Aritech FP2000 Configuration Guide

FP2000 SERIES
NETWORK
CONFIGURATION GUIDE
Revision 1.1 : May 1997
Downloaded from: http://www.guardianalarms.net
CONTENTSCONTENTS
2.1 GENERAL 2
2.2 NETWORK OVERVIEW 3
2.3 RS485 MEDIUM 4
2.3.1 General 4
2.3.2 Multi-drop Wiring 5
2.3.3 Bus Termination 5
2.3.4 Biasing 6
2.3.5 Cable Length / Type, Screening and Earthing 7
2.3.6 Line Extensions — Star Point Connections 7
2.4 RS232 MEDIUM 7
2.4.1 General 7
2.4.2 Restrictions 8
2.4.3 Connections 8
2.5 NETWORK INSTALLATION PARAMETERS 8
2.5.1 Node ID 8
2.5.2 Network Operation Mode 9
2.5.3 Port Allocation (not applicable for UN2000, NA/NH2000) 9
2.5.4 Data Rate For the RS485 medium 10
2.5.5 Baud Rate for the RS232 Medium 10
2.5.6 Node Relationship And Fault Reporting (Not applicable for UN2000, NA/NH2000) 11
3. NETWORKING A 2000 SERIES FIRE PANEL 12
3.1 RS485 NETWORK INTERFACE (NC2000) 12
3.2 SOFTWARE CONFIGURATION 13
3.2.1 Node Identification (see also paragraph 2.5.1) 13
3.2.2 Port Set-Up 13
3.2.3 Network Communication 14
3.2.4 Example 14
3.3 NOTES 14
4. NETWORKING LOCAL REPEATERS / GLOBAL REPEATERS 15
4.1 MODEL OVERVIEW 15
4.2 RS485 NETWORK INTERFACE 15
4.3 SOFTWARE SETTINGS TO BE PERFORMED 15
4.4 EMULATION — OPERATING GUIDELINES 15
4.4.1 Global Repeater 15
4.4.2 Local Repeater 16
5. UNIVERSAL NODE UN2000 17
5.1 GENERAL 17
5.2 HARDWARE OVERVIEW 18
5.2.1 PCB Layout and Rear Panel 18
5.2.2 Power Supply 19
5.2.3 Indicators 19
5.2.4 RS485 Bus Configuration Links (See also paragraph 2.3.3) 19
5.2.5 Node Identification Switches (See also paragraph 2.5.1) 20
5.2.6 General Option Switches 20
5.2.7 Reset Button 21
5.2.8 RS232 Interface 21
5.2.9 RS485 Interface 21
5.2.10 Note 21
5.2.11 Universal Node Specification 21
6. NETWORK AMPLIFIER AND HUBS 23
6.1 GENERAL 23
6.1.1 RS485 Extension 23
6.1.2 Star Point Connection 24
6.2 PRODUCT OVERVIEW 24
6.3 HARDWARE OVERVIEW 25
6.3.1 NA2000 Network Amplifier 25
6.3.2 NH2004/2008 Network Amplifiers 26
6.4 485 CHANNEL CONFIGURATION 27
6.4.1 General 27
6.4.2 Termination Resistor (See also paragraph 2.3.3) 28
6.5 INSTALLATION 29
6.5.1 NA2000 Installation into a FP2864 Fire Panel 29
6.5.2 NA2000 Installation into a Panel without a Front End Processor 30
6.5.3 NH2004 / NH2008 Installation 30
6.6 NETWORK AMPLIFIER SPECIFICATION 31
7. INTERPANEL I/O PROGRAMMING 33
7.1 GENERAL 33
7.2 EXAMPLE 34
8. PRACTICAL EXAMPLE 36
1. SCOPE
This manual serves as a guide to the user when installing and configuring the FP2000 Network.
