Ariston microGENUS II 24 MFFI, microGENUS II 28 MFFI, microGENUS II 31 MFFI User Manual

microGENUS II 24 MFFI
1
2
3
4
5
6
1
2
3
4
5
6
I
I
E
C
microGENUS II 28 MFFI microGENUS II 31 MFFI
Installation and Servicing Instructions
Type C Boilers
G.C.N: 47-116-25 (24kW) G.C.N: 47-116-26 (28kW) G.C.N: 47-116-27 (31kW)
LEAVE THESE INSTRUCTIONS WITH THE END-USER
Country of destination: GB, IE

TABLE OF CONTENTS

1. GENERAL INFORMATION PA
1.1 G
ENERAL INSTRUCTIONS PAGE.3
GE
.3
1.2 OVERALL VIEW PAGE.4
2. INSTALLATION PAGE.4
2.1
R
EFERENCE STANDARDS PAGE.
2.2 SITING THE APPLIANCE PAGE.5
2.3 OVERALL DIMENSIONS PAGE.6
2.4 CLEARANCES PAGE.6
2.5 MOUNTING THE APPLIANCE PAGE.6
2.6 E
LECTRICAL CONNECTION PAGE.7
2.7 GAS CONNECTION PAGE.8
2.8
WA
CONNECTION PAGE.
TER
2.9 FLUE CONNECTION PAGE.10
2.10 C
2.11 D
2.12 R
2.13 ROOM THERMOST
ONTROL PANEL PAGE.18 IGITAL DISPLAY AND FAULT CODES PAGE.18 EMOVING THE FRONT PANEL PAGE.19
AT
CONNECTION PAGE.19
2.14 ELECTRICAL/SYSTEM DIAGRAMS PAGE.20
2.15 WATER CIRCUIT DIAGRAM PAGE.21
5
8
3. COMMISSIONING PAGE.22
3.1 I
3.2 INITIAL STA RT-UP PAGE.23
3.3 OPERATIONAL ADJUSTMENTS PAGE. 23
3.4 C
3.5 PRODUCT OF COMBUSTION
3.6 BOILER SAFETY SYSTEMS PAGE.24
3.7 DRAINING THE SYSTEM PAGE.26
3.8 COMPLETION PAGE.26
3.9
3.10 INSTRUCTING THE END USER PAGE.26
NITIAL PREPARATION PAGE. 22
OMBUSTION ANALYSIS PAGE.24
DISCHARGE MONITORING PAGE. 24
O
PERA
TIONAL
CHECKS PAGE.
26
4. GAS ADJUSTMENTS PAGE.27
4.1 CHANGING THE TYPE OF GAS PAGE.27
4.2
A
DJUSTING
THE
GAS PRESSURES PAGE.
28
6.3.1 REMO
VING THE
COMBUSTION CHAMBER PAGE.35
6.3.2
R
EMOVING THE BURNER
AND
JETS PAGE.
6.3.3 REMOVING THE ELECTR
ODES
PAGE.35
6.3.4 REMOVING THE MAIN HEAT EXCHANGER PAGE.36
6.3.5 REMOVING THE AIR PRESSURE SWITCH PAGE.37
6.3.6 REMO
6.4
VING THE
A
CCESS TO THE GAS VALVE PAGE.
FAN PAGE.38
6.4.1 REMOVING THE SPARK GENERATOR PAGE.38
6.4.2 R
6.5 ACCESS
EMOVING THE GAS VALVE PAGE.39
TO THEWATER
CIRCUIT PAGE.39
6.5.1 REMOVING THE D.H.W. (SECONDARY)
EXCHANGER PAGE.39
6.5.2 REMOVING THE PUMP PRESSURE SWITCH PAGE.40
6.5.3 REMO
VING THE
SAFETY
VALVE PAGE.41
6.5.4 R
EMOVING THE AUTOMATIC
AIR VENT PAGE.41
6.5.5 REMOVING THE PUMP PAGE. 42
6.5.6 REMOVING THE PRESSURE GAUGE PAGE. 43
6.5.7 REMOVING THE EXPANSION VESSEL PAGE.43
6.5.8 REMOVING THE OVERHEAT THERMOSTAT PAGE.44
6.5.9 REMOVING THE C.H. TEMPERATURE PROBE (N.T.C.) PAGE. 44
6.5.10 REMOVING THE D.H.W. TEMPERATURE SENSOR (N.T.C.) PAGE.45 R
6.5.11
VING THE DIVERTOR
EMO
VALVE ACTUATOR PAGE.45
6.5.12 REMOVING THE D.H.W.
W
LO
SWITCH PAGE.
F
THE
6.6
A
CCESS
O
T
CONTROLSYSTEM PAGE.
6.6.1 CHECKING THE FUSES PAGE.46
6.6.2
6.6.3
R R
EMO EMO
VING THE VING
.C.B. P
P
THE
TIME CLOCK PAGE.
A
GE
35
38
45 46
47
.
48
5. MAINTENANCE PAGE.32
33
6. SERVICING INSTRUCTIONS PA
6.1 R
6.2 T
6.2.1 REMOVING THE FRONT
6.2.2 R
6.2.3 R
6.3 ACCESS TO THE COMBUSTION
2
EPLACEMENT OF PARTS PA
O GAIN GENERAL ACCESS PAGE.33
PANEL PAGE.33
EMOVING THE SEALED
CHAMBER FRONT PANEL PAGE.
EMOVING THE SIDE
PANELS PAGE.34
CHAMBER PAGE.
GE
GE
.
.
33
34
35
7. FAULT FINDING PAGE.49
T
F
7.1
UL
A
FINDING GUIDE
(FLOW-CHARTS)PAGE.49
52
8. EXPLODED VIEW PA
GE
.
8.1 SHORT SPARES LIST PAGE.53
9. TECHNICAL INFORMATION PAGE.54

1. GENERAL INFORMATION

This manual is an integral and essential part of the product. be consulted b
Please carefully read the instructions and notices about the unit contained in this manual, as they provide important information regarding the safe installation, use and maintenance of the product.
For operating instructions please consult the separate Users Manual.
It should be kept with the appliance so that it can
y the user and our authorised personnel.

1.1 GENERAL INSTRUCTIONS

Read the instructions and recommendations in these Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance.
eep this manual in a safe place.You may need it for your
K own reference while Servicing Technicians or your installer may need to consult it in the future.
This is a combined appliance for the production of central heating (C.H.) and domestic hot water (D.H.W.) and is intended for use in domestic properties.
This appliance which it is designed. The manufacturer declines all liability for damage caused by improper or negligent use.
No asbestos or other hazardous materials have been used in the fabrication of this product.
Before connecting the appliance, check that the information shown on the data plate and the table in section 9 comply with the electric, water and gas mains of the property.You will find the data plate on the reverse of the control panel. The gas with which this appliance operates is also shown on the data label inside the boiler casing.
must be used only for the purpose for
Do not install this appliance in a damp environment or
close to equipment which spray water or other liquids.
Do not place objects on the appliance. Do not allow children or inexperienced persons to use
the appliance without supervision. If you smell gas in the room,
switches, use the telephone or any other object which
.
might cause spar Open doors and windows immediately to ventilate the room. Shut the gas mains tap (at or adjacent to the gas meter) or the valve of the gas cylinder and call your Gas Supplier immediately If you are going away for a long period of time, remember to shut the mains gas tap or the gas cylinder valve.
Always disconnect the appliance either by unplugging it from the mains or turning off the mains switch before cleaning the appliance or carrying out maintenance.
In the case of faults or failure, switch off the appliance and turn off the gas tap. Do not tamper with the appliance. For repairs, call your local Authorised Servicing Agent and request the use of original spare parts. For in­guarantee repairs contact MTS (GB) Limited.
ks
.
do not turn on or off light
3
26
25
24 23
22 21
20
1918171615
14
13
12
11
10
9
8
7
6
5
4
3
2
1
27

1.2 OVERALL VIEW

LEGEND:
FIG. 1.0
1.
2. Air Intake for Twin Pipe Flue Systems
3. Fan
4. Combustion Chamber Hood
5.
6. Overheat Thermostat
7.
8. Combustion Chamber Insulation Panel
9. Burner
10. Detection Electrode
11. Ignition Electrodes
12. Motorised Valve
13. Domestic Hot Water Temperature Probe
14. Drain Valve
15. Low Water Pressure Switch
16. Secondary Heat Exchanger
17. Gas Valve
18. Spark Generator
19. Cold Water Inlet Filter
20. Pump (w/auto air vent)
21. Safety Valve
22. D.H.W. Flow Switch
23. Combustion Chamber
24. Central Heating Return Temperature Probe
25. Expansion Vessel
26. Air Pressure Switch
27. Combustion Analysis Test Point
Flue Manifold
Main Heat Exchanger
Central Heating Flow Temperature Probe
4

2. INSTALLATION

2.1 REFERENCE ST
The technical inf herein belo
w are intended for the installer / Servicing
ANDARDS
ormation and instructions provided
Technician so that the unit may be installed and serviced correctly and safely.
The appliance is only suitab
le for installation in GB and IE and should be installed in accordance with the rules in force
In GB, the installation must be carried out by a CORGI registered installer. It must be carried out in accordance with the relevant requirements of the Gas Safety (Installation and Use) Regulations, the appropriate Building Regulations either The Building Regulations (Scotland), Building Regulations (Northern Ireland), The Water Fittings Regulations or Water byelaws in Scotland.
, it is necessary to comply with the Water Supply
In GB (Water Fittings) Regulations 1999 (or for Scotland, The Water Byelaws 2000, Scotland).
The microGENUS II is an Approved Product under the Water Regulations.
To comply with the Water Regulations your attention is drawn to The Water Regulations guide, published by the Water Regulations Advisory Service (WRAS) gives full details of the requirements. In IE, the requirements given in the current edition of I.S.813 and the current Building Regulations must be followed.
Installation should also comply with the follo
wing British Standard Codes of Practice In the Republic of Ireland in accordance with the current
BS 7593:1992 Treatment of water in domestic hot water
central heating systems
BS 5546:1990 Installation of hot water supplies for
domestic purposes BS 5440-1:2000 Flues BS 5440-2:2000 Air supply BS 5449:1990 Forced circulation hot water systems BS 6798:1987 Installation of gas fired hot water boilers
of rated input not exceeding 60kW BS 6891:1989 Installation of low pressure gas pipe up to
28mm BS 7671:2001 IEE wiring regulations BS 4814:1990 Specification for expansion vessels BS 5482:1994 Installation of L.P.G.

