2.3 MANUAL CALL POINT (MCP) DM2000 DM2010 DM202012
2.4 ISOLATOR IU201614
2.5 FIRE MONITORING CONTROLLERS16
2.5.1 Zone Monitoring Unit IU205116
2.5.2 Indicating Circuit Controller IU208019
2.6 INPUT / OUTPUT UNITS27
3. LOOP LOAD CALCULATIONS30
3.1 GENERAL30
3.2 CALCULATION PROCEDURE30
3.2.1 Standby Current31
3.2.2 Alarm Current31
3.2.3 Loop Resistance32
1. INTRODUCTION
1.1 SCOPE
This document is a guide for the installation of the Aritech 2000 Series Range of Analogue
Addressable Fire Monitors and Aritech 2000 Series Monitoring Controllers and Input / Output
Units.
Other manuals are:
FP2000 Series Reference GuideLKFP2503
FP2000 Series Network Configuration GuideLKFP2303
FP2000 Series End User Instruction ManualLKFP2403
Product Code
1.2 2000 SERIES PRODUCTS OVERVIEW
Product Part Number Base
Temperature Monitors:
Single LED without remote LED driverDT2053DB2001(U)
Single LED, 7-segment display, remote LED driverDT2073DB2002(U)
Two LED with remote outputDT2063DB2002(U)
Ionisation Smoke Monitors:
Single LED without remote LED driverDI2052DB2001(U)
Single LED, 7-segment display, remote LED driverDI2072DB2002(U)
Two LED with remote outputDI2062DB2002(U)
Optical Smoke Monitors:
Single LED without remote LED driverDP2051DB2001(U)
Single LED, 7-segment display, remote LED driverDP2071DB2002(U)
Two LED with remote outputDP2061DB2002(U)
Manual Call Points:
Manual Call PointDM2000 —
Manual Call Point : IP66DM2010 —
Manual Call Point : yellow for gas releaseDM2020 —
Isolator:
IsolatorIU2016DB2003
Fire Monitoring Controllers:
Zone Monitoring UnitIU2051 —
Indicating Circuit ControllerIU2080 —
Input / Output Units:
4 Inputs / 4 OutputsIO2034 —
2 Inputs / 2 OutputsIO2032 —
2 Inputs / 1 OutputIO2031 —
4 InputsIO2014 —
Optional Housing for I/O units
(123mm (W) x 173mm (L) x 50mm (H))IOBOX —
Table 1 : Aritech 2000 Series Products
2. INSTALLATION
2.1 GENERAL
The FP2000 Series Analogue Addressable Fire Panels can address up to 128 Aritech
devices on a two-wire ring circuit (loop) using digital communication.
The following paragraphs will describe the connection and addressing of Aritech devices
in a fire protection system.
2.2 AUTOMATIC FIRE SENSORS
2.2.1 Where To Place Automatic Fire Sensors
SITING AND SPACING DETECTORS
Please consult local regulations and follow Fire Brigade requirements.
The following apply for flat, horizontal ceilings:
SMOKE
DETECTORS
Max. area coverage100m
Max. horizontal distance between any point in
the area and the nearest detector
Max. ceiling height (general limits)12m6m
Note that these values change if:
• appliance is in small corridors
• there are obstructions
• appliance is in the apex of a pitched roof
2
6m5m
HEAT
DETECTORS
50m
2
SUITABLE LOCATIONS FOR SMOKE & HEAT DETECTORS
General rule : ION:Flaming Fire
OPTICAL :Smouldering Fire
HEAT:Full Combustion Fire
LOCATIONIONOP
T
Corridor / Walkway #Air current may exist
Elevator Shaft / Duct #Air current is present
General Office / Day Room #
Hotel Foyer #
Dining Room #
Theatre Stages / Audience
Hall
Warehouse #Not if diesel fork lifts
School #
Clinic / Nursery Room #
Laboratory #
Studio / Recording Room #Possibility of flaming
Factory #
Church / Chapel #
Cargo Handling Area #Presence of air current
Spirit Fuel Store #Fast, clean burning fire
Library Room #
Central Heating Room #
Dryer Room #
Kitchen #Avoid locations over
All connectors on the base are numbered and have the following function:
1: (+) remote LED
2: (-) remote LED
5: (+) line in and out
6: (-) line in and out
Earth :to continue ground shield
There are 4 different Mounting Bases available for the 2000 Series Sensors:
DB2001:sensor base without remote LED connectors (Ø 10 cm)
DB2001U:sensor base without remote LED connectors (Ø 15 cm)
DB2002:sensor base with remote LED connectors (Ø 10 cm)
DB2002U:sensor base with remote LED connectors (Ø 15 cm)
When sensors with remote LED drivers are being installed (for example DT2073,
DI2072, DP2071), the DB2002 or DB2002U should be used.
