Ariston Microgenus 23 MFFI, MicroGenus 24 HE MFFI User guide

Installation Instructions Type C Boilers
G.C.N: 47-116-14
47-116-15
LEAVE THESE INSTRUCTIONS WITH THE END-USER
2
TABLE OF CONTENTS
1. GENERAL INFORMATION
1.1 GENERAL INSTRUCTIONS
1.2 OVERALL VIEW
2. INSTALLATION
2.1 REFERENCE STANDARDS
2.2 SITING THE APPLIANCE
2.3 OVERALL DIMENSIONS
2.4 CLEARANCES
2.5 MOUNTING THE APPLIANCE
2.6 ELECTRICAL CONNECTION
2.7 GAS CONNECTION
2.8 WATER CONNECTIONS
2.9 FLUE CONNECTION
2.10 ROOM THERMOSTAT CONNECTION
2.11 ELECTRICAL/SYSTEM DIAGRAMS
2.12 WATER CIRCUIT DIAGRAMS
3. COMMISSIONING
3.1 INITIAL PREPARATION
3.2 CONTROL PANEL
3.3 REMOVING THE FRONT PANEL
3.4 INITIAL START UP
3.5 OPERATIONAL ADJUSTMENTS
3.6 COMBUSTION ANALYSIS
3.7 FUME DISCHARGE MONITORING
3.8 BOILER SAFETY SYSTEMS
3.9 DRAINING THE SYSTEM
4. GAS ADJUSTMENTS
GAS ADJUSTMENT TABLE
4.1 CHANGING THE TYPE OF GAS
5. MAINTENANCE
6. MISCELLANEOUS
6.1 WIRING DIAGRAM FOR TWO HEATING ZONES
6.2 WIRING DIAGRAM FOR CONNECTION TO AN ARISTON UNVENTED CYLINDER
7. TECHNICAL INFORMATION
This manual is an integral and essential part of the product. It should be kept with the appliance so that it can be consulted by the user and our authorised personnel.
Please carefully read the instructions and notices about the unit contained in this manual, as they provide important information regarding the safe installation, use and maintenance of the product.
For operating instructions please consult the separate User’s Manual.
Read the instructions and recommendations in these Installation Instructions carefully to ensure proper installation, use and maintenance of the appliance.
Keep this manual in a safe place.You may need it for your own reference while our Servicing Centre technicians or your installer may need to consult it in the future.
This is a combined appliance for the production of central heating (C.H.) and domestic hot water (D.H.W.).
This appliance
must be used only for the purpose for which it is designed. The manufacturer declines all liability for damage caused by improper or negligent use.
No asbestos or other hazardous materials have been used in the fabrication of this product.
Before connecting the appliance, check that the information shown on the data plate and the table on pages 4-5 comply with the electric, water and gas mains of the property.You will find the data plate on the reverse of the control panel. The gas with which this appliance operates is also shown on the label at the bottom of the boiler.
Do not install this appliance in a damp environment or close to equipment which spray water or other liquids.
Do not place objects on the appliance. Do not allow children or inexperienced persons to use the appliance without
supervision. If you smell gas in the room,
do not turn on light switches, use the telephone or any other object which might cause sparks. Open doors and windows immediately to ventilate the room. Shut the gas mains tap (on the gas meter) or the valve of the gas cylinder and call your Gas Supplier immediately. If you are going away for a long period of time, remember to shut the mains gas tap or the gas cylinder valve.
Always disconnect the appliance either by unplugging it from the mains or turning off the mains switch before cleaning the appliance or carrying out maintenance.
In the case of faults or failure, switch off the appliance and turn off the gas tap.Do not tamper with the appliance. For repairs, call your local Authorised Servicing Centre and request the use of original spare parts. For in-guarantee repairs contact MTS (GB) Limited.
Check the following at least once a year:
1 - Check the seals for the water connections; replacement of any faulty seals. 2 - Check the gas seals;replacement of any faulty gas seals. 3 - Visual check of the entire unit. 4 - Visual check of the combustion process or analysis of combustion by-
products (see section 3.6) and cleaning of the burner if needed.
1. GENERAL INFORMATION
3
1.1 GENERAL INSTRUCTIONS
CO034A
4
5 - If called for by point. 3, dismantling and cleaning of the combustion
chamber. 6 - If called for by point. 4, dismantling and cleaning of the burner jets. 7 - Visual check of the primary heat exchanger:
- check for overheating in the blade assembly;
- clean the exhaust fan if needed.
8 - Adjustment of the flow rate of the gas:flow rate for lighting, partial load and
full load. 9 - Check of the heating safety systems:
- safety device for maximum temperature;
- safety device for maximum pressure.
10- Check of the gas safety systems:
- safety device for lack of gas or flame ionisation (detection
electrode);
- safety device for gas cock.
11- Check of the electrical connection (make sure it complies with the instructions
in the manual). 12- Check of domestic hot water production efficiency (flow rate and temperature) 13- General check of the combustion by-products of the discharge/ventilation
system. 14- Check of the general performance of the unit.
LEGEND:
1. Flue connector
2. Air intake for twin pipe flue systems
3. Fan
4. Combustion chamber hood
5. Main heat exchanger
6. Safety thermostat
7. Combustion chamber
8. Combustion chamber insulation panel
9. Burner
10. Detection electrode
11. Ignition electrodes
12. Motorised diverter valve
13. Main circuit temperature probe
14. Main circuit flow switch
15. Domestic hot water temperature probe
16. Gas valve
17. Spark generator
18. Domestic hot water flow switch
19. Domestic cold water inlet filter
20. Secondary heat exchanger
21. Circulation pump with automatic air release valve
22. Safety valve (3 bar)
23. Expansion vessel
24. Air pressure switch
25. Combustion analysis intakes
1.2 OVERALL VIEW
FIG. 1.0
IN013A
5
The technical information and instructions provided herein below are intended for the installer so that the unit may be installed correctly and safely.
The installation and initial start up of the boiler must be by a CORGI Approved Installer in compliance with the installation standards currently in effect, as well as with any and all local health and safety standards i.e.. CORGI .
This appliance must be installed by a competent installer in accordance with current Gas Safety (installation & use) Regulations.
The installation of this appliance must be in accordance with the relevant requirements of the current Gas Safety (installation & use) Regulations, the Local Building Regulations, the current I.E.E. Wiring Regulations, the byelaws of the local water authority, and in Scotland, in accordance with the Building Standards (Scotland) Regulation and Health and Safety document No.635 Electricity at work regs.1989”. Installation should also comply with the following British Standard Codes of Practice:
The appliance may be installed in any room or indoor area, although particular attention is drawn to the requirements of the current I.E.E. Wir ing Regulations, and in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the combined appliance in a room containing a bath or shower.
Where a room-sealed appliance is installed in a room containing a bath or shower the boiler and any electrical switch or appliance control, utilising mains electricity should be situated so that it cannot be touched by a person using the bath or shower.
The location must permit adequate space for servicing and air circulation around the appliance as indicated in paragraph 2.4. The location must permit the provision of an adequate flue and termination. For unusual locations special procedures may be necessary. BS 6798-1987 gives detailed guidance on this aspect. A compartment used to enclose the appliance must be designed specifically for this purpose. No specific ventilation requirements are needed for the installation within a cupboard. This appliance is not suitable for outdoor installation.
The type C appliances (in which the combustion circuit, air vent intake and combustion chamber are air-tight with respect to the room in which the appliance is installed) can be installed in any type of room.
There are no limitations with respect to ventilation and the volume of the room itself.The boiler must be installed on a solid, permanent wall to prevent access to the electrical parts (when live) through the aper ture on the back frame.
2.1 REFERENCE STANDARDS
2. INSTALLATION
Low pressure pipes BS 6891 1988
Boilers of rated input not exceeding 60 kW BS 6798 1987
Forced circulation hot water system BS 5449 1990
Installation of gas hot water supplies for domestic purposes
( 2ndfamily gases) BS 5546 1990 Flues BS 5440-1 1990
Air supply BS 5440-2 1989
2.2 SITING THE APPLIANCE
For safety purposes, have a competent person carefully check the electrical system in the property, as the manufacturer will not be held liable for damage caused by the failure to earth the appliance properly or by anomalies in the supply of power. Make sure that the residential electrical system is adequate for the maximum power absorbed by the unit, which is indicated on the rating plate. In addition, check that the section of cabling is appropriate for the power absorbed by the boiler.
The boiler operates with alternating current, as indicated in the technical information table section in 6, where the maximum absorbed power is also indicated. Make sure that the connections for the neutral and live wires correspond to the indications in the diagram. The appliance electrical connections are situated on the reverse of the control panel (see the servicing manual for further information)
IMPORTANT!
In the event that the power supply cord must be changed, replace it with one with the same specifications. Make the connections to the terminal board located within the control panel, as follows:
- The yellow-green wire should be connected to the terminal marked with the
“”symbol; make sure to re­use the ferrule mounted on the other supply cord;- The blue wire should be connected to the terminal marked N”;
- The brown wire should be connected to the terminal
6
Fasten the boiler in place using the template and anchors supplied with the unit. It is highly recommended that a spirit level be used to position the boiler so that it is perfectly level. For additional information, please consult the instructions contained in the connection kit and the flue kit.
2.7 ELECTRICAL CONNECTION
2.5 MOUNTING THE APPLIANCE
LEGEND:
A = Central Heating Flow (3/4”) B = Domestic Hot Water Outlet (1/2”) C = Gas Inlet (3/4”) D = Domestic Cold Water Inlet (1/2”) E = Central Heating Return (3/4”)
2.3 OVERALL DIMENSIONS
In order to allow for access to the interior of the boiler for maintenance purposes, the boiler must be installed in compliance with the minimum clearances indicated in FIG. 2.2
2.4 CLEARANCES
FIG. 2.1
F
IG. 2.2
F
IG. 2.3
QT002A
DM004A
VR001A
VIEW OF THE BOILER CONNECTIONS
LEGEND:
A = Central Heating Flow B = Domestic Hot Water Outlet C = Gas Inlet D = Domestic Cold Water Inlet E = Central Heating Return F = Safety Valve
CENTRAL HEATING
Detailed recommendations are given in BS 6798:1987 and BS 5449-1:1990, the following notes are given for general guidance.
2.9 WATER CONNECTIONS
2.8 GAS CONNECTION
The local gas region contractor connects the gas meter to the service pipe. If the gas supply for the boiler serves other appliances ensure that an adequate supply is available both to the boiler and the other appliances when they are in use at the same time. Pipe work must be of an adequate size. Pipes of a smaller size than the boiler inlet connection should not be used.
7
marked L”. Note:The diagrams for the electrical system are indicated in section 2.11.
Warning,this appliance must be earthed.
External wiring to the appliance must be carried out by a qualified technician and be in accordance with the current I.E.E. Regulations and applicable local regulations. The Genus range of boilers are supplied for connection to a 230 V
~
50 Hz supply.
The supply must be fused at 3 A.
