ONTROL PANELPAGE.18
IGITAL DISPLAY AND FAULT CODESPAGE.18
EMOVING THE FRONT PANELPAGE.19
AT
CONNECTIONPAGE.19
2.14ELECTRICAL/SYSTEM DIAGRAMSPAGE.20
2.15WATER CIRCUIT DIAGRAMPAGE.21
5
8
3. COMMISSIONINGPAGE.22
3.1I
3.2INITIAL STA RT-UPPAGE.23
3.3OPERATIONAL ADJUSTMENTSPAGE. 23
3.4C
3.5PRODUCT OF COMBUSTION
3.6BOILER SAFETY SYSTEMSPAGE.24
3.7DRAINING THE SYSTEMPAGE.26
3.8COMPLETIONPAGE.26
3.9
3.10INSTRUCTING THE END USERPAGE.26
NITIAL PREPARATIONPAGE. 22
OMBUSTION ANALYSISPAGE.24
DISCHARGE MONITORINGPAGE. 24
O
PERA
TIONAL
CHECKSPAGE.
26
4. GAS ADJUSTMENTSPAGE.27
4.1CHANGING THE TYPE OF GASPAGE.27
4.2
A
DJUSTING
THE
GAS PRESSURESPAGE.
28
6.3.1 REMO
VING THE
COMBUSTION CHAMBERPAGE.35
6.3.2
R
EMOVING THE BURNER
AND
JETSPAGE.
6.3.3 REMOVING THE
ELECTR
ODES
PAGE.35
6.3.4 REMOVING THE MAIN HEAT
EXCHANGERPAGE.36
6.3.5 REMOVING THE AIR
PRESSURE SWITCHPAGE.37
6.3.6 REMO
6.4
VING THE
A
CCESS TO THE GAS VALVEPAGE.
FANPAGE.38
6.4.1 REMOVING THE SPARK
GENERATORPAGE.38
6.4.2 R
6.5ACCESS
EMOVING THE GAS VALVEPAGE.39
TO THEWATER
CIRCUITPAGE.39
6.5.1 REMOVING THE D.H.W. (SECONDARY)
EXCHANGERPAGE.39
6.5.2 REMOVING THE PUMP
PRESSURE SWITCHPAGE.40
6.5.3 REMO
VING THE
SAFETY
VALVEPAGE.41
6.5.4 R
EMOVING THE AUTOMATIC
AIR VENTPAGE.41
6.5.5 REMOVING THE PUMPPAGE. 42
6.5.6 REMOVING THE PRESSURE
GAUGEPAGE. 43
6.5.7 REMOVING THE EXPANSION
VESSELPAGE.43
6.5.8 REMOVING THE OVERHEAT
THERMOSTATPAGE.44
6.5.9 REMOVING THE C.H.
TEMPERATURE PROBE (N.T.C.)PAGE. 44
6.5.10 REMOVING THE D.H.W.
TEMPERATURE SENSOR
(N.T.C.)PAGE.45
R
6.5.11
VING THE DIVERTOR
EMO
VALVE ACTUATORPAGE.45
6.5.12 REMOVING THE D.H.W.
W
LO
SWITCHPAGE.
F
THE
6.6
A
CCESS
O
T
CONTROLSYSTEMPAGE.
6.6.1 CHECKING THE FUSESPAGE.46
6.6.2
6.6.3
R
R
EMO
EMO
VING THE
VING
.C.B.P
P
THE
TIME CLOCKPAGE.
A
GE
35
38
45
46
47
.
48
5. MAINTENANCEPAGE.32
33
6. SERVICING INSTRUCTIONSPA
6.1R
6.2T
6.2.1 REMOVING THE FRONT
6.2.2 R
6.2.3 R
6.3ACCESS TO THE COMBUSTION
2
EPLACEMENT OF PARTSPA
O GAIN GENERAL ACCESSPAGE.33
PANELPAGE.33
EMOVING THE SEALED
CHAMBER FRONT PANELPAGE.
EMOVING THE SIDE
PANELSPAGE.34
CHAMBERPAGE.
GE
GE
.
.
33
34
35
7. FAULT FINDINGPAGE.49
T
F
7.1
UL
A
FINDING GUIDE
(FLOW-CHARTS)PAGE.49
52
8. EXPLODED VIEWPA
GE
.
8.1SHORT SPARES LISTPAGE.53
9. TECHNICAL INFORMATIONPAGE.54
1. GENERAL INFORMATION
This manual is an integral and essential part of the
product.
be consulted b
Please carefully read the instructions and notices about
the unit contained in this manual, as they provide
important information regarding the safe installation, use
and maintenance of the product.
