Ariston microGENUS II 24 MFFI, microGENUS II 28 MFFI, microGENUS II 31 MFFI User Manual

microGENUS II 24 MFFI
1
2
3
4
5
6
1
2
3
4
5
6
I
I
E
C
microGENUS II 28 MFFI microGENUS II 31 MFFI
Installation and Servicing Instructions
Type C Boilers
G.C.N: 47-116-25 (24kW) G.C.N: 47-116-26 (28kW) G.C.N: 47-116-27 (31kW)
LEAVE THESE INSTRUCTIONS WITH THE END-USER
Country of destination: GB, IE

TABLE OF CONTENTS

1. GENERAL INFORMATION PA
1.1 G
ENERAL INSTRUCTIONS PAGE.3
GE
.3
1.2 OVERALL VIEW PAGE.4
2. INSTALLATION PAGE.4
2.1
R
EFERENCE STANDARDS PAGE.
2.2 SITING THE APPLIANCE PAGE.5
2.3 OVERALL DIMENSIONS PAGE.6
2.4 CLEARANCES PAGE.6
2.5 MOUNTING THE APPLIANCE PAGE.6
2.6 E
LECTRICAL CONNECTION PAGE.7
2.7 GAS CONNECTION PAGE.8
2.8
WA
CONNECTION PAGE.
TER
2.9 FLUE CONNECTION PAGE.10
2.10 C
2.11 D
2.12 R
2.13 ROOM THERMOST
ONTROL PANEL PAGE.18 IGITAL DISPLAY AND FAULT CODES PAGE.18 EMOVING THE FRONT PANEL PAGE.19
AT
CONNECTION PAGE.19
2.14 ELECTRICAL/SYSTEM DIAGRAMS PAGE.20
2.15 WATER CIRCUIT DIAGRAM PAGE.21
5
8
3. COMMISSIONING PAGE.22
3.1 I
3.2 INITIAL STA RT-UP PAGE.23
3.3 OPERATIONAL ADJUSTMENTS PAGE. 23
3.4 C
3.5 PRODUCT OF COMBUSTION
3.6 BOILER SAFETY SYSTEMS PAGE.24
3.7 DRAINING THE SYSTEM PAGE.26
3.8 COMPLETION PAGE.26
3.9
3.10 INSTRUCTING THE END USER PAGE.26
NITIAL PREPARATION PAGE. 22
OMBUSTION ANALYSIS PAGE.24
DISCHARGE MONITORING PAGE. 24
O
PERA
TIONAL
CHECKS PAGE.
26
4. GAS ADJUSTMENTS PAGE.27
4.1 CHANGING THE TYPE OF GAS PAGE.27
4.2
A
DJUSTING
THE
GAS PRESSURES PAGE.
28
6.3.1 REMO
VING THE
COMBUSTION CHAMBER PAGE.35
6.3.2
R
EMOVING THE BURNER
AND
JETS PAGE.
6.3.3 REMOVING THE ELECTR
ODES
PAGE.35
6.3.4 REMOVING THE MAIN HEAT EXCHANGER PAGE.36
6.3.5 REMOVING THE AIR PRESSURE SWITCH PAGE.37
6.3.6 REMO
6.4
VING THE
A
CCESS TO THE GAS VALVE PAGE.
FAN PAGE.38
6.4.1 REMOVING THE SPARK GENERATOR PAGE.38
6.4.2 R
6.5 ACCESS
EMOVING THE GAS VALVE PAGE.39
TO THEWATER
CIRCUIT PAGE.39
6.5.1 REMOVING THE D.H.W. (SECONDARY)
EXCHANGER PAGE.39
6.5.2 REMOVING THE PUMP PRESSURE SWITCH PAGE.40
6.5.3 REMO
VING THE
SAFETY
VALVE PAGE.41
6.5.4 R
EMOVING THE AUTOMATIC
AIR VENT PAGE.41
6.5.5 REMOVING THE PUMP PAGE. 42
6.5.6 REMOVING THE PRESSURE GAUGE PAGE. 43
6.5.7 REMOVING THE EXPANSION VESSEL PAGE.43
6.5.8 REMOVING THE OVERHEAT THERMOSTAT PAGE.44
6.5.9 REMOVING THE C.H. TEMPERATURE PROBE (N.T.C.) PAGE. 44
6.5.10 REMOVING THE D.H.W. TEMPERATURE SENSOR (N.T.C.) PAGE.45 R
6.5.11
VING THE DIVERTOR
EMO
VALVE ACTUATOR PAGE.45
6.5.12 REMOVING THE D.H.W.
W
LO
SWITCH PAGE.
F
THE
6.6
A
CCESS
O
T
CONTROLSYSTEM PAGE.
6.6.1 CHECKING THE FUSES PAGE.46
6.6.2
6.6.3
R R
EMO EMO
VING THE VING
.C.B. P
P
THE
TIME CLOCK PAGE.
A
GE
35
38
45 46
47
.
48
5. MAINTENANCE PAGE.32
33
6. SERVICING INSTRUCTIONS PA
6.1 R
6.2 T
6.2.1 REMOVING THE FRONT
6.2.2 R
6.2.3 R
6.3 ACCESS TO THE COMBUSTION
2
EPLACEMENT OF PARTS PA
O GAIN GENERAL ACCESS PAGE.33
PANEL PAGE.33
EMOVING THE SEALED
CHAMBER FRONT PANEL PAGE.
EMOVING THE SIDE
PANELS PAGE.34
CHAMBER PAGE.
GE
GE
.
.
33
34
35
7. FAULT FINDING PAGE.49
T
F
7.1
UL
A
FINDING GUIDE
(FLOW-CHARTS)PAGE.49
52
8. EXPLODED VIEW PA
GE
.
8.1 SHORT SPARES LIST PAGE.53
9. TECHNICAL INFORMATION PAGE.54