The method of connection to the electricity supply must facilitate complete electrical isolation of the appliance, by the use of a fused double pole isolator having a contact separation of at least 3 mm in all poles or alternatively, by
means of a 3 A fused three pin plug and unswitched shuttered socket outlet both complying with BS 1363. The point of connection to the Electricity supply must be readily accessible and adjacent to the appliance unless the appliance is installed in a bathroom when this must be sited outside the bathroom.
FIG. 2.4
FIG. 2.5
KT002A
SC008A
8
PIPE WORK:
Copper tubing to BS EN 1057:1996 is recommended for water pipes. Jointing should be either with capillary soldered or compression fittings. Where possible pipes should have a gradient to ensure air is carried naturally to air release points and water flows naturally to drain taps. The appliance has a built-in automatic air release valve, however it should be ensured as far as possible that the appliance heat exchanger is not a natural collecting point for air. Except where providing useful heat, pipes should be insulated to prevent heat loss and avoid freezing. Particular attention should be paid to pipes passing through ventilated spaces in roofs and under floors.
BY-PASS:
The appliance includes an automatic by-pass valve, which protects the main heat exchanger in case of reduced or interrupted water circulation through the heating system, due to the closing of thermostatic valves or cock-type valves within the system.
SYSTEM DESIGN:
This boiler is suitable only for sealed systems.
Drain Cocks:
These must be located in accessible positions to permit the draining of the whole system. The taps must be at least 15mm nominal size and manufactured in accordance with BS 2870:1980.
SAFETY VALVE DISCHARGE:
The discharge should terminate facing downward on the exterior of the building in a position where discharging (possibly boiling water & steam) will not create danger or nuisance, but in an easily visible position, and not cause damage to electrical components and wiring. The discharge must not be over an entrance or a window or any other type of public access.
AIR RELEASE POINTS:
These must be fitted at all high points where air naturally collects and must be sited to facilitate complete filling of the system. The appliance has an integral sealed expansion vessel to accommodate the increase of water value when the system is heated. It can accept up to 6 l (1.3 gal) of expansion water. If the heating circuit has an unusually high water content, calculate the total expansion and add an additional sealed expansion vessel with adequate capacity.
MAINS WATER FEED - CENTRAL HEATING:
There must be no direct connection to the mains water supply even through a non-return valve, without the approval of the Local Water Authority.
FILLING:
A temporary method for initially filling the system and replacing lost water during servicing in accordance with Water Supply Byelaw 14 must be provided.
DOMESTIC WATER
The domestic water must be in accordance with the relevant recommendation of BS 5546:1990. Copper tubing to BS EN 1057:1996 is recommended for water carrying pipe work and must be used for pipe work carrying drinking water.
RESIDUAL HEAD OF THE BOILER
VR003A
Ø 60/100 mm
FIG. 2.7
The boiler is designed to be connected to a coaxial flue discharge system.
9
2.9 FLUE CONNECTIONS
FLUE SYSTEM
The provision for satisfactory flue ter mination must be made as described in BS 5440-1. The appliance must be installed so that the flue terminal is exposed to outdoor air. The terminal must not discharge into another room or space such as an outhouse or lean-to. It is important that the position of the terminal allows a free passage of air across it at all times. The terminal should be located with due regard for the damage or discolouration that might occur on buildings in the vicinity. In cold or humid weather water vapour may condense on leaving the flue terminal. The effect of such steamingmust be considered. If the terminal is less than 2 metres above a balcony, above ground or above a flat roof to which people have access, then a suitable terminal guard must be fitted. When ordering a ter minal guard, quote the appliance model number. A suitable terminal guard is available from:
TOWER FLUE COMPONENTS Morley Road Tonbridge Kent TN9 1RA
The minimum acceptable spacing from the terminal to obstructions and ventilation openings are specified in FIG. 2.6.
T
ERMINALPOSTION
mm
A - Directly below an open window or other opening 300 B - Below gutters, solid pipes or drain pipes 75 C - Below eaves 200 D - Below balconies or car-port roof 200 E - From vertical drain pipes and soil pipes 75 F - From internal or external corners 300 G - Above ground or below balcony level 300 H - From a surface facing a terminal 600
I - From a terminal facing a terminal 1200
J - From an opening in the car port
(e.g.door, window) into dwelling 1200 K - Vertically from a terminal in the same wall 1500 L - Horizontally from a terminal in the same wall 300
FIG. 2.6
FU010A
FU025A
FU002A
F
HI
BC
D
J
A
E
F
G
K
L
G
Ø 80 mm
The components marked * in FIG 2.9 are present or absent depending on the type of flue system used by the installer.
In addition, it is also possible to use a split (twin pipe) system by fitting a special adaptor to the flue connector and using the aperture for the air vent intake located on the top part of the combustion chamber. To utilise the air intake it is necessary to:
1. Remove the bottom of the air intake by cutting it with a suitable knife (see
FIG.2.8);
2. Insert the elbow into the air intake until it reaches the lower end.(There is no need to use gaskets or sealing componds).
10
IMPORTANT!
For all flue systems, a restrictor must always be inserted into the boilers flue connector; the restrictor must be ø 43 or ø 41 in diameter depending on the length of piping indicated in Table 2.1.
The diagrams illustrate some of the various designs for coaxial or twin pipe flue systems. For further information on discharge/ventilation accessories, see the
FLUE PIPE ACCESSORIES
MANUAL.
COAXIAL SYSTEMS
FIG. 2.8
F
IG. 2.9
F
IG. 2.10
FU05A
FU004A
FU006A
FU001A
Exhaust
Type
C12 (xy) C32 (xy) C42 (xy)
C52 (xy) C82 (xy)
Restrictor
ø 43 mm
L max = 11.5 m
L max = 11,4 m
Maximum Extension Exhaust/Air
43 m 43 m 43 m
40 m
NO
Restrictor
L min = 11.5 m L max = 43 m
L min = 11,4 m L max = 40m
Risk of Condensation Forming
Twin Pipe
Systems
ø 80/80
Piping not insulated
ø 43 restrictor NO
4.3 m 6.9 m
4.3 m 6.9 m
Piping insulated
ø 43 restrictor NO
NONE NONE
5,7 m 21,7 m
L = Sum of the total length of exhaust + air intake piping.
11
Exhaust
Type
C12 (xx) C32 (xx) C42 (xx)
Restrictor
ø 43 mm
L min = 0.5 m
L max = 2 m
Maximum Extension Exhaust/Air
L = 4 m
NO
Restrictor
L min = 2 m
L max = 4 m
Risk of Condensation Forming
Coaxial
Systems
ø 60/100
Piping not insulated
ø 43 restrictor NO
NONE NONE
Piping insulated
ø 43 restrictor NO
NONE NONE
TABLE 2.1
Exhaust
Type
C12 (xy) C32 (xy) C42 (xy)
C52 (xy) C82 (xy)
Restrictor
ø 41 mm
L max = 38 m
L max = 34 m
Maximum Extension Exhaust/Air
62 m 62 m 62 m
54 m
NO Restrictor
L min = 38 m L max = 62 m
L min = 34 m L max = 54 m
Risk of Condensation Forming
Twin Pipe
Systems
ø 80/80
Piping not insulated
ø 41 restrictor NO restrictor
8 m 11 m
8 m 11 m
Piping insulated
ø 41 restrictor NO restrictor
19 m 31 m
19 m 31 m
Exhaust
Type
C12 (xx) C32 (xx) C42 (xx)
Restrictor
ø 41 mm
L min = 0.5 m
L max = 1 m
Maximum Extension Exhaust/Air
L = 4 m
NO Restrictor
L min = 1 m
L max = 4 m
Risk of Condensation Forming
Coaxial
Systems
ø 60/100
Piping not insulated
ø 41 restrictor NO restrictor
NONE NONE
Piping insulated
ø 41 restrictor NO restrictor
NONE NONE
27 MFFI
23 MFFI
12
To connect a room thermostat, it is necessary to:
1. - Open the control panel as indicated in section 3.3.
2.- Remove the link
Afrom the terminal block on the reverse of the control panel.
3. - Insert the thermostat cable through the cable grommet and fasten it by means of the cable-clamp provided.
4. - Then connect the thermostat wires to the terminal block.
5.- If a remote time clock is to be fitted, disconnect the integral time clock from the P.C.B .
6. - Using a volt-free switching time clock, connect the switching wires from the time clock following points 1-4 above.
7. - If using an external time clock and room thermostat, these must be connected in series as points 1-7 above.
Note: Only a two-wire type room thermostat can be used.
An anti-frost device is built-in to the appliance’s electronic regulation system.
2.10 ROOM THERMOSTAT CONNECTION
A
TWIN PIPE
SYSTEMS
FIG. 2.11
In calculating the lengths of the pipes, the maximum length “L” must also take into consideration the values for the exhaust/air intake end terminals, as well as 90° elbows for coaxial systems. The C52 types must comply with the
following requirements:
1 - The exhaust/ air intake pipes must
have the same diameter of
ø 80 mm.
2 - If elbows are to be inserted into the
air intake and/or exhaust system, the calculation of the overall length must take into consideration the values for each elbow, see the
FLUE PIPE
ACCESSORIES MANUAL.
3 - The exhaust pipe must protrude by at
least 0.5 m above the top of the roof in the event that it is located on the opposite side to the side with the air intake (this condition is not obligatory when the air intake and exhaust are located on the same side of the building).
FU007A
Fo016A
Fo017A
2.12 ELECTRICAL DIAGRAM
13
LEGEND:
A = Time Clock Connector B = Central Heating Selection (Winter) and
Temperature Adjustment C = Connector for Total Check System D = Domestic Hot Water Temperature Adjustment E = Soft-light Adjustment F = Maximum Heating Adjustment G = On/Off Switch H = On/Off L.E.D. I = Fume Sensor L.E.D. J = Ignition Failure (Lockout) L.E.D. K = Low System Water Level/Lack of Circulation L.E.D. L = Reset Button M = Economy/Comfort Selector N = Overheat L.E.D. O = Temperature L.E.D.s P = Transformer Q = Circulation Pump Relay R = Fan Relay S = Gas Valv e Relay T = Motorised Diverter Valve Relay V = Spark Generator U = Anti-cycling Device Adjustment for Heating
A01 = Circulation Pump A02 = Fan A03 = Spark Generator/Gas Valve Supply A04 = Motorised Diverter Valve A05 = Flame Detection Circuit A06 = Detection Electrode A07 = Main Circuit Temperature Probe A08 = Domestic Hot Water Temperature Probe A09 = Domestic Hot Water Flow Switch A10 = Main Circuit Flow Switch A11 = Modulator A12 = Air Pressure Switch A13 = Safety Thermostat A14 = External (Room) Thermostat
Colours: Gry = Grey Wh = White Pnk = Pink Brn = Brown Bl = Blue Blk = Black Rd/Blk = Red/Black
FIG. 2.12
SE017A
JK
Blk
Blk
Gry
Gry
Pnk
Pnk
Blk
Blk
Wh
Gry
Gry
Rd/Blk
Pnk
Wh
Wh
Blk
Blk
Wh
Brn
Rd/Blk
Wh
Brn
Rd/Blk
Wh
Wh
Brn
Brn
Blk
14
LEGEND:
1. Fan
2. Main Heat Exchanger
3. Overheat Thermostat
4. Burner
5. Ignition Electrodes
6. Detection Electrode
7. Motorised Valv e
8. Main Circuit Temperature Probe
9. Main Circuit Flow Switch
10. Automatic By-pass
11. Domestic Hot Water Temperature Probe
12. Secondary Heat Exchanger
13. Gas Valve
14. Domestic Hot Water Flow Switch
15. Domestic Water Inlet Filter
16. Pressure Gauge
17. Saf ety V alv e
18. Circulation Pump with Automatic Air Release Valve
19. Expansion Vessel
20. Air Pressure Switch
A. Central Heating Flow B. Domestic Hot Water Outlet C. Inlet Gas D. Domestic Cold Water Inlet E. Central Heating Return
2.13 WATER CIRCUIT DIAGRAM
FIG. 2.14
FIG. 2.13
SF014A
SI017A
ON
R
SQT
K
L
M
UJ
15
MTS (GB) Limited support the initiative.Within the information pack you will find a copy of the logbook. It is important that this is completed in the presence of your customer, they are shown how to us it, and it is signed by them. Please instr uct your customer that they must have their logbook with them whenever they contact a service engineer or us.