For operating instructions please consult the separate
Users Manual.
It should be kept with the appliance so that it can
y the user and our authorised personnel.
1.1GENERAL INSTRUCTIONS
Read the instructions and recommendations in these
Installation and Servicing Instructions carefully to ensure
proper installation, use and maintenance of the
appliance.
eep this manual in a safe place.You may need it for your
K
own reference while Servicing Technicians or your
installer may need to consult it in the future.
This is a combined appliance for the production of central
heating (C.H.) and domestic hot water (D.H.W.) and is
intended for use in domestic properties.
This appliance
which it is designed.
The manufacturer declines all liability for damage caused
by improper or negligent use.
No asbestos or other hazardous materials have been
used in the fabrication of this product.
Before connecting the appliance, check that the
information shown on the data plate and the table in
section 9 comply with the electric, water and gas mains of
the property.You will find the data plate on the reverse of
the control panel.
The gas with which this appliance operates is also shown
on the data label inside the boiler casing.
must be used only for the purpose for
Do not install this appliance in a damp environment or
close to equipment which spray water or other liquids.
Do not place objects on the appliance.
Do not allow children or inexperienced persons to use
the appliance without supervision.
If you smell gas in the room,
switches, use the telephone or any other object which
.
might cause spar
Open doors and windows immediately to ventilate the
room.
Shut the gas mains tap (at or adjacent to the gas meter)
or the valve of the gas cylinder and call your Gas Supplier
immediately
If you are going away for a long period of time, remember
to shut the mains gas tap or the gas cylinder valve.
Always disconnect the appliance either by unplugging it
from the mains or turning off the mains switch before
cleaning the appliance or carrying out maintenance.
In the case of faults or failure, switch off the appliance
and turn off the gas tap. Do not tamper with the
appliance.
For repairs, call your local Authorised Servicing Agent
and request the use of original spare parts. For inguarantee repairs contact MTS (GB) Limited.
ks
.
do not turn on or off light
3
26
25
24
23
22
21
20
1918171615
14
13
12
11
10
9
8
7
6
5
4
3
2
1
27
1.2OVERALL VIEW
LEGEND:
FIG. 1.0
1.
2.Air Intake for Twin Pipe Flue Systems
3.Fan
4.Combustion Chamber Hood
5.
6.Overheat Thermostat
7.
8.Combustion Chamber Insulation Panel
9.Burner
10.Detection Electrode
11.Ignition Electrodes
12.Motorised Valve
13.Domestic Hot Water Temperature Probe
14.Drain Valve
15.Low Water Pressure Switch
16.Secondary Heat Exchanger
17.Gas Valve
18.Spark Generator
19.Cold Water Inlet Filter
20.Pump (w/auto air vent)
21.Safety Valve
22.D.H.W. Flow Switch
23.Combustion Chamber
24.Central Heating Return Temperature Probe
25.Expansion Vessel
26.Air Pressure Switch
27.Combustion Analysis Test Point
Flue Manifold
Main Heat Exchanger
Central Heating Flow Temperature Probe
4
2.INSTALLATION
2.1REFERENCE ST
The technical inf
herein belo
w are intended for the installer / Servicing
ANDARDS
ormation and instructions provided
Technician so that the unit may be installed and serviced
correctly and safely.
The appliance is only suitab
le for installation in GB and IE
and should be installed in accordance with the rules in
force
In GB, the installation must be carried out by a CORGI
registered installer. It must be carried out in accordance
with the relevant requirements of the Gas Safety
(Installation and Use) Regulations, the appropriate
Building Regulations either The Building Regulations
(Scotland), Building Regulations (Northern Ireland), The
Water Fittings Regulations or Water byelaws in Scotland.
, it is necessary to comply with the Water Supply
In GB
(Water Fittings) Regulations 1999 (or for Scotland, The
Water Byelaws 2000, Scotland).
The microGENUS II is an Approved Product under the
Water Regulations.
To comply with the Water Regulations your attention is
drawn to The Water Regulations guide, published by the
Water Regulations Advisory Service (WRAS) gives full
details of the requirements. In IE, the requirements given
in the current edition of I.S.813 and the current Building
Regulations must be followed.
Installation should also comply with the follo
wing British
Standard Codes of Practice
In the Republic of Ireland in accordance with the current
BS 7593:1992Treatment of water in domestic hot water
central heating systems
BS 5546:1990Installation of hot water supplies for
domestic purposes
BS 5440-1:2000 Flues
BS 5440-2:2000 Air supply
BS 5449:1990Forced circulation hot water systems
BS 6798:1987Installation of gas fired hot water boilers
of rated input not exceeding 60kW
BS 6891:1989Installation of low pressure gas pipe up to
28mm
BS 7671:2001IEE wiring regulations
BS 4814:1990Specification for expansion vessels
BS 5482:1994Installation of L.P.G.