1. GENERAL INFORMATION

This manual is an integral and essential part of the product. be consulted b
Please carefully read the instructions and notices about the unit contained in this manual, as they provide important information regarding the safe installation, use and maintenance of the product.
For operating instructions please consult the separate Users Manual.
It should be kept with the appliance so that it can
y the user and our authorised personnel.

1.1 GENERAL INSTRUCTIONS

Read the instructions and recommendations in these Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance.
eep this manual in a safe place.You may need it for your
K own reference while Servicing Technicians or your installer may need to consult it in the future.
This is a combined appliance for the production of central heating (C.H.) and domestic hot water (D.H.W.) and is intended for use in domestic properties.
This appliance which it is designed. The manufacturer declines all liability for damage caused by improper or negligent use.
No asbestos or other hazardous materials have been used in the fabrication of this product.
Before connecting the appliance, check that the information shown on the data plate and the table in section 9 comply with the electric, water and gas mains of the property.You will find the data plate on the reverse of the control panel. The gas with which this appliance operates is also shown on the data label inside the boiler casing.
must be used only for the purpose for
Do not install this appliance in a damp environment or
close to equipment which spray water or other liquids.
Do not place objects on the appliance. Do not allow children or inexperienced persons to use
the appliance without supervision. If you smell gas in the room,
switches, use the telephone or any other object which
.
might cause spar Open doors and windows immediately to ventilate the room. Shut the gas mains tap (at or adjacent to the gas meter) or the valve of the gas cylinder and call your Gas Supplier immediately If you are going away for a long period of time, remember to shut the mains gas tap or the gas cylinder valve.
Always disconnect the appliance either by unplugging it from the mains or turning off the mains switch before cleaning the appliance or carrying out maintenance.
In the case of faults or failure, switch off the appliance and turn off the gas tap. Do not tamper with the appliance. For repairs, call your local Authorised Servicing Agent and request the use of original spare parts. For in­guarantee repairs contact MTS (GB) Limited.
ks
.
do not turn on or off light
3
26
25
24 23
22 21
20
1918171615
14
13
12
11
10
9
8
7
6
5
4
3
2
1
27

1.2 OVERALL VIEW

LEGEND:
FIG. 1.0
1.
2. Air Intake for Twin Pipe Flue Systems
3. Fan
4. Combustion Chamber Hood
5.
6. Overheat Thermostat
7.
8. Combustion Chamber Insulation Panel
9. Burner
10. Detection Electrode
11. Ignition Electrodes
12. Motorised Valve
13. Domestic Hot Water Temperature Probe
14. Drain Valve
15. Low Water Pressure Switch
16. Secondary Heat Exchanger
17. Gas Valve
18. Spark Generator
19. Cold Water Inlet Filter
20. Pump (w/auto air vent)
21. Safety Valve
22. D.H.W. Flow Switch
23. Combustion Chamber
24. Central Heating Return Temperature Probe
25. Expansion Vessel
26. Air Pressure Switch
27. Combustion Analysis Test Point
Flue Manifold
Main Heat Exchanger
Central Heating Flow Temperature Probe
4