Preliminary electrical system checks to ensure electrical safety must be carried out by a competent person i.e. polarity, ear th continuity, resistance to earth and short circuit.
FILLING THE HEATING SYSTEM:
Remove the panels of the case and lower the control panel (see section
3.3 for further information). Open the central heating flow and return cocks supplied with the connection kit. Unscrew the cap on the automatic air release valve one full turn and leave open permanently. Close all air release valves on the central heating system. Gradually open valve(s) at the filling point (filling-loop) connection to the central heating system until water is heard to flow, do not open fully. Open each air release tap starting with the lower point and close it only when clear water, free of air, is visible.
Purge the air from the pump by unscrewing anticlockwise the pump plug and also manually rotate the pump shaft in the direction indicated by the pump label to ensure the pump is free.
Close the pump plug. Continue filling the system until at least 1 bar registers on the pressure gauge. Inspect the system for water soundness and remedy any leaks discovered.
FILLING OF THE D.H.W.SYSTEM:
Close all hot water draw-off taps. Open the cold water inlet cock supplied with the connection kit. Open slowly each draw-off tap and close it only when clear water, free of bubbles, is visible
GAS SUPPLY:
Inspect the entire installation including the gas meter, test for soundness and purge, all as described in BS 6891:1988. Open the gas cock (supplied with the connection kit) to the appliance and check the gas connector on the appliance for leaks.
When the installation and filling are completed turn on the central heating system (section 3.4) and run it until the temperature has reached the boiler operating temperature. The system must then be immediately flushed through. The flushing procedure must be in line with BS 7593:1992 code of practice for treatment of water in domestic hot water central heating systems. During this operation, we highly recommend the use of a central heating flushing detergent (Fernox Superfloc or equivalent), whose function is to dissolve any foreign matter that may be in the system.
Substances different from these could create serious problems to the pump or other components.
The use of an inhibitor in the system such as Fernox MB-1 or equivalent is strongly recommended to prevent corrosion (sludge) damaging the boiler and system.
Failure to carry out this procedure may invalidate the appliance warranty.
3. COMMISSIONING
3.1 INITIAL PREPARA TION
In order to access the inside of the boiler, it is necessary to unscrew the fastening screws Aof the control panel located on the lower part of the panel itself. The control panel moves downward and when pulled forward rotates on two lateral hinges. The panel stays in a semi-horizontal position, which allows access to the inner parts of the boiler. In order to increase the maneuvering space, it is possible to raise the control panel and rotate it to a fully horizontal position.
16
3.3 REMOVING THE FRONT PANEL
B
1
2
3
4
5
A
LEGEND:
A - On/Off knob B - Domestic hot water temperature adjustment knob C - Central heating selection (winter) and temperature
adjustment knob D - On/Off L.E.D.(green) E - Fume sensor L.E.D.(yellow) F - Ignition failure (lockout) L.E.D.(red) G-“Economy/Comfort” mode selection knob H - Ignition failure (lockout) and/or overheat reset button I - Overheat L.E.D.(red) J - Low system water level L.E.D.(red) K - Central heating temperature L.E.D (yellow) L - Time clock M - Heating system pressure gauge
3.2 CONTROL PANEL
FIG. 3.1
To dismantle the front casing panel it is necessary to: 1 - Remove the two screws
B;
2 - Lift the front casing panel
up and forward.
FR025A
FO006A
FO008A
FO009A
FO012A
FO013A
17
3.4. INITIAL START-UP
(See section 3.2 for references) it is possible to:
- Set the temperature of the heating system by adjusting the knob C
- Set the temperature of the domestic hot water by turning knob B
- The selector knob Gallows the user to choose the economy mode (position “E”) or the comfort mode (position “C”). The economy mode is the normal state for the operation of the boiler, since the domestic water is heated up only when a tap is turned on. The comfort mode is a special operating state, because the water contained in the secondary exchanger and in the primary exchanger is kept in a preheated condition, thereby allowing a quicker delivery of domestic water when required. The latter is therefore the more convenient choice.
To access the areas in which adjustments are made, it is necessary to open the control panel, as indicated in section 3.3, then remove the rear inspection cover by unscrewing the two screws. Access is thereby provided to the P.C.B.and to the following components:
1. the power supply cable connector;
2. the fuses;
3. the soft-light potentiometer the setting for which can range from the minimum thermal power to the maximum;
4. the maximum thermal heating power potentiometer adjustable by the minimum to maximum power (already calibrated in the factory to 70% of the maximum thermal power);
5. the potentiometer for adjusting the ignition delay (anti-cycling) feature, which can be set from 0 to 2 minutes (set in the factory at one minute);
6. the time clock connector.
THE CHECKS TO BE RUN BEFORE INITIAL START-UP ARE AS FOLLOWS:
1. Make sure that:
- the screw on the automatic air valve has been loosened when the system is full;
- If the water pressure in the system is below 1 bar, bring it up to the appropriate level;
-Check to see whether the gas cock is closed;
- Make sure that the electrical connection has been made properly and that the earth wire is connected to an efficient earthing system;
- Supply power to the boiler by turning the On/Off switch
A(see FIG.3.1)
- the L.E.D. Dwill illuminate - turn the selector knob Cto the winter /central heating position. This will start the circulation pump. After 7 seconds, the boiler will signal a shutdown due to ignition failure. Leave the boiler as it is until all of the air has been bled from the lines.
-Loosen the cap on the head of the pump to eliminate any air pockets;
-Repeat the procedure for bleeding the radiators of air;
-Open the taps for a brief period;
- Check the system pressure and, if it has dropped, open the filling loop again to bring the pressure back up to 1 bar.
2. Check the exhaust flue for the fumes produced by combustion.
3. Make sure that all gate valves are open;
4. Turn on the gas cock and check the seals on the connections, including the one for the burner, making sure that the meter does not signal the passage of gas.Check the connections with a soap solution and eliminate any leaks.
5. Press the reset button
Afor the lighting system; the spark will light the main burner.If the burner does not light the first time, repeat the procedure.
6. Check the minimum and maximum pressure values for the gas going to the burner; adjust it if needed using the values indicated in the table in section 4 (See the relative section for burner pressure adjustment within the servicing manual).
3.5 OPERATIONAL ADJUSTMENTS
The boiler is fitted with the following devices (see section 3.2 for references).
1 - IGNITION FAILURE:
This control signals an ignition failure on the burner 7 seconds after a lighting failure. The L.E.D. Fwill illuminate to signal the shutdown status. The system can be reset by pressing and releasing the button H” after checking to make sure that the gas cock is open.
2 - CIRCULATION FAILURE:
This control signals that the safety pressure switch on the primary circuit has not sensed a pressure of at least 1 bar within 40 seconds of the activation of the circulation pump; the circulation pump comes to a halt and the red L.E.D. Jilluminates. The system may be reset, after re-establishing the correct level of pressure in the boiler, turning the Aknob.
3 - OVERHEATING:
This control shuts off the boiler in the case where the primary circuit reaches a temperature in excess of 105°C. The red L.E.D.s Iand Fwill illuminate to signal this shutdown status. The system can be reset by waiting a few minutes for the primary exchanger to cool down and then by pressing and releasing the H button.
4. LIMESCALE BUILD-UP: The boiler is equipped with a device that limits the formation of Limescale in the secondary exchanger by controlling the temperature of the domestic hot water (max 61°C) and also controlling the temperature of the water in the primary heating circuit.
18
3.8 BOILER SAFETY SYSTEMS
In the boiler, it is possible to monitor the correct operation of the flue exhaust/air intake, checking for a loss of general pressure in the system. Through the use of a differential manometer connected to the test points of the combustion chamber, it is possible to detect the P of operation of the air pressure switch. The value detected should not be less than 0,55 mbar for 23kW and 0.75 mbar for 27kW under conditions of maximum thermal power in order for the boiler to function properly and without interruption.
The flue connector has two apertures, readings can be
taken for the temperature of the combustion by-products and of the combustion air, as well as of the concentrations of O
2
and CO2, etc. .
To access these intakes it is necessary to unscrew the front screw and remove the metal plate with sealing gasket. The best test conditions, with the maximum heating power, are achieved by turning the selector knob
C” to the max position and removing the electrical connection to the heating sensor (see section 6.).
3.6 COMBUSTION ANALYSIS
3.7 FUME DISCHARGE MONITORING
FU008A
FU009A
19
DRAINING THE HEATING SYSTEM
The heating system must be emptied as follows:
- Turn off the boiler;
- Open the drain valve for the system and place a container below to catch the water that comes out;
- Empty the system at the lowest points (where present). If you plan on not using the heating system for an extended period of time, it is recommended that you add antifreeze with an ethylene glycol base to the water in the heating lines and radiators if the ambient temperature drops below 0°C during the winter. This makes repeated draining of the entire system unnecessary.
DRAINING THE DOMESTIC HOT WATER SYSTEM
Whenever there is the danger of the temperature dropping below the freezing point, the domestic hot water system must be drained as follows:
- Turn off the general water valve for the household plumbing system;
- Turn on all the hot and cold water taps;
- Empty the remaining water from the lowest points in the system (where present).
3.9 DRAINING THE SYSTEM
5. ANTI-FROST DEVICE: The boiler is equipped with a device that, in the event of the water temperature going below 5°C, the 3-way diverter valve switches to domestic hot water and the burner ignites at the minimum power until the boiler water reaches a temperature of about 50°C. This device operates only if the boiler is functioning perfectly and:
- the system pressure is sufficient;
- the boiler is powered electrically;
- the gas is distributed.