Other Manuals are:
Product Code
FP2000 Reference Guide LKFP2503 FP2000 Series Installation & Commissioning Manual LKFP2003 User Manual LKFP2403 2000 Series Sensors Installation Manual LKFP2203 Aritech 950 Series Devices Installation Manual LKFP2103
2. INTRODUCTION
2.1 GENERAL
The FP2000 offers, as an option, unsurpassed networking capabilities with Arcnet using RS485 for rugged, reliable and peerless operation. Products from the FP2000 series can be added and removed from the network which allows for easy expansion of the system.
RS485 nodes are available from the network for connection to Building Management Systems
Remote Maintenance
PC Based Graphic Packages
Interpanel I/O Programming
Remote upload/download capability
In addition, serial ports can be configured to allow for direct access to the network.
The following table lists the devices that can be put on the network:
FP2000 Series Fire Panels FR2000 Series Repeaters RP2000 LCD Repeater UN2000 Universal Node NA2000/NH2000 Series Network Amplifiers
Note: ARCNET is a registered trademark of Datapoint Corporation.
2.2 NETWORK OVERVIEW
The network may best be described by referring to Figure 1 which depicts a typical network with its components.
Figure 1 : A Typical Network
The following components/products are fully compatible with the network and can be included when designing and configuring a system:
ANY FP2000 SERIES ANALOGUE ADDRESSABLE FIRE PANEL (A)
(Refer to paragraph 3).
ANY FR2000 SERIES REPEATER PANEL/EMULATOR (Global and Local) (B)
(Refer to paragraph 4).
The Repeaters/Emulators display on their front panel the status of the fire panel(s). It also allows all fire panel operations to be performed from the Repeater.
ANY RP2000 SERIES LCD REPEATER PANEL (C)
The Repeater Panels displays the status of the fire panel(s). It also enables some operations to be performed on the fire panel(s).
(Refer to paragraph 4).
UNIVERSAL NODE UN2000 (D)
The Universal Node provides an access point for external systems (such as computers) to the FP2000 Arcnet network. It also enables some operations to be performed on the Fire Panel(s).
(Refer to paragraph 5).
NETWORK AMPLIFIER (NA2004/NH2004/NH2008) (E)
The Network amplifier makes RS485 line extension and star point connections to the network possible.
(Refer to paragraph 6).
2.3 RS485 MEDIUM
2.3.1 General
A network can be established using fully isolated RS485 drivers as the electrical medium for communication. The RS485 concept is a two wire "multi drop" system that allows for bi-directional communication at high speed in noisy industrial type environments. While providing one of the easiest forms of network interconnection, the RS485 standard does require certain precautions when putting together a system.
The Arcnet protocol used is a token-passing protocol and is well proven and reliable. It is ideally suited for critical applications as each network event occurs within a predictable and predetermined response time.
2.3.2 Multi-drop Wiring
Multi-drop wiring implies a two wire bus connected to each network node. The recommended method is to wire the nodes in a daisy chain, where the bus enters and leaves each node. Four terminals are usually provided (there are exceptions) on each network component. The use of stub wiring is not recommended. Refer to Figure 2 below for the difference between stub and daisy-chain wiring methods.
Figure 2 : Daisy-Chained and Stub Wiring
2.3.3 Bus Termination
The network two-wire bus must be terminated at each end with a resistor. The spare terminals of the nodes at each end can be used. The value of the termination resistor must be equal to the characteristic impedance of the cable. Links are provided on network equipment for terminating into 120 ohm resistors. Resistors can be added in parallel (with the links not in place) if the characteristic impedance of the cable used is not 120 ohm. The characteristic impedance of cable can vary quite substantially and must be taken into consideration when selecting cable for network applications.
Beldin 9841 cable (recommended) R = 120 Ohm Telephone cable R = 100 Ohm
Figure 3 : Bus Termination
2.3.4 Biasing
There are four sets of bias resistor links, each set consisting of two links are provided for each of the network nodes. One link is for the RS485 positive (+) line and the other for the negative (-) line. These links must be set on all nodes connected to the network. The number of nodes determines the setting of the bias resistor links and needs to be changed if nodes are added or removed from the network. No change of biasing is required if changes to the number of nodes are made within the groups indicated below.