2. INSTALLATION

2.1 REFERENCE ST
The technical inf herein belo
w are intended for the installer / Servicing
ANDARDS
ormation and instructions provided
Technician so that the unit may be installed and serviced correctly and safely.
The appliance is only suitab
le for installation in GB and IE and should be installed in accordance with the rules in force
In GB, the installation must be carried out by a CORGI registered installer. It must be carried out in accordance with the relevant requirements of the Gas Safety (Installation and Use) Regulations, the appropriate Building Regulations either The Building Regulations (Scotland), Building Regulations (Northern Ireland), The Water Fittings Regulations or Water byelaws in Scotland.
, it is necessary to comply with the Water Supply
In GB (Water Fittings) Regulations 1999 (or for Scotland, The Water Byelaws 2000, Scotland).
The microGENUS II is an Approved Product under the Water Regulations.
To comply with the Water Regulations your attention is drawn to The Water Regulations guide, published by the Water Regulations Advisory Service (WRAS) gives full details of the requirements. In IE, the requirements given in the current edition of I.S.813 and the current Building Regulations must be followed.
Installation should also comply with the follo
wing British Standard Codes of Practice In the Republic of Ireland in accordance with the current
BS 7593:1992 Treatment of water in domestic hot water
central heating systems
BS 5546:1990 Installation of hot water supplies for
domestic purposes BS 5440-1:2000 Flues BS 5440-2:2000 Air supply BS 5449:1990 Forced circulation hot water systems BS 6798:1987 Installation of gas fired hot water boilers
of rated input not exceeding 60kW BS 6891:1989 Installation of low pressure gas pipe up to
28mm BS 7671:2001 IEE wiring regulations BS 4814:1990 Specification for expansion vessels BS 5482:1994 Installation of L.P.G.

2.2 SITING THE APPLIANCE

The appliance ma area, although par requirements of, in GB the current I.E.E. Wiring Regulations, in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, and for IE the current edition of I.S. 813 and the current ETCI rules. With respect to the installation of the combined appliance in a room containing a bath or shower, the location of the boiler in a room containing a bath or shower should only be considered if there is no alternative.
Where a room-sealed appliance is installed in a room containing a bath or shower reference must be made to the relevant requirements. In GB this is the current I.E.E. Wiring Regulations and Building Regulations, in IE reference should be made to the current edition of I.S. 813 and the current ETCI rules.
If the boiler is to be fitted into a building of timber frame construction, reference should be made to the current edition of the Institution of Gas Engineers Publication IGE/UP/7 (Gas Installations in Timber Framed Housing).
The location must permit adequate space for servicing and air circulation around the appliance as indicated in Section 2.4. The location must permit the provision of an adequate flue and termination. For unusual locations special procedures may be necessary. BS 6798-1987 gives detailed guidance on this aspect. A compartment used to enclose the appliance must be designed specifically for this purpose. No specific
entilation requirements are needed for the installation
v within a cupboard. This appliance is not suitable for outdoor installation.
The type C appliances (in which the combustion circuit, air vent intake and combustion chamber are air-tight with respect to the room in which the appliance is installed) can be installed in any type of room.
Secondary ventilation is not required with this boiler. The boiler m per
ust be installed on a solid, non-comb
manent wall to prevent access from the rear.
y be installed in any room or indoor
ticular attention is drawn to the
le
ustib
,
Building Regulations, the current ETCI rules for electrical installation and with the following Codes of Practice:
I.S. 813 Domestic Gas Installations
5
FIG. 2.1

2.3 OVERALL DIMENSIONS

LEGEND:
A = Central Heating Flow (3/4”) B = Domestic Hot C = Gas Inlet (3/4”) D = Domestic Cold E = Central Heating Return (3/4”)
Water Outlet (1/2”)
Water Inlet (1/2”)
FIG. 2.2

2.4 CLEARANCES

In order to allow access to the interior of the boiler for maintenance purposes, the boiler must be installed in compliance with the minimum clearances indicated in
FIG. 2.2
2.5 MOUNTING THE APPLIANCE
After removing the boiler from its packaging, remove the template from the separate box containing the connection kit.
O
:
TE
N
Pay particular attention to any test water that
may spill from the appliance.
Place the template in the position the appliance is to be mounted and after ensur to drill the holes for the hanging bracket, connection kit and flue pipe(s) NB: F flue installation please ref CONNECTION. (If the appliance is to be fitted on a wall of combustible material, the wall must be protected by a sheet of fireproof mater If the appliance is to be fitted into a timber framed building, guidance should be sought from the Institute of Gas Engineers document R
ill the w
2.5.1. the connections kit, position the hanging bracket and
6
Dr
ing it is hanging squarely
ther information relating to the
or fur
er to Section 2.9
ial).
EF: IGE/UP/7.
all and plug using those supplied with
, use it
F
LUE
secure with the wall screws supplied, assemble the connection kit and secure to the w recommended that a spirit level be used to position the appliance to ensure that it is perf
2.5.2. Position the appliance on the hanging bracket and connect the connection kit to the boiler connections (see also Sections 2.7 Gas Connections, 2.8 Water Connections & FIG. 2.3).
all.
NOTE: It is highly
ectly level.