2.2SITING THE APPLIANCE
The appliance ma
area, although par
requirements of, in GB the current I.E.E. Wiring
Regulations, in Scotland, the electrical provisions of the
Building Regulations applicable in Scotland, and for IE
the current edition of I.S. 813 and the current ETCI rules.
With respect to the installation of the combined appliance
in a room containing a bath or shower, the location of the
boiler in a room containing a bath or shower should only
be considered if there is no alternative.
Where a room-sealed appliance is installed in a room
containing a bath or shower reference must be made
to the relevant requirements. In GB this is the current
I.E.E. Wiring Regulations and Building Regulations, in
IE reference should be made to the current edition of
I.S. 813 and the current ETCI rules.
If the boiler is to be fitted into a building of timber frame
construction, reference should be made to the current
edition of the Institution of Gas Engineers Publication
IGE/UP/7 (Gas Installations in Timber Framed Housing).
The location must permit adequate space for servicing
and air circulation around the appliance as indicated in
Section 2.4.
The location must permit the provision of an adequate
flue and termination.
For unusual locations special procedures may be
necessary.
BS 6798-1987 gives detailed guidance on this aspect.
A compartment used to enclose the appliance must be
designed specifically for this purpose. No specific
entilation requirements are needed for the installation
v
within a cupboard.
This appliance is not suitable for outdoor installation.
The type C appliances (in which the combustion
circuit, air vent intake and combustion chamber are
air-tight with respect to the room in which the
appliance is installed) can be installed in any type of
room.
Secondary ventilation is not required with this boiler. The
boiler m
per
ust be installed on a solid, non-comb
manent wall to prevent access from the rear.
y be installed in any room or indoor
ticular attention is drawn to the
le
ustib
,
Building Regulations, the current ETCI rules for electrical
installation and with the following Codes of Practice:
I.S. 813Domestic Gas Installations
5
FIG. 2.1
2.3OVERALL DIMENSIONS
LEGEND:
A = Central Heating Flow (3/4”)
B = Domestic Hot
C = Gas Inlet (3/4”)
D = Domestic Cold
E = Central Heating Return (3/4”)
Water Outlet (1/2”)
Water Inlet (1/2”)
FIG. 2.2
2.4CLEARANCES
In order to allow access to the interior of the boiler for
maintenance purposes, the boiler must be installed in
compliance with the minimum clearances indicated in
FIG. 2.2
2.5 MOUNTING THE APPLIANCE
After removing the boiler from its packaging, remove the
template from the separate box containing the connection
kit.
O
:
TE
N
Pay particular attention to any test water that
may spill from the appliance.
Place the template in the position the appliance is to be
mounted and after ensur
to drill the holes for the hanging bracket, connection kit
and flue pipe(s) NB: F
flue installation please ref
CONNECTION. (If the appliance is to be fitted on a wall of
combustible material, the wall must be protected by a
sheet of fireproof mater
If the appliance is to be fitted into a timber framed
building, guidance should be sought from the Institute of
Gas Engineers document R
ill the w
2.5.1.
the connections kit, position the hanging bracket and
6
Dr
ing it is hanging squarely
ther information relating to the
or fur
er to Section 2.9
ial).
EF: IGE/UP/7.
all and plug using those supplied with
, use it
F
LUE
secure with the wall screws supplied, assemble the
connection kit and secure to the w
recommended that a spirit level be used to position the
appliance to ensure that it is perf
2.5.2.Position the appliance on the hanging bracket
and connect the connection kit to the boiler connections
(see also Sections 2.7 Gas Connections, 2.8 Water
Connections & FIG. 2.3).
all.
NOTE: It is highly
ectly level.
2.6ELECTRICAL CONNECTION
For safety purposes, have a competent person carefully
check the electrical system in the property, as the
manufacturer will not be held liable for damage caused by
the failure to earth the appliance properly or by anomalies
in the supply of power. Make sure that the residential
electrical system is adequate for the maximum power
absorbed by the unit, which is indicated on the rating
plate. In addition, check that the section of cabling is
appropriate for the power absorbed by the boiler.
The boiler operates with alternating current, as indicated
in the Technical Information table in Section 10, where the
maximum absorbed power is also indicated. Make sure
that the connections for the neutral and live wires
correspond to the indications in the diagram. The
appliance electrical connections are situated on the
reverse of the control panel.