2.2 SITING THE APPLIANCE

The appliance ma area, although par requirements of, in GB the current I.E.E. Wiring Regulations, in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, and for IE the current edition of I.S. 813 and the current ETCI rules. With respect to the installation of the combined appliance in a room containing a bath or shower, the location of the boiler in a room containing a bath or shower should only be considered if there is no alternative.
Where a room-sealed appliance is installed in a room containing a bath or shower reference must be made to the relevant requirements. In GB this is the current I.E.E. Wiring Regulations and Building Regulations, in IE reference should be made to the current edition of I.S. 813 and the current ETCI rules.
If the boiler is to be fitted into a building of timber frame construction, reference should be made to the current edition of the Institution of Gas Engineers Publication IGE/UP/7 (Gas Installations in Timber Framed Housing).
The location must permit adequate space for servicing and air circulation around the appliance as indicated in Section 2.4. The location must permit the provision of an adequate flue and termination. For unusual locations special procedures may be necessary. BS 6798-1987 gives detailed guidance on this aspect. A compartment used to enclose the appliance must be designed specifically for this purpose. No specific
entilation requirements are needed for the installation
v within a cupboard. This appliance is not suitable for outdoor installation.
The type C appliances (in which the combustion circuit, air vent intake and combustion chamber are air-tight with respect to the room in which the appliance is installed) can be installed in any type of room.
Secondary ventilation is not required with this boiler. The boiler m per
ust be installed on a solid, non-comb
manent wall to prevent access from the rear.
y be installed in any room or indoor
ticular attention is drawn to the
le
ustib
,
Building Regulations, the current ETCI rules for electrical installation and with the following Codes of Practice:
I.S. 813 Domestic Gas Installations
5
FIG. 2.1

2.3 OVERALL DIMENSIONS

LEGEND:
A = Central Heating Flow (3/4”) B = Domestic Hot C = Gas Inlet (3/4”) D = Domestic Cold E = Central Heating Return (3/4”)
Water Outlet (1/2”)
Water Inlet (1/2”)
FIG. 2.2

2.4 CLEARANCES

In order to allow access to the interior of the boiler for maintenance purposes, the boiler must be installed in compliance with the minimum clearances indicated in
FIG. 2.2
2.5 MOUNTING THE APPLIANCE
After removing the boiler from its packaging, remove the template from the separate box containing the connection kit.
O
:
TE
N
Pay particular attention to any test water that
may spill from the appliance.
Place the template in the position the appliance is to be mounted and after ensur to drill the holes for the hanging bracket, connection kit and flue pipe(s) NB: F flue installation please ref CONNECTION. (If the appliance is to be fitted on a wall of combustible material, the wall must be protected by a sheet of fireproof mater If the appliance is to be fitted into a timber framed building, guidance should be sought from the Institute of Gas Engineers document R
ill the w
2.5.1. the connections kit, position the hanging bracket and
6
Dr
ing it is hanging squarely
ther information relating to the
or fur
er to Section 2.9
ial).
EF: IGE/UP/7.
all and plug using those supplied with
, use it
F
LUE
secure with the wall screws supplied, assemble the connection kit and secure to the w recommended that a spirit level be used to position the appliance to ensure that it is perf
2.5.2. Position the appliance on the hanging bracket and connect the connection kit to the boiler connections (see also Sections 2.7 Gas Connections, 2.8 Water Connections & FIG. 2.3).
all.
NOTE: It is highly
ectly level.

2.6 ELECTRICAL CONNECTION

For safety purposes, have a competent person carefully check the electrical system in the property, as the manufacturer will not be held liable for damage caused by the failure to earth the appliance properly or by anomalies in the supply of power. Make sure that the residential electrical system is adequate for the maximum power absorbed by the unit, which is indicated on the rating plate. In addition, check that the section of cabling is appropriate for the power absorbed by the boiler.
The boiler operates with alternating current, as indicated in the Technical Information table in Section 10, where the maximum absorbed power is also indicated. Make sure that the connections for the neutral and live wires correspond to the indications in the diagram. The appliance electrical connections are situated on the reverse of the control panel.
.
FIG. 2.3
IMPORTANT!
In the event that the power supply cord must be changed, replace it with one with the same specifications. Note: The diagrams for the electrical system are indicated in section 2.13.
Warning, this appliance must be earthed.
External wiring to the appliance must be correctly earthed and polar person in accordance with rele in GB reference should be made to the current I.E.E. Regulations and applicable local regulations, in Scotland, the electr applicable in Scotland, and for IE the current edition of I.S. 813 and the current ETCI rules. The appliance is supplied with a fly-lead already connected, this must be connected to a 220-240v supply fused at 3A and must facilitate complete electrical isolation of the appliance, by the use of a fused double pole isolator ha in all poles or alternatively, by three pin plug and unswitched shuttered socket outlet both complying with BS 1363. The point of connection to the Electricity supply must be readily accessible and adjacent to the appliance unless the appliance is installed in a bathroom when this must be sited outside the bathroom (see section 2.2).
ised and must be carried out by a competent
ant regulations and r
v
ical pro
visions of the Building Regulations
ving a contact separation of at least 3 mm
means of a 3 A fused
ules,
Should external controls be required, the design of the
y a
en b
nal electr
xter
e competent person, see Section 2.13 f
mation.
or
inf
ical circuits should be under
tak or fur
ther
7

2.7 GAS CONNECTION

The local gas region contractor connects the gas meter to the ser
vice pipe. If the gas supply for the boiler serves other appliances ensure that an adequate supply is available both to the boiler and the other appliances when they are in use at the same time. Pipe work must be of an adequate size. Pipes of a smaller siz
e than the boiler inlet connection should not be used. The gas installation should also be in accordance with the relevant standards. In GB this is BS 6891, and in IE this is the current edition of I.S. 813.

2.8 WATER CONNECTIONS

VIEW OF THE BOILER CONNECTIONS
LEGEND:
A = Central Heating Flow B = Domestic Hot Water Outlet
G
A
B
C
D
E E
F
C = Gas Inlet D = Domestic Cold Water Inlet E = Central Heating Return F = Safety Valve Outlet G = Drain valve
FIG. 2.4
F
IG. 2.5
KT007A
CENTRAL HEATING
Detailed recommendations are given in BS 6798:1987 and BS 5449-1:1990, the following notes are given for general guidance.
PIPE WORK:
Copper tubing to BS EN 1057:1996 is recommended for water pipes
. Jointing should be either with capillary soldered or compression fittings. Where possible pipes should have a gradient to ensure air is carr
ied natur
ally to air release points and w
ater flows naturally to drain taps. The appliance has a built-in automatic air release valve, however it should be ensured as far as possible that the appliance heat exchanger is not a natural collecting point for air. Except where providing useful heat, pipes should be insulated to pre
vent heat loss and avoid freezing. Particular attention should be paid to pipes passing through ventilated spaces in roofs and under floors.
ASS
BY-P
:
The appliance includes an automatic by-pass valve, which protects the main heat exchanger in case of reduced or interrupted water circulation through the heating system, due to the closing of thermostatic valves or radiators.
SYSTEM DESIGN:
This boiler is suitable only for sealed systems.
DRAIN COCKS:
These must be located in accessible positions to permit the draining of the whole system and should be fitted at all low points. The taps must be at least 15mm nominal
e and manufactured in accordance with BS 2870:1980.
siz
SAFETY VALVEDISCHARGE:
8
The discharge should terminate facing downward on the
xterior of the building in a position where discharging
e (possibly boiling water & steam) will not create danger or
uisance, but in an easily visible position, and not cause
n damage to electrical components and wiring. The discharge must not be over an entrance or a window or any other type of public access.
AIR RELEASE POINTS:
These m
ust be fitted at all high points where air naturally collects and must be sited to facilitate complete filling of the system. The appliance has an integral sealed expansion vessel to accommodate the increase of water volume when the system is heated. It can accept up to 7 litres (1.3 gal) of expansion water. If the heating circuit has an unusually high water content, an additional sealed expansion vessel must be fitted, for GB refer to BS 7074 part 1 and for IE, refer to the current edition of I.S. 813.
MAINS WATER FEED - CENTRAL HEATING:
A method for initially filling the heating system is supplied with the connection kit. The filling loop is connected between the cold water inlet and the central heating flow connections, and incorporates a non-return valve. To operate the filling loop, it is necessary to open both quarter turn handles, once the required pressure has been achieved, close both handles and disconnect the hose in accordance with water byelaws. N
OTE: The
installer should ensure that there are no leaks as frequent filling of the heating system can lead to premature scaling of the main exchanger and failure of hydraulic components.
DOMESTIC WATER:
The domestic water must be in accordance with the relevant recommendation of BS 5546:1990. Copper tubing to BS EN 1057:1996 is recommended for water carrying pipe work and must be used for pipe work carrying drinking water, a scale reducer should also be used to reduce the risk of scale forming in the domestic side of the heat exchanger.
VR003A
RESIDUAL PUMP HEAD,DESIGNED TEMP RISE 20oC
28/31 kW
24 kW
9

