4.2ADJUSTING THE GAS PRESSURES
(SIT SIGMA)PAGE.26
ADJUSTING THE GAS PRESSURES
(HONEYWELL)PAGE.28
6.3.1 REMOVING THE
COMBUSTION CHAMBERPAGE.33
6.3.2 REMOVING THE BURNER
JETSPAGE.33
AND
6.3.3 REMOVING THE
ELECTRODESPAGE.33
6.3.4 REMOVING THE MAIN HEAT
EXCHANGERPAGE.34
6.3.5 REMOVING THE AIR
PRESSURE SWITCHPAGE.35
6.3.6 R
EMOVING THE FANPAGE.35
6.4ACCESS TO THE GAS VALVEPAGE.36
6.4.1 REMOVING THE SPARK
GENERATOR (SIT SIGMA)PAGE.36
6.4.2 REMOVING THE SPARK
GENERATOR (HONEYWELL)PAGE.36
6.4.3 R
EMOVING THE GAS VALVE
(SIT SIGMA)PAGE.37
6.4.4 REMOVING THE GAS VALVE
(HONEYWELL)PAGE.37
6.5A
CCESS TO THE WATER CIRCUITPAGE.38
6.5.1 REMOVING THE PUMP
PRESSURE SWITCHPAGE.38
6.5.2 R
EMOVING THE SAFETY
VALVEPAGE.38
6.5.3 REMOVING THE AUTOMATIC
AIR VENTPAGE.38
6.5.4 REMOVING THE PUMPPAGE.39
6.5.5 REMOVING THE PRESSURE
GAUGEPAGE.40
6.5.6 R
EMOVING THE EXPANSION
VESSELPAGE.40
6.5.7 REMOVING THE OVERHEAT
THERMOSTATPAGE.41
6.5.8 REMOVING THE CENTRAL
HEATING TEMPERATURE
SENSOR (N.T.C.)PAGE.41
6.5.9 REMOVING THE D.H.W.
TEMPERATURE SENSOR
(N.T.C.)PAGE.41
6.5.10 REMOVING THE D.H.W.
FLOW SWITCHPAGE.42
6.6ACCESS TO THE CONTROL SYSTEMPAGE.42
6.6.1 C
HECKING THE FUSESPAGE.42
6.6.2 REMOVING THE TIME CLOCKPAGE.43
6.6.3 REMOVING THE P.C.B.PAGE.43
5. MAINTENANCEPAGE.30
6. SERVICING INSTRUCTIONSPAGE.31
6.1R
6.2TO GAIN GENERAL ACCESSPAGE.31
6.2.1 R
6.2.2 REMOVING THE SEALED
6.2.3 REMOVING THE SIDE
6.3A
2
EPLACEMENT OF PARTSPAGE.31
EMOVING THE FRONT
PANELPAGE.31
CHAMBER FRONT PANELPAGE.32
PANELSPAGE.32
CCESS TO THE COMBUSTION
CHAMBERPAGE.33
7. FAULT FINDINGPAGE.44
7.1F
AULT FINDING GUIDE
(FLOW-CHARTS)PAGE.44
8. SHORT SPARE PARTS LISTPAGE.49
9. TECHNICAL INFORMATIONPAGE.52
1.GENERAL
INFORMATION
This manual is an integral and essential part of the product. It should be kept
with the appliance so that it can be consulted by the user and our authorised
personnel.
Please carefully read the instructions and notices about the unit contained in
this manual, as they provide important information regarding the safe
installation, use and maintenance of the product.
For operating instructions please consult the separate Users Manual.
1.1GENERAL INSTRUCTIONS
Read the instructions and recommendations in these Installation and Servicing
Instructions carefully to ensure proper installation, use and maintenance of the
appliance.
Keep this manual in a safe place. You may need it for your own reference while
Servicing Technicians or your installer may need to consult it in the future.
This is a combined appliance for the production of central heating (C.H.) and
domestic hot water (D.H.W.).
This appliance
The manufacturer declines all liability for damage caused by improper or
negligent use.
No asbestos or other hazardous materials have been used in the fabrication of
this product.
Before connecting the appliance, check that the information shown on the data
plate and the table in section 7 comply with the electric, water and gas mains of
the property.You will find the data plate on the reverse of the control panel.
The gas with which this appliance operates is also shown on the label at the
bottom of the boiler.
Do not install this appliance in a damp environment or close to equipment
which spray water or other liquids.
Do not place objects on the appliance.
Do not allow children or inexperienced persons to use the appliance without
supervision.
must be used only for the purpose for which it is designed.
If you smell gas in the room,
telephone or any other object which might cause sparks.
Open doors and windows immediately to ventilate the room.
Shut the gas mains tap (at or adjacent to the gas meter) or the valve of the gas
cylinder and call your Gas Supplier immediately.
If you are going away for a long period of time, remember to shut the mains gas
tap or the gas cylinder valve.
Always disconnect the appliance either by unplugging it from the mains or
turning off the mains switch before cleaning the appliance or carrying out
maintenance.
In the case of faults or failure, switch off the appliance and turn off the gas
tap. Do not tamper with the appliance.
For repairs, call your local Authorised Servicing Agent and request the use of
original spare parts. For in-guarantee repairs contact MTS (GB) Limited.
do not turn on or off light switches, use the
3
1.2OVERALL VIEW
LEGEND:
1.Flue connector
2.Air intake for twin pipe flue systems
3.Fan
4.Combustion chamber hood
5.“Twin-pass” heat exchanger
6.Domestic hot water temperature probe
7.Combustion chamber
8.Combustion chamber insulation panel
9.Burner
10.Detection electrode
11.Ignition electrodes
12.Gas valve
13.Spark generator
14.Pump pressure switch
15.Safety valve (3 bar)
16.Automatic By-pass
17.D.H.W. Flow switch
18.Domestic hot water inlet filter
19.Circulation pump with automatic air release valve
20.Safety thermostat
21.Main circuit temperature probe
22.Expansion vessel
23.Air pressure switch tube
24.Air pressure switch
25.Combustion analysis points
IN028C
2.INSTALLATION
2.1REFERENCE STANDARDS
FIG. 1.0
The technical information and instructions provided herein
below are intended for the installer / Servicing Technician
so that the unit may be installed and serviced correctly and
safely.
In the United Kingdom the installation and initial start up of
the boiler must be by a CORGI Registered Installer in
accordance with the installation standards currently in
effect, as well as with any and all local health and safety
standards i.e. CORGI.
In the Republic of Ireland the installation and initial start up
of the appliance must be carried out by a Competent
Person in accordance with the current edition of I.S.813
“Domestic Gas Installations”, the current Building
Regulations, reference should also be made to the current
ETCI rules for electrical installation.
This appliance must be installed by a competent
installer in accordance with current Gas Safety
(installation & use) Regulations.
The installation of this appliance must be in accordance
with the relevant requirements of the Local Building
Regulations, the current I.E.E. Wiring Regulations, the
bylaws of the local water authority, in Scotland, in
accordance with the Building Standards (Scotland)
Regulation and Health and Safety document No. 635
4
“Electricity at work regulations 1989” and in the Republic of
Ireland with the current edition of I.S. 813, the Local
Building Regulations (IE).
C.O.S.H.H.
Materials used in the manufacture of this appliance are
non-hazardous and no special precautions are required
when servicing.
Installation should also comply with the following British
Standard Codes of Practice
BS 7593:1992Treatment of water in domestic hot water
central heating systems
BS 5546:1990Installation of hot water supplies for
domestic purposes
BS 5440-1:2000 Flues
BS 5440-2:2000 Air supply
BS 5449:1990Forced circulation hot water systems
BS 6798:1987Installation of gas fired hot water boilers of
rated input not exceeding 60kW
BS 6891:1989Installation of low pressure gas pipe up to
28mm
BS 7671:2001IEE wiring regulations
BS 4814:1990Specification for expansion vessels
BS 5482:1994Installation of L.P.G.