2.6 ELECTRICAL CONNECTION

For safety purposes, have a competent person carefully check the electrical system in the property, as the manufacturer will not be held liable for damage caused by the failure to earth the appliance properly or by anomalies in the supply of power. Make sure that the residential electrical system is adequate for the maximum power absorbed by the unit, which is indicated on the rating plate. In addition, check that the section of cabling is appropriate for the power absorbed by the boiler.
The boiler operates with alternating current, as indicated in the Technical Information table in Section 10, where the maximum absorbed power is also indicated. Make sure that the connections for the neutral and live wires correspond to the indications in the diagram. The appliance electrical connections are situated on the reverse of the control panel.
.
FIG. 2.3
IMPORTANT!
In the event that the power supply cord must be changed, replace it with one with the same specifications. Note: The diagrams for the electrical system are indicated in section 2.13.
Warning, this appliance must be earthed.
External wiring to the appliance must be correctly earthed and polar person in accordance with rele in GB reference should be made to the current I.E.E. Regulations and applicable local regulations, in Scotland, the electr applicable in Scotland, and for IE the current edition of I.S. 813 and the current ETCI rules. The appliance is supplied with a fly-lead already connected, this must be connected to a 220-240v supply fused at 3A and must facilitate complete electrical isolation of the appliance, by the use of a fused double pole isolator ha in all poles or alternatively, by three pin plug and unswitched shuttered socket outlet both complying with BS 1363. The point of connection to the Electricity supply must be readily accessible and adjacent to the appliance unless the appliance is installed in a bathroom when this must be sited outside the bathroom (see section 2.2).
ised and must be carried out by a competent
ant regulations and r
v
ical pro
visions of the Building Regulations
ving a contact separation of at least 3 mm
means of a 3 A fused
ules,
Should external controls be required, the design of the
y a
en b
nal electr
xter
e competent person, see Section 2.13 f
mation.
or
inf
ical circuits should be under
tak or fur
ther
7

2.7 GAS CONNECTION

The local gas region contractor connects the gas meter to the ser
vice pipe. If the gas supply for the boiler serves other appliances ensure that an adequate supply is available both to the boiler and the other appliances when they are in use at the same time. Pipe work must be of an adequate size. Pipes of a smaller siz
e than the boiler inlet connection should not be used. The gas installation should also be in accordance with the relevant standards. In GB this is BS 6891, and in IE this is the current edition of I.S. 813.

2.8 WATER CONNECTIONS

VIEW OF THE BOILER CONNECTIONS
LEGEND:
A = Central Heating Flow B = Domestic Hot Water Outlet
G
A
B
C
D
E E
F
C = Gas Inlet D = Domestic Cold Water Inlet E = Central Heating Return F = Safety Valve Outlet G = Drain valve
FIG. 2.4
F
IG. 2.5
KT007A
CENTRAL HEATING
Detailed recommendations are given in BS 6798:1987 and BS 5449-1:1990, the following notes are given for general guidance.
PIPE WORK:
Copper tubing to BS EN 1057:1996 is recommended for water pipes
. Jointing should be either with capillary soldered or compression fittings. Where possible pipes should have a gradient to ensure air is carr
ied natur
ally to air release points and w
ater flows naturally to drain taps. The appliance has a built-in automatic air release valve, however it should be ensured as far as possible that the appliance heat exchanger is not a natural collecting point for air. Except where providing useful heat, pipes should be insulated to pre
vent heat loss and avoid freezing. Particular attention should be paid to pipes passing through ventilated spaces in roofs and under floors.
ASS
BY-P
:
The appliance includes an automatic by-pass valve, which protects the main heat exchanger in case of reduced or interrupted water circulation through the heating system, due to the closing of thermostatic valves or radiators.
SYSTEM DESIGN:
This boiler is suitable only for sealed systems.
DRAIN COCKS:
These must be located in accessible positions to permit the draining of the whole system and should be fitted at all low points. The taps must be at least 15mm nominal
e and manufactured in accordance with BS 2870:1980.
siz
SAFETY VALVEDISCHARGE:
8
The discharge should terminate facing downward on the
xterior of the building in a position where discharging
e (possibly boiling water & steam) will not create danger or
uisance, but in an easily visible position, and not cause
n damage to electrical components and wiring. The discharge must not be over an entrance or a window or any other type of public access.
AIR RELEASE POINTS:
These m
ust be fitted at all high points where air naturally collects and must be sited to facilitate complete filling of the system. The appliance has an integral sealed expansion vessel to accommodate the increase of water volume when the system is heated. It can accept up to 7 litres (1.3 gal) of expansion water. If the heating circuit has an unusually high water content, an additional sealed expansion vessel must be fitted, for GB refer to BS 7074 part 1 and for IE, refer to the current edition of I.S. 813.
MAINS WATER FEED - CENTRAL HEATING:
A method for initially filling the heating system is supplied with the connection kit. The filling loop is connected between the cold water inlet and the central heating flow connections, and incorporates a non-return valve. To operate the filling loop, it is necessary to open both quarter turn handles, once the required pressure has been achieved, close both handles and disconnect the hose in accordance with water byelaws. N
OTE: The
installer should ensure that there are no leaks as frequent filling of the heating system can lead to premature scaling of the main exchanger and failure of hydraulic components.
DOMESTIC WATER:
The domestic water must be in accordance with the relevant recommendation of BS 5546:1990. Copper tubing to BS EN 1057:1996 is recommended for water carrying pipe work and must be used for pipe work carrying drinking water, a scale reducer should also be used to reduce the risk of scale forming in the domestic side of the heat exchanger.
VR003A
RESIDUAL PUMP HEAD,DESIGNED TEMP RISE 20oC
28/31 kW
24 kW
9

