3.5PRODUCT OF COMBUSTION
DISCHARGE MONITORINGPAGE.32
3.6COMFORT MODEPAGE.32
3.7BOILER SAFETY SYSTEMSPAGE.33
3.8DRAINING THE SYSTEMPAGE.34
3.9COMPLETIONPAGE.35
3.10OPERATIONAL CHECKSPAGE.35
3.11INSTRUCTING THE END USERPAGE.36
31
32
6.2.3 RE
.3A
6
.3.1 R
6
MOVING THESIDEPANELS
CCESS TO THE COMBUSTION CHAMBER PAGE.
EMOVING THE COMBUSTION
PAGE.43
44
CHAMBERPAGE.44
6.3.2 RE
MOVING THEBURNER ANDJETS
PAGE.44
6.3.3 REMOVING THE ELECTRODESPAGE.44
6.3.4 R
EMOVING THE MAIN HEAT EXCHANGERPAGE.45
6.3.5 REMOVING THE AIR PRESSURE SWITCHPAGE.46
6.3.6 REMOVING THE FANPAGE.47
6.3.7 RE
MOVING THEFLUE
SENSORPAGE.
/CO
NDENSATE
47
6.3.8 REMOVING THE RECUPERATORPAGE.48
6.3.9 REMOVING THE RECUPERATOR HOUSING PAGE.49
6.3.10 R
6.4AC
EMOVING THE CONDENSATE TRAPPAGE.49
CESS TO THEGASVALV E
PAGE.50
6.4.1 REMOVING THE SPARK GENERATORPAGE.50
6.4.2 R
EMOVING THE GAS VALVEPAGE.50
6.5ACCESS TO THE WATER CIRCUITPAGE.51
6.5.1 REMOVING THE D.H.W. (SECONDARY)
6.5.2 R
E
XCHANGER
EMOVING THE PUMP PRESSURE
PAGE.51
SWITCHPAGE.52
6.5.3 REMOVING THE SAFETY VALVEPAGE.52
6.5.4 REMOVING THE AUTOMATIC AIR VENTPAGE. 53
6.5.5 REMOVING THE PUMPPAGE. 53
6.5.6 R
6.5.7 R
6.5.8 R
EMO
EMOVING THE EXPANSION VESSELPAGE. 55
EMOVING THE OVERHEAT THERMOSTATPAGE.55
PRESSURE GAUGEPAGE. 54
THE
VING
6.5.9 REMOVING THE C.H. TEMPERATURE
SENSOR (N.T.C.)PAGE.56
6.5.10 REMO
VING
D.H.W.TEMPERA
TURE
THE
SENSOR (N.T.C.)PAGE. 56
6.5.11 REMOVING THE DIVERTER VALVE
ACTUATORPAGE.56
6.5.12 REMOVING THE D.H.W. FLOW
SWITCHPAGE.
57
6.6ACCESS TO THE CONTROL SYSTEMPAGE.57
6.6.1 CHECKING THE FUSESPAGE.57
6.6.2 R
6.6.3
R
EMO
EMO
VING THE
THE
VING
.C.B.P
P
TIME CLOCKPAGE.
58
GE
A
.
59
7.FAULT FINDINGPAGE.60
7.1FAULT FINDING GUIDE (FLOW-CHARTS)PAGE.60
63
8.SHORT SPARE PARTS LISTPA
GE
.
9.TECHNICAL INFORMATIONPAGE.66
GAS ADJUSTMENTS
4.
4.1
4.2
C
HANGING
A
DJUSTING
THE
TYPEOFGASPAGE.
THE
GAS PRESSURESPAGE.
5.MAINTENANCEPA
PAGE.
GE
37
37
37
41
.
6.SERVICING INSTRUCTIONSPAGE.42
6.1REPLACEMENT OF PARTSPAGE.42
6.2TO GAIN GENERAL ACCESSPAGE.42
VING
VING
THE
ONT
FR
THE
SEALED CHAMBER
PANELPAGE.
42
2
R
6.2.1
6.2.2
R
EMO
EMO
FRONT PANELPAGE.43
10. BENCHMARK COMMISSIONING
CHECKLIST
PAGE.68
11. SERVICE INTERVAL RECORDPAGE.69
1. GENERAL INFORMATION
This manual is an integral and essential part of the
roduct. It should be kept with the appliance so that it can
p
e consulted by the user and our authorised personnel.
b
Please carefully read the instructions and notices about
the unit contained in this manual, as they provide
important information regarding the safe installation, use
and maintenance of the product.
For operating instructions please consult the separate End
User Manual.
1.1GENERAL INSTRUCTIONS
Read the instructions and recommendations in these
Installation and Servicing Instructions carefully to ensure
roper installation, use and maintenance of the
p
appliance.
eep this manual in a safe place.You may need it for your
K
own reference while Servicing Technicians or your
installer may need to consult it in the future.
This is a condensing combined appliance for the
production of central heating (C.H.) and domestic hot
water (D.H.W.).
This appliance
The manufacturer declines all liability for damage caused
by improper or negligent use.
No asbestos or other hazardous materials have been
used in the fabrication of this product.
MTS recommends the use of protective clothing when
installing and working on this appliance i.e. gloves.
Before connecting the appliance, check that the
information shown on the data plate and the table in
Section 9 comply with the electric, water and gas mains
of the property.You will find the data plate on the inside of
the left hand casing panel.
The gas with which this appliance operates is also shown
on the label at the bottom of the boiler.
must be used only for domestic use.
Do not install this appliance in a damp environment or
close to equipment which spray water or other liquids.
Do not place objects on the appliance.
Do not allow children or inexperienced persons to use
the appliance without supervision.