6 - EXHAUST DISCHARGE ANOMALY SHUTDOWN:
The boiler is fitted with safety devices, which in the event of defective discharge of exhaust fumes, automatically interrupts the gas supply, thereby shutting off the boiler. The shutdown of the boiler is temporary and is indicated by the illumination of the yellow L.E.D. Efor a period of about 15 minutes. Once this time period has passed and the discharge state of exhaust fumes has returned to normal, the boiler automatically turns back on.
7 - SAFETY SHUTDOWN:
At the start of every lighting phase, the P.C.B. performs a series of internal controls. If a malfunction occurs, the boiler will shutdown until the problem has been resolved.
20
The boiler can be converted to use either methane (natural) gas (G20) or LPG (G30 - G31) by an Authorised Service Centre.
The operations that must be performed are the following:
1. Replace the jets on the main burner (see table in section 4);
2. Adjust the maximum and minimum thermal capacity values for the boiler (see table in section 4);
3. Replace the gas rating plate;
4. Adjust the maximum thermal power setting;
5. Adjust the soft-light feature;
6. Adjust the ignition delay feature for the heating system (can be set from 0 to 2 mins.).
CATEGORY II2H3+
Recommended Soft­light Pressure (mbar)
Methane
Gas
G20
8.0
Liquid
Propane
Gas
G31
16.0
Liquid
Butane
Gas
G30
16.0
4.1 CHANGING THE TYPE OF GAS
The outlet pressure of the gas cock is obtained by completely loosening the screw on the solenoid. The maximum pressure of the gas to the burner will be equal to the nominal delivery pressure minus the head loss within the gas valve.
[1 mbar = 10,197 mmc.a.]
4. GAS ADJUSTMENTS
Lower Wobbe Index (15°C;1013mbar) MJ/m3h Nominal Delivery Pressure mbar Minimum Delivery Pressure mbar
23 MFFI
Main Burner: n. 13 jets (ø)mm Consumption (15°C; 1013mbar) mc/h Consumption (15°C; 1013mbar) Kg/h Gas Cock Outlet Pressure max - min mbar
27 MFFI
Main Burner: n. 15 jets (ø) Consumption (15°C; 1013mbar) mc/h Consumption (15°C; 1013mbar) Kg/h Gas Cock Outlet Pressure: max - min mbar
CATEGORY II2H3+ Methane Gas
G20
Liquid Butane Gas
G30
Liquid Propane Gas
G31
45.67 20 17
1.30
2.72
----
11.0 - 2.0
1.30
3.15
----
11.0 - 1.6
80.58 29 20
0.77
----
2.02
(*) - 6.0
0.77
----
2.34
(*) - 4.6
80.58 37 25
0.77
----
2.02
(*) - 6.0
0.77
----
2.31
(*) - 6.0
21
It is recommended that the following inspections be carried out on the boiler at least once a year:
1 - Check the seals for the water connections; replacement of any faulty
seals. 2 - Check the gas seals;replacement of any faulty gas seals. 3 - Visual check of the entire unit. 4 - Visual check of the combustion process or analysis of combustion by-
products (see section 3.6) and cleaning of the burner if needed. 5 - If called for by point. 3, dismantling and cleaning of the combustion
chamber. 6 - If called for by point. 4, dismantling and cleaning of the burner jets. 7 - Visual check of the primary heat exchanger:
- check for overheating in the blade assembly;
- clean the exhaust fan if needed.
8 - Adjustment of the flow rate of the gas:flow rate for lighting, partial load
and full load. 9 - Check of the heating safety systems:
- safety device for maximum temperature;
- safety device for maximum pressure.
10- Check of the gas safety systems:
- safety device for lack of gas or flame ionisation (detection electrode);
- safety device for gas cock.
11- Check of the electrical connection (make sure it complies with the
instructions in the manual).
12- Check of domestic hot water production efficiency (flow rate and
temperature)
13- General check of the combustion by-products of the
discharge/ventilation system.
14- Check of the general performance of the unit.
5. MAINTENANCE
22
7. MISCELLANEOUS
7.1 WIRING DIAGRAM FOR TWO HEATING ZONES
Based on Honeywell controls
SH010A
BROWN
BLUE
GREY
ORANGE
GREEN/YELLOW
V4043H
VALVE
5 2 9
10
3
14 35 22
T6360B
ROOM
THERMOSTAT
ZONE1
BROWN
BLUE
GREY
ORANGE
GREEN/YELLOW
V4043H
VALVE
8 2 9
10
3
16
TYPICAL
JUNCTION BOX
1
2
3
4
5
6
7
8
9
1
BOILER ELECTRICAL SUPPLY CABLE
ENLmicroGENUS 23-27 MFFI
9 10 3 2
Remove internal time clock plug from the the P.C.B. then connect room stat terminal block on the reverse of the boiler control panel
(see section 2.10)
the junction box.
25 ENL
14 N L
31 N L
74 E1 2
Sunvic ET 1451
Link 2-3-6
Sunvic DHP 2201 6 3 E 1 2
610 2 1
Towerchron FP
64321
Pegler Sunvic
SP 50/100 (Link L-3)
SWITCHMASTER 805, 900
Switchmaster
Symphony, Sonata
Switchmaster 400, 600 3 1 N L
to 9 + 10 on
NL
ON ON
610 2 1
Link 1-5/4-7-9
Towerchron MP
Link 1-4/6-11
Towerchron 2000 HW HTG
36 ENL
42 ENL
ACL LS522, LS722 3 4 N L
Randall 922, 972
Link L-2-5
Randall 3020 P
BOILER
ZONE 1
PROGRAMMER
and 3060
38 22
T6360B
ROOM
THERMOSTAT
ZONE 2
L1 N2 E3
240V
MAINS INPUT (3 AMP)
10
63 N L
64321
Honeywell ST 699B 1002
Link L-5-8
14 ENL
34 N L
ST 6400/ST 6300 ST 6200 3 4 N L
Drayton Tempus 7 3 4 N L
Horstmann 425, 525, 527
Link L-2-5
Landis & Gyr RWB2
Glowworm Mastermind
34 N L
Landis & Gyr RWB20
Microgyr
Potterton Miniminder 3 4 N L
Potterton EP2000/3000 - 3 4 N L
Link L-5 EP2001/3001
Randall 102/102 E 1 2 E 5 6
Link 3-6
Randall 4033
42 E7 6
31 ENL
Link 1-6
Randall 701, 702
Link L-6-5
Sangamo M5 1 8 E 4 3
Link 1-6
18 E4 3
Sangamo 410 Form 1
Link 3-6
If a room thermostat is not requied on Zone 1, insert a link
between 4 + 5 on the junction box.
If a room thermostat is not requied on Zone 2, insert a link
between 6 + 8 on the junction box.
ZONE 1
PROGRAMMER
ZONE 2 ZONE 2
23
7.2 WIRING DIAGRAM FOR CONNECTION TO AN ARISTON UNVENTED CYLINDER
Based on Honeywell controls
SH009A
14 35 22
T6360B
ROOM
THERMOSTAT
BROWN
BLUE
GREY
ORANGE
10
GREEN/YELLOW
V4043H
HEA TING V ALVE
BROWN
BLUE
GREY
ORANGE
10
GREEN/YELLOW
V4043H
HOT W A TER VALVE
1
BOILER ELECTRICAL SUPPLY CABLE
ENL
9 10 3 2
TYPICAL
JUNCTION BOX 5 2 9
3
1
microGENUS 23-27 MFFI
2
3
Remove internal time clock plug from the the P.C.B. then connect room stat terminal block on the reverse of the boiler control panel
(see section 2.10)
to 9 + 10 on
the junction box.
NL
BOILER
4
610 2 1
ON ON
36 ENL
42 ENL
PROGRAMMER
8 2
5
25 ENL
14 N L
31 N L
74 E1 2
64321
610 2 1
9
6
3
7
Pegler Sunvic
SP 50/100 (Link L-3)
Switchmaster
Symphony, Sonata
Switchmaster 400, 600 3 1 N L
SWITCHMASTER 805, 900
Sunvic ET 1451
Link 2-3-6
Sunvic DHP 2201 6 3 E 1 2
Towerchron FP
Link 1-5/4-7-9
Towerchron MP
Link 1-4/6-11
Towerchron 2000 HW HTG
ACL LS522, LS722 3 4 N L
Randall 922, 972
Link L-2-5
Randall 3020 P
and 3060
L1 N2 E3
240V
MAINS INPUT (3 AMP)
Cylinder
thermostat
1
C/P
2
Thermal
cut-out
1 C/P
8
9
10
63 N L
64321
1
P
2
8
6
Not used
Honeywell ST 699B 1002
Link L-5-8
14 ENL
34 N L
ST 6400/ST 6300 ST 6200 3 4 N L
Drayton Tempus 7 3 4 N L
Horstmann 425, 525, 527
Link L-2-5
Landis & Gyr RWB2
Glowworm Mastermind
34 N L
Landis & Gyr RWB20
Microgyr
Potterton Miniminder 3 4 N L
Potterton EP2000/3000 - 3 4 N L
Link L-5 EP2001/3001
Randall 102/102 E 1 2 E 5 6
Link 3-6
Randall 4033
42 E7 6
31 ENL
Link 1-6
Randall 701, 702
Link L-6-5
Sangamo M5 1 8 E 4 3
Link 1-6
18 E4 3
Sangamo 410 Form 1
Link 3-6
PROGRAMMER
Manufacturer: Merloni TermoSanitari SpA - Italy Commercial subsidiary: MTS (GB) LIMITED
MTS Building Hughenden Avenue High Wycombe Bucks HP13 5FT Telephone:(01494) 755600 Fax:(01494) 459775 internet: http://www.mtsgb.ltd.uk E-mail: info@mtsgb.ltd.uk
Technical Service Hot Line: (01494) 539579
23 99 84 1469 312 - Stampa: bieffe RECANATI
CE Certification Heat Input max/min kW Heat Output max/min kW Efficiency of Nominal Heat Input % Efficiency at 30% of Nominal Heat Input % Heat Loss to the Casing (T=50°C) % Flue Heat Loss with Burner Operating % Flue Heat Loss with Burner Off % Maximum Discharge of Fumes (G20) Kg/h Residual Discharge Head mbar
Consumption at Nominal Capacity(G20) m3/h Gas Consumption after 10 Minutes* m
3
(15°C, 1013 mbar) (G30-G31) Kg/h Temp. of exhaust fumes at nominal capacity °C CO
2
Content %
O
2
Content %
CO Content ppm Minimum Ambient Temperature °C Head Loss on Water Side (max) (T=20°C) mbar Residual Head of System bar Heating Temperature max/min °C Domestic Hot Water Temperature max/min °C D.H.W.Flow Rate ∆T=35°C l/min D.H.W.Flow Rate ∆T=35°C gal/min D.H.W. Minimum Flow Rate l/min Pressure of Domestic Hot Water max/min bar Expansion V essel Capacity l Expansion Vessel Pre-load Pressure bar Maximum Water Content of System l Maximum Heating Pressure bar Nominal Pressure Natural Gas (G20) mbar
LPG (G30-G31) mbar Electrical Supply V/Hz Power Consumption W Protection Grade of Electrical System IP Internal Fuse Rating Weight Kg
G.C. Number
27 MFFI
7. TECHNICAL INFORMATION
63AU4549
25.6/11.0
92.9
91.1
1.0
6.1
0.4
49.5
0.96
2.72
0.32/0.39
2.02/2.00 123
7.2
7.5
51.9 +5
200
0.25
82/42 56/36
9.7
2.2
2.6
8/0.2
6 1
130
3
20
30-37
230 / 50
140
X4D
FAST 2 AT
38
47-116-14
63AU4549
29.8/12.0
93.5
90.7
0.2
6.3
0.4 60
1.60
3.15
0.37
2.34/2.31
128.8
6.9
8.1 48
+5
200
0.25 82/42 56/36
11.4
2.6
2.6
8/0.2
6 1
130
3
20
30-37
230 / 50
155
X4D
FAST 2 AT
39
47-116-15
23 MFFI
*Calculated at 70% maximum output
Servicing Instructions Type C Boilers
G.C.N: 47-116-14
47-116-15
LEAVE THESE INSTRUCTIONS WITH THE END-USER
2
B063
1. SERVICING INSTRUCTIONS
1.1 REPLACEMENT OF PARTS
1.2 TO GAIN GENERAL ACCESS
- Removing the front panel
- Removing the sealed chamber frontal cover
- Removing the side panels
1.3 ACCESS TO THE COMBUSTION CHAMBER
- Removing the combustion cover
- Removing the burner and jets
- Removing the electrodes
- Removing the main heat exchanger
- Removing the air pressure switch
- Removing the fan
- Removing the venturi device
1.4 SERVICING AND REMOVAL OF THE GAS VALVE
- Setting the gas pressures
- Removing the spark generator
- Removing the gas valve
1.5 ACCESS TO THE WATER CIRCUIT
- Removing the D.H.W.(secondary) exchanger
- Removing the safety valve
- Removing the automatic air vent
- Removing the main circuit flow switch
- Removing the pump
- Removing the pressure gauge
- Removing the expansion vessel
- Removing the overheat thermostat
- Removing the heating temperature sensor (N.T.C.)