Please refer to Figure 1 for Class A, and Figure 2 for Class B (no return) wiring.
It is not necessary to observe polarity on terminals 5 and 6 as the fire monitors are not
polarity sensitive, but when the remote LED driver is being used, polarity must be
observed !
To install a detector head, insert the head and rotate it clockwise until it is properly
aligned and "sets" into the base (Figure 3). Then rotate it an additional 15º to lock it in
place.
Each 2000 Series Universal Mounting Base is equipped with a moulded locking
mechanism to prevent unauthorised removal of the sensor head (Figure 4). If you want
detectors to be locked into the base, remove tab before inserting into the base. To
remove the sensor head, insert a small screwdriver into the slot on the side of the base
and press in while simultaneously turning the sensor head counter clockwise (Figure 5).
The different Aritech Mounting Bases are designed so that the fire sensors will not
operate in the Isolator Mounting Base DB2003 and vice versa. The 2000 Series Range
of Fire Sensors will also not fit the base of another Aritech Range of Sensors.
A ground shield is strongly recommended, but not required. The shield must be
connected to the earth ground at one point only, preferably via an earth stud in the fire
control panel.
Address tags are available to write the address of the detector on. The address tag
should be positioned before the base is mounted.
Figure 1 : Class A Wiring
Figure 2: Class B Wiring
Figure 3Figure 4Figure 5
2.2.3 Addressing
To install a detector address (see Figure 6), use a screw driver to adjust the two rotary
switches on the back of the sensor. Set the left rotary switch (0 through 12) for the 10's
and 100's digit and the right rotary switch for the 0 through 9 digit.
Figure 6 : Address Setting for 2000 Series Fire Sensors
2.2.4 Technical Data
Operating Voltage17 - 28 V DC
Current Consumption :
quiescent @ 24V
Remote Indicatormax. 4Ma
Max. Air Flow10 m/s
Relative Humidity0 - 95% no condensation
IP - RatingIP43
Ionisation Source0.9 µCi Am 241
2000
IONISATION
LED = 2mA
2000
OPTICAL
< 150 µA
7-Segment = 2mA
2000
HEAT
Operating Temperature-20 to +70ºC (no icing)
Storage Temperature-30 to +85ºC
DimensionsH = 5 cm Ø =10 cm
2.2.5 7-Segment Indication
The 207X models have a 7-segment display. The information displayed depends on the
panel the sensors are connected to.
When the 2000 Series Sensors are being installed with the Aritech FP2000 Fire Panel,
the following indications are available:
Figure 7 : Indications on 7-Segment Display
Notes: (Combined with FP2000)
• At the fire panel this information can be programmed to be always available (On) or
only when the sensor is being polled (Blinking).
• When the complete zone is disabled, nothing will appear on the 7-segment display of
the disabled devices.
• The maximum number of 7-segment displays active at the same moment can be
programmed at the panel (in ‘On’ mode).
• The test conditions mentioned above are tests initiated at the panel and not from the
sensor itself (see paragraph 2.2.6).
2.2.6 Diagnostics and Sensitivity Test Modes
Diagnostic and sensitivity test modes are available on the 2000 Series Detectors. The
2000 Series Smoke Detectors provide obscuration or temperature information to the Fire
Panel. Obscuration or temperature is determined by the number of counts received at
the Fire Panel when a 2000 Series Detector is polled.
The DP2071, DI2072 and DT2073 models have a seven segment display that allows
sensitivity, diagnostic and address data to be displayed at the detector head. Holding a
magnet near the integral reed switch (Figure 8) will initiate the diagnostic routine at the
Fire Panel.
Figure 8 : Initiating the Diagnostic Routine
The following sequence will be displayed on the sensor :
First, the address of the sensor will be displayed (e.g. 35), followed by the real-time
value (e.g. 56), which is displayed twice.
Figure 9 : Sequences Displayed on 7-Segment Display
2.2.7 Testing, Maintenance and Cleaning
All 2000 Series Smoke Detectors are shipped with a plastic dust cover for use in areas
where construction is on-going. Smoke Detectors will not work with the dust cover in
place. Remove the dust cover when installation is completed, prior to testing.
All Smoke Detectors should be tested in place at least annually or according to local
regulations, to ensure smoke entry into the sensing chamber and alarm response. If
canned smoke (test aerosol) is used, carefully follow the manufacturer's directions to
avoid damage to the detector.
Test Heat Sensors by using a hot air gun (Figure 10A). Aim at heat sensor from 15 to
25cm away. Be careful not to melt the plastic.
The sensing chamber of the 2000 Series Photo-electric Detector unsnaps for easy field
cleaning and service (Figure 10B). Whenever the diagnostics indicates that cleaning is
necessary, remove the photoelectric detector cap, snap off and throw away the optical
block chamber (Figure 10C). Then blow off the optical block base and snap a new
optical block chamber back in place, replace the cap and verify sensitivity.