2.9 FLUE CONNECTIONS

FLUE SYSTEM
The pro made in GB this must be in accordance with BS 5440-1,
or IE recommendations are given in the current edition of
f I.S.813. The appliance must be installed so that the flue terminal is exposed to outside air. The terminal must not discharge into another room or space such as an outhouse or lean-to. It is important that the position of the terminal allows a free passage of air across it at all times The terminal should be located with due regard for the damage or discolouration that might occur on buildings in the vicinity and consideration must be given to adjacent boundaries. In cold or humid weather water vapour may condense on leaving the flue terminal. The effect of such “pluming” must be considered. If the terminal is less than 2 metres above a balcony, above ground or above a flat roof to which people have access, then a suitable terminal guard must be fitted. When ordering a terminal guard, quote the appliance model number. A suitable terminal guard is available from:
vision for satisfactory flue termination must be
.
FIG. 2.6
FU010D
NOTE:THE FLUE MUST NOT TERMINATE IN A PLACE LIKELY TO
CAUSE NUISANCE
TOWER FLUE COMPONENTS Morley Road Tonbridge Kent TN9 1RA
The minimum acceptable spacing from the terminal to obstructions and ventilation openings are specified in FIG.
2.6.
T
ERMINALPOSITION
A - Directly above or below an openable window
or other opening
B - Below gutters, solid pipes or drain pipes 75
es 200
v
w ea
Belo
-
C
Below balconies or car-port roof 200
-
D E - From vertical drain pipes and soil pipes 150 F - From internal or external corners 300 G - Above ground or balcony level 300
From a surface facing a terminal 600
-
H
I - From a terminal facing a terminal 1200
J - From an opening in the car port
(e.g. door, window) into dwelling 1200 Vertically from a terminal in the same wall 1500
-
K L - Horizontally from a terminal in the same wall 300
izontally from an opening window 300
Hor
-
M N - Fixed by vertical flue terminal
mm
300
10
Ø 60/100 mm
FITTING
(F
THECOAXIAL
or Telscopic, Vertical Flue and Twin Pipe Instructions
FLUE (HORIZONTAL)
see page 12)
CONTENTS: 1X SILICONE O-RING (60mm) 1X ELBOW (90O) 2X WALL SEALS (INTERNAL &
E
XTERNAL)
1X ALUMINIUM FLUE PIPE INCLUDING TERMINAL (1 METRE ­60/100) 2X FLUE CLAMPS 8X SCREWS 2X FOAM SEALS
Once the boiler has been positioned on the wall, insert the elbow into the socket required position.
NOTE: It is possible to rotate the elbow
(FIG 2.7) and rotate to the
360oon its vertical axis.
FIG. 2.7
FU002A/Rev.1
Using the flue clamps, seals and screws supplied
(FIGS
2.7 AND 2.9) secure the elbow to the boiler.
The 1 metre horizontal flue kit (705958) supplied is
le for an exact
suitab
X dimension of 823mm, and the
750mm horizontal flue kit (705785) is suitable for an exact X dimension of 573mm.
Measure the distance from the face of the external wall to the face of the flue elbow (X - FIG 2.7), add 22 mm to this measurement, you now have the total length of flue required (including the terminal), this figure must now be subtracted from 860mm, you now have the total amount to be cut from the plain end of the flue.
Cut the flue to the required length ensuring that the distance between the inner and the outer flue is maintained (FIG 2.10).
FIG 2.8
FIG 2.9
11
FIG 2.10
e.g. X = 508mm + 22mm = 530mm
860 - 530 = 330mm (Length to be cut from the plain
end of the flue).
Once cut to the required length, ensure that the flue is free from burrs and reassemble the flue. If fitting the flue from inside of the building attach the grey outer wall seal to the flue terminal and push through the flue through the
, once the wall seal has passed through the hole, pull
hole the flue back until the seal is flush with the wall.
natively, the flue can be installed from outside of the
Alter building, the grey outer seal being fitted last.
WARNING
THE FLUE IS LONGER THAN
IF
RESTRICTOR (FIG. 2.11). IF THE FLUE IS BETWEEN 0-1 METRE
THE RESTRICTOR REMAINS FITTED
1 METRE, REMO
.
VE THE
SEE TABLE 2.1 (PAGE 17).
FIG 2.11
FITTING THE TELESCOPIC FLUE KIT (HORIZONTAL)
CONTENTS: 1X SILICONE O-RING (60
X ELBOW (90
1
O
)
mm)
2X WALL SEALS (INTERNAL &EXTERNAL) 1X ALUMINIUM FLUE PIPE INCLUDING TERMINAL (TELESCOPIC ­60/100) 2X FLUE CLAMPS 8X SCREWS 2X FOAM SEALS
The telscopic flue is suitable for use with an exact minimum X dimension of 270mm and an exact maximum X dimension 470mm.
IMPORTANT!! Do not extend the telescopic flue to an X dimension of more than 470mm. If longer lengths are required use extension pieces as necessary. Under no circumstances must the flue be cut.
The wall must then be made good around the flue (ensuring a fall of 1ois maintained away from the boiler to the flue terminal). Once made good, place the inner (white) wall seal over the flue and push up to the w
all, secure the flue to the
elbow by using the clamp supplied.
FIG 2.12
12
or each additional 90oelbo
F
w 1 metre m
ust be removed from the total flue length (maximum 4 metres including the 1st elbow). For each additional 45oelbow 0.5 metre must be subtracted from the total flue length (
FIG 2.13).
FITTING THE COAXIAL FLUE (VERTICAL)
(For Twin Pipe Instructions see page 13)
CONTENTS: 1X SILICONE O-RING (60mm) 1X ELBOW (90O) 2X WALL SEALS (INTERNAL &EXTERNAL) 1X ALUMINIUM FLUE PIPE INCLUDING TERMINAL (TELESCOPIC ­60/100) 2X FLUE CLAMPS 8X SCREWS 2X FOAM SEALS
The vertical flue kit is supplied with a specially designed weather proof terminal fitted, it can be used either with a flat roof or a pitched roof. (see FIGS 2.12, 2.13).
FIG 2.13
Vertical flue kits maximum and minimum useable
The lengths with both flat and pitched roof flashings are indicated in (Figs.
2.14 & 2.15).
Before proceeding to fit the flue, ensure that the maximum flue length has not been exceeded and that all
ws and bends have been taken into consideration,
elbo the maxim
o
90
um flue length is 5 metres, for each additional
elbow 1 metre must be subtracted from the total flue
length, and for each 45o0.5 metres must be subtracted from the total flue length (the offset and height of 2 x
45ocan be seen in Fig. 2.16).
Mark the position of the flue hole in the ceiling and/or roof
(see FIG. 2.14 for distance from wall to the centre of the flue).
NOTE:MAX LENGTH = a+a+a +
b+b = a+a+a+0.5+0.5 COMBINED LENGTH NOT
TO EXCEED 5m
Cut a 125mm diameter hole through the ceiling and/or roof and fit the flashing plate to the roof. Should it be necessary to cut the flue DO NOT cut the outer white air inlet tube, cut the aluminium exhaust flue 6mm longer than the outer white air tube when used at minimum length.
DO NOT cut more that 250mm from the
inner aluminium exhaust flue.
To connect the vertical flue kit directly to the boiler, place the adaptor
(see FIG 2.12) (supplied with vertical flue kit)
onto the exhaust manifold and secure with the clamp, the vertical flue kit must then be inserted through the roof flashing, this will ensure that the correct clearance above the roof is provided as the terminal is a fixed height.
Should extensions be required, they are available in 1
(Part No. 705786), 500mm (Part No. 705790) and
metre 160mm lengths (Part No. 705812), they must be connected directly to the boiler and secured with the clamp supplied before connecting the adaptor to allow the vertical flue kit to be fitted. In the event that extension pieces need to be shortened, they the male end and it m
ust be ensured that the distance
between the inner and outer flue are kept
must only be cut at
(Fig. 2.10).
FIG 2.14
When utilising the vertical flue system, action must be taken to ensure that the flue is supported adequately to prevent the weight being transferred to the appliance flue connection. When the flue passes through a ceiling or wooden floor, there must be an air gap of 25mm between any part of the flue system and any combustible material. The use of a ceiling plate will facilitate this. Also when the flue passes from one room to another a fire stop must be fitted to prevent the passage of smoke or fire, irrespective of the structural material through which the flue passes.
FITTING
Where it is not possib distance per be used b and using the aper the comb
THE
FLUE (TWIN PIPE)
minate the flue within the
, the twin flue pipe can
mitted f
le to ter
or coaxial flues
y fitting a special adaptor to the flue connector
ture f
ustion chamber
or the air intak
.
e located on top of
13
Considerations necessary for twin flue installation;
It is most important to avoid any possible condense
ormation entering the appliance.
f
FIG 2.15
WARNING
F THE FLUE IS LONGER THAN 1 METRE, REMOVE THE
I
RESTRICTOR METRE THE RESTRICTOR REMAINS FITTED.
(FIG. 2.11). IF THE FLUE IS BETWEEN 0-1
SEE TABLE 2.1 (PAGE 17).
According to Table 2.1
(Page 17) decide if condensation
will form within the flue. If yes, there are two options;
Where condense will form but can be negated with
1)
insulated flue, install insulated the flue with a fall of 5mm in every metre away from the boiler.
2) The exhaust flue will have a fall of 3oback to the boiler
and a suitable trap will be fitted on the exhaust as close to the boiler as possible, condense will then be suitably disposed of.
Where the flue runs through cold spots, i.e. loft areas, condense is likely to be formed, therefore a fall back to the boiler and a trap is required. Always ensure that the flue is adequately supported, avoiding low points. (MTS supply suitable clamps as Part No. 705778).
To utilise the air intake it is necessary to:
Remove the ‘knockout’ of the air intake by cutting it with a suitable knife
(FIG. 2.17).
Insert the elbow/flue pipe into the air intake until it stops.
Minimum offset distance when using 2x 45obends
The twin flue pipes can be fitted with or without additional elbows and need no clamps, simply ensure that the red o­ring is inserted in the female end of the flue pipe and push the extension piece fully into the previous section of flue pipe or elbow, check that the o-ring is not dislodged when assembling the flue.
Twin pipe can also be converted back to Coaxial flue to enable vertical termination with a coaxial kit by using the pipe br
idge (Twin - Coaxial Adaptor - Part No. 705767). When running the twin flue pipe vertically, a condense trap must always be used on the exhaust pipe.
It is not recommended that the pipe bridge for horizontal termination, however in the unlikely event that this proves to be a necessity it is extremely important that the entire
o
flue has a fall of 3
back to the boiler, is suitably trapped and where the 60mm inner flue of the concentric terminal connects to the pipe bridge, this point must be adequately sealed with silicone sealant to avoid condense leakage at this point.
NOTE: Vertical twin flue installations must have a trap on
the exhaust. MTS supply a suitable condense
art No. 705774 and recommend that this be
ap P
tr
m
used in the e condense
.
ent that the flue ma
v
y not f
or
FIG 2.16
14
When siting the twin flue pipe
, the air intak
e and e
xhaust terminals must terminate on the same wall, the centres of the terminal centres
must be a minimum of 280 mm apart
FIG 2.17
IMPORTANT!!! WHERE CONDENSE WILL FORM WITHIN THE FLUE SYSTEM,
ENSURE THERE IS A FALL BACK TO THE BOILER OF 3OAND A SUITABLE TRAP IS FITTED AS CLOSE TO THE BOILER AS POSSIBLE
. MTS SUPPLY A SUITABLE COLLECTOR PART NO. 705798 OR A CONDENSATE DISCHARGE T WITH BUILT IN TRAP PART NO. 705774.
and the air intake must not be sited above the exhaust ter
minal
(ref
er to F
2.21).The air intake pipe can be
IG.
run horizontally, however, the terminal and the final 1 metre of flue m
ust be installed with a fall away from the
boiler to avoid rain ingress.
It is also strongly recommended that the air intake pipe
un be constructed of insulated pipe to prevent condense
r
orming on the outside of the tube.
f
The maximum permissible flue length for twin flue is dependent on the type of run used.
For flue runs with the intake and exhaust pipes under the same atmospheric conditions (T
YPE 4) the maximum
length is 60 metres (28kW), 46 metres (28kW) and 47 metres (31kW). For runs with the terminals under different atmospheric conditions (TYPE 5) the exhaust terminal must extend 0.5 metres above the ridge of the roof (this is not obligatory if the exhaust and air intake pipes are located on the same side of the building). For
YPE 5 also, the maximum permissible combined length is
T 59 metres (24kW), 48 metres (28kW) and 42 metres (31kW). Flue types are shown on Page 16 (FIG. 2.20).
The maximum length is reached by combining the total lengths of both the air intake and exhaust pipes. Therefore a maximum length of 40 metres for example, will allow a flue run of 20 metres for the air intake and 20 metres for the exhaust pipes, also for each 90oelbow 1.3 metres must be subtracted from the total length and for each 45oelbow 1 metre must be subtracted from the total flue length. Some of the acceptable flue configurations are detailed on page 16
(FIG. 2.20).
FIG 2.18
For further information relating to flue runs not illustrated, please contact the Technical Department on 01494
539579.
FIG 2.19
15
EXHAUST
AIR INTAKE
AIR INTAKE
AIR INTAKE MUST NOT BE
FITTED ABOVE THE EXHAUST
TYPE 1
TYPE 2
TYPE 3
TYPE 4
TYPE 5
NOTE: DRAWINGS ARE INDICATIVE OF FLUEING OPTIONS ONLY.
FIG. 2.20
FIG 2.21
16
NOTE:WHERE 280MM CENTRES CANNOT BE ACHEIVED,THE EXHAUST TERMINAL
CAN BE EXTENDED TO PROTRUDE FROM THE WALL BY 300MM.
TABLE 2.1
24 MFFI
Coaxial
Systems
ø 60/100
Twin Pipe
Systems
ø 80/80
28 MFFI
Coaxial
Systems
ø 60/100
Exhaust
Type
TYPE 1 TYPE 2
YPE 3
T
Exhaust
Type
TYPE 4
T
YPE 5
Exhaust
Type
TYPE 1 TYPE 2 TYPE 3
Exhaust
Type
Use the
ø 41 mm
Restrictor
Between
500 mm - 1 m
Use the
ø 41 mm
Restrictor
Between
1m - 20 m
Between
1m - 25 m
Use the
ø 43 mm
Restrictor
Between
500 mm - 1 m
Use the
ø 43 mm
Restrictor
Do not use the
Restrictor
een 1m - 4m
Betw
Between 1m - 5m
Do not use the
Restrictor
Between
20 m - 60 m
Between
25 m - 59 m
Do not use the
Restrictor
Between 1m - 4m
Between 1m - 5m
Do not use the
Restrictor
Maximum
Flue
Length
4 m
5 m
Maximum
Flue
Length
60 m
59 m
Maximum
Flue
Length
4 m
5 m
Maximum
Flue
Length
Risk of Condensation Forming
T APPLICABLE
NO
NOT APPLICABLE
Risk of Condensation Forming
Standard Twin Pipe
After:
3 m
with a
ø 41 mm restrictor
3 m
with a ø 41 mm restrictor
4 m
without a ø 41 mm
restrictor
4 m
without a ø 41 mm restrictor
Insulated Twin Pipe
After:
3 m
with a
ø 41 mm restrictor
3 m
with a ø 41 mm restrictor
Risk of Condensation Forming
NOT APPLICABLE
NOT APPLICABLE
Risk of Condensation Forming With:
Standard Twin Pipe
After:
Insulated Twin Pipe
After:
With:
4 m
without a ø 41 mm
restrictor
4 m
without a ø 41 mm restrictor
Twin Pipe
Systems
ø 80/80
31 MFFI
Coaxial
Systems
ø 60/100
Twin Pipe
Systems
ø 80/80
TYPE 4
T
YPE 5
Exhaust
Type
TYPE 1 T
YPE 2 YPE 3
T
Exhaust
Type
TYPE 4
YPE 5
T
Between
1m - 14 m
Between
1m - 21 m
Use the
ø 42 mm
Restrictor
Between
500 mm - 1 m
Use the
ø 42 mm
Restrictor
Between
1m - 4 m
Between
1m - 11.5 m
Between
14 m - 46 m
Between
21 m - 48 m
Do not use the
Restrictor
Between 1m - 4m
Between 1m - 5m
Do not use the
Restrictor
Between
4 m - 47 m
Between
11.5 m - 42 m
46 m
48 m
Maximum
Flue
Length
4 m
5 m
Maximum
Flue
Length
47 m
42 m
4 m
with a
ø 43 mm restrictor
4 m
with a
ø 43 mm
ictor
restr
5 m
without a ø 43 mm
restrictor
5 m
without a ø 43 mm restrictor
4 m
with a ø 43 mm
restrictor
4 m
with a ø 43 mm restrictor
Risk of Condensation Forming
NOT APPLICABLE
NOT APPLICABLE
Risk of Condensation Forming With:
Standar
2 m
with a
ø 42 mm
ictor
restr
7.4 m
with a
ø 42 mm
ictor
restr
Twin Pipe
d
After:
without a ø 42 mm
restrictor
without a ø 42 mm restrictor
7.5 m
7.4 m
Insulated
2 m
with a ø 42 mm
restrictor
7.4 m
with a ø 42 mm restrictor
T
After:
5 m
without a ø 43 mm
restrictor
5 m
without a ø 43 mm restrictor
win Pipe
7,5 m
without a ø 42 mm
restrictor
7,4 m
without a ø 42 mm
ictor
restr
Where there is no risk of condense forming (and,
*
therefore no requirement for a condense collector), ensure a minimum fall of 5mm per metre a
way from
the appliance.
NOTE:UNDER SOME CIRCUMSTANCES, CONDENSE MAY FORM AT
TERMINAL
THE PAID WITH REGARD TO POSSIBLE CONDENSE DRIPPING
TERMINAL
THE
OM
FR
, SPECIAL
.
UST
EXHA
TTENTION
A
MUST
BE
17
1
2
3
4
5
6
1
2
3
4
5
6
EC
II
IJK
FR020A
* Warning the flue analysis mode must only be selected by a
qualified service engineer.
FIG. 2.22

