a successful DNS reply, the encoder uses the IP address received from the DNS server, and tries TCP connections to that address. If the factory default name is unknown too, or if a DNS server is not available at all, the encoder sends a service discovery request.
Note: 14/14 b, (15/15b) and 16 will go on in a round robin way until the encoder has reached the server.
ASSA ABLOY Hospitality
28
66 1001 001-7

Appendix E: More about how the encoder finds the server (Visionline only)

Introduction
This appendix describes the process of how the encoder finds the server. The solution is based on DNS (Domain Name System) as well as on announcement broadcast, which is a proprietary implementation of zero config; see section 4.1.1 for details about zero config.
Note: For more information about setting up DNS entries etc, contact the hotel IT department. A general description of this cannot be made in this document, since this varies with the type of DNS server that is used.
There are three challenges when the encoder is connected to the network:
1. A new encoder must be able to find the server even if it is located on a separate subnet.
2. The encoder must be able to locate a backup server in case the primary server fails. The backup server is assumed to have the latest database from the primary server.
3. The above must be fulfilled even if there are multiple Visionline servers on the same network.
To commission encoders:
Single server - to commission encoders with DNS Multiple servers - to commission encoders with DNS To commission encoders without DNS
To switch to backup server
Single server - to switch to backup server with DNS Multiple servers - to switch to backup server with DNS To switch to backup server without DNS
ASSA ABLOY Hospitality
29
66 1001 001-7

To commission encoders with DNS

Figure D1
If the encoder is located on the same subnet as the server, the encoder will locate the server using announcement broadcast without any need for manual configuration. However, the normal case is that the server and the encoder are located on different subnets. The first encoder for each subnet requires help from the DNS to locate the server.

Single server

1. Add a DNS entry called timeloxserver and let its IP address be the address of the Visionline server to which the new encoder shall connect. The encoder will then make a DNS query using the name timeloxserver and in this way get the IP address of the server.
2. Connect the encoder to Ethernet and wait for it to appear in the SysMon ZigBee tree.

Multiple servers

In the steps below, it is necessary to know the Visionline system code. To find it, double click on System settings under Reports in the Visionline navigation window.
1. For each Visionline server, add a new DNS entry with the system name for the concerned server. The system name is timelox_12-character system code without dashes, e.g. timelox_D124BD233D13.
2. In order to find the correct server at first installation, the encoders must be installed for one server at a time.
3. Let timeloxserver refer to the IP address of the first Visionline server.
4. When all encoders have been installed for one server, the DNS entry for timeloxserver must be changed to the IP address of the next server.
5. When all encoders for the last server have been installed, the timeloxserver entry must be removed.
Note: Every set of encoders that is connected with a particular Visionline server will receive the system name of that server, once connection to the server is established. If an encoder for some reason needs to use DNS again in the future, the system name (e.g. timelox_D124BD233D13) will "win" over the default name. When the encoder makes a DNS request, the system name will connect it to the correct Visionline server.
ASSA ABLOY Hospitality
30
66 1001 001-7

To commission encoders without DNS

1. Connect one encoder to each subnet. Use the web interface for the encoder to configure the IP address of the Visionline server; see chapter 7 for details. Note: This is only needed for the first encoder for each subnet, since the other encoders on the same subnet will retrieve the server IP address from the first one by announcement broadcast.
2. Continue adding encoders. They will automatically obtain the IP address of the Visionline server from the encoders on the same subnet that are already online with the server.

To switch to backup server

Single server - to switch to backup server with DNS

1. Change the IP address of the timeloxserver entry in the DNS so it points to
the backup server. The encoders will then connect to the backup server if the connection to the primary server is lost and cannot be re-established.

Multiple servers - to switch to backup server with DNS

1. For the concerned Visionline server, change the IP adress of the system name entry in the DNS so it points to the backup server. The encoders will then connect to the backup server if the connection to the primary server is lost and cannot be re-established.

To switch to backup server without DNS

1. Remove the primary server from the network.
2. Assign the IP address of the primary server to the backup server
OR
Enter the IP address of the backup server in the web interface for one encoder per subnet. Note: It will take one hour after the primary server closes its sockets until the rest of the encoders enable their announcement broadcast.
ASSA ABLOY Hospitality
31
66 1001 001-7

Revision history

Date
Change
By
March 8, 2012
Initial version
KG
April 13, 2012
Updated section Connecting via TCP/IP Updated section Mounting kit
KG
October 17, 2012
Updated section Connecting via TCP/IP Added information about the USBXpress driver Updated screenshot 'Select Firmware Files for Bootload' Added information about configuration utility Updated web interface Added chapter about reset Updated Quick reference of technical data with information about PoE class 1 and maximum current consumption for the encoder Removed information about bootloader tool Added appendix More about how the RFID encoder finds the server
KG
January 25, 2013
'Emulate KDE' is now implemented
KG
July 3, 2013
Added information about VingCard Vision
KG
January 13, 2014
Modified chapter about web interface Modified chapter about installing USB Xpress driver Added chapter about boot-up procedure
KG
December 21, 2015
Updated layout
KG
ASSA ABLOY Hospitality
32
66 1001 001-7
ASSA ABLOY Hospitality APAC
E-mail: apac.hospitality@assaabloy.com
Phone: +65 6305 7670
ASSA ABLOY Hospitality EMEA
E-mail: emea.hospitality@assaabloy.com
Phone: +47 69 24 50 00
ASSA ABLOY Hospitality North America
E-mail: northam.hospitality@assaabloy.com
Phone: +1 972 907 2273
ASSA ABLOY Hospitality Latin America
E-mail: lam.hospitality@assaabloy.com
Phone: +52 55 36 40 12 00
www.assaabloyhospitality.com
ASSA ABLOY Hospitality
33
66 1001 001-7
Loading...