2.2SITING THE APPLIANCE
and in the Republic of Ireland in accordance with the
following Codes of Practice:
I.S. 813Domestic Gas Installations
The appliance may be installed in any room or indoor area,
although particular attention is drawn to the requirements
of the current I.E.E. Wiring Regulations, and in Scotland,
the electrical provisions of the Building Regulations
applicable in Scotland, with respect to the installation of
the combined appliance in a room containing a bath or
shower, the location of the boiler in a room containing a
bath or shower should only be considered if there is no
alternative.
Where a room-sealed appliance is installed in a room
containing a bath or shower the appliance and any
electrical switch or appliance control, utilising mains
electricity should be situated so that it cannot be
touched by a person using the bath or shower,
specifically in accordance with current IEE Wiring
Regulations.
The location must permit adequate space for servicing and
air circulation around the appliance as indicated in Section
2.4.
The location must permit the provision of an adequate flue
and termination.
For unusual locations special procedures may be
necessary.
BS 6798-1987 gives detailed guidance on this aspect.
A compartment used to enclose the appliance must be
designed specifically for this purpose. No specific
ventilation requirements are needed for the installation
5
within a cupboard.
This appliance is not suitable for outdoor installation.
The type C appliances (in which the combustion
circuit, air vent intake and combustion chamber are
air-tight with respect to the room in which the
appliance is installed) can be installed in any type of
room.
Secondary ventilation is not required with this boiler. The
boiler must be installed on a solid, non-combustible,
permanent wall to prevent access from the rear.
2.3OVERALL DIMENSIONS
LEGEND:
A = Central Heating Flow (3/4”)
B = Domestic Hot Water Outlet (1/2”)
C = Gas Inlet (3/4”)
D = Domestic Cold Water Inlet (1/2”)
E = Central Heating Return (3/4”)
FIG. 2.1
QT002A
2.4CLEARANCES
In order to allow access to the interior of the boiler for
maintenance purposes, the boiler must be installed in
compliance with the minimum clearances indicated in FIG.
2.2
FIG. 2.2
6
DM001B
2.5 MOUNTING THE APPLIANCE
After removing the boiler from its packaging, remove the
template from the separate box containing the connection
OTE: Pay particular attention to any test water that
kit. N
may spill from the appliance.
Place the template in the position the appliance is to be
mounted and after ensuring it is hanging squarely, use it to
drill the holes for the hanging bracket and flue pipe(s)
For further information relating to the flue installation
please refer to Section 2.9 FLUE CONNECTION. (If the
appliance is to be fitted on a wall of combustible material,
the wall must be protected by a sheet of fireproof
material).
If the appliance is to be fitted into a timber framed building,
guidance should be sought from the Institute of Gas
Engineers document R
EF: IGE/UP/7.
2.5.1.Drill the wall and plug using those supplied with
the connections kit, position the bracket and secure with
the wall bolts supplied. NOTE: It is highly recommended
that a spirit level be used to position the appliance to
ensure that it is perfectly level.
NB:
FIG. 2.3
2.5.2.Position the appliance on the hanging bracket and
connect the isolating valves supplied in the connection kit
as shown on the wall template (see also Sections 2.7 Gas
Connections, 2.8 Water Connections & F
IG. 2.3).
2.6ELECTRICAL CONNECTION
For safety purposes, have a competent person carefully
check the electrical system in the property, as the
manufacturer will not be held liable for damage caused by
the failure to earth the appliance properly or by anomalies
in the supply of power. Make sure that the residential
electrical system is adequate for the maximum power
absorbed by the unit, which is indicated on the rating plate.
In addition, check that the section of cabling is appropriate
for the power absorbed by the boiler.
The boiler operates with alternating current, as indicated in
the Technical Information table in Section 10, where the
maximum absorbed power is also indicated. Make sure
that the connections for the neutral and live wires
correspond to the indications in the diagram. The
appliance electrical connections are situated on the
reverse of the control panel.
IMPORTANT!
In the event that the power supply cord must be changed,
replace it with one with the same specifications.
Note: The diagrams for the electrical system are indicated
in section 2.13.
Warning, this appliance must be earthed.
External wiring to the appliance must be carried out by a
competent person and be in accordance with the current
I.E.E. Regulations and applicable local regulations.
The appliance is supplied with a fly-lead already
connected, this must be connected to a 240v supply fused
7
at 3A and must facilitate complete electrical isolation of the appliance, by the
use of a fused double pole isolator having a contact separation of at least 3
mm in all poles or alternatively, by
means of a 3 A fused three pin plug and
unswitched shuttered socket outlet both complying with BS 1363.
The point of connection to the Electricity supply must be readily accessible
and adjacent to the appliance unless the appliance is installed in a bathroom
when this must be sited outside the bathroom (see section 2.2).
Should external controls be required, the design of the external electrical
circuits should be undertaken by a competent person, see section 2.12 for
further information.
2.7GAS CONNECTION
2.8WATER CONNECTIONS
The local gas region contractor connects the gas meter to the service pipe.
If the gas supply for the boiler serves other appliances ensure that an
adequate supply is available both to the boiler and the other appliances
when they are in use at the same time.
Pipe work must be of an adequate size. Pipes of a smaller size than the
boiler inlet connection should not be used.
VIEW OF THE BOILER CONNECTIONS
FF
F
IG. 2.5
8
KT007A
FIG. 2.4
LEGEND:
A = Central Heating Flow
B = Domestic Hot Water Outlet
C = Gas Inlet
D = Domestic Cold Water Inlet
E = Central Heating Return
F = Safety Valve Outlet
SC005A
PIPE WORK:
Copper tubing to BS EN 1057:1996 is recommended for water pipes.
Jointing should be either with capillary soldered or compression fittings.
Where possible pipes should have a gradient to ensure air is carried
naturally to air release points and water flows naturally to drain taps.
The appliance has a built-in automatic air release valve, however it should
be ensured as far as possible that the appliance heat exchanger is not a
natural collecting point for air.
Except where providing useful heat, pipes should be insulated to prevent
heat loss and avoid freezing.
FIG. 2.6
Particular attention should be paid to pipes passing through ventilated
spaces in roofs and under floors.
BY-PASS:
The appliance includes an automatic by-pass valve, which protects the main
heat exchanger in case of reduced or interrupted water circulation through
the heating system, due to the closing of thermostatic valves or radiators.
SYSTEM DESIGN:
This boiler is suitable only for sealed systems.
DRAIN COCKS:
These must be located in accessible positions to permit the draining of the
whole system and should be fitted at all low points.The taps must be at least
15mm nominal size and manufactured in accordance with BS 2870:1980.
SAFETY VALVE DISCHARGE:
The discharge should terminate facing downward on the exterior of the
building in a position where discharging (possibly boiling water & steam) will
not create danger or nuisance, but in an easily visible position, and not
cause damage to electrical components and wiring.
The discharge must not be over an entrance or a window or any other type
of public access.
AIR RELEASE POINTS:
These must be fitted at all high points where air naturally collects and must
be sited to facilitate complete filling of the system.
The appliance has an integral sealed expansion vessel to accommodate the
increase of water volume when the system is heated.
It can accept up to 6 litres (1.3 gal) of expansion water. If the heating circuit
has an unusually high water content, calculate the total expansion and add
an additional sealed expansion vessel with adequate capacity. This should
be located on the return pipe work as close as possible to the pump inlet.
MAINS WATER FEED - CENTRAL HEATING:
There must be no direct connection to the mains water supply even through
a non-return valve, without the approval of the Local Water Authority,
therefore a temporary method for initially filling the system and replacing lost
water during servicing in accordance with current Water Regulations and
bylaws must be provided
(FIG. 2.6). NOTE: The installer should ensure that
there are no leaks as frequent filling of the heating system can lead to
premature scaling of the main exchanger and failure of hydraulic
components.