If you smell gas in the room, do not turn on or off light
switches, use the telephone or any other object which
might cause spar
Open doors and windows immediately to ventilate the
room.
Shut the gas mains tap (at or adjacent to the gas meter)
or the valve of the gas cylinder and call your Gas Supplier
immediately.
ou are going away for a long period of time, remember
If y
to shut the mains gas tap or the gas cylinder valve.
Always disconnect the appliance either by unplugging it
from the mains or turning off the mains switch before
cleaning the appliance or carrying out maintenance.
In the case of faults or failure, switch off the appliance
and turn off the gas tap. Do not tamper with the
appliance.
For repairs, call your local Authorised Servicing Agent
and request the use of or
guarantee repairs contact MTS (GB) Limited.
ks.
iginal spare par
ts. For in-
3
25
26
27
24
23
22
21
20
1918171615
14
13
12
11
10
9
8
7
6
5
4
3
2
1
28
1.2OVERALL VIEW
FIG. 1.0
LEGEND:
.Flue Manifold
1
2.Air Intake for Twin Pipe Flue Systems
3.Fan
4.Combustion Chamber Hood
.Main Heat Exchanger
5
6.Overheat Thermostat
.Central Heating Flow Temperature Probe
7
8.Combustion Chamber Insulation Panel
9.Burner
10.Detection Electrode
11.Ignition Electrodes
12.Motorised Valve
13.Condensate trap
14.Domestic Hot Water Temperature Probe
15.Low Water Pressure Switch
16.Secondary Heat Exchanger
17.Gas Valve
18.Spark Generator
19.Cold Water Inlet Filter
20.Pump (w/auto air vent)
21.Safety Valve
22.D.H.W. Flow Switch
23.Condensate Trap Tube
24.Combustion Chamber
25.Condensate Sensor
26.Latent Heat Collector
27.Air Pressure Switch
28.Combustion Analysis Test Point
4
2.INSTALLATION
2.1RE
he technical information and instructions provided
T
erein below are intended for the installer / Servicing
h
FERENCESTANDARDS
Technician so that the unit may be installed and serviced
correctly and safely.
n the United Kingdom the installation and initial start up
I
of the boiler must be by a CORGI Registered Installer in
accordance with the installation standards currently in
effect, as well as with any and all local health and safety
standards i.e. CORGI.
In the Republic of Ireland the installation and initial start
up of the appliance must be carried out by a Competent
Person in accordance with the current edition of I.S.813
“Domestic Gas Installations”, the current Building
Regulations, reference should also be made to the
current ETCI rules for electrical installation.
This appliance must be installed by a competent
installer in accordance with current Gas Safety
(installation & use) Regulations.
The installation of this appliance must be in accordance
with the relevant requirements of the Local Building
Regulations, the current I.E.E. Wiring Regulations, the
bylaws of the local water authority, in Scotland, in
accordance with the Building Standards (Scotland)
Regulation and Health and Safety document No. 635
“Electricity at work regulations 1989” and in the Republic
of Ireland with the current edition of I.S. 813, the Local
Building Regulations (IE).
2.2SI
he appliance may be installed in any room or indoor
T
rea, although particular attention is drawn to the
a
TING THEAPPLIANCE
requirements of the current I.E.E. Wiring Regulations, and
in Scotland, the electrical provisions of the Building
Regulations applicable in Scotland, with respect to the
installation of the combined appliance in a room
containing a bath or shower, the location of the boiler in a
room containing a bath or shower should only be
considered if there is no alternative.
Where a room-sealed appliance is installed in a room
containing a bath or shower the appliance and any
electrical switch or appliance control, utilising mains
electricity should be situated so that it cannot be
touched by a person using the bath or shower,
specifically in accordance with current IEE Wiring
Regulations.
The location must permit adequate space for servicing
and air circulation around the appliance as indicated in
Section 2.4.
The location must permit the provision of an adequate
flue and termination.
For unusual locations special procedures may be
necessary.
BS 6798-2000 gives detailed guidance on this aspect.
A compartment used to enclose the appliance must be
designed specifically for this purpose. No specific
ventilation requirements are needed for the installation
within a cupboard.
This appliance is not suitable for outdoor installation.
C.O.S.H.H.
Materials used in the manufacture of this appliance are
non-hazardous and no special precautions are required
when servicing.
Installation should also comply with the following Br
itish
Standard Codes of Practice
BS 7593:1992Treatment of water in domestic hot water
central heating systems
BS 5546:2000Installation of hot water supplies for
domestic purposes
BS 5440-1:2000 Flues
BS 5440-2:2000 Air supply
BS 5449:1990Forced circulation hot water systems
BS 6798:2000Installation of gas fired hot water boilers
of rated input not e
BS 6891:1998Installation of low pressure gas pipe up to
28mm
BS 7671:2001IEE wiring regulations
BS 4814:1990Specification for expansion vessels
BS 5482:1994Installation of L.P.G.
xceeding 70kW
and in the Republic of Ireland in accordance with the
wing Codes of Pr
ollo
f
actice:
The type C appliances (in which the combustion
cuit, air vent intake and combustion chamber are
cir
air-tight with respect to the room in which the
appliance is installed) can be installed in any type of
room.However, as the appliance has many
functioning components, pay particular attention
when siting the appliance in room such as bedrooms
as operating noise may be a nuisance.
Secondary ventilation is not required with this boiler. The
boiler must be installed on a solid, non-combustible,
permanent wall to prevent access from the rear.
I.S.