2.9 FLUE CONNECTIONS

FLUE SYSTEM
The pro made in GB this must be in accordance with BS 5440-1,
or IE recommendations are given in the current edition of
f I.S.813. The appliance must be installed so that the flue terminal is exposed to outside air. The terminal must not discharge into another room or space such as an outhouse or lean-to. It is important that the position of the terminal allows a free passage of air across it at all times The terminal should be located with due regard for the damage or discolouration that might occur on buildings in the vicinity and consideration must be given to adjacent boundaries. In cold or humid weather water vapour may condense on leaving the flue terminal. The effect of such “pluming” must be considered. If the terminal is less than 2 metres above a balcony, above ground or above a flat roof to which people have access, then a suitable terminal guard must be fitted. When ordering a terminal guard, quote the appliance model number. A suitable terminal guard is available from:
vision for satisfactory flue termination must be
.
FIG. 2.6
FU010D
NOTE:THE FLUE MUST NOT TERMINATE IN A PLACE LIKELY TO
CAUSE NUISANCE
TOWER FLUE COMPONENTS Morley Road Tonbridge Kent TN9 1RA
The minimum acceptable spacing from the terminal to obstructions and ventilation openings are specified in FIG.
2.6.
T
ERMINALPOSITION
A - Directly above or below an openable window
or other opening
B - Below gutters, solid pipes or drain pipes 75
es 200
v
w ea
Belo
-
C
Below balconies or car-port roof 200
-
D E - From vertical drain pipes and soil pipes 150 F - From internal or external corners 300 G - Above ground or balcony level 300
From a surface facing a terminal 600
-
H
I - From a terminal facing a terminal 1200
J - From an opening in the car port
(e.g. door, window) into dwelling 1200 Vertically from a terminal in the same wall 1500
-
K L - Horizontally from a terminal in the same wall 300
izontally from an opening window 300
Hor
-
M N - Fixed by vertical flue terminal
mm
300
10
Ø 60/100 mm
FITTING
(F
THECOAXIAL
or Telscopic, Vertical Flue and Twin Pipe Instructions
FLUE (HORIZONTAL)
see page 12)
CONTENTS: 1X SILICONE O-RING (60mm) 1X ELBOW (90O) 2X WALL SEALS (INTERNAL &
E
XTERNAL)
1X ALUMINIUM FLUE PIPE INCLUDING TERMINAL (1 METRE ­60/100) 2X FLUE CLAMPS 8X SCREWS 2X FOAM SEALS
Once the boiler has been positioned on the wall, insert the elbow into the socket required position.
NOTE: It is possible to rotate the elbow
(FIG 2.7) and rotate to the
360oon its vertical axis.
FIG. 2.7
FU002A/Rev.1
Using the flue clamps, seals and screws supplied
(FIGS
2.7 AND 2.9) secure the elbow to the boiler.
The 1 metre horizontal flue kit (705958) supplied is
le for an exact
suitab
X dimension of 823mm, and the
750mm horizontal flue kit (705785) is suitable for an exact X dimension of 573mm.
Measure the distance from the face of the external wall to the face of the flue elbow (X - FIG 2.7), add 22 mm to this measurement, you now have the total length of flue required (including the terminal), this figure must now be subtracted from 860mm, you now have the total amount to be cut from the plain end of the flue.
Cut the flue to the required length ensuring that the distance between the inner and the outer flue is maintained (FIG 2.10).
FIG 2.8
FIG 2.9
11
FIG 2.10
e.g. X = 508mm + 22mm = 530mm
860 - 530 = 330mm (Length to be cut from the plain
end of the flue).
Once cut to the required length, ensure that the flue is free from burrs and reassemble the flue. If fitting the flue from inside of the building attach the grey outer wall seal to the flue terminal and push through the flue through the
, once the wall seal has passed through the hole, pull
hole the flue back until the seal is flush with the wall.
natively, the flue can be installed from outside of the
Alter building, the grey outer seal being fitted last.
WARNING
THE FLUE IS LONGER THAN
IF
RESTRICTOR (FIG. 2.11). IF THE FLUE IS BETWEEN 0-1 METRE
THE RESTRICTOR REMAINS FITTED
1 METRE, REMO
.
VE THE
SEE TABLE 2.1 (PAGE 17).
FIG 2.11