- Removing the D.H.W.temperature sensor (N.T.C.)
- Removing the divertor valve actuator
- Removing the D.H.W.flow switch
1.6 ACCESS TO THE CONTROL SYSTEM
- Checking the fuses
- Removing the time clock
- Removing the P.C.B.
2. FAULT FINDING
2.1 FAULT FINDING GUIDE (FLOW-CHART)
3. ELECTRICAL DIAGRAMS
4. SHORT SPARE PARTS LIST
TABLE OF CONTENTS
2. The control panel moves downward and when pulled forward,
rotates on two lateral hinges; the panel stays in a semi­horizontal position, which allows access to the inner parts of the boiler (F
IG. 1.2);
3. In order to increase the manouvering space, it is possible to raise the control panel and rotate it to a fully horizontal position (F
IG. 1.3);
4. Remove the screws “B” from the front panel bottom lip (F
IG. 1.4);
5. Lift the front panel from the raised screws at the the top of the casing (FIG. 1.5).
FIG. 1.4
B
FIG. 1.5
3
B063
1. SERVICING INSTRUCTIONS
The life of individual components varies and they will need servicing or replacing as and when faults develop. The fault finding sequence chart in chapter 2 will help to locate which component is the cause of any malfunction, and instructions for removal, inspection and replacement of the individual parts are given in the following pages.
1.1 REPLACEMENT OF PARTS
1.2 TO GAIN GENERAL ACCESS
All testing and maintenance operations on the boiler require the control panel to be lowered. This will also require the removal of the casing.
Removing the front panel
1. Loosen the fastening screws Aof the control panel located on
the lower part of the panel itself. (F
IG. 1.1);
A
FIG. 1.3
FIG. 1.1
FIG. 1.2
To ensure efficient safe operation, it is recommended that the boiler is serviced annually by a competent person.
Before starting any servicing work, ensure both the gas and electrical supplies to the boiler are isolated and the boiler is cool.
Before and after servicing, a combustion analysis should be made via the flue sampling point (please refer to the Installation Manual for further details).
After servicing, preliminary electrical system checks must be carried out to ensure electrical safety (i.e.polarity, earth continuity , resistance to earth and shor t circuit).
19.eps
14.eps
13.eps
FO016A/15.eps
16.eps
4
B063
Removing the sealed chamber frontal cover
1. Remove the screws C(FIG. 1.6);
2. Lift the sealed chamber frontal cover from the locating pins
(FIG. 1.7).
FIG. 1.6
C
C
FIG. 1.7
Removing the side panels
1. Remove the four screws Dfor each side panel (FIG.1.8);
2. Pull the panel away from the boiler, then lift the panel up and
remove from the boiler (FIG.1.9).
D
D
D
FIG. 1.8
FIG. 1.9
18.eps
98.tif
17 eps 97.tif
Removing the electrodes
Before carrying out this procedure, unscrew and slide the burner forward (see previous section).
1. Remove rubber gasket G(Fig. 1.13);
2. To remove the detection electrode disconnect the cable
at its connection point close to the P.C.B. (Fig. 1.14);
FIG. 1.13
G
FIG. 1.14
Removing the burner and jets
1.
Remove the screws “F” from the burner (FIG. 1.11);
2. Remove the burner (FIG. 1.12);
3. Remove the jets using a No.7 socket spanner;
4. Replace in reverse order.
5
B063
Removing the combustion cover
1.
Remove the screws “E” (FIG. 1.10);
2. Lift off the combustion cover.
1.3 ACCESS TO THE COMBUSTION CHAMBER
E
E
E
FIG. 1.10
FIG. 1.11
Fig. 1.12
F
F
99.tif
12 eps
78 eps
49 eps
50 eps
6
B063
3. Remove screw H(FIG. 1.15);
4. Gently slide the electrode downward (FIG.1.16).
To replace, repeat the steps in reverse order, paying particular attention to the following: a -Centre the electrode in the positioning hole carefully,
otherwise the electrode may break;
b -Check that the cables have been connected correctly; c -Check that the rubber gasket covers the cable/ electrode
connection point completely.
FIG. 1.15
FIG. 1.16
H
1. Drain the boiler of water;
2. Release the overheat thermostat sensor I(FIG. 1.17);
3. Release the two connection nuts Jconnecting the
exchanger to the flow and return pipes (FIG. 1.18);
4. Pull it straight out (FIG. 1.19).
Removing the main heat exchanger
FIG. 1.18
J
Fig. 1.17
I
FIG. 1.19
51 eps
11 eps
52 eps
75 eps
76 eps
6 eps
1. Disconnect electrical connections Nand silicon pipes
O(FIG.1.23);
2. Remove screw “Pand remove the fan collar clamp Q
(FIG.1.24);
3. Remove screws R(FIG.1.25);
4. Remove fan and mounting plate (FIG.1.26).
Removing the fan
1. Disconnect the electrical connections Kand silicon pipes
L” from their connection points (F
IG. 1.20);
2. Remove screws “Mon the top of the sealed chamber (FIG. 1.21);
3. Unscrew to remove switch from the plate (FIG. 1.22).
FIG. 1.21
FIG. 1.20
7
B063
Removing the air pressure switch
L
K
M
M
FIG. 1.22
FIG. 1.25
R
R
FIG. 1.24
P
Q
FIG. 1.23
N
N
O
FIG. 1.26
91.tif
90.tif
93.tif
94.tif
95.tif
96.tif
8
B063
1.4 SERVICING AND REMOVAL
OF THE
GAS VALVE
Setting the gas pressures
1
2
3
4
A
B
C
E
F
D
Setting the minimum and the maximum power of the boiler
1. Check that the supply pressure to the gas valve is a minimum of 20 mbar
for natural gas.
2. To do this, remove the screw “A”. Fit the pipe of the pressure gauge to the pressure connection of the gas valve B”. When you have completed this operation, replace the screw
Asecurely
into its housing to seal off the gas.
3. To check the pressure supplied by the gas valve to the burner, remove the screw C. Fit the pipe of the pressure gauge to the pressure outlet of the gas valve
D. Disconnect the compensation pipe either from the gas valve or from the sealed chamber.
4. Set the On/Off button to position < I > and the summer/winterswitch to the winter position. To set the maximum power, turn on the hot water tap and allow the hot water tap to run at a rate of about 8 litres/minute so that the main burner lights. Adjust nut
Eon the modureg to set the gas pressure (displayed on the
pressure gauge) corresponding to the maximum power (see
TABLE A page
9).
5. To set the minimum po wer, disconnect a supply terminal from the modureg and adjust screw F”. Turn the screw clockwise to increase the pressure and coun­ter-clockwise to decrease the pressure (displayed on the pressure gauge) corresponding to the minimum power (see
TABLE A” page
9).
6. When you have completed the above operations, turn off the hot water tap, re-connect the supply terminal to the modureg on the gas valve and replace the cap on the screw of the modureg.
Setting the maximum heating circuit power
7. To set the maximum heating circuit power, place the
On/Off button to position < I > and the “summer/winter” switch to winter position. Turn the knob of the heating thermostat clockwise to maximum.
8. Remove the inspection panel of the P.C.B. and fit a small cross-head
screwdriver in to the right hand potentiometer.Turn clockwise to increase the pressure or counter-clockwise to reduce the pressure. Adjust the setting to the required heating pressure value (displayed on the pressure gauge), as indicated in the diagrams shown in page 10.
9. Turn off the boiler by placing the main switch to the "Off" position.
Setting pressure for soft ignition.
Disconnect the detection electrode connection from the P.C.B.. Start the boiler and during the ignition sequence adjust the left hand potentiometer until the gas pressure reads the required gas pressure as per the table below. Once the gas pressure is set turn off the boiler and re-connect the connection to the P.C.B. NB.:It may be necessary to reset the flame failure reset a number of times during this operation.
VG001Aa
VG001Ac
VG001Ab
VG001Ad
NATURAL GAS (G20) BUTANE GAS (G30) PROPANE GAS (G31)
Recommended pressure for soft-light ignition
8 mbar
16 mbar
16 mbar
9
B063
Regulating the heating power for
natural gas (G20)
Regulating the heating power for
butane gas (G30)
Regulating the heating power for
propane gas (G31)
TABLE “A”
CG007A
CG008A
CG009A
TB012A
model 23 model 27
model 23 model 27
23 MFFI
2.70
1.16 20
11.0
2.0
40 38 36 34
model 23 model 27
2.01 Kg/h
0.87 Kg/h 28 mbar
27.7 mbar
6.0 mbar
2.00 Kg/h
0.85 Kg/h 37 mbar
35.5 mbar
7.3 mbar
27 MFFI
3.15
1.26 20
11.0
1.6
14 x 1.30
12 x 0.77
2.34 Kg/h
0.94 Kg/h 28 mbar
27.7 mbar
4.6 mbar
14 x 0.77
12 x 0.77
2.31 Kg/h
0.93 Kg/h 37 mbar
35.5 mbar
6.0 mbar 14 x 0.77
10
B063
Removing the spark generator
1.