813
Domestic Gas Installations
5
120
FIG. 2.1
2.3OVERALL DIMENSIONS
GEND
LE
A = Central Heating Flow (3/4” - 22mm Copper Tail)
B = Domestic Hot Water Outlet (1/2” - 15mm Copper Tail)
C
D = Domestic Cold Water Inlet (1/2” - 15mm Copper Tail)
E = Central Heating Return (3/4” - 22mm Copper Tail)
:
= Gas Inlet (3/4” - 15mm Copper Tail)
FIG. 2.2
2.4CLEARANCES
In order to allow access to the interior of the boiler for
maintenance purposes, the boiler must be installed in
compliance with the minimum clearances indicated in
*Clearance for Servicing 25mm if behind a temporary
closure i.e. door.
2.5
After removing the boiler from its packaging, remove the
template from the separate box containing the connection
kit. NOTE: Pay particular attention to any test water that
may spill from the appliance.
M
OUNTING
THE
APPLIANCE
FIG. 2.2
Place the template in the position the appliance is to be
mounted and after ensuring it is hanging squarely, use it
to mark the holes for the hanging bracket, connection kit
and flue pipe(s) NB: For further information relating to the
flue installation please refer to Section 2.9 FLUE
CONNECTION. (If the appliance is to be fitted on a wall of
combustible material, the wall must be protected by a
sheet of fireproof material).
If the appliance is to be fitted into a timber fr
uilding, guidance should be sought from the Institute of
b
6
Gas Engineers document
R
EF:
IGE/UP/7.
amed
2.5.1.Drill the wall and plug using those supplied with
85 mm
220 mm
he connections kit, position the hanging bracket and
t
secure with the wall bolts supplied, assemble the
onnection kit and secure to the wall.
c
NOTE: I
t is highly
recommended that a spirit level be used to position the
appliance to ensure that it is perfectly level.
.5.2.Position the appliance on the hanging bracket
2
nd connect the connection kit to the boiler connections.
a
(see also Sections 2.7 Gas Connections, 2.8 Water
Connections & F
I
. 2.3).
G
FIG. 2.3
2.6EL
ECTRICALCONNECTION
For safety purposes, have a competent person carefully
check the electrical system in the property, as the
manufacturer will not be held liable for damage caused by
the failure to earth the appliance properly or by anomalies
in the supply of power. Make sure that the residential
electrical system is adequate for the maximum power
absorbed by the unit, which is indicated on the rating
plate. In addition, check that the section of cabling is
appropriate for the power absorbed by the boiler.
The boiler operates with alternating current, as indicated
in the Technical Information table in Section 9, where the
maximum absorbed power is also indicated. Ensure that
the connections for the live, neutral and earth wires
correspond with the indications in the diagram (Fig. 2.4).
The appliance electrical connections are situated on the
PCB, see Section 2.17
TANT
IMPOR
!
In the event that the power supply cord must be changed,
replace it with one with the same specifications.
Note: The diagrams for the electrical system are indicated
in Section 2.17.
FIG. 2.4
Warning, this appliance must be earthed.
ing to the appliance must be carried out by a
nal wir
Exter
competent person and be in accordance with the current
I.E.E. Regulations and applicable local regulations.
The appliance is supplied with a fly-lead already
connected, this must be connected to a 240v supply
fused at 3A and must facilitate complete electrical
isolation of the appliance, by the use of a fused double
pole isolator having a contact separation of at least 3 mm
in all poles or alternatively, by means of a 3 A fused
three pin plug and unswitched, shuttered socket outlet
both complying with BS 1363.
The point of connection to the Electricity supply must be
readily accessible and adjacent to the appliance unless
the appliance is installed in a bathroom when this must
be sited outside the bathroom (see Section 2.2).
Should external controls be required, the design of the
external electrical circuits should be undertaken by a
competent person, see Section 2.13 f
mation.
or
inf
or fur
ther
7
2.7GAS CONNECTION
The local gas region contractor connects the gas meter to
he service pipe.
t
If the gas supply for the boiler serves other appliances
nsure that an adequate supply is available both to the
e
boiler and the other appliances when they are in use at
the same time.
Pipe work must be of an adequate size. Pipes of a
maller size than the boiler inlet connection should not be
s
sed.
u
2.8WA
F
FIG. 2.5
TERCONNECTIONS
G
C
A
B
VIEW OF THE BOILER CONNECTIONS
LEGEND:
A = Central Heating Flow
B = Domestic Hot Water Outlet
C = Gas Inlet
D = Domestic Cold Water Inlet
E = Central Heating Return
F = Condensate discharge
G = Drain valve
H = Safety Valve Outlet
CENTRAL HEATING
D
E
H
Detailed recommendations are given in BS 6798:2000
and BS 5449-1:1990, the following notes are given for
general guidance.
PIPE WORK:
Copper tubing to BS EN 1057:1996 is recommended for
water pipes. Jointing should be either with capillary
soldered or compression fittings.
Where possible pipes should have a gradient to ensure
air is carried naturally to air release points and water
flows naturally to drain taps.
The appliance has a b
uilt-in automatic air release v
alve,
however it should be ensured as far as possible that the
appliance heat exchanger is not a natur
al collecting point
for air.
Except where providing useful heat, pipes should be
insulated to pre
ent heat loss and a
v
void freezing.
Particular attention should be paid to pipes passing
through ventilated spaces in roofs and under floors.
F
IG. 2.6
8
KT007A
BY-PASS:
The appliance includes an automatic by-pass valve,
which protects the main heat e
xchanger in case of
reduced or interrupted water circulation through the
heating system, due to the closing of thermostatic valves
or radiators.
SYSTEM DESIGN:
This boiler is suitable only for sealed systems.
DRAIN COCKS:
These must be located in accessible positions to permit
the draining of the whole system and should be fitted at
all low points. The taps must be at least 15mm nominal
size and manufactured in accordance with BS 2870:1980.