DOMESTIC WATER:
The domestic water must be in accordance with the relevant
recommendation of BS 5546:1990. Copper tubing to BS EN 1057:1996 is
recommended for water carrying pipe work and must be used for pipe work
carrying drinking water, a scale reducer should also be used to reduce the
risk of scale forming in the domestic side of the heat exchanger.
CENTRAL HEATING
Fill01
Detailed recommendations are given in BS 6798:1987 and BS 5449-1:1990,
the following notes are given for general guidance.
RESIDUAL HEAD OF THE BOILER
VR003A
9
2.9FLUE CONNECTIONS
IMPORTANT!
FORALLFLUESYSTEMS,A
RESTRICTOR MAY NEED TO BE
INSERTEDINTOTHEEXHAUST
MANIFOLD
RESTRICTOR AND DETAILS OF FITTING
REQUIREMENTS ARE SHOWN IN
,THESIZEOFTHE
TABLE
2.1 (PAGE 16).
FLUE SYSTEM
The provision for satisfactory flue termination must be made in accordance
with BS 5440-1.
The appliance must be installed so that the flue terminal is exposed to outside air.
The terminal must not discharge into another room or space such as an
outhouse or lean-to.
It is important that the position of the terminal allows a free passage of air
across it at all times.
The terminal should be located with due regard for the damage or
discolouration that might occur on buildings in the vicinity and consideration
must be given to adjacent boundaries.
In cold or humid weather water vapour may condense on leaving the flue
terminal. The effect of such “pluming” must be considered.
If the terminal is less than 2 metres above a balcony, above ground or above
a flat roof to which people have access, then a suitable terminal guard must
be fitted. When ordering a terminal guard, quote the appliance model
number.
A suitable terminal guard is available from:
TOWER FLUE COMPONENTS
Morley Road
Tonbridge
Kent TN9 1RA
The minimum acceptable spacing from the terminal to obstructions and
ventilation openings are specified in FIG. 2.7.
FIG. 2.7
Ø 60/100 mm
T
ERMINALPOSITION
A -Directly below an openable window or other opening300
B -Below gutters, solid pipes or drain pipes75
C -Below eaves200
D -Below balconies or car-port roof200
E -From vertical drain pipes and soil pipes150
F -From internal or external corners300
G -Above ground or balcony level300
H -From a surface facing a terminal600
I -From a terminal facing a terminal1200
J -From an opening in the car port
(e.g. door, window) into dwelling1200
K -Vertically from a terminal in the same wall1500
L -Horizontally from a terminal in the same wall300
M -Horizontally from an opening window300
FU010ARev1
N -Fixed by vertical flue terminal
NOTE:THE FLUE MUST NOT TERMINATE IN A PLACE LIKELY TO CAUSE NUISANCE
mm
FIG. 2.8
10
FU003A
FU002A/Rev.1
FITTING THE COAXIAL FLUE (HORIZONTAL)
(For Telscopic Instructions see below and
for Vertical Flue and Twin Pipe Instructions
see page 12)
Once the boiler has been positioned on the
wall, insert the elbow into the socket
(FIG
2.8) and rotate to the required position.
NOTE: It is possible to rotate the elbow 360
on its vertical axis.
Using the flue clamps, seals and screws
supplied
(FIG 2.8) secure the elbow to the
boiler.
The 1 metre horizontal flue kit (705958)
supplied is suitable for an exact
dimension
of 823mm, and the 750mm
horizontal flue kit (705785) is suitable for an
exact X dimension of 573mm.
o
FIG 2.9
X
Measure the distance from the face of the
external wall to the face of the flue elbow
IG 2.8), add 22 mm to this measurement,
-F
(X
you now have the total length of flue
required (including the terminal), this figure
must now be subtracted from 860mm, you
now have the total amount to be cut from
the plain end of the flue.
FIG 2.11
IMPORTANT!
FOR ALL FLUE SYSTEMS, A RESTRICTOR MAY
NEED TO BE INSERTED INTO THE EXHAUST
MANIFOLD
DETAILS OF FITTING REQUIREMENTS ARE
SHOWN IN
, THE SIZE OF THE RESTRICTOR AND
TABLE 2.1 (PAGE 16).
FIG 2.10
Cut the flue to the required length ensuring that the distance
between the inner and the outer flue is maintained (FIG 2.10).
e.g. X = 508mm + 22mm = 530mm
860 - 530 = 330mm (Length to be cut from the plain end
of the flue).
Once cut to the required length, ensure that the flue is free
from burrs and reassemble the flue. If fitting the flue from
inside of the building attach the grey outer wall seal to the flue
terminal and push through the flue through the hole, once the
wall seal has passed through the hole, pull the flue back until
the seal is flush with the wall. Alternatively, the flue can be
installed from outside of the building, the grey outer seal
being fitted last.
1X ALUMINIUM FLUE PIPE INCLUDING TERMINAL (TELESCOPIC 60/100)
X FLUE CLAMPS
2
8X SCREWS
2X SEALS
The telscopic flue is suitable for use with an exact
minimum X dimension of 270mm and an exact maximum
X dimension 470mm.
IMPORTANT!!
Do not extend the telescopic flue to an X dimension of
more than 470mm. If longer lengths are required use
extension pieces as necessary.Under no
circumstances must the flue be cut.
The wall must then be made good around the flue
(ensuring a fall of 1ois maintained away from the boiler to
the flue terminal).
Once made good, place the inner (white) wall seal over the
flue and push up to the wall, secure the flue to the elbow
by using the clamp supplied.
o
For each additional 90
elbow 1 metre must be removed
from the total flue length (maximum 4 metres including the
1st elbow). For each additional 45oelbow 0.5 metre must
be subtracted from the total flue length (FIG 2.13).
FIG 2.12
FITTING THE COAXIAL FLUE (VERTICAL)
(For Twin Pipe Instructions see page 13)
CONTENTS:
1X SILICONE O-RING (60mm)
X CONICAL ADAPTOR (60/100mm)
1
1X VERTICAL FLUE KIT (80/125mm)
3X SCREWS
The vertical flue kit is supplied with a specially designed
weather proof terminal fitted, it can be used either with a
flat roof or a pitched roof. (see FIGS 2.12, 2.13).
The Vertical flue kits maximum and minimum useable
lengths with both flat and pitched roof flashings are
indicated in
(Figs. 2.14 & 2.15).
Before proceeding to fit the flue, ensure that the maximum
flue length has not been exceeded and that all elbows and
bends have been taken into consideration, the maximum
o
flue length is 4 metres, for each additional 90
elbow 1
metre must be subtracted from the total flue length, and for
o
each 45
0.5 metres must be subtracted from the total flue
length (the offset and height of 2 x 45ocan be seen in
Fig. 2.16).
NOTE:MAX LENGTH = a+a+a +
b+b = a+a+a+0.5+0.5
OMBINED LENGTH NOT
C
TO EXCEED 3m
FIG 2.13
Mark the position of the flue hole in the ceiling and/or roof
(see FIG. 2.14 for distance from wall to the centre of the
flue).
Cut a 110mm diameter hole through the ceiling and/or roof
and fit the flashing plate to the roof.
Should it be necessary to cut the flue
DO NOT cut the
outer white ar inlet tube, cut the aluminium exhaust flue
6mm longer than the outer white air tube when used at
minimum length.
12
DO NOT cut more that 250mm from the
FIG 2.14
inner aluminium exhaust flue.
To connect the vertical flue kit directly to the boiler, place
the adaptor
(see FIG 2.12) (supplied with vertical flue kit)
onto the exhaust manifold and secure with the clamp, the
vertical flue kit must then be inserted through the roof
flashing, this will ensure that the correct clearance above
the roof is provided as the terminal is a fixed height.