2.10 CONTROL PANEL

LEGEND:
On/Off Button
A ­B - Domestic Hot Water Temperature Adjustment C - Central Heating Temperature Adjustment D - Reset Button/Flue Test analysis mode* E - Comfort Mode Selector F - Summer Mode LED (Green)
Ignition/Overheat Lockout LED (Red)
G ­H - Central Heating (Winter Mode) LED (Green) I - Digital Display (Fault Code/Water Temperature) J - Time Clock K- Central Heating System Pressure Gauge
2.11 DIGITIAL DISPLAY AND FAULT CODES
DISPLAY CAUSE
1
AA001
AA003
AA997 AA998 AA999
EE002 EE004
EE005
EE006
EE007
EE008
EE009
EE220 EE221
EE333
EE334
EE999
3
7 8 9
2 4
5
6
7
8
9
0 1
3
4
9
No flame after safety time (7 seconds) The heating flow temperature exceeds
o
C during operation
103 Problem with the electronic monitoring Problem with the electronic monitoring Problem with the electronic monitoring
Insufficient water pressure Domestic hot water temperature probe in open circuit Domestic hot water temperature probe short circuited Heating flow temperature probe in open circuit Heating flow temperature probe short circuited Heating return temperature probe in open circuit Heating return temperature probe short circuited Flame detected with gas valve closed Error in the electrical connection (live and neutral crossed) The air pressure switch is closed before the ignition sequence The air pressure switch does not close when the fan runs More than 5 RESETS of the boiler in 15
minutes.
The Control Panel has a 3 digit display, during normal operation the display will show one of three things on the
o right hand digits;
tw
During Stand-by (no demand for Central Heating or D.H.W.) ‘on’ will be shown on the display and no LEDs will light.
During a demand for Domestic Hot Water, the temperature of the outgoing hot water is displayed in oC (e.g. 38) and the summer mode LED will light (F - FIG. 2.22).
During a demand for Central Heating, the temperature of the central heating flow will be displayed in oC (e.g. 65) and the central heating mode LED will light (H - FIG.2.22).
ing the oper
Dur display will show ‘
ation of the flue analysis mode* the sc’.
Should a fault occur the display will show the fault code and one of two letters, for a non-volatile shutdown the letter the f
will be sho
A
ault eg.
A02
ed b
w
ollo
wn f
and the red
y the tw
LED (
o digit code f
G - FIG.
2.22)will
or
light, a non-volatile shutdown will require the reset button (D - FIG. 2.22) to be pushed before the boiler will attempt to relight, should the boiler lockout again, the assistance
ised Service Engineer should be sought.
of an A
uthor
Should the boiler develop a fault that cannot be corrected
y resetting the boiler
b
, the letter
followed by a two digit code (e.g.
olatile shutdo
v
wn code
, in the e the boiler will automatically resume oper cause behind it is resolv
ised Ser
of an A
uthor
ed. Should it not the assistance
vice Engineer would be required.
Ewill be displa
E33) indicating a
ent of such a shutdown,
v
ation once the
ed
y
18
A list of the fault codes can be found opposite.
1
A

2.12 REMOVING THE FRONT PANEL

In order to access the inside of the boiler, it is necessary to unscre located on the lower part of the panel itself. The control panel moves downward and when pulled forward rotates on two lateral hinges. The panel sta access to the inner parts of the boiler. To dismantle the front casing panel it is necessary to: 1 - Remove the two screws “B”; 2 - Move the front casing panel up and lift forward.
w the fastening screws
ys in a horizontal position, which allows
“A” of the control panel
2
B
A
A

2.13 ROOM THERMOSTAT CONNECTION

To connect a room thermostat, it is necessary to:
1. - Open the control panel as indicated in
2.- Remove the screws “A” from the terminal block on
the reverse of the control panel.
3. - Insert the thermostat cable through the cable grommet and fasten it by means of the cable-clamp provided.
4. - Connect the thermostat wires to the terminal block
(Diagram A).
5.- If a remote time clock is to be fitted, disconnect the integral time clock from the P.C.B.
6. - Using a volt-free switching time clock, connect the switching wires from the time clock following points 1­4 above
7. - If using an external time clock and room thermostat, these must be connected in series as points 1-7 above
Note: Only a low voltage room thermostat capable of
(Diagram B).
(Diagram C).
volt free switching must be used. Factory fitted integral wiring must not be disturbed when wiring external controls. Do not run low voltage cables alongside supply cables.
SECTION 2.12.
FIG. 2.22
19

2.14 ELECTRICAL/SYSTEM DIAGRAMS

F
USE
FUSE
1 2 4 5 63
ON
5
6
A
B
C
N203 CN206
CN206 CN205CN203 CN201 CN303 CN302
C
N201
C
N300
CN302
CN303
CN304
C
N205
C
N200
H
L
M
I
N
O
P
Q
A16
Y/G
Blk
Blk
Blk
Gry
Gry
Gry
Gry
Pnk
Pnk
Pnk
Pnk
Gry or Bl
Wh
Wh
Wh
Rd
Blk
Blk
Blk
Blk
Brn
Brn
Brn
Bl
BlBlBl
Blk
Or
Or
H
ATTENTION
When replacing the P.C.B. disconnect the EEPROM key (leave it attached to the control panel) and reconnect to the new PCB.
FIG. 2.23
A - Dip Switch:
y set in position B)
actor
Do Not Use (jumper is f
1 ­2 - Anti-Cycling Device Adjustment for Heating
Position A = 0 mins Position B = 2 mins 3 - Do Not Use (jumper is factory set in position B) 4 - Do Not Use (jumper is factory set in position B) 5 - Fan over-run selector (after D.H.W. is drawn)
Position A = ON Position B = OFF 6 - Do Not Use (jumper is factory set in position B)
B - Summer/Winter Switch - Central Heating Temperature
Regulation C - Connector for Remote Control (Climate Manager) D - Domestic Hot Water Temperature Regulation E - Soft-light Regulation F - Maximum Central Heating Temperature Regulation G - ON/OFF Selector H - EEPROM I - Time Clock Connector L - Reset Push Button M - Economy/Comfort Selector N - EASY Teleservice (optional) P.C.B. Section O - Display P.C.B. Connector P - Transformer Q- Modem Connection (optional - EASY Teleservice)
20
A01 - Circulation Pump A02 - F A03 - Spark Generator Power Supply
an
A04 - Gas Valve Power Supply
alve
V
ised
Motor
A05 ­A07 - Flame Sensor A08 - Central Heating Flow NTC A09 ­A10 - Domestic Hot Water Flow Switch
Domestic Hot
ater NTC
W
A11 - Low Water Pressure Switch
Modulator
A12 ­A13 - Air Pressure Switch A14 - Overheat Thermostat
Timer/Room Thermostat
nal
Exter
A15 ­A16 - Central Heating Return NTC
COLOURS:
Gy - Grey Wh - White
Red
-
Rd Br - Brown Bl - Blue
Black
-
Blk Pk - Pink
1
2 3
4 5
6 7
8
9
10
11
AB C D E
12 13 14 15 16
17
18
20
19
21
22

2.15 WATER CIRCUIT DIAGRAM

FIG. 2.24
SI016C
LEGEND:
1. Fan
2. Heat Exchanger erheat Thermostat
Ov
3.
al Heating Flo
Centr
4.
5. Burner
Detection Electrode
6.
Ignition Electrodes
7.
e
alv
V
ter
er
Div
8.
9. Low Water Pressure Switch
10. Drain Valve
11. Domestic Hot Water NTC
12. Secondary Heat Exchanger
13. Gas Valve
14. D.H.W. Flow Switch
15. D.H.W. Inlet Filter
16. Automatic By-pass
17. Safety Valve
18. Pressure Gauge
19. Circulation Pump with Automatic Air Release Valve
20. Central Heating Return NTC
21. Expansion Vessel
22. Air Pressure Switch
w NTC
Centr
A.
Domestic Hot
.
B C. Gas Inlet
Domestic Cold Water Inlet
.
D
Centr
E.
al Heating Flo
al Heating Retur
w
ater Outlet
W
n
21