FITTING THE TELESCOPIC FLUE KIT (HORIZONTAL)
CONTENTS: 1X SILICONE O-RING (60
X ELBOW (90
1
O
)
mm)
2X WALL SEALS (INTERNAL &EXTERNAL) 1X ALUMINIUM FLUE PIPE INCLUDING TERMINAL (TELESCOPIC ­60/100) 2X FLUE CLAMPS 8X SCREWS 2X FOAM SEALS
The telscopic flue is suitable for use with an exact minimum X dimension of 270mm and an exact maximum X dimension 470mm.
IMPORTANT!! Do not extend the telescopic flue to an X dimension of more than 470mm. If longer lengths are required use extension pieces as necessary. Under no circumstances must the flue be cut.
The wall must then be made good around the flue (ensuring a fall of 1ois maintained away from the boiler to the flue terminal). Once made good, place the inner (white) wall seal over the flue and push up to the w
all, secure the flue to the
elbow by using the clamp supplied.
FIG 2.12
12
or each additional 90oelbo
F
w 1 metre m
ust be removed from the total flue length (maximum 4 metres including the 1st elbow). For each additional 45oelbow 0.5 metre must be subtracted from the total flue length (
FIG 2.13).
FITTING THE COAXIAL FLUE (VERTICAL)
(For Twin Pipe Instructions see page 13)
CONTENTS: 1X SILICONE O-RING (60mm) 1X ELBOW (90O) 2X WALL SEALS (INTERNAL &EXTERNAL) 1X ALUMINIUM FLUE PIPE INCLUDING TERMINAL (TELESCOPIC ­60/100) 2X FLUE CLAMPS 8X SCREWS 2X FOAM SEALS
The vertical flue kit is supplied with a specially designed weather proof terminal fitted, it can be used either with a flat roof or a pitched roof. (see FIGS 2.12, 2.13).
FIG 2.13
Vertical flue kits maximum and minimum useable
The lengths with both flat and pitched roof flashings are indicated in (Figs.
2.14 & 2.15).
Before proceeding to fit the flue, ensure that the maximum flue length has not been exceeded and that all
ws and bends have been taken into consideration,
elbo the maxim
o
90
um flue length is 5 metres, for each additional
elbow 1 metre must be subtracted from the total flue
length, and for each 45o0.5 metres must be subtracted from the total flue length (the offset and height of 2 x
45ocan be seen in Fig. 2.16).
Mark the position of the flue hole in the ceiling and/or roof
(see FIG. 2.14 for distance from wall to the centre of the flue).
NOTE:MAX LENGTH = a+a+a +
b+b = a+a+a+0.5+0.5 COMBINED LENGTH NOT
TO EXCEED 5m
Cut a 125mm diameter hole through the ceiling and/or roof and fit the flashing plate to the roof. Should it be necessary to cut the flue DO NOT cut the outer white air inlet tube, cut the aluminium exhaust flue 6mm longer than the outer white air tube when used at minimum length.
DO NOT cut more that 250mm from the
inner aluminium exhaust flue.
To connect the vertical flue kit directly to the boiler, place the adaptor
(see FIG 2.12) (supplied with vertical flue kit)
onto the exhaust manifold and secure with the clamp, the vertical flue kit must then be inserted through the roof flashing, this will ensure that the correct clearance above the roof is provided as the terminal is a fixed height.
Should extensions be required, they are available in 1
(Part No. 705786), 500mm (Part No. 705790) and
metre 160mm lengths (Part No. 705812), they must be connected directly to the boiler and secured with the clamp supplied before connecting the adaptor to allow the vertical flue kit to be fitted. In the event that extension pieces need to be shortened, they the male end and it m
ust be ensured that the distance
between the inner and outer flue are kept
must only be cut at
(Fig. 2.10).
FIG 2.14
When utilising the vertical flue system, action must be taken to ensure that the flue is supported adequately to prevent the weight being transferred to the appliance flue connection. When the flue passes through a ceiling or wooden floor, there must be an air gap of 25mm between any part of the flue system and any combustible material. The use of a ceiling plate will facilitate this. Also when the flue passes from one room to another a fire stop must be fitted to prevent the passage of smoke or fire, irrespective of the structural material through which the flue passes.
FITTING