For 2000 Series Ionisation Detectors, remove the detector cover and clean the sensing
chamber and chamber screen whenever diagnostics indicate cleaning is necessary
(Figure 10D). Use a vacuum and/or filtered compressed air to remove dirt from the
chamber's interior. After cleaning, replace the chamber screen and detector cover and
verify sensitivity. If sensitivity remains out of limits, replace the sensor and return the
removed one to the manufacturer for cleaning and re-calibration.
Ionisation Sensors contain a radioactive source and should not be opened any further
than to clean as per above.
A
B
Figure 10 : Testing, Maintenance and Cleaning
C
D
2.3 MANUAL CALL POINT (MCP) DM2000 DM2010 DM2020
INSTALLATION
Figure 11 : Wiring Diagram for DM20X0
ADDRESSING
Addressing is by means of a DIL-switch on the rear side of the MCP: ON = 0; OFF = 1
An isolator is a “device” which prevents a loop going down completely when a short circuit in
that loop occurs. When isolators are used, only the devices between two isolators will go down.
The IU2016 can be placed in the loop and is completely transparent for the protocol (in normal
condition). No address setting is required.
High-end fire panels, like FP2000, have built-in isolators per loop. This means that no isolators
have to be placed at the beginning and end of the loop.
INDICATORS
The yellow LED will start blinking when the isolator goes active i.e. when one side is isolated.
The short-circuit will always be located between two active isolators or between one active
isolator and the panel
INSTALLATION
The Isolator is fitted into the Isolator Mounting Base DB2003.
There are four single terminals, namely:
1. (+) IN:Line in
2. (+) OUT:Line out
3. (-):Common negative
4. Single terminal :This terminal is intended as a through connection point for cable
shields or for an earth connection.
Isolators are - unlike the other 2000 Series devices - polarity sensitive. The connection must be
as follows:
Figure 12 : Class A Loop with Isolator IU2016
Note : According to the EN54-directive, isolators should be placed at least every 32 devices.
The use of isolators per zone is recommended.
Please consult local regulations and follow Fire Brigade requirements.
TECHNICAL DATA:
Operating Voltage...........................................17 - 38 V
Non - isolated current......................................<205 µA
The IU2051 can be used to connect conventional detectors, fire beams, etc. on the
analogue loop. It is important to note that the total current load of the conventional loop
must not exceed 3.5 mA. This is typically 30 detectors.
The PCB has to be put in a housing, according to environmental conditions.
INDICATORS
Yellow LED:Indicates an open circuit or short on the two-wire
conventional loop.
Ind +/- connectors:An extra LED can be connected to indicate a Fire Alarm
condition on the conventional loop.
ADDRESS SETTING
Please refer to paragraph 2.2.3.
TECHNICAL DATA
Operating voltage: ......................................20-28V at the communication loop terminals
Total standby current:.................................<7.5mA, 4.5mA typical (no conventional
detectors connected) at the communication
loop terminals
Maximum alarm current: .............................< 60 mA at communication loop
Maximum no. of conventional detectors: ....30. Do not exceed 3.5 mA + EOL load current
Maximum capacitance:...............................1 µF
Maximum line length:..................................not to exceed 2km or not greater than
100 Ohms
End-of-Line resistor value:..........................10 k ± 5%, 1/4 W
Supply Voltage conventional loop:.............. 17 - 25 V DC
Zone impedances @ 24V: Short circuit:.....< 120 Ohms
Fire: .................120 - 1 K
Quiescent: .......1K - 26 K
Open circuit: ....> 26 K
Extra remote output:...................................current limited at 4.5 mA
Physical dimensions & mounting holes:......dimensions in mm
INSTALLATION
Figure 13 : Wiring Diagram for Zone Monitoring Unit
Note: Where (non-addressable) intrinsically safe detectors are to be used, the Zener
barrier must be placed in the safe area adjacent to the hazardous area.
2.5.2 Indicating Circuit Controller IU2080
GENERAL DESCRIPTION
The IU2080 provides an interface between the two wire multiplexed ring circuit and local
supply loop sounders and strobes with their associated user supplied external power
supply. The local supply loop circuit can be selected for a 12V or 24V application. The
selection is done by the S2 switch located on the board. If the switch is closed, the loop
is set to the 12V application and if the switch is open the loop is set to the 24V
application. The external power supply provides the power to drive the sounders and
strobes. A number of devices totalling up to 3A may be connected to the sounder spur
(750 mA in applications requiring AFNOR approvals).