3. COMMISSIONING

3.1 INITIAL PREPARATION

MTS (GB) Limited support the initiative. Within the information pack you will find a copy of the logbook. presence of your customer, they are shown how to use it, and it is signed b that they must have their logbook with them whenever they contact a service engineer or us.
Preliminary electrical system checks to ensure electrical
ety must be carried out by a competent person i.e.
saf polarity, earth continuity, resistance to earth and short circuit.
FILLING THE HEATING SYSTEM:
Lower the control panel and remove the case panels (see Open the central heating flow and return cocks supplied with the connection kit. Unscrew the cap on the automatic air release valve one full turn and leave open permanently. Close all air release valves on the central heating system. Gradually open valve(s) at the filling point (filling-loop) connection to the central heating system until water is heard to flow, do not open fully. Open each air release tap starting with the lowest point and close them only when clear water, free of air, is visible.
Purge the air from the pump by unscrewing the pump plug anticlockwise, also manually rotate the pump shaft in the direction indicated by the pump label to ensure the pump is free.
It is important that this is completed in the
y them. Please instruct your customer
SECTION 2.12 for further information).
the other appliances when they are in use at the same time.
Pipework must be of an adequate size. Pipes of less than 22mm should not be used.
Open the gas cock (supplied with the connection kit) to the appliance and check the gas connection on the appliance for leaks.
When the installation and filling are completed, flush the system while cold, refill, turn on the Central Heating system (SECTION 3.2) and run it until the temperature has reached the boiler operating temperature. The system must then be immediately flushed through. The flushing procedure must be in line with BS 7593:1992 code of practice for treatment of water in domestic hot water central heating systems. During this operation, we highly recommend the use of a central heating flushing detergent (Fernox Superfloc or equivalent), whose function is to dissolve any foreign matter that may be in the boiler and system following the flushing procedure.
Substances different from these could create serious problems to the pump or other components.
The use of an inhibitor in the system such as Fernox MB­1 or equivalent is strongly recommended to prevent corrosion (sludge) damaging the boiler and system.
Failure to carry out this procedure may invalidate the appliance warranty.
Refit the pump plug. Continue filling the system until at least 1.5 bar registers on the pressure gauge.
ater soundness and remedy
Inspect the system f any leaks discovered.
FILLING
GAS SUPPLY:
OF THE
Close all hot water draw-off taps. Open the cold water inlet cock supplied with the connection kit. Open slowly each draw-off tap and close them only when clear water, free of bubbles, is visible.
Inspect the entire installation including the gas meter and test for soundness. The entire installation should be in accordance with the relevant standards. In GB this is BS 6891 and in IE this is the current edition of I.S.813.
The connection to the appliance is a 15mm copper tail located at the rear of the gas service cock (
If the gas supply serves other appliances, ensure that an adequate supply is available both to the boiler and
.H.W. S
D
or w
YSTEM:
FIG. 2.5).
22
3.2 INITIAL ST
1
2
3
4
5
6
1
2
3
4
5
6
E
C
II
1
2
3
4
5
6
1
2
3
4
5
6
E
C
I
I
A
C
D
ART
-UP
FIG. 2.27
FIG. 2.28
THE CHECKS TO BE RUN BEFORE INITIAL START-UP ARE AS
FOLLOWS:
Make sure that:
1.
-the screw on the automatic air valve has been loosened when the system is full;
- If the water pressure in the system is below 1.5 bar, bring it up to the appropriate level;
-Ensure that the gas cock is closed;
-Make sure that the electrical connection has been made proper
ly and that the earth wire is connected to
an efficient earthing system;
- Supply power to the boiler by turning the On/Off knob “A” (see FIG. 2.27) - “on” will appear on the display. Turn the knob “C” to maximum and switch the time
clock to constant and turn up the room stat where fitted. After 7 seconds, the boiler will signal a shutdown due to ignition failure. Leave the boiler as it is until all of the air has been bled from the system.
-Loosen the cap on the head of the pump to eliminate any air pockets;
-Repeat the procedure for bleeding the radiators of air;
-Open the hot water taps for a brief period;
-Check the system pressure and, if it has dropped, open the filling loop again to bring the pressure back up to 1.5 bar.
2. Make sure that all radiator valves are open;
3. Turn on the gas cock and check the seals on the connections with an approved soap solution and eliminate any leaks.
4. Press the reset button
“D” (see FIG. 2.28) the boiler
will re-attempt ignition. If the burner does not light the first time, wait 1 minute and repeat the procedure.
5. Check the minimum and maximum burner pressure values; adjust if necessary using the values indicated in the tab
le in
SECTION 4 (
age 27)
P
.

3.3 OPERATIONAL ADJUSTMENTS

A
To access the areas in which adjustments are made, it is necessary to open the control panel, as indicated in SECTION 2.12, then remove the rear inspection cover by unscrewing the two screws “A”. Access is thereby provided to the P.C.B. and to the following components:
1. The power supply cable connector;
2. The fuses;
3. The soft-light potentiometer the setting for which can er to the
ange from the minim
r
um ther
mal po
w
maximum;
wer potentiometer
er
um po
w
y (anti-
utes
A
The maxim
4.
adjustab
um ther
le b
mal heating po
y the minim
um to maxim
(already calibrated in the factory to 70% of the
um thermal power);
maxim The jumper f
5.
cycling) f
or adjusting the ignition dela
, which can be set from 0 to 2 min
eature
(set in the factory at one minute);
un (Electrical Diagram). When the
an/Pump Ov
6.
F jumper is set to position A the F activated. (The jumper is factory set in position B) The time clock connector (see pae 20).
7.
er-r
an and Pump o
v
er-r
un is
23

3.4 COMBUSTION ANALYSIS

1
2
3
4
5
6
1
2
3
4
5
6
EC
II
3.5 PR
ODUCT OF
COMB
USTION
DISCHARGE MONITORING
FU008A
The flue connector has two apertures, readings can be
en for the temperature of the combustion by-products
tak and of the combustion air, as well as of the concentrations of O2 and CO2, etc. To access these intakes it is necessary to unscrew the front screw and remove the metal plate with sealing
et.
gask It is possible to activate the flue test mode (maximum output) by pressing and holding the RESET button “D” for
c
10 seconds, will retur
ssc
will be shown on the display. The boiler
n to normal operation after 5 minutes. The boiler can be returned to normal operation sooner by switching the boiler off and on again.
In the boiler, it is possible to monitor the correct operation of the flue exhaust/air intake, checking for a loss of general pressure in the system. Through the use of a differential manometer connected to the test points of the combustion chamber, it is possible to detect the P of operation of the air pressure switch. The value detected should not be less than 0.90 mbar (31 kW) under conditions of maximum thermal power in order for the boiler to function properly and without interruption.
FU009A

3.6 BOILER SAFETY SYSTEMS

WARNING!
The boiler is still powered.
D
The boiler is protected from malfunctioning by means of internal checks by the P.C.B., which brings the boiler to a stop if necessary.
There are two types of shut-off:
SHUTDOWN (A)
SAFETY SHUTDOWN (E)
SHUTDOWN“
AA
This type of appliance shutdown is called “volatile”, and is indicated on the display by a number preceded by the letter (A), and by the symbol GFIG. 2.22 Page 18), as illustrated in the table below:
Important
If this shutdown occurs frequently, contact an authorised Service Centre for assistance. For safety reasons, the boiler will allow a
maximum of 5 reset
operations to take place in 15 minutes (pressing the
RESET button). If the shutdown is occasional or an isolated ev not necessarily a problem.
24
ent, this is
DISPLAY CAUSE
1
AA001
3
AA003
7
AA997
8
AA998
9
AA999
No flame after saf
The heating flow temperature exceeds 103oC during operation
lem with the electronic monitor
Prob
lem with the electronic monitor
Prob Problem with the electronic monitoring
ety time (7 seconds)
ing ing
SAFETY SHUTDOWN E
1
2
3
4
5
6
1
2
3
4
5
6
EC
II
In the event of a safety cut-off (displayed with the code shown in the table), the boiler will automatically try to reset itself and relight. Should this not be the case, contact an
ised Service Centre for assistance.
author
DISPLAY CAUSE
2
EE002 EE004
5
EE005
EE006
7
EE007
8
EE008
9
EE009
0
EE220
EE221
3
EE333
EE334
9
EE999
4
6
1
4
Insufficient water pressure Domestic hot w
ater temperature probe in open circuit Domestic hot water temperature probe short circuited Heating flow temperature probe in open circuit Heating flow temperature probe short circuited Heating return temperature probe in open circuit Heating retur
n temperature probe short circuited Flame detected with gas valve closed Error in the electrical connection (live and
al crossed)
neutr The air pressure switch is closed before the ignition sequence The air pressure switch does not close when the fan runs More than 5 RESETS of the boiler in 15
minutes.
ANTI-FROST DEVICE:
The boiler is fitted with a device which, in the event that the water temperature falls below 3
wer until the boiler reaches a temperature
the minim
um po
˚C, the burner ignites at
of approximately 33˚C in the heating circuit. This device only operates if the boiler is functioning perfectly and:
- the system pressure is sufficient;
- the boiler is powered electrically;
- the gas is turned on.
PUMP /DIVERTER VALVE PROTECTION:
To prevent the pump and diverter valve from siezing the
y 21 hours
er
boiler will activ
ate the pump f
or 20 seconds e
v
after it’s last operation and activate the diverter valve.
25

3.7 DRAINING THE SYSTEM

3.10 INSTRUCTING THE END USER

DRAINING
The heating system must be drained as follows:
- Turn off the boiler;
- Attach a hose pipe and open the drain valve;
- Drain the system at the lowest points (where present). When the heating system is unused for an extended period of time, it is recommended that you add antifreeze with an ethylene glycol base to the water in the heating pipe work and radiators if the ambient temperature drops below 0°C during the winter. This makes repeated draining of the entire system unnecessary.
DRAINING THE DOMESTIC HOT WATER SYSTEM
Whenever there is the danger of the temperature dropping below the freezing point, the domestic hot water system must be drained as follows:
- Turn off the general water valve for the household plumbing system;
- Turn on all the hot water taps;
- Empty the remaining water from the lowest points in the system (where present).
THE
HEA
TING
SYSTEM

3.8 COMPLETION

1. Hand over the copy of the End User Instructions supplied with the appliance, together with these instructions, and e
xplain how to use the timeclock and room thermostat.
2. Show the End User how to switch the appliance off quickly, and indicate the position of the electric supply isolator.
3. Inform the End User of the location of all drains, isolating valves and air vents.
4. Explain how to turn the appliance off for both short and long periods and advise on the precautions necessary to prevent damage in the event that the appliance is inoperative when freezing conditions occur.
5. Instruct the End User on the correct procedure for checking and refilling the boiler.
6. Finally advise the End User that, for continued safe and efficient operation, the appliance must be serviced by a competent person at least once a year.
For the Republic of Ireland it is necessary to complete a “Declaration of Conformity” to indicate compliance to I.S.
813. An example of this is given in the current edtion of I.S.
813. In addition it is necessary to complete the Log Book.