.
FIG. 2.3
IMPORTANT!
In the event that the power supply cord must be changed,
replace it with one with the same specifications.
Note: The diagrams for the electrical system are indicated
in section 2.13.
Warning, this appliance must be earthed.
External wiring to the appliance must be correctly earthed
and polar
person in accordance with rele
in GB reference should be made to the current I.E.E.
Regulations and applicable local regulations, in Scotland,
the electr
applicable in Scotland, and for IE the current edition of
I.S. 813 and the current ETCI rules.
The appliance is supplied with a fly-lead already
connected, this must be connected to a 220-240v supply
fused at 3A and must facilitate complete electrical
isolation of the appliance, by the use of a fused double
pole isolator ha
in all poles or alternatively, by
three pin plug and unswitched shuttered socket outlet
both complying with BS 1363.
The point of connection to the Electricity supply must be
readily accessible and adjacent to the appliance unless
the appliance is installed in a bathroom when this must
be sited outside the bathroom (see section 2.2).
ised and must be carried out by a competent
ant regulations and r
v
ical pro
visions of the Building Regulations
ving a contact separation of at least 3 mm
means of a 3 A fused
ules,
Should external controls be required, the design of the
y a
en b
nal electr
xter
e
competent person, see Section 2.13 f
mation.
or
inf
ical circuits should be under
tak
or fur
ther
7
2.7GAS CONNECTION
The local gas region contractor connects the gas meter to
the ser
vice pipe.
If the gas supply for the boiler serves other appliances
ensure that an adequate supply is available both to the
boiler and the other appliances when they are in use at
the same time.
Pipe work must be of an adequate size. Pipes of a
smaller siz
e than the boiler inlet connection should not be
used.
The gas installation should also be in accordance with the
relevant standards. In GB this is BS 6891, and in IE this
is the current edition of I.S. 813.
2.8WATER CONNECTIONS
VIEW OF THE BOILER CONNECTIONS
LEGEND:
A = Central Heating Flow
B = Domestic Hot Water Outlet
G
A
B
C
D
E
E
F
C = Gas Inlet
D = Domestic Cold Water Inlet
E = Central Heating Return
F = Safety Valve Outlet
G = Drain valve
FIG. 2.4
F
IG. 2.5
KT007A
CENTRAL HEATING
Detailed recommendations are given in BS 6798:1987
and BS 5449-1:1990, the following notes are given for
general guidance.
PIPE WORK:
Copper tubing to BS EN 1057:1996 is recommended for
water pipes
. Jointing should be either with capillary
soldered or compression fittings.
Where possible pipes should have a gradient to ensure
air is carr
ied natur
ally to air release points and w
ater
flows naturally to drain taps.
The appliance has a built-in automatic air release valve,
however it should be ensured as far as possible that the
appliance heat exchanger is not a natural
collecting point for air.
Except where providing useful heat, pipes should be
insulated to pre
vent heat loss and avoid freezing.
Particular attention should be paid to pipes passing
through ventilated spaces in roofs and under floors.
ASS
BY-P
:
The appliance includes an automatic by-pass valve,
which protects the main heat exchanger in case of
reduced or interrupted water circulation through the
heating system, due to the closing of thermostatic valves
or radiators.
SYSTEM DESIGN:
This boiler is suitable only for sealed systems.
DRAIN COCKS:
These must be located in accessible positions to permit
the draining of the whole system and should be fitted at
all low points. The taps must be at least 15mm nominal
e and manufactured in accordance with BS 2870:1980.
siz
SAFETY VALVEDISCHARGE:
8
The discharge should terminate facing downward on the
xterior of the building in a position where discharging
e
(possibly boiling water & steam) will not create danger or
uisance, but in an easily visible position, and not cause
n
damage to electrical components and wiring.
The discharge must not be over an entrance or a window
or any other type of public access.
AIR RELEASE POINTS:
These m
ust be fitted at all high points where air naturally
collects and must be sited to facilitate complete filling of
the system.
The appliance has an integral sealed expansion vessel to
accommodate the increase of water volume when the
system is heated.
It can accept up to 7 litres (1.3 gal) of expansion water. If
the heating circuit has an unusually high water content,
an additional sealed expansion vessel must be fitted, for
GB refer to BS 7074 part 1 and for IE, refer to the current
edition of I.S. 813.