SA
FETYVALV EDISCHARGE
he discharge should terminate facing downward on the
T
:
exterior of the building in a position where discharging
possibly boiling water & steam) will not create danger or
(
nuisance, but in an easily visible position, and not cause
damage to electrical components and wiring.
The discharge must not be over an entrance or a window
r any other type of public access.
o
AIRRE
LEASEPOINTS
:
These must be fitted at all high points where air naturally
collects and must be sited to facilitate complete filling of
the system.
The appliance has an integral sealed expansion vessel to
accommodate the increase of water volume when the
system is heated.
It can accept up to 6 litres (1.3 gal) of expansion water. If
the heating circuit has an unusually high water content,
calculate the total expansion and add an additional
sealed expansion vessel with adequate capacity. This
should be located on the return pipe work as close as
possible to the pump inlet.
MAINS WATER FEED - CENTRAL HEATING:
A method for initially filling the heating system is supplied
with the connection kit. The filling loop is connected
between the cold water inlet and the central heating flow
connections, and incorporates a non-return valve. To
operate the filling loop, it is necessary to open both
quarter turn handles, once the required pressure has
been achieved, close both handles and disconnect the
hose in accordance with water byelaws. N
OTE: The
installer should ensure that there are no leaks as frequent
filling of the heating system can lead to premature scaling
of the main exchanger and failure of hydraulic
components.
DO
MESTICWATER
he domestic water must be in accordance with the
T
:
relevant recommendation of BS 5546:1990. Copper
ubing to BS EN 1057:1996 is recommended for water
t
carrying pipe work and must be used for pipe work
carrying drinking water, a scale reducer should also be
used to reduce the risk of scale forming in the domestic
ide of the heat exchanger.
s
WATER TREATMENT
The boiler is equipped with a secondary heat exchanger
(recuperator) made from stainless steel as well as the
copper main heat exchanger.
The detailed recommendations for water treatment are
given in BS 7593:1992 (Treatment of water in domestic
hot water central heating systems); the following notes
are given for general guidance;
- If the boiler is installed on an existing system, any
unsuitable additives must be removed;
- Under no circumstances should the boiler be fired
before the system has been thoroughly flushed; the
flushing procedure must be in line with BS7593:1992.
We highly recommend the use of a flushing detergent
appropriate for the metals used in the circuit. These
include cleansers produced by Fernox and
BetzDearborn, whose function is to dissolve any
foreign matter that may be in the system;
In hard water areas or where large quantities of water
are in the system the treatment of the water to prevent
premature scaling of the main heat exchanger is
necessary.
The formation of scale strongly compromises the
efficiency of the thermic exchange because small
areas of scale cause a high increase of the
temperature of the metallic walls and therefore add to
the thermal stress of the heat exchanger.
Demineralised water is more aggressive so in this
VR003A
RESIDUALHEAD
OF
THE
BOILER D T 20°C
FIG. 2.7
9
1
2
3
4
5
6
1
2
3
4
5
6
EC
II
situation it is necessary to treat the water with an
ppropriate corrosion inhibitor.
a
- Any treatment of water by additives in the system for
rost protection or for corrosion inhibition has to be
f
absolutely suitable for all the metals used in the circuit.
The use of a corrosion inhibitor in the system such as
Fernox MB-1, BetzDeaborn Sentinel X100 or Fernox
ystem Inhibitor is recommended to prevent corrosion
S
sludge) damaging the boiler and systems;
(
- If anti-freeze substances are to be used in the system,
check carefully that they are compatible with the metals
used in the circuit.
MTS suggests the use of suitable anti-freeze products
such as Fernox ALPHI 11, which will prevent rust and
incrustation taking place.
Periodically check the pH of the water/anti-freeze
mixture of the boiler circuit and replace it when the
amount measured is out of the range stipulated by the
manufacturer ( 7 < pH < 8).
DO NOT MIX DIFFERENT TYPES OF ANTI-FREEZE
- In under-floor systems, the use of plastic pipes without
protection against penetration of oxygen through the
walls can cause corrosion of the systems metal parts
(metal piping, boiler, etc), through the formation of
oxides and bacterial agents.
To prevent this problem, it is necessary to use pipes
with an “oxygen-proof barrier”, in accordance with
standards DIN 4726/4729
. If pipes of this kind are
not used, keep the system separate by installing
heat exchanger
s of those with a specific system
water treatment.
IMPORTANT
Failure to carry out the water treatment procedure will
invalidate the appliance warranty.
2.8.1 CONDENSATE REMIOVAL
CONDENSATEDISCHARGE:
1. Internal termination of condensate drainage pipe to
internal stack
A flexible hose connected to the bottom of the boiler
should be inser
I
NOTE:
THE CONDENSATE HOSE OUT OF THE BOTTOM OF THE BOILER
T
The condensate discharge hose from the boiler m
ted into a tundish (not supplied).
O REMOVE THE CASING TO PULL
T
MA
BE
Y
NECESSAR
Y
.
ust
have a continuous fall of at least 2.5° and must be
connected to a visible tundish and inserted by at least
50mm into a suitab
le acid resistant pipe with a nominal
diameter of 32mm e.g. plastic waste pipe or overflow
pipe. The condensate discharge pipe must have a
continuous fall and preferably be installed and terminated
ent freezing.
within the b
uilding to pre
v
The discharge pipe must be terminated in one of the
following positions, allowing for a safe discharge:
10
i) Connecting in to an internal soil stack (at least 450 mm
above the invert of the stack). A trap giving a water
seal of at least 75 mm m
ust be incorporated into the
pipe run, there also must be an air break upstream of
the trap i.e. tundish.