Should extensions be required, they are available in 1
(Part No. 705786), 500mm (Part No. 705790) and
metre
160mm lengths (Part No. 705812), they must be
connected directly to the boiler and secured with the clamp
supplied before connecting the adaptor to allow the
vertical flue kit to be fitted. In the event that extension
pieces need to be shortened, they must only be cut at the
male end and it must be ensured that the distance
between the inner and outer flue are kept (Fig. 2.10).
When utilising the vertical flue system, action must be
taken to ensure that the flue is supported adequately to
prevent the weight being transferred to the appliance flue
connection.
When the flue passes through a ceiling or wooden floor,
there must be an air gap of 25mm between any part of the
flue system and any combustible material. The use of a
ceiling plate will facilitate this. Also when the flue passes
from one room to another a fire stop must be fitted to
prevent the passage of smoke or fire, irrespective of the
structural material through which the flue passes.
FITTING THE FLUE (TWIN PIPE)
Where it is not possible to terminate the flue within the
distance permitted for coaxial flues, the twin flue pipe can
be used by fitting a special adaptor to the flue connector
and using the aperture for the air intake located on top of
the combustion chamber.
FIG 2.15
IMPORTANT!
FORALLFLUESYSTEMS,A
RESTRICTOR MAY NEED TO BE
INSERTEDINTO THEEXHAUST
MANIFOLD
RESTRICTOR AND DETAILS OF FITTING
REQUIREMENTS ARE SHOWN IN TABLE
,THESIZEOF THE
2.1 (PAGE 16).
Minimum offset distance when using 2x 45obends
Considerations necessary for twin flue installation;
It is most important to avoid any possible condense
formation entering the appliance.
According to Table 2.1
(Page 16) decide if condensation
will form within the flue. If yes, there are two options;
1) Where condense will form but can be negated with
insulated flue, install insulated the flue with a fall of 5mm in
every metre away from the boiler.
o
2) The exhaust flue will have a fall of 3
back to the boiler
and a suitable trap will be fitted on the exhaust as close
to the boiler as possible, condense will then be suitably
disposed of.
Where the flue runs through cold spots, i.e. loft areas,
condense is likely to be formed, therefore a fall back to the
boiler and a trap is required.
Always ensure that the flue is adequately supported,
avoiding low points. (MTS supply suitable clamps as Part
No. 705778).
FIG 2.16
13
To utilise the air intake it is necessary to:
Remove the ‘knockout’ of the air intake by cutting it with a
suitable knife
(FIG. 2.16).
Insert the elbow/flue pipe into the air intake until it stops.
The twin flue pipes can be fitted with or without additional
elbows and need no clamps, simply ensure that the red oring is inserted in the female end of the flue pipe and push
the extension piece fully into the previous section of flue
pipe or elbow, check that the o-ring is not dislodged when
assembling the flue.
Twin pipe can also be converted back to Coaxial flue to
enable vertical termination with a coaxial kit by using the
pipe bridge (Twin - Coaxial Adaptor - Part No. 705767).
When running the twin flue pipe vertically, a condense trap
must always be used on the exhaust pipe.
FIG 2.16
It is not recommended that the pipe bridge for horizontal
termination, however in the unlikely event that this proves
to be a necessity it is extremely important that the entire
flue has a fall of 3
o
back to the boiler, is suitably trapped
and where the 60mm inner flue of the concentric terminal
connects to the pipe bridge, this point must be adequately
sealed with silicone sealant to avoid condense leakage at
this point.
NOTE:Vertical twin flue installations must have a trap on
the exhaust. MTS supply a suitable condense
trap Part No. 705774 and recommend that this be
used in the event that the flue may not form
condense.
When siting the twin flue pipe, the air intake and exhaust
terminals must terminate on the same wall, the centres of
the terminals
must be a minimum of 280 mm apart and
the air intake must not be sited above the exhaust
terminal (refer to FIG. 2.20). The air intake pipe can be
run horizontally, however, the terminal and the final 1
metre of flue must be installed with a fall away from the
boiler to avoid rain ingress.
It is also strongly recommended that the air intake pipe run
be constructed of insulated pipe to prevent condense
forming on the outside of the tube.
The maximum permissible flue length for twin flue is
dependent on the type of run used.
IMPORTANT!!!
HERE CONDENSE WILL FORM WITHIN
W
THE FLUE SYSTEM
FALL BACK TO THE BOILER OF
SUITABLE TRAP IS FITTED AS CLOSE TO
THE BOILER AS POSSIBLE
A SUITABLE COLLECTOR
705798
OR A CONDENSATE DISCHARGE
, ENSURE THERE IS A
O
3
AND A
. MTS SUPPLY
PART NO.
T WITH BUILT IN TRAP PART NO.
705774.
For flue runs with the intake and exhaust pipes under the
same atmospheric conditions (TYPE 4) the maximum
length is 43 metres (23kW) and 28 metres (27kW), for
runs with the terminals under different atmospheric
conditions (TYPE 5) the exhaust terminal must extend 0.5
metres above the ridge of the roof (this is not obligatory if
the exhaust and air intake pipes are located on the sa,e
side of the building). For TYPE 5 also, the maximum
permissible combined length is 40 metres.
The maximum length is reached by combining the total
lengths of both the air intake and exhaust pipes. Therefore
a maximum length of 40 metres for example, will allow a
flue run of 20 metres for the air intake and 20 metres for
the exhaust pipes, also for each 90oelbow 1.3 metres must
be subtracted from the total length and for each 45oelbow
1 metre must be subtracted from the total flue length.
Some of the acceptable flue configurations are detailed on
below (FIG. 2.19).
For further information relating to flue runs not illustrated,
please contact the Technical Department on 01494
539579.
14
FIG 2.17
FIG 2.18
EXHAUST
AIR INTAKE
AIR INTAKE
AIR INTAKE MUST NOT BE
FITTED ABOVE THE EXHAUST
TYPE 1
TYPE 2
TYPE 3
TYPE 4
TYPE 5
NOTE:DRAWINGS ARE INDICATIVE OF FLUEING OPTIONS ONLY.
FIG. 2.19
FIG 2.20
15
23 MFFI
TABLE 2.1
Coaxial
Systems
ø 60/100
Twin Pipe
Systems
ø 80/80
Exhaust
Type
TYPE 1
YPE 2
T
TYPE 3
Exhaust
Type
TYPE 4
YPE 5
T
Use the
ø 43 mm
Restrictor
Between
0.5 m - 2 m
Use the
ø 43 mm
Restrictor
Up to 11.5 m
Up to 11.4 m
Do not use the
Restrictor
Between
2 m - 4 m
Do not use the
Restrictor
Between
11.5 m - 43 m
Between
11.4 m - 40 m
Maximum
Flue
Length
4 m
Maximum
Flue
Length
43 m
40 m
Risk of Condensation Forming
NOT APPLICABLE
NOT APPLICABLE
Risk of Condensation Forming With:
Standard Twin Pipe
After:
Insulated Twin Pipe
After:
N/A*
4.3 m
with a
ø 43 mm
restrictor
6.9 m
without a
ø 43 mm
restrictor
5.7 m*
with a
ø 43 mm
restrictor
N/A*
21.7 m*
without a
ø 43 mm
restrictor
Coaxial
Systems
ø 60/100
Twin Pipe
Systems
ø 80/80
27 MFFI
Exhaust
Type
TYPE 1
TYPE 2
YPE 3
T
Exhaust
Type
TYPE 4
YPE 5
T
Use the
ø 45 mm
Restrictor
Between
345 mm - 1 m
Use the
ø 45 mm
Restrictor
Up to 14 m
Up to 21 m
Do not use the
Restrictor
Between
1 m - 4 m
Do not use the
Restrictor
Between
14 m - 28 m
Between
21 m - 51 m
Maximum
Flue
Length
4 m
Maximum
Flue
Length
28 m
51 m
Risk of Condensation Forming
NOT APPLICABLE
NOT APPLICABLE
Risk of Condensation Forming With:
Standard Twin Pipe
After:
7 m
with a
ø 45 mm
restrictor
7 m
without a
ø 45 mm
restrictor
Insulated Twin Pipe
After:
10 m*
with a
ø 45 mm
restrictor
24 m*
with a
ø 45 mm
restrictor
24 m*
without a
ø 45 mm
restrictor
28 m*
without a
ø 45 mm
restrictor
Where there is no risk of condense forming (and, therefore no requirement for a condense collector), ensure a minimum
*
fall of 5mm per metre away from the appliance.