MAINS WATER FEED - CENTRAL HEATING:
A method for initially filling the heating system is supplied
with the connection kit. The filling loop is connected
between the cold water inlet and the central heating flow
connections, and incorporates a non-return valve. To
operate the filling loop, it is necessary to open both
quarter turn handles, once the required pressure has
been achieved, close both handles and disconnect the
hose in accordance with water byelaws. N
OTE: The
installer should ensure that there are no leaks as frequent
filling of the heating system can lead to premature scaling
of the main exchanger and failure of hydraulic
components.
DOMESTIC WATER:
The domestic water must be in accordance with the
relevant recommendation of BS 5546:1990. Copper
tubing to BS EN 1057:1996 is recommended for water
carrying pipe work and must be used for pipe work
carrying drinking water, a scale reducer should also be
used to reduce the risk of scale forming in the domestic
side of the heat exchanger.
VR003A
RESIDUAL PUMP HEAD,DESIGNED TEMP RISE 20oC
28/31 kW
24 kW
9
2.9FLUE CONNECTIONS
FLUE SYSTEM
The pro
made in GB this must be in accordance with BS 5440-1,
or IE recommendations are given in the current edition of
f
I.S.813.
The appliance must be installed so that the flue terminal is
exposed to outside air.
The terminal must not discharge into another room or
space such as an outhouse or lean-to.
It is important that the position of the terminal allows a
free passage of air across it at all times
The terminal should be located with due regard for the
damage or discolouration that might occur on buildings in
the vicinity and consideration must be given to adjacent
boundaries.
In cold or humid weather water vapour may condense on
leaving the flue terminal. The effect of such “pluming”
must be considered.
If the terminal is less than 2 metres above a balcony,
above ground or above a flat roof to which people have
access, then a suitable terminal guard must be fitted.
When ordering a terminal guard, quote the appliance
model number.
A suitable terminal guard is available from:
vision for satisfactory flue termination must be
.
FIG. 2.6
FU010D
NOTE:THE FLUE MUST NOT TERMINATE IN A PLACE LIKELY TO
CAUSE NUISANCE
TOWER FLUE COMPONENTS
Morley Road
Tonbridge
Kent TN9 1RA
The minimum acceptable spacing from the terminal to
obstructions and ventilation openings are specified in FIG.
2.6.
T
ERMINALPOSITION
A -Directly above or below an openable window
or other opening
B -Below gutters, solid pipes or drain pipes75
es200
v
w ea
Belo
-
C
Below balconies or car-port roof200
-
D
E -From vertical drain pipes and soil pipes150
F -From internal or external corners300
G -Above ground or balcony level300
From a surface facing a terminal600
-
H
I -From a terminal facing a terminal1200
J -From an opening in the car port
(e.g. door, window) into dwelling1200
Vertically from a terminal in the same wall1500
-
K
L -Horizontally from a terminal in the same wall300
izontally from an opening window300
Hor
-
M
N -Fixed by vertical flue terminal
mm
300
10
Ø 60/100 mm
FITTING
(F
THECOAXIAL
or Telscopic, Vertical Flue and Twin Pipe Instructions
1X ALUMINIUM FLUE PIPE INCLUDING TERMINAL (1 METRE 60/100)
2X FLUE CLAMPS
8X SCREWS
2X FOAM SEALS
Once the boiler has been positioned on the wall, insert
the elbow into the socket
required position.
NOTE: It is possible to rotate the elbow
(FIG 2.7) and rotate to the
360oon its vertical axis.
FIG. 2.7
FU002A/Rev.1
Using the flue clamps, seals and screws supplied
(FIGS
2.7 AND 2.9) secure the elbow to the boiler.
The 1 metre horizontal flue kit (705958) supplied is
le for an exact
suitab
X dimension of 823mm, and the
750mm horizontal flue kit (705785) is suitable for an exact
X dimension of 573mm.
Measure the distance from the face of the external wall to
the face of the flue elbow (X - FIG 2.7), add 22 mm to this
measurement, you now have the total length of flue
required (including the terminal), this figure must now be
subtracted from 860mm, you now have the total amount
to be cut from the plain end of the flue.
Cut the flue to the required length ensuring that the
distance between the inner and the outer flue is
maintained (FIG 2.10).
FIG 2.8
FIG 2.9
11
FIG 2.10
e.g. X = 508mm + 22mm = 530mm
860 - 530 = 330mm (Length to be cut from the plain
end of the flue).
Once cut to the required length, ensure that the flue is
free from burrs and reassemble the flue. If fitting the flue
from inside of the building attach the grey outer wall seal
to the flue terminal and push through the flue through the
, once the wall seal has passed through the hole, pull
hole
the flue back until the seal is flush with the wall.
natively, the flue can be installed from outside of the
Alter
building, the grey outer seal being fitted last.