2. External termination of condensate drainage pipe via
internal discharge branch (e.g. sink waste) and condensate
siphon
3. External termination of condensate drainage pipe via
internal discharge branch (e.g. sink waste - proprietary fitting).
ii) Connecting into the waste system of the building such
s a washing machine or sink trap. The connection
a
must be upstream of the washing machine/sink (If the
onnection is down stream of the waste trap then an
c
additional trap giving a minimum water seal of 75 mm
and an air break must be incorporated in the pipe run,
as above.
ii)Terminating into a gully, below the grid level but above
i
the water level.
iv)Into a soakway.
NOTE: If any condensate pipe work is to be installed
externally, then it should be kept to a minimum and be
insulated with a waterproof insulation and have a
continuous fall.
Some examples of the type of condensate drains can
be found in this section.
4. External termination of condensate drainage pipe via
condensate siphon
11
2.9.CONNECTING THE FLUE
4
E
E
IMPORTANT!!
BEFORE CONNECTING THE FLUE, ENSURE THAT 1 LITRE OF
WATER HAS BEEN POURED INTO THE EXHAUST CONNECTION TO
F
FILL THE CONDENSATE TRAP
E
MPTY THERE IS A TEMPORARY RISK OF FLUE GASSES
ESCAPING INTO THE ROOM.
2.8).
(
IG.
SHOULD THE TRAP BE
FIG. 2.8
FLUE SYSTEM
The provision for satisfactory flue termination must be made
as described in BS 5440-1.
The appliance must be installed so that the flue terminal is
exposed to outdoor air.
The terminal must not discharge into another room or space
such as an outhouse or lean-to.
It is important that the position of the terminal allows a free
passage of air across it at all times.
The terminal should be located with due regard for the
damage or discolouration that might occur on buildings in the
vicinity, it must also be located in a place not likely to cause
nuisance.
In cold or humid weather water vapour may condense on
leaving the flue terminal.
The effect of such “steaming” must be considered.
If the terminal is 2.1 metres above a balcony, above ground
or above a flat roof to which people have access, then a
suitable stainless steel terminal guard must be fitted.
The minimum acceptable spacing from the terminal to
obstructions and ventilation openings are specified in Fig.
2.9.
FIG. 2.9
Ø 60/100 mm
TERMINAL POSITIONmm
A - Directly below an open window or other opening300
B - Below gutters, solid pipes or drain pipes75
C - Below eaves200
D - From vertical drain pipes and soil pipes75
E - From internal or external corners300
F - Above ground on a public walkway or patio2100
G - From a surface facing a terminal2500
H - From a terminal facing a terminal
I - Vertically from a terminal in the same wall1500
J - Horizontally from a terminal in the same wall300
K - Horizontally from an opening window 300
L - Fixed by vertical flue terminal
2500
Fig. 2.10
12
Warning
118
The exhaust gas ducts must not be in contact with or close to
inflammable material and must not pass through building
structures or walls made of inflammable material.
When replacing an old appliance, the flue system must be
changed.
Important
Ensure that the flue is not blocked.
Ensure that the flue is supported and
assembled in accordance with these
instructions.
Installation without extension
Installation with extension
2.9.1 FITTING THE COAXIAL FLUE
(Ø 60 / 100 HORIZONTAL)
SEE PAGE 19 FOR MAX AND MIN FLUE RUNS
Level
Fig. 2.11
Level
Fig. 2.12
PART NO: 3318073
CONTENTS:
X SILICONE O-RING (60mm)
1
X ELBOW (90
1
2X WALL SEALS (INTERNAL & EXTERNAL)
1X FLUE PIPE INCLUDING TERMINAL (1 METRE - 60/100)
2
X FLUE CLAMPS
4X SCREWS
2x Seals
O
)
Once the boiler has been positioned on the wall, insert
the elbo
w into the sock
position. NOTE:
It is possible to rotate the elbow 360
et and rotate to the required
o
on
its vertical axis.
Using the flue clamps, seals and screws supplied (
Fig
2.13) secure the elbow to the boiler.
The 1 metre horizontal flue kit (3318073) supplied is
suitable for an exact X dimension of 823mm.
Measure the distance from the face of the external wall
to the face of the flue elbow (X - Fig 2.10), this figure
must now be subtracted from 815mm, you now have
the total amount to be cut from the plain end of the flue.
Draw a circle around the outer flue and cut the flue to
the required length taking care not to cut the inner flue,
next cut the inner flue ensuring that the length between
the inner and outer flue is maintained. (Fig 2.13).
.g.
e
X = 555mm
823-555 = 268mm (Length to be cut from the plain
end of the flue).
13
Seal
Clamp
Screws
Once cut to the required length, ensure that the flue is
ree from burrs and reassemble the flue. If fitting the
f
flue from inside of the building attach the grey outer
all seal to the flue terminal and push the flue through
w
the hole, once the wall seal has passed through the
hole, pull the flue back into the elbow (ensuring that the
flue seal is not dislodged) until the external wall seal is
lush with the wall, and that the flue is securely located
f
nto the elbow, finally secure the flue to the elbow with
i
the clamp provided. Alternatively, the flue can be
installed from outside of the building, the grey outer
seal being fitted last.
Fig. 2.13
2.9.2 FITTING THE 5” FLUE
(Ø 80 / 125 HORIZONTAL/VERTICAL)
Should the flue require extending, the flue connections are
push fit, however, one flue bracket should be used to
secure each metre of flue.