NOTE:UNDER SOME CIRCUMSTANCES, CONDENSE MAY FORM AT THE EXHAUST TERMINAL, SPECIAL ATTENTION MUST BE PAID WITH
REGARD TO POSSIBLE CONDENSE DRIPPING FROM THE TERMINAL
16
.
2.10CONTROL PANEL
LEGEND:
A - On/Off button
B - Central heating temperature adjustment
C - Domestic hot water temperature adjustment
D - Heating system pressure gauge
E - Time clock
F - Central heating selector
G - Central heating L.E.D. (green)
H - Flue sensor L.E.D. (yellow)
I - Overheat and/or ignition failure (lockout) L.E.D. (red)
J - Ignition failure (lockout) and/or overheat reset
button/Flue Test analysis mode*
K- ON/OFF L.E.D. (green)
FR019A
* Warning the flue analysis mode must only be selected by a
qualified service engineer.
FIG. 2.20
2.11REMOVING THE
FRONT PANEL
1
A
2
In order to access the inside of the boiler, it is necessary to unscrew
the fastening screws “A” of the control panel located on the lower part
of the panel itself.
The control panel moves downward and when pulled forward rotates
on two lateral hinges.
The panel stays in a semi-horizontal position, which allows access to
the inner parts of the boiler.
In order to increase the manouvering space, it is possible to raise the
control panel and rotate it to a fully horizontal position.
4
B
5
3
To dismantle the front
casing panel it is necessary
to:
1 - Remove the two screws
“B”;
2 - Move the front casing
panel up and lift forward.
17
2.12 ROOM THERMOSTAT
CONNECTION
To connect a room thermostat, it is necessary to:
1. - Open the control panel as indicated in
SECTION 2.11.
2.- Remove the link “A” from the terminal block on the reverse of the control panel.
3. - Insert the thermostat cable through the cable grommet and fasten it by means of the
cable-clamp provided.
4. - Connect the thermostat wires to the terminal block
(Diagram A).
5.- If a remote time clock is to be fitted, disconnect the integral time clock from the P.C.B.
6. - Using a volt-free switching time clock, connect the switching wires from the time clock
following points 1-4 above
(Diagram B).
7. - If using an external time clock and room thermostat, these must be connected in
series as points 1-7 above (Diagram C).
Note:Only a low voltage room thermostat capable of volt free switching must
be used. Factory fitted integral wiring must not be disturbed when wiring
external controls.
A
FO016A
FO017A
18
FIG. 2.21
2.13ELECTRICAL/SYSTEM DIAGRAMS
A
B
CN103
CN104
CN201
CN300
CN204
CN202
CN200
CN102
CN100
CN101
5
4
3
2
1
B
A
C
D
E
F
G
H
I
J
L
K
M
N
O
Q
R
P
A
B
CN103
CN104
CN102
CN100
CN101
5
4
3
2
1
A
S
FIG. 2.22
A - Jumper:
B - Central Heating Temperature Adjustment
C - Connector for Remote Control (Climate Manager)
D - Domestic Hot Water Temperature Adjustment
E - Soft-light Adjustment
F - Maximum Heating Adjustment
G - Time Clock Connector
H - On/Off Switch
I -Fume Sensor L.E.D.
J - Central Heating Selector
K - Ignition Failure (Lockout) L.E.D.
L - On/Off L.E.D.
M - Reset Button
N - Central Heating L.E.D.
O - Transformer
P - Spark Generator I.C.
Q- Gas Valve Relay
R - Circulation Pump Relay
S - Fan Relay
1 -Don’t move (jumper is factory set in position B)
2 -Anti-cycling Device Adjustment for Heating
3 -Don’t move (jumper is factory set in position B)
4 -Don’t move (jumper is factory set in position B)
5 -Fan/Pump over-run selector
Position A = 0 minsPosition B = 2 mins
Position A = OFFPosition B = ON
A01 - Circulation Pump
A02 - Fan
A03 - Spark Generator/Gas Valve Supply
A04 - Detection Electrode
A05 - Main Circuit Temperature Probe
A06 - Domestic Hot Water Temperature Probe
A07 - D.H.W. Flow switch
A08 - Pump Pressure Switch
A09 - Modulator
A10 - Air Pressure Switch
A11 - Safety Thermostat
A12 - External (Room) Thermostat
COLOURS:
Gr - Grey
Bi - White
Rs - Red
Mr - Brown
Bl - Blue
Nr - Black
Ro - Pink
19
10
16
2.14WATER CIRCUIT DIAGRAM
FIG. 2.23
SI016C
LEGEND:
1.Fan
2.“Twin-pass” Heat Exchanger
3.Domestic Hot Water Temperature Probe
4.Burner
5.Detection Electrode
6.Ignition Electrodes
7.Gas Valve
8.Pump pressure switch
9.Safety Valve
10. D.H.W. inlet filter
11. D.H.W. Flow Switch
12. Automatic By-pass
13. Pressure Gauge
14. Circulation Pump with Automatic Air Release Valve
15. Overheat Thermostat
16. Main Circuit Temperature Probe
17. Expansion Vessel
18. Air Pressure Switch
A. Central Heating Flow
B. Domestic Hot Water Outlet
C. Gas Inlet
D. Domestic Cold Water Inlet
E. Central Heating Return
20
3.COMMISSIONING
3.1INITIAL PREPARATION
MTS (GB) Limited support the initiative. Within the information pack
you will find a copy of the logbook. It is important that this is
completed in the presence of your customer, they are shown how to use it,
and it is signed by them. Please instruct your customer that they must have
their logbook with them whenever they contact a service engineer
or us.
Preliminary electrical system checks to ensure electrical safety must be
carried out by a competent person i.e. polarity, earth continuity, resistance to
earth and short circuit.
FILLING THE HEATING SYSTEM:
Lower the control panel and remove the case panels (see SECTION 2.11 for
further information).
Open the central heating flow and return cocks supplied with the
connection kit (there are two isolation points on the return connection).
Unscrew the cap on the automatic air release valve one full turn and leave
open permanently.
Close all air release valves on the central heating system.
Gradually open valve(s) at the filling point (filling-loop) connection to the
central heating system until water is heard to flow, do not open fully.
Open each air release tap starting with the lowest point and close them
only when clear water, free of air, is visible.
Purge the air from the pump by unscrewing the pump plug
anticlockwise, also manually rotate the pump shaft in the direction
indicated by the pump label to ensure the pump is free.
Refit the pump plug.
Continue filling the system until at least 1.5 bar registers on the pressure
gauge.
Inspect the system for water soundness and remedy any leaks
discovered.
FILLING OF THE D.H.W. SYSTEM:
Close all hot water draw-off taps.
Open the cold water inlet cock supplied with the connection kit.
Open slowly each draw-off tap and close them only when clear water, free
of bubbles, is visible.
GAS SUPPLY:
Inspect the entire installation including the gas meter, test for tightness
and purge the supply as described in BS 6891:1988.
Open the gas cock (supplied with the connection kit) to the appliance and
check the gas connections on the appliance for leaks.
When the installation and filling are completed, flush the system while cold,
refill, turn on the Central Heating system (
temperature has reached the boiler operating temperature.The system must
then be immediately flushed through.
The flushing procedure must be in line with BS 7593:1992 code of practice
for treatment of water in domestic hot water central heating systems.
During this operation, we highly recommend the use of a central heating
flushing detergent (Fernox Superfloc or equivalent), whose function is to
dissolve any foreign matter that may be in the system.