Where it is not possib distance per be used b and using the aper the comb
THE
FLUE (TWIN PIPE)
minate the flue within the
, the twin flue pipe can
mitted f
le to ter
or coaxial flues
y fitting a special adaptor to the flue connector
ture f
ustion chamber
or the air intak
.
e located on top of
13
Considerations necessary for twin flue installation;
It is most important to avoid any possible condense
ormation entering the appliance.
f
FIG 2.15
WARNING
F THE FLUE IS LONGER THAN 1 METRE, REMOVE THE
I
RESTRICTOR METRE THE RESTRICTOR REMAINS FITTED.
(FIG. 2.11). IF THE FLUE IS BETWEEN 0-1
SEE TABLE 2.1 (PAGE 17).
According to Table 2.1
(Page 17) decide if condensation
will form within the flue. If yes, there are two options;
Where condense will form but can be negated with
1)
insulated flue, install insulated the flue with a fall of 5mm in every metre away from the boiler.
2) The exhaust flue will have a fall of 3oback to the boiler
and a suitable trap will be fitted on the exhaust as close to the boiler as possible, condense will then be suitably disposed of.
Where the flue runs through cold spots, i.e. loft areas, condense is likely to be formed, therefore a fall back to the boiler and a trap is required. Always ensure that the flue is adequately supported, avoiding low points. (MTS supply suitable clamps as Part No. 705778).
To utilise the air intake it is necessary to:
Remove the ‘knockout’ of the air intake by cutting it with a suitable knife
(FIG. 2.17).
Insert the elbow/flue pipe into the air intake until it stops.
Minimum offset distance when using 2x 45obends
The twin flue pipes can be fitted with or without additional elbows and need no clamps, simply ensure that the red o­ring is inserted in the female end of the flue pipe and push the extension piece fully into the previous section of flue pipe or elbow, check that the o-ring is not dislodged when assembling the flue.
Twin pipe can also be converted back to Coaxial flue to enable vertical termination with a coaxial kit by using the pipe br
idge (Twin - Coaxial Adaptor - Part No. 705767). When running the twin flue pipe vertically, a condense trap must always be used on the exhaust pipe.
It is not recommended that the pipe bridge for horizontal termination, however in the unlikely event that this proves to be a necessity it is extremely important that the entire
o
flue has a fall of 3
back to the boiler, is suitably trapped and where the 60mm inner flue of the concentric terminal connects to the pipe bridge, this point must be adequately sealed with silicone sealant to avoid condense leakage at this point.
NOTE: Vertical twin flue installations must have a trap on
the exhaust. MTS supply a suitable condense
art No. 705774 and recommend that this be
ap P
tr
m
used in the e condense
.
ent that the flue ma
v
y not f
or
FIG 2.16
14
When siting the twin flue pipe
, the air intak
e and e
xhaust terminals must terminate on the same wall, the centres of the terminal centres
must be a minimum of 280 mm apart
FIG 2.17
IMPORTANT!!! WHERE CONDENSE WILL FORM WITHIN THE FLUE SYSTEM,
ENSURE THERE IS A FALL BACK TO THE BOILER OF 3OAND A SUITABLE TRAP IS FITTED AS CLOSE TO THE BOILER AS POSSIBLE
. MTS SUPPLY A SUITABLE COLLECTOR PART NO. 705798 OR A CONDENSATE DISCHARGE T WITH BUILT IN TRAP PART NO. 705774.
and the air intake must not be sited above the exhaust ter
minal
(ref
er to F
2.21).The air intake pipe can be
IG.
run horizontally, however, the terminal and the final 1 metre of flue m
ust be installed with a fall away from the
boiler to avoid rain ingress.
It is also strongly recommended that the air intake pipe
un be constructed of insulated pipe to prevent condense
r
orming on the outside of the tube.
f
The maximum permissible flue length for twin flue is dependent on the type of run used.
For flue runs with the intake and exhaust pipes under the same atmospheric conditions (T
YPE 4) the maximum
length is 60 metres (28kW), 46 metres (28kW) and 47 metres (31kW). For runs with the terminals under different atmospheric conditions (TYPE 5) the exhaust terminal must extend 0.5 metres above the ridge of the roof (this is not obligatory if the exhaust and air intake pipes are located on the same side of the building). For