Fig. 2.14
14
Once the boiler has been positioned on the w
necessary to insert the
Ø80/125 adaptor (FIG. 2.14)
all, it is
raised horizontal and vertical flue runs into the boiler flue
et (not supplied with flue kit - Par
sock
Push the adaptor onto the boilers flue connection, g
the seals then add e
xtensions or elbo
t No 3318095
ws as required,
).
rease
secure the adaptor, using the clamp and screws provided.
o fit e
T
xtensions or elbo
ws it is first necessar
y to ensure
that the lip seal is fitted correctly into the inner flue, once
verified, it is simply necessary to push them together, no
clamps are necessary to secure the flue components.
efore proceeding to fit the flue, ensure that the
B
maximum flue length has not been exceeded (See the
ables on Page 19) and that all elbows and bends have
t
been taken into consideration, the maximum flue length
is 10 metres, for each additional 90oelbow 1 metre
must be subtracted from the total flue length, and for
ach 45
e
lue length
f
o
.5 metres must be subtracted from the total
0
the height of the vertical adaptor and a
(
45obend can be seen in Fig. 2.15 and a 90obend
(raised horziontal only) in Fig. 2.16).
NOTE: DO NOT CUT THE VERTICAL FLUE KIT.
2.9.3. FITTING
(Ø 60 / 100 VERTICAL)
Fig. 2.17
THECOAXIAL
FLUE
Fig. 2.15
Fig. 2.16
NOTE:SEE PAGE 19 FOR MAXIMUM AND MINIMUM FLUE
RUNS.
PART NO: 33108080 (BLACK) / 3318081 (RED)
ONTENTS:
C
1X SILICONE O-RING (60mm)
1X CONICAL ADAPTOR (60/100mm)
1
X VERTICAL FLUE KIT (80/125mm)
The vertical flue kit is supplied with a specially
designed w
either with a flat roof or a pitched roof.
Vertical flue kits useable lengths with the pitched
The
roof flashings are indicated in
Before proceeding to fit the flue, ensure that the
maximum flue length has not been exceeded (See
the tables on Page 19) and that all elbows and bends
have been taken into consideration, the maximum
flue length is 4 metres, for each additional 90oelbow
1 metre must be subtracted from the total flue length,
and for each 45o0.5 metres must be subtracted from
the total flue length (the height of the verticaladaptor and a 45obend can be seen in Fig. 2.18).
k the position of the flue hole in the ceiling and/or
Mar
eather proof terminal fitted, it can be used
Fig. 2.17.
15
Fig. 2.18
roof (see Fig. 2.16 for distance from the wall to the centre
f the flue).
o
ut a 120mm diameter hole through the ceiling and/or
C
roof and fit the flashing plate to the roof.
DO NOT cut the vertical flue kit.
o connect the vertical flue kit directly to the boiler, place
T
the vertical starter kit (Part No. 3318079) (see Fig. 2.17)
onto the exhaust manifold and secure with the clamp, fit
the vertical adaptor onto the vertical starter kit (note: there
is no need to use a clamp to secure this as it is a push fit
connection), the vertical flue kit must then be inserted
through the roof flashing, this will ensure that the correct
clearance above the roof is provided as the terminal is a
fixed height.
Should extensions be required, they are available in 1
metre
(Part No. 3318077), 500mm (Part No. 3318078)
and 160mm lengths, they must be connected directly to
the vertical starter kit before connecting the adaptor to
allow the vertical flue kit to be fitted. In the event that
extension pieces need to be shortened, they
must only
be cut at the male end and it must be ensured that the
inner and outer flue remain flush.
2.9.4. FITTING THE TWIN PIPE (Ø80 / 80)
When utilising the vertical flue system, action must be
taken to ensure that the flue is supported adequately to
prevent the weight being transferred to the appliance flue
connection by using 1 flue bracket per extension.
When the flue passes through a ceiling or wooden floor,
there must be an air gap of 25mm between any part of the
flue system and any combustible material. The use of a
ceiling plate will facilitate this. Also when the flue passes
from one room to another a fire stop must be fitted to
prevent the passage of smoke or fire, irrespective of the
structural material through which the flue passes.
S
NOTE:
EE
PA GE
19 FOR
MAXIMUM AND MINIMUM FLUE RUNS
.
Where it is not possible to terminate the flue within the
distance permitted for coaxial flues, the twin flue pipe can
be used by fitting a special adaptor to the flue connector
and using the aperture for the air intake located on top of
the combustion chamber.
Always ensure that the flue is adequately supported, using
one flue bracket per extension and avoiding low points.
(MTS supply suitable clamps as Part No. 705778).
Fig. 2.18A
16
o utilise the e
T
xhaust manifold it is necessary to connect
the adaptor (Part No: 3318017) to the exhaust manifold
and secure with the clamp (see FIG. 2.18A), add elbows or
extensions as required.
To utilise the air intake it is necessary to:
Remove the ‘knockout’ of the air intake by cutting it with a
suitable knife (FIG. 2.18B).
Insert the elbow/flue pipe into the air intake until it stops.
The twin flue pipes can be fitted with or without additional
lbows and need no clamps, simply ensure that the red o-
e
ring is inserted in the female end of the flue pipe and push
he extension piece fully into the previous section of flue pipe
t
or elbow, check that the o-ring is not dislodged when
assembling the flue.
he twin flue pipes can be fitted with or without additional
T
lbows and need no clamps, simply ensure that the red o-
e
ring is inserted in the female end of the flue pipe and push
the extension piece fully into the previous section of flue
pipe or elbow, check that the o-ring is not dislodged when
assembling the flue (greasing the seal will aid assembly).
Twin pipe can also be converted back to Coaxial flue to
enable vertical termination with a coaxial kit by using the
pipe bridge (Twin - Coaxial Adaptor - Part No. 3318089).
When running the twin flue pipe vertically.
Fig. 2.18B
It is not possible to terminate concentrically horizontally.