Substances different from these could create serious problems to the
pump or other components.
The use of an inhibitor in the system such as Fernox MB-1 or equivalent is
strongly recommended to prevent corrosion (sludge) damaging the boiler
and system.
Failure to carry out this procedure may invalidate the appliance
warranty.
SECTION 3.2) and run it until the
21
3.2INITIAL STA RT-UP
THE CHECKS TO BE RUN BEFORE INITIAL START-UP ARE AS FOLLOWS:
1. Make sure that:
-the screw on the automatic air valve has been loosened when the
system is full;
- If the water pressure in the system is below 1.5 bar, bring it up to the
appropriate level;
-Ensure that the gas cock is closed;
-Make sure that the electrical connection has been made properly and
that the earth wire is connected to an efficient earthing system;
- Supply power to the boiler by pushing the On/Off button
2.16) - the L.E.D. “K” will illuminate. Then push the button “F” in for
central heating - the L.E.D.
circulation pump. After 7 seconds, the boiler will signal a shutdown due
to ignition failure. Leave the boiler as it is until all of the air has been bled
from the system.
-Loosen the cap on the head of the pump to eliminate any air pockets;
-Repeat the procedure for bleeding the radiators of air;
-Open the taps for a brief period;
-Check the system pressure and, if it has dropped, open the filling loop
again to bring the pressure back up to 1.5 bar.
2. Make sure that all gate valves are open;
3. Turn on the gas cock and check the seals on the connections with an
approved soap solution and eliminate any leaks.
4. Press the reset button
main burner. If the burner does not light the first time, wait 1 minute and
repeat the procedure.
5. Check the minimum and maximum burner pressure values; adjust if
needed using the values indicated in the table in
SECTION 4.
“J” for the lighting system; the spark will light the
“G” will illuminate. This will start the
“A” (see FIG.
3.3OPERATIONAL
ADJUSTMENTS
To access the areas in which adjustments are made, it is necessary to open
the control panel, as indicated in SECTION 2.11, then remove the rear
inspection cover by unscrewing the two screws. Access is thereby provided
to the P.C.B. and to the following components:
1. The power supply cable connector;
2. The fuses;
3. The soft-light potentiometer the setting for which can range from the
minimum thermal power to the maximum;
4. The maximum thermal heating power potentiometer adjustable by the
minimum to maximum power (already calibrated in the factory to 70% of
the maximum thermal power);
5. The jumper for adjusting the ignition delay (anti-cycling) feature, which
can be set from 0 to 2 minutes (set in the factory at one minute);
6.
Fan/Pump Over-run (Electrical Diagram). When the jumper is set to position
A the Fan and Pump over-run is activated. (The jumper is factory set in
position B)
7. The time clock connector.
22
3.4COMBUSTION ANALYSIS
3.5PRODUCT OF COMBUSTION
DISCHARGE MONITORING
FU008A
The flue connector has two apertures, readings can be taken for
the temperature of the combustion by-products and of the
combustion air, as well as of the concentrations of O
etc.
To access these intakes it is necessary to unscrew the front
screw and remove the metal plate with sealing gasket.
It is possible to activate the flue test mode (maximum
output) by pressing and holding the RESET button
10 seconds, the yellow L.E.D. “
return to normal operation after 5 minutes. The boiler can
be returned to normal operation sooner by switching the
boiler off and on again.
In the boiler, it is possible to monitor the correct operation of
the flue exhaust/air intake, checking for a loss of general
pressure in the system. Through the use of a differential
manometer connected to the test points of the combustion
chamber, it is possible to detect the ∆P of operation of the air
pressure switch.
The value detected should not be less than 0.55 mbar (23
Kw) - 0.90 mbar (27Kw) under conditions of maximum
thermal power in order for the boiler to function properly and
without interruption.
H” will light. The boiler will
2
and CO2,
“J” for
3.6BOILER SAFETY SYSTEMS
FU009A
The boiler is fitted with the following devices (see SECTION 2.10 for
references).
1 - IGNITION FAILURE:
This indicates ignition failure when a flame is not detected within 7
seconds of starting an ignition sequence. The L.E.D. “I” will illuminate
to signal the shutdown status.
The system can be reset by pressing and releasing the button “J” after
checking to make sure that the gas cock is open.
2 - INSUFFICIENT SYSTEM PRESSURE:
In the event of insufficient water pressure in the heating system, a
safety device will shutdown the boiler. Check the system pressure on
the pressure gauge “D” and if it is less than 0.4 bar refill the system to
1.5 bar. Once the system pressure is at the correct level the boiler will
reset automatically.
3 - OVERHEATING:
This control shuts off the boiler in the case where the primary circuit
reaches a temperature in excess of 105°C.
The red L.E.D. “I” will illuminate to signal this shutdown status.
The system can be reset by waiting a few minutes for the primary
exchanger to cool down and then by pressing and releasing the “J”
button.
4. ANTI-FROST DEVICE:
The boiler is fitted with a device which, in the event that the water
temperature falls below 3
˚C, the burner ignites at the minimum power
until the boiler reaches a temperature of 33˚C.
This device only operates if the boiler is functioning perfectly and:
- the system pressure is sufficient;
23
- the boiler is powered electrically;
- the gas is turned on.
6 - EXHAUST DISCHARGE ANOMALY SHUTDOWN:
The boiler is fitted with safety devices, which in the event of defective
discharge of exhaust products, automatically interrupts the gas supply,
thereby shutting off the boiler.
The shutdown of the boiler is temporary and is indicated by the
illumination of the yellow L.E.D. “H” for a period of about 15 minutes.
Once this time period has passed and the discharge state of exhaust
fumes has returned to normal, the boiler automatically turns back on.
7 - PUMP PROTECTION:
To prevent the pump from seizing the boiler will activate the pump for 20
seconds every 21 hours after it’s last operation.
3.7DRAINING THE SYSTEM
3.8COMPLETION
DRAINING THE HEATING SYSTEM
The heating system must be drained as follows:
-Turn off the boiler;
-Attach a hose pipe and open the drain valve;
- Drain the system at the lowest points (where present). When the heating
system is unused for an extended period of time, it is recommended that you
add antifreeze with an ethylene glycol base to the water in the heating pipe
work and radiators if the ambient temperature drops below 0°C during the
winter.
This makes repeated draining of the entire system unnecessary.
DRAINING THE DOMESTIC HOT WATER SYSTEM
Whenever there is the danger of the temperature dropping below the
freezing point, the domestic hot water system must be drained as follows:
-Turn off the general water valve for the household plumbing system;
-Turn on all the hot and cold water taps;
-Empty the remaining water from the lowest points in the system (where
present).
For the Republic of Ireland it is necessary to complete a “Declaration of
Conformity” to indicate compliance to I.S. 813. An example of this is given in the
current edtion of I.S. 813. In addition it is necessary to complete the
Log Book.
3.9OPERATIONAL CHECKS
24
1. The flue system must be visibly checked for soundness.
2. On Central Heating allow the system to warm up and manipulate the Central
Heating temperature control knob, check the burner modulates up and down
between the high and low settings.
3. Range rate the thermal power for Central Heating, as detailed in
4. Run the Domestic Hot Water, manipulate the Domestic Hot Water
temperature control knob to check the burner modulates up and down
between the high and low settings.
5. Balance the Central Heating system until all return temperatures are correct
and equal.
6. Turn ON/OFF button OFF, disconnect the pressure Gauge, retighten screw
and relight boiler.
7. Re-examine Central Heating, Domestic Hot Water and Cold Water supplies
for soundness.
SECTION 4.2
8. Check the appearance of the gas flame to assess the adequacy of the
combustion air supply.
9. If external controls have been disconnected, reconnect and test.
10. Refit boiler casing.
3.10INSTRUCTING THE END USER
1. Hand over the copy of the End User Instructions supplied with the appliance,
together with these instructions, and explain how to use the timeclock and
room thermostat if fitted.