Disconnect ignition leads “T” by pulling upward (FIG. 1.27);
2. Remove the screw V(FIG. 1.28);
3. Remove the spark generator (FIG. 1.29).
10. Remove the pipe from the pressure gauge and connect screw Cto the pressure outlet in order to seal off the gas.
11.Carefully check the pressure outlets for gas leaks (v alve inlet and outlet).
IMPORTANT!
Whenever you disassemble and reassemble the gas connections, always chec k f or leaks using a soap and water solution.
FIG. 1.27
FIG. 1.28
FIG. 1.29
T
V
Soft-light
Adjustment
Max Heating
Adjustment
61.eps
45.eps
43.eps
44.eps
VR015A.eps
11
B063
Important! Before any component is removed, the boiler must be drained of all water.
Removing the D.H.W. (secondary) exchanger
1.Remove the screws Y(FIG 1.33 + FIG 1.34);
2.Push the exchanger tow ards the rear of the boiler , and lift
upwards and remove out of the front of the boiler (FIG 1.35);
3.Before replacing the exchanger ensure that the O-rings are in good condition and replace if necessary.
1.6 ACCESS TO THE WATER CIRCUIT
FIG. 1.30
FIG. 1.31
FIG. 1.32
FIG. 1.33
W
X
X
Removing the gas valve
1.
Disconnect all the cables from the solenoid and modureg;
2. Remove the spark generator (see previous section);
3. Release the top nut W(FIG. 1.30);
4. Remove the screws Xfrom the bottom of the gas valve
pipe (FIG. 1.31);
5. Remove the gas valve (FIG. 1.32).
Y
FIG. 1.34
FIG. 1.35
Y
47.eps
48.eps
38.eps
22.eps
21.eps
68.eps
12
B063
Removing the safety valve
1.
Loosen nut “Z” (FIG. 1.36);
2. Unscrew and remove the valve (FIG. 1.37).
Removing the automatic air vent
1. Unscrew valve top A1(FIG. 1.38);
2. Remove valve (Fig 1.39).
Removing the main circuit flow switch
1.
Remove the cable of the main circuit flow switch “B1” (FIG. 1.40);
2. Remove the screws C1(FIG. 1.41);
3. Remove the main circuit flow switch.
FIG. 1.36
Fig. 1.38
FIG. 1.40
Z
B1
C1
C1
FIG. 1.37
A1
Fig. 1.39
FIG. 1.41
40.eps
37.eps
39.eps
41.eps
53.eps
54.eps
13
B063
Removing the pump
1.
Remove the U-clip “ D1” (FIG. 1.41);
2. Remove the retaining clip E1(FIG. 1.42);
3. Remove the U-clip F1(FIG. 1.43);
4. Release the nut G1(FIG. 1.44);
5. Remove the pipe H1(FIG. 1.45);
6. Remove the screws I1(FIG. 1.46);
7. Remove the pump (FIG. 1.47).
D1
FIG. 1.41
FIG. 1.42
FIG. 1.43
FIG. 1.44
E1
F1
FIG. 1.45
FIG. 1.46
FIG. 1.47
G1
H1
I1
I1
31.eps
33.eps
34.eps
42.eps
32.eps
35.eps
25.eps
14
B063
Removing the expansion vessel
1.
Loosen nuts “K1” and remove the gas pipe (FIG. 1.50);
2. Loosen nut L1(FIG. 1.51);
3. Remove back nut M1(FIG. 1.52);
4. Remove the expansion vessel (FIG. 1.53).
Removing the pressure gauge
1.
Remove the U-clip “J1” and remove the pressure gauge coupling (FIG. 1.48);
2. Push the pressure gauge through the control panel from the rear (FIG. 1.49).
FIG. 1.48
FIG. 1.50
J1
FIG. 1.49
K1
L1
FIG. 1.51
FIG. 1.52
FIG. 1.53
K1
M1
34.eps
27.eps
77.eps
57.eps
58.eps
59.eps
15
B063
Removing the overheat thermostat
1.
Disconnect the overheat thermostat electrical connections N1(FIG. 1.54);
2. Then remove the thermostat from its mounting by releasing the securing clip (FIG. 1.55).
Removing the heating temperature sensor (N.T.C.)
1.
Pull off the electrical connector “P1” and unscrew the sensor probe using a suitable spanner (FIG. 1.56).
FIG. 1.54
FIG. 1.55
Removing the D.H.W. temperature sensor (N.T.C.)
1.
Pull off the electrical connector “Q1” and unscrew the sensor probe using a suitable spanner (FIG. 1.57).
FIG. 1.57
Removing the divertor valve actuator
1. Unplug the electrical connector R1(FIG. 1.58);
2. Release the retaining clip S1and remove the divertor
valve actuator.
FIG. 1.58
Removing the D.H.W. flow switch
1. Unplug the electrical connector T1(FIG. 1.59);
2. Release the retaining clip V1and remove the D.H.W.
flow switch.
FIG. 1.59
N1
P1
Q1
S1
R1
FIG. 1.56
T1
V1
80.eps
83.eps
87.eps
60.eps
74.eps
30.eps
16
B063
Checking the fuses
1.
Remove the inspection cover on the reverse of the control panel (FIG. 1.60);
2. Remove the fuses (FIG. 1.61).
1.6 ACCESS TO THE CONTROL SYSTEM
Removing the time clock
1.
Unplug electrical connection “W1” from the clock (FIG.
1.62);
2. Remove the screws W2(see fig. 1.63);
3. Remove the clock from the panel (see fig. 1.64).
FIG. 1.60
FIG. 1.62
FIG. 1.61
FIG. 1.64
W1
72.eps
61.eps
69.eps
1190.tif
FIG. 1.63
1189.jpg
W2
17
B063
Removing the P.C.B.
1.
Isolate electricity;
2. Remove the inspection cover from the reverse of the
control panel;
3. Unplug all electrical connections from the P.C.B. (FIG.
1.65);
4. Remove the screws X1(FIG. 1.66);
5. Separate the facia panel from the rear of the control
panel (FIG. 1.67);
7. Remove the screws “Y1and remove the P.C.B. (FIG.
1.68).
FIG. 1.66
X1
X1
X1
X1
X1
X1
FIG. 1.65
FIG. 1.67
FIG. 1.68
Y1
Y1
64.eps
1187.eps
65.eps
82.eps
18
B063
2. FAULT FINDING
PRELIMARY CHECKS
MAKE SURE THAT:
IS
THE POWER
L.E.D.
ON?
POSTION
OF THE
SELECTOR
NO
NO
WINTERES TAT ESUMMER
NONO
YESYES
YESYES
YESYES
YESYES
YESYES
NONO
NONO
NONO
NONO
NONO
NONO
NONO
YESYES
YESYES
YESYES
1 - Check the fuses 2 - Check the power supply cable, plug and outlet 3 - Check/replace the power supply to the P.C.B.
TURN ON THE ON/OFF
SWITCH
D.H.W. IS
BEING DRAWN?
D.H.W. IS
BEING DRAWN?
FOR BOILERS
WITH ELECTRONIC
ANTI-FROST DEVICE:
PROTECTION IS ACTIVATED
IF HEATING TEMP
IS < 5
°
C
FOR BOILERS
WITH ELECTRONIC
ANTI-FROST DEVICE:
PROTECTION IS ACTIVATED
IF HEATING TEMP
IS < 5
°
C
MUST
TIME CLOCK
AND/OR ROOM
THERMOSTAT
BE ACTIVATED?
A
ECONOMY/
COMFORT
SELECTOR
TEMP.
C.H. < 34°C
Comfort
Comfort
Economy
Economy
1 - There is sufficient water in the system 2 - The gas is turned on 3 - The electrical supply is turned on
1 - Check/reset system pressure 2 - Check/restore gas supply 3 - Check/replace short­ circuited heating probe 4 - Check/replace siezed pump
1 - Check/reset the system pressure 2 - Check/restore gas supply 3 - Check/replace short­ circuited heating probe 4 - Check/replace siezed pump
TEMP.
C.H. < 34°C
ECONOMY/
COMFORT
SELECTOR
It is possible to detect and correct any defect by using the standard fault finding diagrams described in this chapter.
2.1 FAULT FINDING GUIDE (FLOW-CHARTS)
FC004Aa
19
B063
IS THE PUMP
RUNNING?
YES
NO
NO
NO
YES
YESYES
POWER T O
THE PUMP?
DOES THE
"NO WA TER" L.E.D.
ILLUMINATE
(WITHIN 40 SECS)?
1 - Check if there is air in the system 2 - Check main circuit flow switch operation 3 - Check pressure on the water gauge and fill system to return to 1 bar
1 - Turn the boiler off then on (protection reset)
1 - Check that the pump is not stuck 2 - Release/replace pump
1 - Check pump cable 2 - Check/replace P.C.B. 3 - Check main flow main switch operation when drawing D.H.W.
A
B
FC004Ab
20
B063
IS THE FAN
RUNNING?
BOILER
SHUTDOWN?
POWER
TO FAN?
NO
YES
YES
YES
NO
YES
NO
NO
NO
YES
1 - Check/replace main circuit flow switch 2 - Check/replace connection cable 3 - Check/replace P.C.B.
1 - Check/replace air pressure switch 2 - Check if reset button is jammed 3 - Check/replace flame detection electrodes
1 - Check/replace connection cable 2 - Check/replace P.C.B. 3 - Check/replace air pressure switch
1 - Replace fan
1 - Reset the boiler
PUMP PROTECTION
ACTIVATED?
INTERNAL
P.C.B. PROTECTION
ACTIVATED?
B
C
FC004Ac
21
B063
IS THE BURNER
ALIGHT?
YES
NO
YES
YES
YES
NO
NO
NO
NO
YES
1 - Check/replace ignition electrode 2 - Check ignition cable 3 - Check spark generator 4 - Check ignition electrode cable 5 - Check/replace P.C.B.
1 - Check if flame strikes detection electrode 2 - Check soft-light gas pressure 3 - Check/replace detection electrode 4 - Check/replace P.C.B.
1 - Check power supply of gas valve 2 - Check/replace P.C.B. 3 - Check efficiency of gas valve 4 - Replace gas valve
Shutdown L.E.D. off
fan restarts
IS THE
AIR PRESSURE SWITCH
ACTIVATED?
CHECK
P ON TEST
PRESSURE
INTAKE
IS FLUE
DISCHARGE
NORMAL?
HAS THE
BOILER SAFETY
SHUTDOWN BEEN
ACTIVATED?
