ASO WIRE POSITIONING NOTICE
Valid: 01/11/2018
ASO KS8/KS4 WIRE POSITIONING NOTICE
Dear ASO Installer
In relation to your enquiry, it can be normal for the core wires to be extruded off centre as ASO made a
change in the design of the safety edges around 6 years ago. With the introduction of the KS8-assembly-
system the conductive material blocks changed which meant it was no longer required to hit the pins of
the KS8 plug directly with the wire during assembly. This operating principle was also retained when
switching to the current KS4-assembly-system.
When assembling the only thing to watch is to ensure that both the upper and lower conductive blocks
are penetrated properly by the KS8/KS4 pins (illustrated below). The reading resistance value should be
8.2kOhm (+ or – 500 Ohms) so we are looking for a value of between 7.7 - 8.7kOhm.
KS 4 EDGE SERIES KS 8 EDGE SERIES
We have aached assembly instructions for your installers to help refresh on this, but we would be happy
to provide some more training at your convenience. If your installers or customers have any concerns
please do ask them to call us to discuss. If there have been any specific issues where the resistance values
are radically higher or lower than 8.2kohm this could be an issue with materials or assembly process, so
in these cases please do always contact technical support so we can resolve for you.
Just to add to this, the maximum number of edges joined in series that ASO recommend is 5 edges and no
more than 25 Meters of cabling in total from controller to end of line resistor in any one channel or series
of edges. For example the INDUS kit controller ISK 71‐242 has 4 channels, so you could run up to 5 edges
for 25 Meters in to each stationary edge input if required. I hope this information helps, if there are any
questions please do contact us directly so we can assist you.
Web: www.easygatesdirect.co.uk
E-Mail: info@easygatesdirect.co.uk
Phone: 0845 054 50 70
Address: Easygates Ltd, Unit 16 James Sco Rd B63 2QT
01

Valid: 01/11/2018
KS4 ASSEMBLY INSTRUCTIONS
KS4 ASSEMBLY INSTRUCTIONS (SENTIR EDGE GF & F SERIES
(
ASSEMBLY INSTRUCTIONS SAFETY CONTACT EDGES MAY ONLY BE MANUFACTURED AND INSTALLED BY AUTHORISED PERSONS)
1. Cuing the safety contact edge
Cut the safety edge material 24mm shorter
than the required finished length of the
contact edge.
!WARNING! USE ONLY THE APPROVED
LOWE 3306/3316 CUTTING TOOLS.
2a. Preparing end caps (drainage holes)
If the edge is to be mounted horizontally,
remove the drain plugs from both ends. If the
edge is mounted vertically, just remove the
plugs from the end closest to the ground.
)
For the TTLL & TTLa profiles, remove a notch
from the end cap to allow the sealing flaps to
2b. Preparing end caps (sealing lip)
protrude through the end cap.
Choose the desired cable exit of the endcap,
2c. Connection cable
then cut out the appropriate mark using a
small cuing tool.
5. Place end caps
Push the endcaps neatly over each end of the
safety contact edge to secure the build.
Push in the lock cap including the aached
3. Insert the lock cap
plug into the hollow spaces surrounding the
switching chamber and push it tight to the cut
surface of the safety contact edge.
6. Insert fixation clips
Fasten the endcaps, by pushing the fixation
clip into the given space until it clicks into
place. For bigger contact edges an additional
fixation clip is used to fasten the caps.
Insert the aatched plug into the electrical
4. Insert the contact plug
switching chamber of the safety contact edge,
be sure that the plug is pressed in tightly until the
upper notch of the plug fits closely to the lock cap.
7. Electrical testing of contact-safety-edge
Measure the contact edge with a multimeter. In
rest position, the resistance value has to be 8.2
kΩ ± 500 Ω (7.7 - 8.7 kΩ). When edge is activated,
the resistance should not exceed 500 tΩ.
Web: www.easygatesdirect.co.uk
E-Mail: info@easygatesdirect.co.uk
Phone: 0845 054 50 70
Address: Easygates Ltd, Unit 16 James Sco Rd B63 2QT
02

Valid: 01/11/2018
KS8 ASSEMBLY INSTRUCTIONS
KS8 ASSEMBLY INSTRUCTIONS (SENTIR EDGE GE F SERIES
(
ASSEMBLY INSTRUCTIONS SAFETY CONTACT EDGES MAY ONLY BE MANUFACTURED AND INSTALLED BY AUTHORISED PERSONS)
)
Pre-assembled ASO delivered end cap with contact plug includes:
Lock cap
Contact plug
End cap
Butyl seal
Clip
Contact plug with cable Contact plug with resistor
en
im
d
h
gt
l len
a
Fin
gth
len
g
ttin
cu
n
sio
a
fin
=
m
m
0
-2
gth
n
l le
1. Cuing the safety-contact-edge
The safety-contact-edge is cut 20 mm shorter than the final length
dimension to allow for the length of the end caps on each end.
Make sure that the safety-contact-edge is cut clean and straight,
using the approved LOWE cuing tool ONLY.
Markers
(inside)
ck
a
b
ward
Water drain plugs
s
id
eward
s
s
downwards
Cable exit
2. Preparing end caps
a) Notch for the weather-sealing lip
When assembling safety-contact-edges with
weather-sealing lips, the end caps have to
be notched where indicated to allow for the
weather-sealing lip(s).
Web: www.easygatesdirect.co.uk
E-Mail: info@easygatesdirect.co.uk
b) Connection cable
The connection cable exits the boom of
the end cap.
c) Water drain plugs
For installations in contact with water, it
is necessary to remove water drain plugs.
If the edge is to be mounted horizontally,
remove drain plugs from both ends. If the
edge is mounted vertically, just remove
the lower drain plug.
Phone: 0845 054 50 70
Address: Easygates Ltd, Unit 16 James Sco Rd B63 2QT
03

KS8 ASSEMBLY INSTRUCTIONS
Valid: 01/11/2018
! NOTE: ! The ambient temperature during assembly should be between 10° and 30°C and the relative humidity between 40% and 70%. It is
not recommended to aempt assembly in atmospheric conditions outside of these values, any aempt to do so may invalidate the product
warranty. The profile should be stored in dry conditions and checked thoroughly before the cuing & assembly process for the presence of
any moisture or damage.
max. 6,5 m
m
3. Insert the contact plug
- Insert the plug, which is fixed to the end
cap, into the electrical switching chamber
of the safety-contact-edge.
- Please ensure that the plug is inserted
parallel to the chamber so that both pins
penetrate the conductive material blocks.
- The elastic butyl seal has to be pressed on
tight to the edge (Max. 6,5 mm from plug
base to profile)
electrical switching
chamber
4) Put on end caps
Release the contact plug from end cap and then snap in the contact
lock cap on the contact plug until it clicks into place. Apply pressure to
ensure the end cap plug is fully inserted into the contact edge.
5) Electrical testing of the contact edge
Measure the contact edge with a multi meter. In rest position, the
resistance value has to be 8,2 kΩ ± 500 Ω (7,7 - 8,7 kΩ).
When edge is activated, the resistance should not exceed 500 Ω.
6) Cuing mounting rail
The mounting rail has to be 20 mm shorter than the final dimension of
the contact edge.
10 mm
ASO GmbH & EasyGates exclude all liability for damage caused by incorrect installation of contact edges!