2. Show the End User how to switch the appliance off quickly, and indicate the
position of the electric supply isolator.
3. Inform the End User of the location of all drains, isolating valves and air
vents.
4. Explain how to turn the appliance off for both short and long periods and
advise on the precautions necessary to prevent damage in the event that the
appliance is inoperative when freezing conditions occur.
5. Finally advise the End User that, for continued safe and efficient operation,
the appliance must be serviced by a competent person at least once a year.
Consumption (15°C; 1013mbar)m3/h
Consumption (15°C; 1013mbar)Kg/h
Gas Burner Pressure
max - minmbar
Consumption (15°C; 1013mbar)m
Consumption (15°C; 1013mbar)Kg/h
Gas Burner Pressure
max - minmbar
The boiler can be converted to use either methane (natural) gas (G20)
TYPE OF GAS
or L.P.G. (G30 - G31) by an Authorised Service Centre.
The operations that must be performed are the following:
45.67
20
20
1.30
2.78
----
11.0 - 2.0
3
/h
1.3
3.10 - 1.16
---
12.2 - 1.7
1. Replace the jets on the main burner (see table in section 4);
2. Adjust the maximum and minimum thermal capacity values for the boiler
(see table in section 4 and 4.2 Adjusting the Gas Pressures);
3. Adjust the maximum thermal power setting;
4. Adjust the soft-light feature
pressure);
5. Adjust the ignition delay feature for the heating system by adjusting the
potentiometer as shown in
Liquid Butane Gas
G30
80.58
29
28
0.77
----
2.02
27.7 - 6.0
0.77
---
2.31 - 0.87
27.8 - 5
Liquid Propane Gas
G31
80.58
37
36
0.77
----
2.00
35.5 - 7.3
0.77
---
2.27 - 0.85
35.8 - 5.3
(see table below for recommended
FIG. 4.1 (can be set from 0 to 2 mins.).
CATEGORY
II2H3+
Recommended
Soft-light
Pressure
(mbar)
4.2ADJUSTING THE GAS PRESSURES (SIT SIGMA)
Setting the minimum and the maximum power of the boiler
1. Check that the supply pressure and dynamic pressure to the gas valve is
a minimum of 20 mbar for natural gas.
2. To do this, loosen the screw “A”.
Fit the pipe of the pressure gauge to the inlet pressure connection of the
gas valve “B” and check for the correct standing pressure, then operate
the appliance and check for the correct working pressure.
When you have completed this operation, replace the screw “A” securely
into its housing to seal off the gas (check for tightness).
3. To check the pressure supplied by the gas valve to the burner, loosen the
screw “C”. Fit the pipe of the pressure gauge to the pressure outlet test
Model
Microcombi
Methane Gas
G20
Liquid
Butane Gas
Propane Gas
G30
23 MFFI8.016.016.0
27 MFFI6.71212
Liquid
G31
26
4.2ADJUSTING THE GAS PRESSURES (SIT SIGMA)
point of the gas valve “D”.
1
B
A
2
Disconnect the compensation pipe “D1” either from the gas valve or from
the sealed chamber.
4. Push the On/Off button to “ON” position -green light- and ensure that the
hot water temperature control knob is set to maximum.
Turn on the boiler by running a hot water tap.
Adjust the 10mm nut “E” on the modureg to set the maximum gas
pressure, turn the nut clockwise to increase and anti clockwise to
decrease the pressure until the required pressure is achieved (see TABLE
A page 30).
5. To set the minimum power, disconnect a supply terminal “F1” from the
modureg and adjust screw “F” (ensure that the 10mm nut is held in
position). Turn the screw clockwise to increase the pressure and anticlockwise to decrease the pressure (displayed on the
pressure gauge) corresponding to the minimum power (see TABLE A page
30).
6. When you have completed the above operations, turn off the
hot water tap, reconnect the supply terminal to the modureg
on the gas valve, reconnect the compensation pipe and replace the cap
on the screw of the modureg.
D1
D
C
3
E
Setting the maximum heating circuit power
7. To set the maximum heating circuit power, push the On/Off button to the
“ON” position -green light- and push the Heating button and set the time
clock and any external controls to the “ON” position -green light. Turn the
knob of the heating thermostat clockwise to maximum.
8. Remove the inspection panel of the P.C.B. and fit a small cross-head
screwdriver in to the right hand potentiometer (see below). Turn clockwise
to increase the pressure or counter-clockwise to reduce the pressure.
Adjust the setting to the required heating pressure value (displayed on the
pressure gauge), as indicated in the charts shown on pages 30 and 31.
9. Turn off the boiler by placing the main switch to the "OFF" position.
Setting the pressure for soft-light ignition.
Disconnect the detection electrode connection close to the P.C.B. (FIG.
2.13).
Start the boiler and during the ignition sequence adjust the left hand
potentiometer until the gas pressure reads the required gas pressure (seethe table on page 29).
Once the gas pressure is set turn off the boiler and re-connect the
detection electrode to the P.C.B.
NB.: It may be necessary to reset the flame failure reset a number of
times during this operation.
10. Remove the pipe from the test point and tighten the screw “C” to the
pressure test point in order to seal off the gas.
11. Carefully check the pressure test points for gas leaks (valve inlet and
outlet).
IMPORTANT!
Whenever you disassemble and reassemble the gas connections, always
check for leaks using a leak detection fluid.
4
F1
F
Soft-light
Adjustment
Max Heating
Adjustment
27
4.2ADJUSTING THE GAS VALVE (HONEYWELL)
AA
BB
C
D
Recommended pressure for
soft-light ignition
8 mbar
NATURAL GAS (G20)BUTANE GAS (G30)PROPANE GAS (G31)
16 mbar
16 mbar
6.7 mbar 12 mbar
12 mbar
23 Kw
27 Kw
E
F
Setting the minimum and the maximum power of the boiler
1
B
A
2
D1
C
D
1. Check that the supply pressure and dynamic pressure to the gas valve is
a minimum of 20 mbar for natural gas.
2. To do this, loosen the screw “A”.
Fit the pipe of the pressure gauge to the inlet pressure connection of the
gas valve “B” check for the correct standing pressure, then operate the
appliance and check for the correct working pressure.
When you have completed this operation, replace the screw “A” securely
into its housing to seal off the gas (check for tightness).
3. To check the pressure supplied by the gas valve to the burner, loosen the
screw “C”. Fit the pipe of the pressure gauge to the pressure outlet test
point of the gas valve “D”.
Disconnect the compensation pipe “D1” either from the gas valve or from
the sealed chamber.
4. Push the On/Off button to “ON” position -green light- and ensure that the
hot water temperature control knob is set to maximum.
Turn on the boiler by running a hot water tap.
Adjust the 10mm nut “E” on the modureg to set the maximum gas
pressure, turn the nut clockwise to increase and anti clockwise to
decrease the pressure until the required pressure is achieved (see TABLE
A page 30)
5. To set the minimum power, disconnect a supply terminal “F1” from the
modureg and adjust screw “F” (ensure the 10mm nut is held in position).
Turn the screw clockwise to increase the gas pressure and counterclockwise to decrease the gas pressure (displayed on the
pressure gauge) corresponding to the minimum power (see TABLE A page
30).
6. When you have completed the above operations, turn off the
hot water tap, re-connect the supply terminal to the modureg
on the gas valve and replace the cap on the screw of the
modureg.
Setting the maximum heating circuit power
7. To set the maximum heating circuit power, push the On/Off button to the
“ON” position -green light- and push the Heating button and set the time
clock and any external controls to the “ON” position -green light. Turn the
3
knob of the heating thermostat clockwise to maximum.
8. Remove the inspection panel of the P.C.B. and fit a small cross-head
screwdriver in to the right hand potentiometer (see page 28). Turn
clockwise to increase the pressure or counter-clockwise to reduce the
pressure. Adjust the setting to the required heating pressure value
E
(displayed on the pressure gauge), as indicated in the charts shown on
pages 30 amd 31.