WARNING
THE FLUE IS LONGER THAN
IF
RESTRICTOR (FIG. 2.11). IF THE FLUE IS BETWEEN 0-1
METRE
The telscopic flue is suitable for use with an exact
minimum X dimension of 270mm and an exact maximum
X dimension 470mm.
IMPORTANT!!
Do not extend the telescopic flue to an X dimension
of more than 470mm. If longer lengths are required
use extension pieces as necessary. Under no
circumstances must the flue be cut.
The wall must then be made good around the flue
(ensuring a fall of 1ois maintained away from the boiler to
the flue terminal).
Once made good, place the inner (white) wall seal over
the flue and push up to the w
all, secure the flue to the
elbow by using the clamp supplied.
FIG 2.12
12
or each additional 90oelbo
F
w 1 metre m
ust be removed
from the total flue length (maximum 4 metres including
the 1st elbow). For each additional 45oelbow 0.5 metre
must be subtracted from the total flue length (
The vertical flue kit is supplied with a specially designed
weather proof terminal fitted, it can be used either with a
flat roof or a pitched roof. (see FIGS 2.12, 2.13).
FIG 2.13
Vertical flue kits maximum and minimum useable
The
lengths with both flat and pitched roof flashings are
indicated in (Figs.
2.14 & 2.15).
Before proceeding to fit the flue, ensure that the
maximum flue length has not been exceeded and that all
ws and bends have been taken into consideration,
elbo
the maxim
o
90
um flue length is 5 metres, for each additional
elbow 1 metre must be subtracted from the total flue
length, and for each 45o0.5 metres must be subtracted
from the total flue length (the offset and height of 2 x
45ocan be seen in Fig. 2.16).
Mark the position of the flue hole in the ceiling and/or roof
(see FIG. 2.14 for distance from wall to the centre of
the flue).
NOTE:MAX LENGTH = a+a+a +
b+b = a+a+a+0.5+0.5
COMBINED LENGTH NOT
TO EXCEED 5m
Cut a 125mm diameter hole through the ceiling and/or
roof and fit the flashing plate to the roof.
Should it be necessary to cut the flue DO NOT cut the
outer white air inlet tube, cut the aluminium exhaust flue
6mm longer than the outer white air tube when used at
minimum length.
DO NOT cut more that 250mm from the
inner aluminium exhaust flue.
To connect the vertical flue kit directly to the boiler, place
the adaptor
(see FIG 2.12) (supplied with vertical flue kit)
onto the exhaust manifold and secure with the clamp, the
vertical flue kit must then be inserted through the roof
flashing, this will ensure that the correct clearance above
the roof is provided as the terminal is a fixed height.
Should extensions be required, they are available in 1
(Part No. 705786), 500mm (Part No. 705790) and
metre
160mm lengths (Part No. 705812), they must be
connected directly to the boiler and secured with the
clamp supplied before connecting the adaptor to allow the
vertical flue kit to be fitted. In the event that extension
pieces need to be shortened, they
the male end and it m
ust be ensured that the distance
between the inner and outer flue are kept
must only be cut at
(Fig. 2.10).
FIG 2.14
When utilising the vertical flue system, action must be
taken to ensure that the flue is supported adequately to
prevent the weight being transferred to the appliance flue
connection.
When the flue passes through a ceiling or wooden floor,
there must be an air gap of 25mm between any part of
the flue system and any combustible material. The use of
a ceiling plate will facilitate this. Also when the flue
passes from one room to another a fire stop must be
fitted to prevent the passage of smoke or fire, irrespective
of the structural material through which the flue passes.
FITTING
Where it is not possib
distance per
be used b
and using the aper
the comb
THE
FLUE (TWIN PIPE)
minate the flue within the
, the twin flue pipe can
mitted f
le to ter
or coaxial flues
y fitting a special adaptor to the flue connector
ture f
ustion chamber
or the air intak
.
e located on top of
13
Considerations necessary for twin flue installation;
It is most important to avoid any possible condense
ormation entering the appliance.
f
FIG 2.15
WARNING
F THE FLUE IS LONGER THAN 1 METRE, REMOVE THE
I
RESTRICTOR
METRE THE RESTRICTOR REMAINS FITTED.
(FIG. 2.11). IF THE FLUE IS BETWEEN 0-1
SEE TABLE 2.1 (PAGE 17).
According to Table 2.1
(Page 17) decide if condensation
will form within the flue. If yes, there are two options;
Where condense will form but can be negated with
1)
insulated flue, install insulated the flue with a fall of
5mm in every metre away from the boiler.