The ICC monitors the local power supply for a low voltage condition and the external
fault relay contacts (via fault +-ve) for an open condition. An end of line resistor is used
to ensure that the local supply loop is intact. The ICC monitors for loop shorts as well as
for loop open circuits via this resistor. Moreover, the ICC can provide a means for EOL
monitoring via a Z-style connection back to the ICC itself.
The PCB has to be put in a housing, according to environmental conditions.
INDICATORS
The IU2080 contains a red LED that will light when the relay is in a position to cause the
sounders and sirens to be energised. The green LED indicates that the external power
supply voltage is present and greater than approximately 8 volts.
ADDRESSING
The address of the ICC is set by a dip switch on the ICC circuit board. The decimal
address of the ICC must be converted to a binary number to set the dip switch. Please
refer to paragraph 2.3 (MCP) for the complete table.
TECHNICAL DATA
Operating voltage ........................... 17 - 28V (at the communication loop terminals)
Total standby current...................... < 350 mA (< 200 µA typical)
Maximum loop alarm current........... < 3.5 mA
End of line resistor value ................ 10 K 1/4W, 5%
Bell loop impedances at 24V:
Short circuit..................................... < 3.3 K
Quiescent ....................................... 3.3 K - 13.0 K
Open circuit..................................... > 13.0 K
Physical dimensions ....................... See paragraph 2.5.1, Zone Monitoring Unit
Mounting holes ............................... See paragraph 2.5.1, Zone Monitoring Unit
Operating & storage temperature ... See paragraph 2.2.4
INSTALLATION
Figure 14 : Location of Jumpers and Connectors on the PCB
Figure 15: Style Y Operation without Power Supply Trouble Relay
Figure 16 : Fault Signal Indication with Open Collector Driver
Figure 17 : Style Y Operation with Power Supply Trouble Relay
Figure 18 : Style Z Operation without Power Supply Trouble Relay
Figure 19 : Style Z Operation with Power Supply Trouble Relay
Figure 20 : AC Operation
2.6 INPUT / OUTPUT UNITS
GENERAL
The Aritech 2000 Series input-output modules allow for connecting an external signal (input) by
a voltage free contact for further processing in the Fire panel . These inputs are supervised and
faults can be signalled at the panel. Furthermore, relay contacts (output) can be used for
triggering devices, external to the loop.
All 2000 Series IO-modules are loop powered (no additional power supply required).
The PCB has to be put in a housing, according to environmental conditions.
Depending on the amount of supervised inputs and outputs, the following models are available:
IO2034:4 Inputs / 4 Outputs module
IO2032:2 Inputs / 2 Outputs module
IO2031:2 Inputs / 1 Output module
IO2014:4 Inputs module
INDICATORS
A yellow LED indicates a fault condition in one of the supervised inputs. The definition of this
fault condition (open, short, open or short) must be programmed at the panel. The indication
stays until the panel is reset.
ADDRESSING
The address of a Input / Output Unit is set by means of two rotary switches on the unit. Please
refer to paragraph 2.2.3 on how to set the address.
TECHNICAL DATA
Operating voltage .........................................17 -28V
Total standby current....................................<250 µA
When designing a Series 2000 system it is important to calculate the designed loop
configuration to ensure that it operates within the minimum and maximum voltage parameters
under worst case voltage and current conditions.
The low voltage limit is normally 20 volt DC for systems that include Zone Monitoring Units and
for systems without such units it is 17 volt DC.
The voltages mentioned only refer to the minimum DC voltage level, the AC voltage level must
be maintained at 5 to 9 volt above the DC level.
The calculation procedure and expressions shown in the following paragraphs give a rough
method of checking whether the DC conditions are satisfied.
The calculations are based on the DC voltage only and the attenuation of the AC voltage
signals is theoretically relative to that of the DC voltage. In most cases, the AC voltage will be
within specification when the DC voltage is within specification limits, provided that the AC
voltage level is well above the minimum DC level (5 volt) to begin with.
3.2 CALCULATION PROCEDURE
1. Calculate the total quiescent (standby) current for the loop devices using Table 2.
2. Calculate the worst case condition for additional alarm and LED current using Table
3.
Notes :
• The ‘worst case’ condition should still be considered as a ‘realistic’ condition,
taking into account the physical location of the sensor, remote indicators and
so on. In most of the applications, 10 sensors in alarm at the same moment
(per loop) is a good indication.
• In some panels (like FP2000), the max. number of LED’s in alarm per loop at
the same time can be programmed.
3. Determine the total loop resistance, using Table 4.
• The cable values given are "per core", therefore for a two core cable the
resistance must be multiplied by two.
• The 10 ohm source impedance is related to the FP2000.
4. Multiply the total current and the total resistance and subtract the result from the
central control equipment loop voltage. This will give the minimum voltage that a
device in the worst possible position on the loop can experience under power fail
conditions.