Termination is only possible with separate air and exhaust
terminals.
When siting the twin flue pipe, the air intake and exhaust
terminals must terminate on the same wall, the centres of
the terminals must be a minimum of 280 mm apart and
the air intake
must not be sited above the exhaust
terminal (refer to Fig. 2.22). The air intake pipe can be run
horizontally, however, the terminal and the final 1 metre of
flue must be installed either horizontally or with a slight fall
away from the boiler to avoid rain ingress.
It is also strongly recommended that the air intake pipe run
be constructed of insulated pipe to prevent condense
forming on the outside of the tube.
The maximum permissible flue length for twin flue is
dependent on the type of run used.
For flue runs with the intake and exhaust pipes under the
same atmospheric conditions (T
length is 40 metres
, for runs with the terminals under
different atmospheric conditions (T
YPE 4) the maximum
YPE 5) the exhaust
terminal must extend 0.5 metres above the ridge of the
roof (this is not obligatory if the exhaust and air intake
pipes are located on the same side of the building). For
TYPE 5 also, the maximum permissible combined length is
40 metres.
The maximum length is reached by combining the total
lengths of both the air intake and exhaust pipes. Therefore
a maximum length of 40 metres for example, will allow a
flue run of 20 metres for the air intake and 20 metres for
the exhaust pipes, also for each 90oelbow 2.2 metres must
be subtracted from the total length and for each 45oelbow
1.4 metres must be subtracted from the total flue length.
Some of the acceptab
le flue configurations are detailed on
page 20.
mation relating to flue r
or fur
F
ther inf
or
please contact the
echnical
T
Depar
uns not illustrated,
tment on 0870 241
8180.
17
ø 100
60 mm
In the event that the air intake and exhaust are run to the
left, it will be necessary to reduce the height of the air
ntake by cutting 20mm from the base of the air intake
i
elbow (see Fig. 2.19)
In the event that twin flue pipes are used, and the boiler
has a side clearance of less than 60mm from the wall, it
is necessary to cut a larger diameter hole for the flue
pipe, this should be ø10 cm, this will then allow for easier
assembly of the air intake elbow and the tube outside the
wall (see Fig. 2.20).
Fig. 2.19
or coaxial systems, the maximum development value,
F
mentioned in the table below also takes into account an
w.
elbo
For twin flue systems the maximum development value,
mentioned in the table includes the exhaust gas/air intake
terminal.
Type 5 outlets should respect the following instructions:
1- Use the same ø 80 mm flue pipes for the air intakes
and exhaust gas ducts.
2- If you need to insert elbows in the air intake and
exhaust gas ducts, you should consider for each one
the equivalent length to be included in the calculation
of developed length.
3- The exhaust gas duct should jut above the roof by at
least 0.5 m.
4- The intake and exhaust gas ducts in Type 5 must be
installed on the same wall, or where the exhaust is
vertical and the air intake horizontal, the terminals must
be on the same side of the building.
18
Fig. 2.20
The flue restr
on the boiler. Please refer to the table on page 19 to
determine whether it will be necessary to remove it.
o remove the restrictor it is simply necessary to lift the
T
restrictor from the exhuast manifold (Fig. 2.20A)
ictor is factory fitted in the exhaust manifold
Fig. 2.20A
24 MFFI
Coaxial
Systems
ø 60/100
Coaxial
ystems
S
ø 80/125
Exhaust Type
Type 1
Type 2
Type 3
Type 1
ype 2
T
Type 3
Do not remove the
ø 40 mm
Restrictor
Between
500 mm - 1 m
BC
T
Remove the
Restrictor
(Fig.2.20A)
Between
1 m - 4 m
BC
T
aximum Flue
M
Length
Length
Reduction 45
elbow (m)
4 m0.5 m1.0 m
1
0 m
BC
T
Length
o
Reduction 90
elbow (m)
BC
T
o
Twin Pipe
Systems
ø 80/80
28 MFFI
Coaxial
Systems
ø 60/100
Coaxial
Systems
ø 80/125
Twin Pipe
Systems
ø 80/80
Type 4
Type 5
Exhaust Type
Type 1
Type 2
Type 3
Type 1
Type 2
Type 3
Type 4
ype 5
T
Between
1m - 10 m
Between
1m - 10 m
Do not remove the
ø 41 mm
Restrictor
Between
500 mm - 1 m
TBCTBC10 m TBCTBC
Between
1m - 10 m
een
Betw
1m - 10 m
Between
10 m - 40 m
Between
10 m - 40 m
Remove the
Restrictor
(Fig.2.20A)
Between
1 m - 4 m
Between
10 m - 40 m
Between
10 m - 40 m
40 m1.4 m2.2 m
40 m1.4 m2.2 m
Maxim
Length
um Flue
Length
Reduction 45
elbow (m)
o
4 m0.5 m1.0 m
40 m1.4 m2.2 m
40 m1.4 m2.2 m
Length
Reduction 90
elbow (m)
o
32 MFFI
Coaxial
Systems
ø 60/100
Coaxial
Systems
ø 80/125
Twin Pipe
Systems
ø 80/80
Exhaust
Type 1
Type 2
Type 3
Type 1
ype 2
T
Type 3
Type 4
Type 5
Do not remove the
Type
Restrictor
500 mm - 1 m
ø 43 mm
Between
Remove the
Restrictor
(Fig.2.20A)
Between
1 m - 4 m
Maximum Flue
Length
4 m0.5 m1.0 m
Length
Reduction 45
elbow (m)
o
Reduction 90
elbow (m)
TBCTBC10 m TBCTBC
Between
1m - 10 m
Between
1m - 10 m
een
Betw
10 m - 40 m
een
Betw
10 m - 40 m
40 m1.4 m2.2 m
40 m1.4 m2.2 m
Length
o
19
TYPE 1
TYPE 2
TYPE 3
TYPE 4
TYPE 5
NOTE: DRAWINGS ARE INDICATIVE OF FLUEING OPTIONS ONLY.