2) The exhaust flue will have a fall of 3oback to the boiler
and a suitable trap will be fitted on the exhaust as
close to the boiler as possible, condense will then be
suitably disposed of.
Where the flue runs through cold spots, i.e. loft areas,
condense is likely to be formed, therefore a fall back to
the boiler and a trap is required.
Always ensure that the flue is adequately supported,
avoiding low points. (MTS supply suitable clamps as Part
No. 705778).
To utilise the air intake it is necessary to:
Remove the ‘knockout’ of the air intake by cutting it with a
suitable knife
(FIG. 2.17).
Insert the elbow/flue pipe into the air intake until it stops.
Minimum offset distance when using 2x 45obends
The twin flue pipes can be fitted with or without additional
elbows and need no clamps, simply ensure that the red oring is inserted in the female end of the flue pipe and
push the extension piece fully into the previous section of
flue pipe or elbow, check that the o-ring is not dislodged
when assembling the flue.
Twin pipe can also be converted back to Coaxial flue to
enable vertical termination with a coaxial kit by using the
pipe br
idge (Twin - Coaxial Adaptor - Part No. 705767).
When running the twin flue pipe vertically, a condense
trap must always be used on the exhaust pipe.
It is not recommended that the pipe bridge for horizontal
termination, however in the unlikely event that this proves
to be a necessity it is extremely important that the entire
o
flue has a fall of 3
back to the boiler, is suitably trapped
and where the 60mm inner flue of the concentric terminal
connects to the pipe bridge, this point must be adequately
sealed with silicone sealant to avoid condense leakage at
this point.
NOTE: Vertical twin flue installations must have a trap on
the exhaust. MTS supply a suitable condense
art No. 705774 and recommend that this be
ap P
tr
m
used in the e
condense
.
ent that the flue ma
v
y not f
or
FIG 2.16
14
When siting the twin flue pipe
, the air intak
e and e
xhaust
terminals must terminate on the same wall, the centres of
the terminal centres
must be a minimum of 280 mm apart
FIG 2.17
IMPORTANT!!!
WHERE CONDENSE WILL FORM WITHIN THE FLUE SYSTEM,
ENSURE THERE IS A FALL BACK TO THE BOILER OF 3OAND A
SUITABLE TRAP IS FITTED AS CLOSE TO THE BOILER AS
POSSIBLE
. MTS SUPPLY A SUITABLE COLLECTOR PART NO.
705798 OR A CONDENSATE DISCHARGE T WITH BUILT IN TRAP
PART NO. 705774.
and the air intake must not be sited above the exhaust
ter
minal
(ref
er to F
2.21).The air intake pipe can be
IG.
run horizontally, however, the terminal and the final 1
metre of flue m
ust be installed with a fall away from the
boiler to avoid rain ingress.
It is also strongly recommended that the air intake pipe
un be constructed of insulated pipe to prevent condense
r
orming on the outside of the tube.
f
The maximum permissible flue length for twin flue is
dependent on the type of run used.
For flue runs with the intake and exhaust pipes under the
same atmospheric conditions (T
YPE 4) the maximum
length is 60 metres (28kW), 46 metres (28kW) and 47
metres (31kW). For runs with the terminals under
different atmospheric conditions (TYPE 5) the exhaust
terminal must extend 0.5 metres above the ridge of the
roof (this is not obligatory if the exhaust and air intake
pipes are located on the same side of the building). For
YPE 5 also, the maximum permissible combined length is
T
59 metres (24kW), 48 metres (28kW) and 42 metres
(31kW). Flue types are shown on Page 16 (FIG. 2.20).
The maximum length is reached by combining the total
lengths of both the air intake and exhaust pipes.
Therefore a maximum length of 40 metres for example,
will allow a flue run of 20 metres for the air intake and 20
metres for the exhaust pipes, also for each 90oelbow 1.3
metres must be subtracted from the total length and for
each 45oelbow 1 metre must be subtracted from the total
flue length.
Some of the acceptable flue configurations are detailed
on page 16
(FIG. 2.20).
FIG 2.18
For further information relating to flue runs not illustrated,
please contact the Technical Department on 01494
539579.
FIG 2.19
15
EXHAUST
AIR INTAKE
AIR INTAKE
AIR INTAKE MUST NOT BE
FITTED ABOVE THE EXHAUST
TYPE 1
TYPE 2
TYPE 3
TYPE 4
TYPE 5
NOTE: DRAWINGS ARE INDICATIVE OF FLUEING OPTIONS ONLY.
FIG. 2.20
FIG 2.21
16
NOTE:WHERE 280MM CENTRES CANNOT BE ACHEIVED,THE EXHAUST TERMINAL
CAN BE EXTENDED TO PROTRUDE FROM THE WALL BY 300MM.