3.9 OPERATIONAL CHECKS

1. The flue system must be visibly checked for soundness.
2. On Central Heating allow the system to warm up and adjust the Central Heating temperature control knob, check the burner modulates up and down between the high and low settings.
3. Range rate the thermal power for Central Heating, as detailed in
4. Run the Domestic Hot Water and adjust to the correct water flow rate, adjust the Domestic Hot Water temper up and down between the high and low settings.
5. Balance the Central Heating system until all return temperatures are correct and equal.
SECTION 4.2, Page 29.
ature control knob to check the burner modulates
6. Turn the ON/OFF button OFF, disconnect the pressure Gauge, retighten screw and relight boiler.
7. Re-examine Central Heating, Domestic Hot Water and Cold Water supplies for soundness.
8. Check the appearance of the gas flame to assess the adequacy of the combustion air supply.
9. If external controls have been disconnected, reconnect
and test.
10. Refit boiler casing.
26

4. GAS ADJUSTMENTS

TABLE A
TEGORY II2H3+
CA
Lower Wobbe Index (15°C;1013mbar) MJ/m3h Nominal Delivery Pressure mbar
microGenus II 24 MFFI
Main Burner: n. 14 jets (ø) mm Consumption (15°C; 1013mbar) max - min m3/h Consumption (15°C; 1013mbar) max - min Kg/h Gas Burner Pressure max - min mbar
oGenus II 28 MFFI
micr
Main Burner: n. 14 jets (ø) mm Consumption (15 Consumption (15°C; 1013mbar) max - min Kg/h Gas Burner Pressure max - min mbar
microGenus II 31 MFFI
Main Burner: n. 14 jets (ø) mm Consumption (15°C; 1013mbar) max - min m Consumption (15°C; 1013mbar) max - min Kg/h Gas Burner Pressure max - min mbar
°C; 1013mbar) max - min m
3
/h
3
/h
Methane Gas
G20
45.67 20
1.25
2.80 - 1.16
---
10.3 - 2.0
1.30
3.15 - 1.27
---
10.8 - 2.0
1.35
3.54 - 1.48
---
11.5 - 2.1
Liquid Butane Gas
G30
80.58 29
0.72
---
2.09 - 0.87
28.1 - 5.0
0.77
---
2.35 - 0.95
28.0 - 5.0
0.80
---
2.64 - 1.10
26.8 - 5.3
Liquid Pr
2.06 - 0.85
35.6 - 6.8
2.31 - 0.93
36.0 - 6.0
2.60 - 1.09
34 - 6.5
opane Gas
G31
80.58 37
0.72
---
0.77
---
0.80
---
4.1 CHANGING THE TYPE OF GAS
The boiler can be converted to use either methane (natural) gas (G20) or L.P.G. (G30 - G31) by an Authorised Service Centre.
The operations that must be performed are the following:
1. Replace the jets on the main burner
(see table in section 4);
2. Adjust the maximum and minimum thermal capacity values for the boiler
(see table in section 4 and 4.2 Adjusting the Gas Pressures);
3. Adjust the maximum thermal power setting (see tables in section 4.3 and FIG. 4.1);
4. Adjust the soft-light feature
(see table below for recommended pressure and Fig. 4.1);
5. Adjust the ignition delay feature for the heating system by adjusting the Jumper as indicated in Section 2.14
(FIG. 2.23). It can be set from 0 to 2 mins.).
RECOMMENDED SOFT LIGHT PRESSURES
CATEGORY
II2H3+
Recommended
Soft-light
Pressure (mbar)
24 kW
28 kW
31 kW
Methane
Gas
G20
5.0
5.0
4.5
Liquid
Butane
Gas
G30
12.0
12.0
12.0
Liquid
Propane
Gas
G31
12.0
12.0
12.0
27

4.2 ADJUSTING THE GAS PRESSURES

AA
BB
C
D
E
F
1
B
A
2
D1
C
3
D
E
Setting the minimum and the maximum power of the boiler
1.
Check that the supply pressure and dynamic working pressure to the gas valve is a minimum of 20 mbar for natural gas.
o do this, loosen the screw
2. T
“A”.
Fit the pipe of the pressure gauge to the inlet pressure connection of the gas valve “B” and check for the correct standing pressure, then operate the appliance and check for the correct working pressure. When y
ou have completed this operation, replace the
screw “A” securely into its housing to seal off the gas (check for tightness).
3. To check the pressure supplied by the gas valve to the
burner, loosen the screw
“C”. Fit the pipe of the
pressure gauge to the pressure outlet test point of the gas valve
“D”.
Disconnect the compensation pipe “D1” either from the gas valve or from the sealed chamber.
4. Turn the On/Off knob to “ON” position -green light- and
ensure that the hot water temperature control knob is set to maximum. Turn on the boiler by running a hot water tap. Adjust the 10mm nut “E” on the modureg to set the maximum gas pressure, turn the nut clockwise to increase and anti clockwise to decrease the pressure until the required pressure is achieved (see TABLE A Page 27).
5. To set the minimum power, disconnect a supply terminal “F1” from the modureg and adjust screw “F” (ensure that the 10mm nut is held in position). Turn the screw clockwise to increase the pressure and anti­clockwise to decrease the pressure (displayed on the pressure gauge) corresponding to the minimum power (see TABLE A Page 27).
e completed the above operations, turn
6. When you ha
v off the hot water tap, reconnect the supply terminal to the modureg on the gas valve, reconnect the compensation pipe and replace the cap on the scre of the modureg.
w
28
4
F
F1
1 2 4 5 63
ON
AB
C
N203 CN206
C
N201
C
N200
Soft-light
Adjustment
M
ax Heating
Power
IMPORTANT!
Whenever you disassemble and reassemble the gas connections, always check for leaks using a leak detection fluid.
Setting the maximum heating circuit power
o set the maximum heating circuit power, turn the
7. T
On/Off knob to the “ON” position and set the time clock and an
y external controls to the “ON” position. Turn the
knob of the heating thermostat clockwise to maximum.
8. Remove the inspection panel of the P.C.B. and fit a
small cross-head screwdriver in to the right hand potentiometer (see belo the pressure or anti-cloc
w). Turn clockwise to increase
kwise to reduce the pressure. Adjust the setting to the required heating pressure value (displayed on the pressure gauge), as indicated in the charts shown on Page 31.
9. Turn off the boiler by placing the main switch to the
"OFF" position.
Setting the pressure for soft-light ignition.
Disconnect the detection electrode connection close to the P.C.B. (SECTION 6.3.3). Start the boiler and during the ignition sequence adjust the left hand potentiometer until the gas pressure reads the required gas pressure (see the table on page 27). Once the gas pressure is set turn off the boiler and re­connect the detection electrode to the P.C.B. NB.: It may be necessary to reset the flame failure reset a number of times during this operation.
10. Remove the pipe from the test point and tighten the
screw “
C” to the pressure test point in order to seal off
the gas.
11. Carefully check the pressure test points for gas leaks
(both inlet and outlet).
29
microGENUS II 24 MFFI
NATURAL GAS (G20)
kW 10 12 14 16 18 20 22 24
mbar 2.5 3 3.75 4.75 5.75 7 8 10
LIQUID GAS (G30)
kW 10 12 14 16 18 20 22 24
mbar 5.5 8 10 12.5 15.5 18.5 22 26
LIQUID GAS (G31)
kW 10 12 14 16 18 20 22 24
mbar 7 9 12 15.5 19 24 28 34
microGENUS II 28 MFFI
NATURAL GAS (G20)
kW 11 13 15 17 19 21 23 25 27
mbar 2 2.75 3.5 4.5 5 6 7 8.5 10
LIQUID GAS (G30)
kW 11 13 15 17 19 21 23 25 27
mbar 5 6.5 8.5 10.5 13 15.5 18.5 21 25
LIQUID GAS (G31)
kW 11 13 15 17 19 21 23 25 27
mbar 6.5 8 10 12 14.5 17.5 21 25.5 31
microGENUS II 31 MFFI
NATURAL GAS (G20)
kW 13 15 17 19 21 23 25 27 29 31
mbar 2.5 3 3.5 4.5 5.5 6.5 7.5 8.5 10 11.5
LIQUID GAS (G30)
kW 13 15 17 19 21 23 25 27 29 31
mbar 5 7 8 10 12 14 17 20 23 27
LIQUID GAS (G31)
kW 13 15 17 19 21 23 25 27 29 31
mbar 7 9 11 13 15 18 21 24 28 34
NOTE: THIS TABLE CAN BE USED IN CONJUNCTION WITH THE GRAPH ON PAGE31.
30
FIG. 4.1
3434
3636
3838
4040
modello 24
modello 28 modello 31
modello 24
modello 28 modello 31
modello 24
modello 28 modello 31
Regulating the heating po
natural gas (G20)
Regulating the heating po
butane gas (G30)
wer for
model 24 model 28 model 31
Burner pressure
wer for
model 24
model 28
model 31
Regulating the heating power for
propane gas (G31)
Burner pressure
model 24
model 28
model 31
Burner pressure

5. MAINTENANCE

It is recommended that the following inspections be carried out on the boiler at least once a y
1 - Check the seals for the water connections; replace
any faulty seals. 2 - Check the gas seals; replace any faulty gas seals. 3 - Visual check of the entire unit.
Visual check of the combustion process or analysis
4 -
of combustion by-products (see
cleaning of the burner if needed. 5 - If necessary, dismantling and cleaning of the
combustion chamber. 6 - If necessary, dismantling and cleaning of the burner
jets. 7 - Visual check of the primary heat exchanger:
- check for overheating in the blade assembly;
- clean the exhaust fan if needed.
8 - Adjustment of the gas pressure, gas rate and soft-
light, partial load and full load. 9 - Check of the heating safety systems:
- safety device for maximum temperature (overheat thermostat);
- safety device for maximum pressure (safety valve).
10- Check of the gas safety systems:
- safety device for lack of gas or flame ionisation (detection electrode).
Check of the electrical connection (ensure it
11-
complies with the instructions in the manual).
12- Check of Domestic Hot Water production efficiency
(flow rate and temperature)
13- General check of the combustion by-products of the
discharge/ventilation system.
14- Check of the general performance of the unit.
SECTION 3.4) and
ear:
NOTE: THESE CHECKS ARE NOT EXHAUSTIVE

6. SERVICING INSTRUCTIONS

To ensure efficient safe operation, it is recommended that the boiler is ser
Before starting any servicing work, ensure both the gas and electrical supplies to the boiler are isolated and the boiler is cool.
Before and after servicing, a combustion analysis should be made via the flue sampling point (please refer to SECTION 3.4 for further details).
After servicing, preliminary electrical system checks must be carried out to ensure electrical safety (i.e. polarity, earth continuity, resistance to earth and short circuit).
6.1 REPLA
The life of individual components vary and they will need servicing or replacing as and when faults develop. The fault finding sequence chart in which component is the cause of any malfunction, and instructions for removal, inspection and replacement of the individual parts are given in the following pages.

6.2 TO GAIN GENERAL ACCESS

viced annually by a competent person.
CEMENT OF
TS
PAR
SECTION 7 will help to locate
2. The control rotates on two lateral hinges; the panel stays in a
horizontal position, which allows access to the inner parts of the boiler (F
3. Remove the screws “B” from the front panel bottom lip
(F
IG. 6.3);
4. Lift the front panel up and forward from the raised screws at the
the top of the casing (F
FIG. 6.3
IG. 6.2);
IG. 6.4).
B
All testing and maintenance operations on the boiler require the control panel to be lowered. This will also require the removal of the casing.