Group Number of Nodes
1 1 to 6 2 7 to 14 3 15 to 22 4 23 to 32
For details on setting the biasing resistor links refer to the relevant equipment documentation in the next paragraphs.
2.3.5 Cable Length / Type, Screening and Earthing
The maximum cable length is determined by three factors:
1. The data rate of the network
2. The capacitance/Km of the cable (both core to core and core to shield)
3. The loop resistance (core size ) of the cable The maximum recommended length using Beldin 9841 cable or equivalent is 1500m
(1.5 km). Twisted pair unshielded cable can be used in low noise environments, but is not
recommended. Specification: Single twisted pair with screen and earth drain
Capacitance : 41.7 pF/m core to core
: 75 pF/m each core to screen
Characteristic Impedance : 120 Ohm
Screens of the RS485 line must be earthed at one point only. Terminals are provided on network components to terminate and to continue the screen of the cable.
2.3.6 Line Extensions — Star Point Connections
The Network Amplifier provides the user the ability to:
Extend the length of the ARCNET RS485 line of the FP2000 range of fire panels.
Make star point connections to the ARCNET RS485 thereby increasing the flexibility of the network cabling.
(Please refer to paragraph 6).
2.4 RS232 MEDIUM
2.4.1 General
A network can also be set up via the RS232 ports provided on the FP2000 range of fire panels.
Typical applications are:
Remote alarm reporting (via modem)
Graphic package with only one fire panel
Remote maintenance (via modem)
Configuration of panel (using “remote maintenance manager” software)
2.4.2 Restrictions
The maximum distance is limited (typically 10m). Distance can eventually be increased by means of line drivers.
The connection is always point-to-point.
Networking via RS232 between two 2000 series devices (universal node, repeaters, panels) is not recommended; the “other” side should always be a PC or modem.
2.4.3 Connections
When a PC is connected, a crossed cable (“null-modem”) has to be used.
When a modem is connected, a “straight” cable can be used.
For cable configurations, please refer to Appendix A.
2.5 NETWORK INSTALLATION PARAMETERS
2.5.1 Node ID
All 2000 network devices must have a unique non-zero node identification address (ID) to be able to communicate with other 2000 devices.
The node ID has the following structure: P/R. (Panel number / Repeater number) There are three different kinds of node ID’s:
1. Panel:
Node ID on which detectors are connected FP2416, FP2864, FP2432 Structure: P/0 (second part is always 0)
2. Global Repeater:
The node will be able to repeat and in some cases emulate all other programmed
panels on the network.
Structure: O/R (First part always 0)
3. Local Repeater:
The node will repeat and in some cases emulate only one panel on the network. Structure: P/R P : Panel ID it has to repeat R : Number of Repeater from Panel P.
Examples:
Fire Panel 3 : 3/0
Global Repeater 4 : 0/4
Local Repeater 7 of Fire Panel 3 : 3/7
2.5.2 Network Operation Mode
The maximum number of panels, local and global repeaters that can be put on the network depends on the operation mode.
There are three (3) modes namely: 15/15 (Default Setting)
Max. 15 Panels Max. 15 Global Repeater Panels Max. 15 Local Repeater Panels per panel
7/31
Max. 7 Panels Max. 31 Global Repeater Panels Max. 31 Local Repeater Panels per panel
31/7
Max. 31 Panels Max. 7 Global Repeater Panels Max. 7 Local Repeater Panels per panel
The amount of nodes can never exceed 255 irrespective of the mode selected (excluding electrical restrictions of the RS485 line) (see paragraph 2.3).
2.5.3 Port Allocation (not applicable for UN2000, NA/NH2000)
The following ports can be available for network purposes: SER1 : RS232 serial ports
SER2 : ARC1 : RS485 ports ARC2 :
The ARC1/2 or SER1/2 ports on the devices are to be allocated to the Network Communication Functions NET1/2.
None (default) - No network communications NET1 (normally used) - All network communications set-up to NET1 will
communicate via the selected port.
NET2 - All network communications set-up to NET2 will
communicate via the selected port.
+ 32 hidden pages