TABLE 2.1
24 MFFI
Coaxial
Systems
ø 60/100
Twin Pipe
Systems
ø 80/80
28 MFFI
Coaxial
Systems
ø 60/100
Exhaust
Type
TYPE 1
TYPE 2
YPE 3
T
Exhaust
Type
TYPE 4
T
YPE 5
Exhaust
Type
TYPE 1
TYPE 2
TYPE 3
Exhaust
Type
Use the
ø 41 mm
Restrictor
Between
500 mm - 1 m
Use the
ø 41 mm
Restrictor
Between
1m - 20 m
Between
1m - 25 m
Use the
ø 43 mm
Restrictor
Between
500 mm - 1 m
Use the
ø 43 mm
Restrictor
Do not use the
Restrictor
een 1m - 4m
Betw
Between 1m - 5m
Do not use the
Restrictor
Between
20 m - 60 m
Between
25 m - 59 m
Do not use the
Restrictor
Between 1m - 4m
Between 1m - 5m
Do not use the
Restrictor
Maximum
Flue
Length
4 m
5 m
Maximum
Flue
Length
60 m
59 m
Maximum
Flue
Length
4 m
5 m
Maximum
Flue
Length
Risk of Condensation Forming
T APPLICABLE
NO
NOT APPLICABLE
Risk of Condensation Forming
Standard Twin Pipe
After:
3 m
with a
ø 41 mm
restrictor
3 m
with a
ø 41 mm
restrictor
4 m
without a
ø 41 mm
restrictor
4 m
without a
ø 41 mm
restrictor
Insulated Twin Pipe
After:
3 m
with a
ø 41 mm
restrictor
3 m
with a
ø 41 mm
restrictor
Risk of Condensation Forming
NOT APPLICABLE
NOT APPLICABLE
Risk of Condensation Forming With:
Standard Twin Pipe
After:
Insulated Twin Pipe
After:
With:
4 m
without a
ø 41 mm
restrictor
4 m
without a
ø 41 mm
restrictor
Twin Pipe
Systems
ø 80/80
31 MFFI
Coaxial
Systems
ø 60/100
Twin Pipe
Systems
ø 80/80
TYPE 4
T
YPE 5
Exhaust
Type
TYPE 1
T
YPE 2
YPE 3
T
Exhaust
Type
TYPE 4
YPE 5
T
Between
1m - 14 m
Between
1m - 21 m
Use the
ø 42 mm
Restrictor
Between
500 mm - 1 m
Use the
ø 42 mm
Restrictor
Between
1m - 4 m
Between
1m - 11.5 m
Between
14 m - 46 m
Between
21 m - 48 m
Do not use the
Restrictor
Between 1m - 4m
Between 1m - 5m
Do not use the
Restrictor
Between
4 m - 47 m
Between
11.5 m - 42 m
46 m
48 m
Maximum
Flue
Length
4 m
5 m
Maximum
Flue
Length
47 m
42 m
4 m
with a
ø 43 mm
restrictor
4 m
with a
ø 43 mm
ictor
restr
5 m
without a
ø 43 mm
restrictor
5 m
without a
ø 43 mm
restrictor
4 m
with a
ø 43 mm
restrictor
4 m
with a
ø 43 mm
restrictor
Risk of Condensation Forming
NOT APPLICABLE
NOT APPLICABLE
Risk of Condensation Forming With:
Standar
2 m
with a
ø 42 mm
ictor
restr
7.4 m
with a
ø 42 mm
ictor
restr
Twin Pipe
d
After:
without a
ø 42 mm
restrictor
without a
ø 42 mm
restrictor
7.5 m
7.4 m
Insulated
2 m
with a
ø 42 mm
restrictor
7.4 m
with a
ø 42 mm
restrictor
T
After:
5 m
without a
ø 43 mm
restrictor
5 m
without a
ø 43 mm
restrictor
win Pipe
7,5 m
without a
ø 42 mm
restrictor
7,4 m
without a
ø 42 mm
ictor
restr
Where there is no risk of condense forming (and,
*
therefore no requirement for a condense collector),
ensure a minimum fall of 5mm per metre a
way from
the appliance.
NOTE:UNDER SOME CIRCUMSTANCES, CONDENSE MAY FORM AT
TERMINAL
THE
PAID WITH REGARD TO POSSIBLE CONDENSE DRIPPING
TERMINAL
THE
OM
FR
, SPECIAL
.
UST
EXHA
TTENTION
A
MUST
BE
17
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.