HAS THE
BOILER SAFETY
SHUTDOWN BEEN
ACTIVATED?
1 - Check exhaust discharge 2 - Check venturi & pipes 3 - Check fan efficiency
1 - Check A.P. switch cable 2 - Check/replace A.P. switch 3 - Check/replace P.C.B.
C
D
P 1.2 mbar
P 1.2 mbar
FC004Ad
22
B063
IS
THERE STILL
A PROBLEM?
NORMAL
OPERATION
NO
YES
FAULTS
POSSIBILE CAUSES
1
2
3
4
5
6
7
8
9
D
Drawing D.H.W: When you turn on a tap burner switches off
Drawing D.H.W: radiators heat up in summer mode
Drawing D.H.W: insufficient hot water temperature
Drawing D.H.W: noisy operation
Decrease/increase heating circuit pressure
Repeated shutdowns
Repeated intervention of safety thermostat
When cold water tap turned off, the boiler ignites
Insufficient radiator temperature
- air in secondary heat exchanger
- faulty main circuit flow switch
- faulty D.H.W. flow switch
- faulty 3-way valve
- check C.H./D.H.W. temperature probes
- check gas pressures
- check water flow rate
- check secondary heat exchanger
- primary heat exchanger faulty or lime-scale deposits
- low heating system water pressure
- check gas pressures
-
check C.H./D.H.W. temperature probes
- check for leaks on the heating circuit
- faulty filling-loop
- faulty secondary heat exchanger
- expansion vessel faulty
- faulty detection electrodes
- check gas settings
- check flame detection electric circuit
- C.H./D.H.W. temperature probes open circuit
- overheat thermostat not calibrated correctly
- air in primary water circuit
- drop in pressure in the water mains, with consequent water hammer
- check C.H. temperature probe
- check by-pass
- check gas pressures
FC004Ae
23
B063
3. ELECTRICAL DIAGRAMS
LEGEND:
A = Time Clock Connector B = Central Heating Selection (Winter) and
Temperature Adjustment C = Connector for Total Check System D = Domestic Hot Water Temperature Adjustment E = Soft-light Adjustment F = Maximum Heating Adjustment G = On/Off Switch H = On/Off L.E.D. I = Fume Sensor L.E.D. J = Ignition Failure (Lockout) L.E.D. K = Low System Water Level/Lack of Circulation L.E.D. L = Reset Button M = Economy/Comfort Selector N = Overheat L.E.D. O = Temperature L.E.D.s P = Transformer Q = Circulation Pump Relay R = Fan Relay S = Gas Valve Relay T = Motorised Diverter Valve Relay V = Spark Generator U = Anti-cycling Device Adjustment for Heating
A01 = Circulation Pump A02 = Fan A03 = Spark Generator/Gas Valve Supply A04 = Motorised Diverter Valve A05 = Flame Detection Circuit A06 = Detection Electrode A07 = Main Circuit Temperature Probe A08 = Domestic Hot Water Temperature Probe A09 = Domestic Hot Water Flow Switch A10 = Main Circuit Flow Switch A11 = Modulator A12 = Air Pressure Switch A13 = Safety Thermostat A14 = External (Room) Thermostat
Colours: Gry = Grey Wh = White Pnk = Pink Brn = Brown Bl = Blue Blk = Black Rd/Blk = Red/Black
24
B063
microGENUS 23/27 MFFI
JK
SE017A
SF014A
Blk
Blk
Gry
Gry
Pnk
Pnk
Blk
Blk
Wh
Gry
Gry
Rd/Blk
ON
Pnk
Wh
Wh
Blk
Blk
SQT
Wh
Brn
R
Wh
Rd/Blk
Brn
Rd/Blk
Wh
Wh
Brn
Brn
Blk
K
L
M
UJ
25
B063
4. SHORT SPARE PARTS LIST
microGENUS 23/27 MFFI
1
2
3
4
9 95762 596061 56
63
56
55 53
58
54
52 51
50
304
5
6 7
8 9
10
11 12 13
14
15
16
17
12
13
77
64
5
9
10
70
78
9
65
66
67
68
69
71
72 73
76
77
79
75
80
81
9
56
74
84
83
82
87
14
108
107
106
105
104
103
102
71
100
14
85 86
88
56
101
98
99
95
93
91
25
90
89
301 302 303
96
42
94
92
49
48
47
97
46
45
44
43
42 41
34 40
331
332
code 998613
code 998099
371
372
373
374
375
1814 18 22
334
333
2320 2119 3635 38
code 998940
311
351
2826 2724 25 34
32 333029 31
codes 998836
999091
352
353
354
code 997089
MODELS CHARACTERISTICS SERIAL NO:
VALIDITY
MICROGENUS 23 MFFI METHANE 2320005600001 A MICROGENUS 23 MFFI LPG 2320005600001 B
321
MICROGENUS 27 MFFI METHANE 2320005600001 C MICROGENUS 27 MFFI LPG 2320005600001 D
37 39
REF.
26
B063
microGENUS 23/27 MFFI
998616 573521 998077 573520 997147 997077 569236 998613 571547 998099 998940 998424 574279 998645 997089 998836 999091 999599 998947 999245 573989 571651 999397 998894 997206 998620 998893 998618 998669 998887 998939 571646 573295 573825 573172 998623 998622 998624 998941 997029 998490 998718 998975 998974 998644 998643 998738 998961 999207 571547 571772 571771 571770 998172 998716 998717
Key
no.
G.C. part
no.
ARISTON
Part No.
Description
2
5 12 14 16 17 18 19 20 21 24 25 26 27 28 33 AB 33 CD 38 41 43
52AB 52CD 66AB 66CD
72
74AB
74CD
75C
75D 76AB 76CD
75A
75B
77 79 98 99
100 311 321 331 332 333 334 351 352 353 354 AB 354 CD 371 372 373 374 375 381 382
379816
E61 468 164 282 E61 475 164 225 E25 427 E61 429 164 338 E61 478 E24 077 E61 479 E61 482 E61 483 E25 529 E61 848 E61 485 E61 490 E61 881
E61 519 E61 520 E61 530 E03 818
E61 967 E25 425
E61 546 E61 547 E61 549 E61 972 E61 974 E26 767 E26 657 E26 658 E26 378 E61 565 E61 567 E61 569
E25 582 E61 647 E61 648 E61 649 E61 650 E61 652 E61 654 E61 656 E61 660 E62 030 E24 077 E24 077 E24 076 E24 075 E61 663 E61 665 E61 667
Expansion vessel Gasket 3/8" O-ring Gasket 3/4" Motor (3- Way valve) Fixing clip (motor) Temperature probe (C.H.W.) Flow group Diaphragm (main flow switch) Main circuit flow switch Return group O-ring Gasket Spark generator Gas valve (SIT 845 SIGMA) Pump Pump Time clock P.C.B. (CMP1-FFI) Pressure gauge Air pressure switch Air pressure switch Fan Fan Thermostat (overheat) Main exchanger Main exchanger Burner 12 ramp (natural gas) Burner 12 ramp (LPG) Burner 14 ramp (natural gas) Burner 14 ramp (LPG) Secondary exchanger (p-type 23kW) Secondary exchanger (p-type 27kW) O-ring (secondary exchanger) Safety valve (1/2" 3 bar) Electrode (Ignition R.H.) Electrode (Ignition L.H.) Detection electrode D.H.W. actuator kit Operator coils (SIT SIGMA) Central heating by-pass kit Heating spring kit 3-way spring kit Actuator bush Gasket (auto air vent) Auto air vent Gasket (pump head) Pump head (Gold 15/5) Pump head Diaphragm (main flow switch) Magnet (main flow switch) Spring (main flow switch) Main flow switch top cap Main flow switch reed system Burner jet 1.25 full kit (Natural gas) Burner jet 0.72 full kit (LPG)
1 1
1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1
1 1
1 1
1 1 1
1 1 1 1 1 1 1 1 1 1 1 1
23 99 84 1470 312 - Stampa: Bieffe Recanati
Manufacturer: Merloni TermoSanitari SpA - Italy Commercial subsidiary: MTS (GB) LIMITED
MTS Building Hughenden Avenue High Wycombe Bucks HP13 5FT Telephone: (01494) 755600 Fax:(01494) 459775 internet: http://www.mtsgb.ltd.uk E-mail: info@mtsgb.ltd.uk
Technical Service Hot Line: (01494) 539579
SPARE PARTS EXPLODED VIEW GAS WALL BOILERS
Models
MICROGENUS 23 MFFI MICROGENUS 27 MFFI
Edition 1 of 1 December 1999
9 95762 596061 56
58
55 53
54
4
10
11 12
13
14
15
16
17
52 51
1
50
2
63
3
56
80
81
72
82
9
56
85
14
105
104
103
102
101
100
99
69
14
83 84
86
97
25
96
56
98
87
92
95
93
42
91
90 89 88
65
74
75
9
64
66
67
69
70
71
73
77
78
79
5
12
75
13
76
5
9
10
68
6 7
8 9
304
301 302 303
94
49
48
47 46
45
44
43
42 41
34 40
331
332
code 998613
code 998099
371
372
373
374
375
1814 18 22
334
333
2320 2119 3635 38
code 998940
311
351
2826 2724 25 34
32 333029 31
code 998836
352
353
354
code 997089
MODELS CHARACTERISTICS SERIAL NO:
VALIDITY
MICROGENUS 23 MFFI METHANE 9932200020 A MICROGENUS 23 MFFI LPG 9932300018 B
321
MICROGENUS 27 MFFI METHANE 9932500011 C MICROGENUS 27 MFFI LPG 9932400027 D
37 39
REF.