FIG. 2.21
20
Fig. 2.22
1
2
3
4
5
6
1
2
3
4
5
6
E
C
II
I
JK
F
R020A
* Warning the flue analysis mode must only be selected by a
qualified service engineer. See Section 3.4 for further
instructions
FIG. 2.23
2.10CONTROL PANEL
LEGEND:
On/Off Button
A B - Domestic Hot Water Temperature Adjustment
C - Central Heating Temperature Adjustment
D - Reset Button/Flue Test analysis mode*
E - Comfort Mode Selector
F - Summer Mode LED (Green)
Ignition/Overheat Lockout LED (Red)
G H - Central Heating (Winter Mode) LED (Green)
I - Digital Display (Fault Code/Water Temperature)
J - Time Clock
K- Central Heating System Pressure Gauge
2.11DIGITIAL DISPLAY AND FAULT CODES
DISPLAYCAUSE
AA 0011
AA 0033
No flame after safety time (7 seconds)
The heating flow temperature exceeds 103oC
during operation
Condensate Trap full of water
AA 7777
Condensate sensor short circuited
Condensate sensor in open circuit
AA 7755
AA 9977
AA 9988
AA 9999
EE 0022
EE 0044
EE 0055
EE 0066
EE 0077
EE 0088
EE 0099
EE 2200
EE 2211
EE 3333
EE 3344
EE 9999
Problem with the flue stat
Problem with the electronic monitoring
Problem with the electronic monitoring
Problem with the electronic monitoring
Insufficient w
Domestic hot w
ater pressure
ater temper
open circuit
Domestic hot w
ater temper
short circuited
Heating flo
w temper
ature probe in open
circuit
Heating flo
w temper
ature probe shor
circuited
Heating retur
n temper
circuit
Heating return temperature probe shor
circuited
Flame detected with gas valve closed
Error in the electrical connection (live and
neutral crossed)
The air pressure switch is closed before the
ignition sequence has begun
The air pressure switch does not close
when the fan runs
More than 5 RESETS of the boiler
in 15 minutes.
ature probe in
ature probe
t
ature probe in open
t
The Control Panel has a 3 digit display, during normal
operation the display will show one of six things on the
two right hand digits;
During Stand-by (no demand for Central Heating or D.H.W.)
on’ will be shown on the display and no LEDs will light.
‘
During a demand for Domestic Hot Water, the temperature of
the outgoing hot water is displayed in oC (e.g. 38) and the
summer mode LED will light (F - FIG. 2.23).
During a demand for Central Heating, the temperature of the
central heating flow will be displayed in oC (e.g. 65) and the
central heating mode LED will light (H - FIG.2.23).
ing the oper
Dur
display will show ‘
ation of the flue analysis mode* the
sc’.
Should a fault occur the display will show the fault code
and one of two letters, for a non-volatile shutdown the
letter ‘
the f
will be shown follow
A’
ault eg.
‘
A02’
ed b
and the red
y the tw
LED (
o digit code f
G - FIG.
2.23)will
or
light, a non-volatile shutdown will require the reset button
(D - FIG. 2.23) to be pressed once before the boiler will
attempt to relight, should the boiler lockout again, the
ised Service Engineer should be
assistance of an A
uthor
sought.
Should the boiler develop a fault that cannot be corrected
by resetting the boiler, the letter ‘
E’ will be displayed
followed by a two digit code (e.g. E33) indicating a
olatile shutdown code, in the ev
v
ent of such a shutdo
the boiler will automatically resume oper
Should it not, the assistance
cause behind it is resolv
ised Ser
of an A
uthor
ed.
vice Engineer w
ould be required.
ation once the
wn,
A list of the fault codes can be found opposite.
21
1
A
2.12REMOVING THE FRONT PANEL
In order to access the inside of the boiler, it is necessary
to unscrew the fastening screws “A” of the control panel
ocated on the lower part of the panel itself.
l
he control panel moves downward and when pulled
T
forward rotates on two lateral hinges.
The panel stays in a horizontal position, which allows
access to the inner parts of the boiler.
To dismantle the front casing panel it is necessary to:
1 - Remove the two screws
- Move the front casing panel up and lift forward.
2
“B”;
2
2.13 ROOMTH
ERMOSTAT
MOTECLOCK
/ RE
CONNECTION
To connect a room thermostat, it is necessary to:
1. - Open the control panel as indicated in SECTION 2.12.
B
3
A1
A1
4
2.- Remove the screws “A1” from the reverse of the
control panel (picture 3).
3. - Insert the thermostat cable through the cable
grommet and fasten it by means of the cable-clamp
provided.
4. - Connect the thermostat wires to the terminal block
A2 (Picture 4) (Diagram A - Fig. 2.24).
5.- If a remote time clock is to be fitted, disconnect the
integral time clock from the P.C.B.
6. - Using a volt-free switching time clock, connect the
switching wires from the time clock following points 14 above
7. - If using an external time clock and room thermostat,
these must be connected in series as Diagram C -
Fig. 2.24.
Note: Only a low voltage room thermostat capable of
(Diagram B - Fig. 2.24).
volt free switching must be used.
A2
Factory fitted integral wiring must not be
disturbed when wiring external controls.
Ensure high voltage and low voltage circuits
are cabled separately to avoid induced voltage
in the low voltage circuits.
22
FIG. 2.24
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.