YPE 5 also, the maximum permissible combined length is
T 59 metres (24kW), 48 metres (28kW) and 42 metres (31kW). Flue types are shown on Page 16 (FIG. 2.20).
The maximum length is reached by combining the total lengths of both the air intake and exhaust pipes. Therefore a maximum length of 40 metres for example, will allow a flue run of 20 metres for the air intake and 20 metres for the exhaust pipes, also for each 90oelbow 1.3 metres must be subtracted from the total length and for each 45oelbow 1 metre must be subtracted from the total flue length. Some of the acceptable flue configurations are detailed on page 16
(FIG. 2.20).
FIG 2.18
For further information relating to flue runs not illustrated, please contact the Technical Department on 01494
539579.
FIG 2.19
15
EXHAUST
AIR INTAKE
AIR INTAKE
AIR INTAKE MUST NOT BE
FITTED ABOVE THE EXHAUST
TYPE 1
TYPE 2
TYPE 3
TYPE 4
TYPE 5
NOTE: DRAWINGS ARE INDICATIVE OF FLUEING OPTIONS ONLY.
FIG. 2.20
FIG 2.21
16
NOTE:WHERE 280MM CENTRES CANNOT BE ACHEIVED,THE EXHAUST TERMINAL
CAN BE EXTENDED TO PROTRUDE FROM THE WALL BY 300MM.
TABLE 2.1
24 MFFI
Coaxial
Systems
ø 60/100
Twin Pipe
Systems
ø 80/80
28 MFFI
Coaxial
Systems
ø 60/100
Exhaust
Type
TYPE 1 TYPE 2
YPE 3
T
Exhaust
Type
TYPE 4
T
YPE 5
Exhaust
Type
TYPE 1 TYPE 2 TYPE 3
Exhaust
Type
Use the
ø 41 mm
Restrictor
Between
500 mm - 1 m
Use the
ø 41 mm
Restrictor
Between
1m - 20 m
Between
1m - 25 m
Use the
ø 43 mm
Restrictor
Between
500 mm - 1 m
Use the
ø 43 mm
Restrictor
Do not use the
Restrictor
een 1m - 4m
Betw
Between 1m - 5m
Do not use the
Restrictor
Between
20 m - 60 m
Between
25 m - 59 m
Do not use the
Restrictor
Between 1m - 4m
Between 1m - 5m
Do not use the
Restrictor
Maximum
Flue
Length
4 m
5 m
Maximum
Flue
Length
60 m
59 m
Maximum
Flue
Length
4 m
5 m
Maximum
Flue
Length
Risk of Condensation Forming
T APPLICABLE
NO
NOT APPLICABLE
Risk of Condensation Forming
Standard Twin Pipe
After:
3 m
with a
ø 41 mm restrictor
3 m
with a ø 41 mm restrictor
4 m
without a ø 41 mm
restrictor
4 m
without a ø 41 mm restrictor
Insulated Twin Pipe
After:
3 m
with a
ø 41 mm restrictor
3 m
with a ø 41 mm restrictor
Risk of Condensation Forming
NOT APPLICABLE
NOT APPLICABLE
Risk of Condensation Forming With:
Standard Twin Pipe
After:
Insulated Twin Pipe
After:
With:
4 m
without a ø 41 mm
restrictor
4 m
without a ø 41 mm restrictor
Twin Pipe
Systems
ø 80/80
31 MFFI
Coaxial
Systems
ø 60/100
Twin Pipe
Systems
ø 80/80
TYPE 4
T
YPE 5
Exhaust
Type
TYPE 1 T
YPE 2 YPE 3
T
Exhaust
Type
TYPE 4
YPE 5
T
Between
1m - 14 m
Between
1m - 21 m
Use the
ø 42 mm
Restrictor
Between
500 mm - 1 m
Use the
ø 42 mm
Restrictor
Between
1m - 4 m
Between
1m - 11.5 m
Between
14 m - 46 m
Between
21 m - 48 m
Do not use the
Restrictor
Between 1m - 4m
Between 1m - 5m
Do not use the
Restrictor
Between
4 m - 47 m
Between
11.5 m - 42 m
46 m
48 m
Maximum
Flue
Length
4 m
5 m
Maximum
Flue
Length
47 m
42 m
4 m
with a
ø 43 mm restrictor
4 m
with a
ø 43 mm
ictor
restr
5 m
without a ø 43 mm
restrictor
5 m
without a ø 43 mm restrictor
4 m
with a ø 43 mm
restrictor
4 m
with a ø 43 mm restrictor
Risk of Condensation Forming
NOT APPLICABLE
NOT APPLICABLE
Risk of Condensation Forming With:
Standar
2 m
with a
ø 42 mm
ictor
restr
7.4 m
with a
ø 42 mm
ictor
restr
Twin Pipe
d
After:
without a ø 42 mm
restrictor
without a ø 42 mm restrictor
7.5 m
7.4 m
Insulated
2 m
with a ø 42 mm
restrictor
7.4 m
with a ø 42 mm restrictor
T
After:
5 m
without a ø 43 mm
restrictor
5 m
without a ø 43 mm restrictor
win Pipe
7,5 m
without a ø 42 mm
restrictor
7,4 m
without a ø 42 mm
ictor
restr
Where there is no risk of condense forming (and,
*
therefore no requirement for a condense collector), ensure a minimum fall of 5mm per metre a
way from
the appliance.
NOTE:UNDER SOME CIRCUMSTANCES, CONDENSE MAY FORM AT
TERMINAL
THE PAID WITH REGARD TO POSSIBLE CONDENSE DRIPPING
TERMINAL
THE
OM
FR
, SPECIAL
.
UST
EXHA
TTENTION
A
MUST
BE
17
Loading...
+ 39 hidden pages