PART. CODE DESCRIPTION REF. NOTE
1 ------ Frame 11 2 998616 Expansion vessel 3 998776 Bush 4 998581 3/8" lock nut 5 573521 3/8" gasket 6 998584 Pipe (expansion vessel) 7 998580 Cable holder 8 ------ Hydraulic group support 11
9 570717 Spring (fastening) 10 998569 Pivot 11 998589 By-pass pipe 12 998077 O-ring gasket 13 998064 Spring (by-pass pipe) 14 573520 Gasket 3/4" 15 998815 Pipe (flow) 16 997147 Motor (3-Way valve) 17 997077 Fixing clip (motor) 18 569236 Temperature probe (C.H.W.) 19 998613 Flow group 20 571547 Diaphragm (main flow switch) 21 998099 Main circuit flow switch 22 998632 Cable (temperature probes) 23 999075 D.H.W. flow switch 24 998940 Return group 25 998424 O-ring 26 574279 Gasket 27 998645 Spark generator 28 997089 Gas valve (SIT 845 SIGMA) 29 998606 Pump bracket 30 998568 Pump plug 31 997182 Gasket 32 998452 Lock washer 33 998836 Pump 34 998570 L.E.D. 35 998575 Spindle (temperature knob) 36 998603 Control knob 37 998572 Spindle (on/off knob) 38 997207 Time clock 39 998827 Front cover 40 998824 Control panel 41 998642 Printed circuit board (CMP1-FFI) 42 569711 Nylon bush (10mm) 43 998625 Pressure gauge 44 ------ Control panel 11 45 ------ Cable holder cover 11 46 571548 Clip (Main Flow Switch) 47 998861 Cable (power supply) 48 998859 High voltage wiring 49 998863 Low voltage wiring 50 573327 "Y" piece (air pressure) 51 571575 Silicone pipe (positive signal) 52 571651 Air pressure switch CD 52 573989 Air pressure switch AB 53 997203 Support plate (Air pressure switch) 54 573329 Pressure intake cover 55 569662 Silicone pipe 56 998516 10x6 adhesive gasket 57 ------ Sealed chamber 11 58 998565 Cover (flue test point) 59 998636 Gasket (flue test point) 60 998602 Flue (exhaust manifold/header) 61 998637 Flange gasket 62 998595 Plug (air intake) 63 998648 Sealed chamber wiring 64 998566 Fixing clamp (fan)
PART. CODE DESCRIPTION REF. NOTE
65 998601 Fixing plate (fan) AB 66 998621 Fan AB 66 998894 Fan CD 67 998640 Insulation panel (Rear) AB 67 998896 Insulation panel (Rear) CD 68 998600 Panel (combustion chamber - L.H. side) 69 998639 Insulation panel (Side) 70 997206 Thermostat (overheat) 71 998583 Fixing spring (Limit thermostat) 72 998620 Main exchanger AB 72 998893 Main exchanger CD 73 998618 Burner 12 ramp (natural gas) A 73 998669 Burner 12 ramp (LPG) B 73 998887 Burner 14 ramp (natural gas) C 73 998939 Burner 14 ramp (LPG) D 74 571646 Secondary exchanger (p-type 23kW) AB 74 573295 Secondary exchanger (p-type 27kW) CD 75 573825 O-Ring (secondary exchanger) 76 998629 Cable (3-way valve motor) 77 998567 Safety valve exhaust pipe ring nut 78 573176 Pipe (safety valve outlet) 79 573172 Safety valve (1/2" 3 bar) 80 573576 Compensation tube 81 573325 Rivet 82 569443 Silicone seal 83 572138 Burner jet washer 84 998714 Burner jet (NG 1.30) AC 84 998715 Burner jet (LPG 0.77) BD 85 998729 Pipe (gas valve) 86 998732 Pipe (C.H. return) 87 997153 U-clip 88 998604 Reset button 89 998571 Reset button (insert) 90 998605 Selector button (comfort) 91 998579 Spindle (comfort) 92 998862 Cable (detection electrode) 93 569720 Blind grommet 94 998517 Gasket 95 998623 Electrode (Ignition R.H.) 96 998622 Electrode (Ignition L.H.) 97 998624 Detection electrode 98 998147 Ignition electrode cable rubber 99 998599 Panel (combustion chamber - R.H.side)
100 998598 Panel (combustion chamber front) AB 100 998924 Panel (combustion chamber front) CD 101 998719 Flue hood AB 101 998925 Flue hood CD 102 998638 Insulation panel (Front) AB 102 998895 Insulation panel (Front) CD 103 998076 View window glass gasket 104 998075 View window glass 105 998610 Panel (front - sealed chamber)
301 998477 Case panel (L.H. side) 302 998596 Insert case 303 998476 Case panel (R.H. side) 304 998607 Panel (front case)
311 998941 D.H.W. actuador kit
321 997029 Operator coils (Sit Sigma)
331 998490 Central heating by-pass kit 332 998718 3-Way spring kit (C.H.) 333 571447 3-Way spring kit
PART. CODE DESCRIPTION REF. NOTE
334 998013 Heating actuador bush
351 998644 O-ring (A.A.V.) 352 998643 Auto Air Vent 353 998738 Gasket (pump head) 354 998961 Pump head
371 571547 Diaphragm (main flow switch) 372 571772 Magnet (main flow switch) 373 571771 Spring (main flow switch) 374 571770 Main flow switch top cap 375 998172 Main flow switch reed system
381 998716 Natural gas burner jet full kit 12 382 998717 LPG burner jet full kit 12
NOTE DESCRIPTION
11 Not supplied as a spare part
12 Not illustrated
SPARE PARTS EXPLODED VIEW GAS WALL BOILERS
Models
MICROGENUS 23 MFFI MICROGENUS 27 MFFI
Edition 1 of 1 December 1999
9 95762 596061 56
58
55 53
54
4
10
11 12
13
14
15
16
17
52 51
1
50
2
63
3
56
80
81
72
82
9
56
85
14
105
104
103
102
101
100
99
69
14
83 84
86
97
25
96
56
98
87
92
95
93
42
91
90 89 88
65
74
75
9
64
66
67
69
70
71
73
77
78
79
5
12
75
13
76
5
9
10
68
6 7
8 9
304
301 302 303
94
49
48
47 46
45
44
43
42 41
34 40
331
332
code 998613
code 998099
371
372
373
374
375
1814 18 22
334
333
2320 2119 3635 38
code 998940
311
351
2826 2724 25 34
32 333029 31
code 998836
352
353
354
code 997089
MODELS CHARACTERISTICS SERIAL NO:
VALIDITY
MICROGENUS 23 MFFI METHANE 9932200020 A MICROGENUS 23 MFFI LPG 9932300018 B
321
MICROGENUS 27 MFFI METHANE 9932500011 C MICROGENUS 27 MFFI LPG 9932400027 D
37 39
REF.
PART. CODE DESCRIPTION REF. NOTE
1 ------ Frame 11 2 998616 Expansion vessel 3 998776 Bush 4 998581 3/8" lock nut 5 573521 3/8" gasket 6 998584 Pipe (expansion vessel) 7 998580 Cable holder 8 ------ Hydraulic group support 11
9 570717 Spring (fastening) 10 998569 Pivot 11 998589 By-pass pipe 12 998077 O-ring gasket 13 998064 Spring (by-pass pipe) 14 573520 Gasket 3/4" 15 998815 Pipe (flow) 16 997147 Motor (3-Way valve) 17 997077 Fixing clip (motor) 18 569236 Temperature probe (C.H.W.) 19 998613 Flow group 20 571547 Diaphragm (main flow switch) 21 998099 Main circuit flow switch 22 998632 Cable (temperature probes) 23 999075 D.H.W. flow switch 24 998940 Return group 25 998424 O-ring 26 574279 Gasket 27 998645 Spark generator 28 997089 Gas valve (SIT 845 SIGMA) 29 998606 Pump bracket 30 998568 Pump plug 31 997182 Gasket 32 998452 Lock washer 33 998836 Pump 34 998570 L.E.D. 35 998575 Spindle (temperature knob) 36 998603 Control knob 37 998572 Spindle (on/off knob) 38 997207 Time clock 39 998827 Front cover 40 998824 Control panel 41 998642 Printed circuit board (CMP1-FFI) 42 569711 Nylon bush (10mm) 43 998625 Pressure gauge 44 ------ Control panel 11 45 ------ Cable holder cover 11 46 571548 Clip (Main Flow Switch) 47 998861 Cable (power supply) 48 998859 High voltage wiring 49 998863 Low voltage wiring 50 573327 "Y" piece (air pressure) 51 571575 Silicone pipe (positive signal) 52 571651 Air pressure switch CD 52 573989 Air pressure switch AB 53 997203 Support plate (Air pressure switch) 54 573329 Pressure intake cover 55 569662 Silicone pipe 56 998516 10x6 adhesive gasket 57 ------ Sealed chamber 11 58 998565 Cover (flue test point) 59 998636 Gasket (flue test point) 60 998602 Flue (exhaust manifold/header) 61 998637 Flange gasket 62 998595 Plug (air intake) 63 998648 Sealed chamber wiring 64 998566 Fixing clamp (fan)
PART. CODE DESCRIPTION REF. NOTE
65 998601 Fixing plate (fan) AB 66 998621 Fan AB 66 998894 Fan CD 67 998640 Insulation panel (Rear) AB 67 998896 Insulation panel (Rear) CD 68 998600 Panel (combustion chamber - L.H. side) 69 998639 Insulation panel (Side) 70 997206 Thermostat (overheat) 71 998583 Fixing spring (Limit thermostat) 72 998620 Main exchanger AB 72 998893 Main exchanger CD 73 998618 Burner 12 ramp (natural gas) A 73 998669 Burner 12 ramp (LPG) B 73 998887 Burner 14 ramp (natural gas) C 73 998939 Burner 14 ramp (LPG) D 74 571646 Secondary exchanger (p-type 23kW) AB 74 573295 Secondary exchanger (p-type 27kW) CD 75 573825 O-Ring (secondary exchanger) 76 998629 Cable (3-way valve motor) 77 998567 Safety valve exhaust pipe ring nut 78 573176 Pipe (safety valve outlet) 79 573172 Safety valve (1/2" 3 bar) 80 573576 Compensation tube 81 573325 Rivet 82 569443 Silicone seal 83 572138 Burner jet washer 84 998714 Burner jet (NG 1.30) AC 84 998715 Burner jet (LPG 0.77) BD 85 998729 Pipe (gas valve) 86 998732 Pipe (C.H. return) 87 997153 U-clip 88 998604 Reset button 89 998571 Reset button (insert) 90 998605 Selector button (comfort) 91 998579 Spindle (comfort) 92 998862 Cable (detection electrode) 93 569720 Blind grommet 94 998517 Gasket 95 998623 Electrode (Ignition R.H.) 96 998622 Electrode (Ignition L.H.) 97 998624 Detection electrode 98 998147 Ignition electrode cable rubber 99 998599 Panel (combustion chamber - R.H.side)
100 998598 Panel (combustion chamber front) AB 100 998924 Panel (combustion chamber front) CD 101 998719 Flue hood AB 101 998925 Flue hood CD 102 998638 Insulation panel (Front) AB 102 998895 Insulation panel (Front) CD 103 998076 View window glass gasket 104 998075 View window glass 105 998610 Panel (front - sealed chamber)
301 998477 Case panel (L.H. side) 302 998596 Insert case 303 998476 Case panel (R.H. side) 304 998607 Panel (front case)
311 998941 D.H.W. actuador kit
321 997029 Operator coils (Sit Sigma)
331 998490 Central heating by-pass kit 332 998718 3-Way spring kit (C.H.) 333 571447 3-Way spring kit
PART. CODE DESCRIPTION REF. NOTE
334 998013 Heating actuador bush
351 998644 O-ring (A.A.V.) 352 998643 Auto Air Vent 353 998738 Gasket (pump head) 354 998961 Pump head
371 571547 Diaphragm (main flow switch) 372 571772 Magnet (main flow switch) 373 571771 Spring (main flow switch) 374 571770 Main flow switch top cap 375 998172 Main flow switch reed system
381 998716 Natural gas burner jet full kit 12 382 998717 LPG burner jet full kit 12
NOTE DESCRIPTION
11 Not supplied as a spare part 12 Not illustrated
Loading...