6.2.1 Removing the front panel

1. Loosen the fastening screws “A” of the control panel located
on the lower part of the panel itself. (F
FIG. 6.1
IG. 6.1);
A
FIG. 6.2
FIG. 6.4

6.2.2 Removing the sealed chamber front cover

6.2.3 Removing the side panels

1. Remo
ve the screws “C” (F
IG.
6.5);
2. Lift the sealed chamber front cover from the locating pins
IG. 6.6).
(F
C
C
1. Remo
ve the four screws “D” for each side panel (F
IG.6.7
);
2. Pull the panel away from the boiler at the base, then lift the
panel up and remove from the boiler (F
6.7
FIG.
IG.6.8).
D
D
FIG. 6.5
D
D
FIG. 6.8
FIG.
6.6

6.3 ACCESS TO THE COMBUSTION CHAMBER

6.3.1 Removing the combustion cover

1. Remo
ve the screws “E” (F
2. Lift off the comb
FIG. 6.9
ustion cover.
E
E
IG.
6.9);
6.11
Fig.

6.3.3 Removing the electrodes

Before carrying out this procedure, unscrew and slide the burner forward (see previous section).
E
1. Remove rubber gasket “G” (FIG. 6.12);
2. To remove the detection electrode disconnect the cable at
its connection point close to the P.C.B. (FIG. 6.13);
E
3. Remove screw “H” (FIG. 6.14);
4. Gently slide the electrode downward (FIG. 6.15).

6.3.2 Removing the burner and jets

1. Remove the screws “F” from the burner (FIG. 6.10);
2. Remove the burner (FIG. 6.11);
3. Disconnect the electrodes (see SECTION 6.3.3);
4. Remo
e the jets using a No
v
. 7 socket spanner;
5. Replace in reverse order.
FIG. 6.10
F
F
FIG. 6.12
G
FIG. 6.13

6.3.4 Removing the main heat exchanger

FIG.
6.14
1. Drain the boiler of water;
2. Remove the side panels (see 6.2.3)
3. Remo
4. Remo
H
5. Release the connection nut “K” (FIG. 6.17);
6. Release the connection nut “L” (FIG. 6.18);
ve the overheat thermostat sensor “I” (F ve the clips “J” (F
IG.
6.16);
IG.
6.16);
7. Pull down the pipe (FIG. 6.19);
4. Pull the exchanger out (FIG. 6.20).
I
J
J
Fig. 6.16
FIG. 6.15
ying
o replace
T
, repeat the steps in re
erse order
v
, pa
particular attention to the following:
Centre the electrode in the positioning hole carefully
a -
otherwise the electrode ma
y break;
b -Ensure that the left hand and right hand electrodes are
located the correct w
e the correct spar
giv
ay round (facing each other), to
k gap;
c -Check that the cables have been connected correctly; d -Check that the rubber gasket seals the cable/
electrode connection point completely.
K
6.17
FIG.
,
L
FIG. 6.18

6.3.5 Removing the air pressure switch

1. Disconnect the electrical connections “M” and silicone
pipes “N” from their connection points (F
IG. 6.21);
2. Remove screws “O” on the top of the sealed chamber
(FIG. 6.22);
3. Lift out the air pressure switch (FIG. 6.23);
4. Unscrew to remove the switch from the plate.
FIG. 6.21
6.19
Fig.
Fig. 6.20
FIG. 6.22
M
N
N
O
O
FIG. 6.23

6.3.6 Removing the fan

6.4 ACCESS TO THE GAS VALVE

1. Disconnect electrical connections “P” and silicone pipe
“Q” (FIG.6.24);
2. Remove screw “R” and remove the fan collar clamp “R”
(
FIG.6.25
3. Remove screws “S” (FIG.6.26);
4. Remove fan and mounting plate (FIG.6.27).
);
P
P
Q
FIG. 6.24
6.4.1. Removing the spark generator (HONEYWELL Gas Valve)
1. Disconnect ignition leads
“T” by pulling upward
(FIG. 6.28);
2. Remove the screw “U” (FIG. 6.29);
3. Remove the spark generator by pulling forward from
the gas v
alve (F
IG.
6.30).
T
FIG. 6.28
R
FIG. 6.25
U
S
FIG. 6.29
S
S
FIG. 6.26
FIG. 6.27
FIG. 6.30
6.4.2 Removing the gas valve (Honeywell)

6.5 ACCESS TO THE WATER CIRCUIT

Important! Before removing the gas valve, ensure the gas supply is tur
ned off.
1. Disconnect all the cables from the solenoid and
modureg;
2. Remo
3. Release the n
ve the spark generator (see previous section);
uts “V” (F
IG.
6.31);
4. Remove the screws “W” from the bottom of the gas
valve (FIG. 6.32);
5. Remove the gas valve (FIG. 6.33).
V
V
Important! Before any component is removed, the boiler must be drained of all water.
Removing the D.H.W. (secondary) exchanger
6.5.1
1.
Remove the screws “X” (FIG 6.34);
2.Disconnect the cable “Y” (FIG 6.35);
3.Push the insulation of the exchanger towards the rear
of the boiler, and lift upwards and remove from the front of the boiler (FIG 6.36);
4.Push the exchanger towards the rear of the boiler, and
lift upwards and remove out of the front of the boiler (FIG 6.37);
5.Before replacing the exchanger ensure that the O-rings
are in good condition and replace if necessary.
W
W
FIG. 6.31
FIG. 6.32
X
X
FIG. 6.34
Y
6.35
FIG.
FIG.
6.33
FIG. 6.36

6.5.2 Removing the pump pressure switch

1.Remove the pump pressure switch electrical connections
(F
“Z”
2.Unscrew the pump pressure switch by
IG 6.38
);
using
a spanner on
the nut (FIG 6.39);
3.Remove the pump pressure switch (FIG 6.40).
FIG. 6.37
Z
FIG. 6.38
FIG. 6.39
FIG. 6.40

6.5.3 Removing the safety valve

1. Disconnect the discharge pipe work from below the
;
boiler
2. Unscrew the fixing screw “A1” (FIG. 6.42)
3. Pull the valve upwards for removal (FIG. 6.43).
FIG. 6.41

6.5.4 Removing the automatic air vent

1. Remo
ve the U-clip “B1” (F
IG.
6.44);
2. Remove valve complete with float using a screwdriver
F
(
IG 6.45-FIG 6.46
).
B1
FIG. 6.44
A1
FIG. 6.42
6.43
FIG.
FIG. 6.45
FIG. 6.46

6.5.5 Removing the pump

1. Remove the electrical connection “ C1” (FIG. 6.47);
2. Release the n
ut “D1” (F
IG.
6.48);
3. Remove the retaining clip “E1” from the bottom of the
boiler (FIG. 6.49);
4. Remove the screw “F1” (FIG. 6.50);
5. Remo
ve the U-clip “G1” and remove the pressure
gauge connection (
F
6.51);
IG.
6. Remove the U-clip “H1” and remove the automatic air
vent (FIG. 6.52);
7. Remove the pump.
C1
G1
F1
FIG.
6.50
FIG. 6.47
D1
6.48
FIG.
FIG. 6.51
H1
FIG. 6.52
E1
FIG.
6.49

6.5.6 Removing the pressure gauge

6.5.7 Removing the expansion vessel

1. Remove the U-clip “I1” (FIG. 6.53)
2. Lift the pressure gauge from the rear of the control
panel using a screwdriver (FIG. 6.54-6.55).
I1
FIG. 6.53
1. Release nut “J1” (FIG. 6.56);
2. Remo
ve back-nut “K1” (F
IG.
6.57);
3. Remove the expansion vessel (FIG. 6.58).
J1
K1
FIG. 6.56
FIG. 6.54
FIG. 6.55
FIG. 6.57
6.58
FIG.

6.5.8 Removing the overheat thermostat

6.5.9 Removing the C.H. temperature probe (N.T.C.)
1. Disconnect the overheat thermostat electrical
connections
“L1” (F
IG.
6.59);
2. Then remove the thermostat from its mounting by
releasing the securing clip (FIG. 6.60-6.61).
L1
FIG. 6.59
1. Pull off the electrical connector and remove the sensor
.(F
probe
6.62-6.63).
IG.
FIG. 6.62
FIG. 6.60
6.61
FIG.
FIG. 6.63
6.5.10 Removing the D.H.W. temperature sensor .C.)
(N.T
1. Pull off the electr
ical connector and unscrew the
sensor probe using a suitable spanner (FIG. 6.64).
FIG. 6.64

6.5.11 Removing the diverter valve actuator

6.5.12 Removing the D.H.W. flow switch
1. Unplug the electrical connector “O1” (FIG. 6.66);
2. Remo
ve the D.H.W. flow switch using a screwdriver
(FIG. 6.67-6.68).
O1
FIG. 6.66
1. Unplug the electrical connector “M1” (FIG. 6.65);
2. Release the retaining clip “N1” and remove the divertor
valve actuator
M1
N1
FIG. 6.65
FIG. 6.67
FIG.
6.68

6.6 ACCESS TO THE CONTROL SYSTEM

6.6.1 Checking the fuses

Important! Isolate the electrical supply to the boiler
ore accessing the control panel.
bef
1. Remove the inspection cover on the reverse of the
control panel and unscre
w the screws “P1”(F
IG.
6.69);
2. Remove the fuses (FIG. 6.70).
P1
P1
FIG. 6.69
FIG. 6.70
6.6.2 Removing the P.C.B.
1. Isolate electricity;
2. Remo
ve the inspection cover from the reverse of the
control panel, unscrew the screws “Q1” (FIG. 6.71);
3. Unplug all electrical connections from the P.C.B (FIG.
6.72);
4. Carefully unplug the EEPR
5. Remo
ve the screws “S1” (F
OM key “R1” (F
6.74);
IG.
IG.
6.73);
6. Separate the facia panel from the rear of the control
panel ;
7. Remove the main P.C.B., unscrew the screws “T1”
(FIG. 6.75);
8. Unscew the display P.C.B. mounting screws “T2” and
disconnect the P.C.B. connection cable “T3” (FIG. 6.76);
9. Remove the display P.C.B. (FIG. 6.77);
10.Replace either P.C.B. in reverse order.
11.Refit the EEPROM key “R1”
S1
S1
S1
S1
FIG. 6.74
Q1
Q1
FIG. 6.71
T1
T3
T1
T2
T3
T1
FIG. 6.75
6.76
FIG.
R1
FIG.
FIG.
6.72
6.73
FIG.
6.77

6.6.3 Removing the time clock

1. Disconnect the electrical connections “U1” from the
cloc
k (F
IG.
6.78);
2. Remove screws “V1” (FIG. 6.78);
3. Lift the time clock out from the control panel (FIG. 6.79).
U1
V1
FIG. 6.78
FIG. 6.79

7. FAULT FINDING

PRELIMINARY CHECKS
MAKE SURE THAT:
IS
THE POWER
DISPLAY
ON?
POSTION
OF THE
SELECTOR
NONO
NONO
CENTRALCENTRAL
HEAHEATINGTING
ESTAT E
HOT WATER
ONLY
NONO
YESYES
YESYES
YESYES
YESYES
YESYES
NONO
NONO
NONO
NONO
NONO
NONO
NONO
YESYES
YESYES
YESYES
TURN ON THE ON/OFF
SWITCH
IS D.H.W.
BEING DRAWN?
IS D.H.W.
BEING DRAWN?
FOR BOILERS
WITH ELECTRONIC
ANTI-FROST DEVICE:
PROTECTION IS ACTIVATED
IF HEATING TEMP
IS < 5
°
C
FOR BOILERS
WITH ELECTRONIC
ANTI-FROST DEVICE:
PROTECTION IS ACTIVATED
IF HEATING TEMP
IS < 5
°
C
MUST
TIME CLOCK
AND/OR ROOM
THERMOSTAT
BE ACTIVATED?
A
ECONOMY/
COMFORT
SELECTOR
TEMP.
C.H. < 42°C
Comfort
Comfort
Economy
Economy
1
- There is sufficient water in 
the system
2
- The gas is turned on 
3
- The electrical supply is
turned on
1 - Check/reset system pressure 2 - Check/restore gas supply 3 - Check/replace short- circuited heating probe 4 - Check/replace siezed pump
1 - Check/reset the system pressure 2 - Check/restore gas supply 3 - Check/replace short- circuited heating probe 4 - Check/replace siezed pump
TEMP.
C.H. < 42°C
ECONOMY/
COMFORT
SELECTOR
YESYES
D
OES AN ERROR CODE
APPEAR ON THE DISPLAY?
1
. Check the fuses
2. Check the power supply to the control panel 3
. Check/replace the ON/OFF button 4
. Check the connection between
the main and display P.C.B.s
see section 3.6
5. Check/replace the
main and display P.C.B.s
7.1 FA
o ensure that the external controls do
T not interfere with the fault finding, disconnect the wires from the terminal block on the rear of the control panel and provide a solid link between the terminals.
ULT
FINDING GUIDE
(FLOW-CHARTS)
These fault finding guides are not exhaustive. However, it is possible to detect and correct many defects by using the standard fault finding diagrams described in this chapter, ensure these guides are carried out in the set order.
YESYES
YESYES
NONO
IS THE
P
UMP RUNNING?
1. Check if there is air in the system
2. Check the main circuit flow switch operation
3. Check the pressure on the water gauge and fill system to 1 bar
1. Check pump cable
2. Check/replace main P.C.B.
Release/replace
pump
Turn the
ON/OFF Control Knob
POWER TO
THE PUMP?
YESYES
YESYES
IS
THE LOW WATER
PRESSURE SWITCH
WORKING CORRECTLY?
E02: does not reset
N
ONO
NONO
A
B
1. Check the fan cable
2. Replace the fan
3. Replace the main P.C.B.
1. Check/replace ignition electrode
2. Check ignition cable
3. Check/replace the main P.C.B.
Replace
the main P.C.B.
IS THE FAN
RUNNING?
DOES CODE
E
33 APPEAR?
IGNITION
SPARKS ARE GENERATED
REGULARLY?
YESYES
NONO
NONO
YESYES
YESYES
NONO
1. Check the power supply of the gas valve.
2. Check for an air pressure signal
3. Check the gas pressure on the burner
4. Check the soft-light adjustment
5. Replace the gas valve
6. Check/replace the main P.C.B.
1. See section 3.6
2. Press RESET
1. See section 3.6
IS THE BURNER
ALIGHT?
BOILER HAS SHUTDOWN?
YESYES
YESYES
NONO
NONO
IS
THERE STILL
A PROBLEM?
NORMAL
OPERATION
NONO
YESYES
B
8. EXPLODED VIEW
2
3
4
1
5
7
6
17
15
104
101
103
102
109
112
111 110
35
51
52
50
49
48
114
115
113
47
301 302 303
304
305
305
15
8 9
10
9
10
73 74
72
72
75
2219 20
18
142321
13
25 28 30 30 3126
12
11
14
16
64
63
7
5359 555758
47
54
7
56
7
47
60
7
81
82
49
32
36
41
45
46
24
14
88
91
67
65
66
66
105
105
106
100
17
42
43
44
99
98
29
39
40
95
97
96
71
70
68
69
37
93
38
38
92
90
7
94
83
85
84
87
86
17
80
79
78
34
33
27
89
107
76
77
47
62
63
108
61
998616 998077 997147 573520
65100547
569390 995903
998458 65101427 65101257 65101426 65101417
999599 65100695 65100716
998484
573521 61011136 61010017
990686
996065
997077
997088
573528 65100249 65100244 65101368 65100709 65100871 65100693 65100694 65100692
999397 65100719 65101428 65100540
Key
no.
ARISTON
Part No.
Description
2
9 13 17 18 20 21 22 23
26
37 40 50
63 68
69 70 74 75 76 78 80 94 95 97
101 102 103 109
551
Expansion vessel O-ring Motor (3- Way valve) Gasket 3/4" Flow group Gasket 1/4" Low water pressure switch Temperature probe (D.H.W.) Return group (24 MFFI) Return group (28/31 MFFI) Pump (24 MFFI) Pump (28/31 MFFI) Clock Pressure gauge Air pressure switch (28/31 MFFI) Air pressure switch (24 MFFI) Gasket (3/8") Heat exchanger (28/31 MFFI) Heat exchanger (24 MFFI) Temperature probe & clip (C.H.) Thermostat (overheat) Fixing clip (motor) Safety valve (3 bar) Gasket (1/2") Spark generator Gas valve EEPROM key CMP3 (microGENUS II) P.C.B. (display) P.C.B. (main) Electrode (ignition R.H.) Electrode (ignition L.H.) Electrode (detection) Fan (24 MFFI) Fan (31 MFFI) Fan (28 MFFI) Flow detection kit (w/magnet)
1
1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1
1 1
1
1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1
(Not Illustrated)
8.1 SHORTSP
ARES
LIST

9. TECHNICAL INFORMATION

Name CE Certification Flue
General Info
Energy Performance
Emissions
Central Heating
Type
Heat Input max/min kW Heat Output max/min kW Efficiency of Nominal Heat Input % Efficiency at 30% of Nominal Heat Input Efficiency at Minum Input %
UK Rating Band
SEDB Heat Loss to the Casing (∆T=50°C) % Flue Heat Loss with Burner Operating % Flue Heat Loss with Burner Off %
Max Discharge of Products of Combustion (G20) Kg/h Residual Discharge Head mbar
emp. of exhaust fumes at nominal capacity °C
T
2 Content %
CO O2 Content % CO Content ppm Nox Class Minimum Ambient Temperature °C
Head Loss on Water Side (max) (T=20°C) mbar Residual Head of System bar Expansion Vessel Pre-load Pressure bar Maximum Heating Pressure bar Expansion Vessel Capacity l Maximum Water Content of System l Heating Temperature max/min °C
%
microGenus II 24 MFFI
0694BO4008
C12-C32-C42-C52-C82-B22-B32
29.4 / 12.2
24.8 / 9.7
84.3
81.6
79.6 D
1.2
5.1
0.4
51.4
1.23
106.9
7.15
7.9
39.3 3
+5
200
0.25
0.7 3 7
130
82 / 42
microGenus II 28 MFFI
0051BO2494
C12-C32-C42-C52-C82-B22-B32
33.1 / 13.3 28 / 10.5
84.5
80.5
78.7 D
1.1
5.7
0.4
61.9
0.65
115.4
6.67
8.4
36.8
3
+5
200
0.25
0.7 3 7
130
82 / 42
Domestic Hot Water Temperature (approx) max/min °C Specific Flow Rate (10 minutes/DT 30°C) l/min D.H.W. Flow Rate T=25°C l/min D.H.W. Flow Rate T=35°C l/min
Minimum Flow Rate l/min
.
.H.W
D
ater max/min
Pressure of Domestic Hot
W
Domestic Hot Water
Nominal Pressure Natural Gas (G20) mbar
LPG (G30-G31)
Consumption at Nominal Capacity(G20) m3/h
Gas
(15°C, 1013 mbar) (G30-G31) Kg/h Gas Consumption after 10 Minutes* m
Electrical Supply (V ± 5%) V/Hz Power Consumption W Protection Grade of Electrical System Internal Fuse Rating
Electrical Data
Dry Weight Kg Dimensions (W/D/H) mm Maximum Flue Length (Horizontal) m Maximum Flue Length (Vertical) m
bar
mbar
3
IP
56 / 36
11.8
14.2
10.2
2.5
6 / 0.2
20
28/30 - 37
2.80
2.09 - 2.06
0.33
230/50
125
X4D
2A FAST
34
700x400x315
4 5
56 / 36
13.3
15.9
11.4
2.5
6 / 0.2
20
28/30 - 37
3.15
2.35 - 2.31
0.37
230/50
140
X4D
2A FAST
35
700x400x315
4 5
G.C. Number
*Calculated at 70% maximum output
47-116-25
47-116-26
Name CE Certification Flue
General InfoEnergy Performance
Type

microGenus II 31 MFFI

0694BO4008
12-C32-C42-C52-C82-B22-B32
C
Heat Input max/min kW Heat Output max/min kW Efficiency of Nominal Heat Input Efficiency at 30% of Nominal Heat Input % Efficiency at Min
um Input % SEDBUK Rating Band Heat Loss to the Casing (T=50°C) % Flue Heat Loss with Burner Operating % Flue Heat Loss with Burner Off %
Max Discharge of Products of Combustion (G20) Kg/h Residual Discharge Head mbar
emp. of exhaust fumes at nominal capacity °C
T
2 Content %
CO O2 Content CO Content ppm
Emissions
Nox Class Minimum Ambient Temperature °C
Head Loss on Water Side (max) (T=20°C) mbar Residual Head of System bar Expansion Vessel Pre-load Pressure bar Maximum Heating Pressure bar Expansion Vessel Capacity l Maximum Water Content of System l
Central Heating
Heating Temperature max/min °C
%
%
37.2 / 15.5
31.1 / 12.1
83.6 81
78.1
D
1.5
5.7
0.4
64.7
1.6
121.2
7.19
7.8
60.5
3
+5
200
0.25
0.7 3 7
130
82 / 42
Domestic Hot Water Temperature (approx) max/min °C Specific Flow Rate (10 minutes/DT 30°C) l/min D.H.W. Flow Rate T=25°C l/min
Flow Rate T=35°C l/min
.
.H.W
D
.H.W. Minimum Flow Rate l/min
D Pressure of Domestic Hot Water max/min bar
Domestic Hot Water
Nominal Pressure
Natural Gas (G20) mbar LPG (G30-G31) mbar
Consumption at Nominal Capacity(G20) m
Gas
(15°C, 1013 mbar) (G30-G31) Kg/h Gas Consumption after 10 Minutes* m
Electrical Supply (V ± 5%) V/Hz Power Consumption W Protection Grade of Electrical System IP Internal Fuse Rating
Elettrical Data
Dry Weight Kg Dimensions (W/D/H) mm Maximum Flue Length (Horizontal) m Maximum Flue Length (Vertical) m
56 / 36
14.8
17.8
12.7
2.5
6 / 0.2
20
28/30 - 37
3
/h
3.54
2.64 - 2.60
3
0.41
230/50
165
X4D
2A FAST
36
700x400x315
4 5
G.C. Number
*Calculated at 70% maximum output
47-116-27
Manufacturer: Merloni TermoSanitari SpA - Italy
Commercial subsidiaries: MTS (GB) Limited
MTS Building Hughenden Avenue Damastown Avenue High Wycombe Mulhuddart Bucks HP13 5FT
Telephone: (01494) 755600 Telephone: (01) 810 3723 Fax: (01494) 459775 Fax: (01) 810 3727 Internet: www.mtsgroup.com/uk Internet: www.mtsgroup.com/ie E-mail: info@uk.mtsg
Technical Advice: 0870 241 8180 Technical Advice: (01) 437 0121 Customer Service: 0870 600 9888 Customer Service: (01) 437 0121
MTS Heating Limited
k
ar
Damasto
Dub
roup.com E-mail: info@ie.mtsgroup.com
wn Industr
lin 15
ial P
0 99 84 1854 211 Edition 2 04/04
Loading...