9. Turn off the boiler by placing the main switch to the "OFF" position.
Setting pressure for soft ignition.
Disconnect the detection electrode connection close to the P.C.B. (FIG.
11.14).
Start the boiler and during the ignition sequence adjust the left hand
potentiometer until the gas pressure reads the required gas pressure as
per the table below.
Once the gas pressure is set turn off the boiler and re-connect the
4
connection to the P.C.B.
NB.: It may be necessary to reset the flame failure reset a number of
times during this operation.
10. Remove the pipe from the test point and tighten the screw “C” to the
pressure test point in order to seal off the gas.
F
11. Carefully check the pressure test points for gas leaks (valve inlet and
outlet).
28
IMPORTANT!
Whenever you disassemble and reassemble the gas connections, always
F1
check for leaks using a leak detection fluid.
NOTE: ALWAYS CHECK THE GAS RATES FOLLOWING ADJUSTMENT.
23 MFFI
2.78
20
11.0
2.0
1.16
2.02 Kg/h
0.87 Kg/h
27.5 mbar
6.2 mbar
28 mbar
12 x 0.77
2.00 Kg/h
0.85 Kg/h
35.5 mbar
7.3 mbar
37 mbar
12 x 0.77
TABLE A
Regulating the heating power for
natural gas (G20)
Regulating the heating power for
butane gas (G30)
CG010A
CG011A
29
Regulating the heating power for
propane gas (G31)
5.MAINTENANCE
It is recommended that the following inspections be carried out on the
boiler at least once a year:
1 - Check the seals for the water connections; replace any faulty seals.
2 - Check the gas seals; replace any faulty gas seals.
3 - Visual check of the entire unit.
4 - Visual check of the combustion process or analysis of combustion by-
products (see SECTION 3.4) and cleaning of the burner if needed.
5 - If necessary, dismantling and cleaning of the combustion
chamber.
6 - If necessary, dismantling and cleaning of the burner jets.
7 - Visual check of the primary heat exchanger:
-check for overheating in the blade assembly;
-clean the exhaust fan if needed.
8 - Adjustment of the gas pressure, gas rate and soft-light, partial load and
full load.
9 - Check of the heating safety systems:
-safety device for maximum temperature (overheat thermostat);
-safety device for maximum pressure (safety valve).
10- Check of the gas safety systems:
-safety device for lack of gas or flame ionisation (detection
electrode).
11- Check of the electrical connection (ensure it complies with the
instructions in the manual).
12- Check of Domestic Hot Water production efficiency (flow rate and
temperature)
13- General check of the combustion by-products of the
discharge/ventilation system.
14- Check of the general performance of the unit.
30
6.SERVICING INSTRUCTIONS
To ensure efficient safe operation, it is recommended that the
boiler is serviced annually by a competent person.
Before starting any servicing work, ensure both the gas and
electrical supplies to the boiler are isolated and the boiler is
cool.
Before and after servicing, a combustion analysis should be
made via the flue sampling point (please refer to SECTION 3.4 for
further details).
After servicing, preliminary electrical system checks must be
carried out to ensure electrical safety (i.e. polarity, earth
continuity, resistance to earth and short circuit).
6.1REPLACEMENT OF PARTS
The life of individual components vary and they will need
servicing or replacing as and when faults develop.
The fault finding sequence chart in
which component is the cause of any malfunction, and
instructions for removal, inspection and replacement of the
individual parts are given in the following pages.
6.2TO GAIN GENERAL ACCESS
SECTION 7 will help to locate
2. The control panel moves downward and when pulled forward,
rotates on two lateral hinges; the panel stays in a semihorizontal position, which allows access to the inner parts of
the boiler (F
3. In order to increase the manoeuvring space, it is possible to
raise the control panel and rotate it to a fully horizontal
position (F
4. Remove the screws “B” from the front panel bottom lip
(FIG. 6.4);
5. Lift the front panel up and forward from the raised screws at the
the top of the casing (F
FIG. 6.4
IG. 6.2);
IG. 6.3);
IG. 6.5).
B
All testing and maintenance operations on the boiler require the
control panel to be lowered. This will also require the removal of
the casing.
6.2.1 Removing the front panel
1. Loosen the fastening screws “A” of the control panel located
on the lower part of the panel itself. (F
FIG. 6.1
IG. 6.1);
A
FIG. 6.2
FIG. 6.5
FIG. 6.3
31
6.2.2 Removing the sealed chamber front cover
6.2.3 Removing the side panels
1. Remove the screws “C” (FIG. 6.6);
2. Lift the sealed chamber front cover from the locating pins (FIG.
6.7).
C
C
1. Remove the four screws “D” for each side panel (FIG.6.8);
2. Pull the panel away from the boiler at the base, then lift the
panel up and remove from the boiler (FIG.6.9).
FIG. 6.8
D
D
FIG. 6.6
D
D
FIG. 6.9
32
FIG. 6.7
6.3ACCESS TO THE COMBUSTION CHAMBER
6.3.1 Removing the combustion cover
Remove the screws “E” (FIG. 6.10);
1.
2. Lift off the combustion cover.
Fig. 6.12
6.3.3 Removing the electrodes
E
E
E
FIG. 6.10
6.3.2 Removing the burner and jets
1. Remove the screws “F” from the burner (FIG. 6.11);
2. Remove the burner (FIG. 6.12);
3. Disconnect the electrodes (see SECTION 6.3.3);
4. Remove the jets using a No. 7 socket spanner;
5. Replace in reverse order.
Before carrying out this procedure, unscrew and slide the
burner forward (see previous section).
1. Remove rubber gasket “G” (FIG. 6.13);
2. To remove the detection electrode disconnect the cable
at its connection point close to the P.C.B. (FIG. 6.14);
3. Remove screw “H” (FIG. 6.15);
4. Gently slide the electrode downward (FIG. 6.16).
FIG. 6.13
G
FIG. 6.11
F
F
FIG. 6.14
33
6.3.4 Removing the main heat exchanger
FIG. 6.15
1. Drain the boiler of water;
2. Remove the overheat thermostat sensor, D.H.W. sensor
and heating sensor “I” (FIG. 6.17);
3. Release the four connection nuts “J” connecting the
exchanger to the flow and return pipes (F
H
4. Pull it straight out (FIG. 6.19).
IG. 6.18);
I
I
Fig. 6.17
FIG. 6.16
To replace, repeat the steps in reverse order, paying
particular attention to the following:
a -Centre the electrode in the positioning hole carefully,
otherwise the electrode may break;
b -Ensure that the left hand and right hand electrodes are
located the correct way round (facing each other), to
give the correct spark gap;
c -Check that the cables have been connected correctly;
d -Check that the rubber gasket seals the cable/ electrode
connection point completely.
J
FIG. 6.18
FIG. 6.19
34
6.3.5 Removing the air pressure switch
6.3.6 Removing the fan
1. Disconnect the electrical connections “K” and silicone
pipes “L” from their connection points (F
IG. 6.20);
2. Remove screws “M” on the top of the sealed chamber (FIG.
6.21);
3. Lift out the air pressure switch (FIG. 6.22);
4. Unscrew to remove the switch from the plate.
FIG. 6.20
K
L
L
FIG. 6.21
1. Disconnect electrical connections “N” and silicone pipe “O”
IG.6.23);
(F
2. Remove screw “P” and remove the fan collar clamp “Q”
(FIG.6.24);
3. Remove screws “R” (FIG.6.25);
4. Remove fan and mounting plate (FIG.6.26).
FIG. 6.23
N
N
O
M
M
Q
P
FIG. 6.24
R
R
FIG. 6.25
FIG. 6.22
FIG. 6.26
35
6.4ACCESS TO THE GAS VALVE
6.4.1. Removing the spark generator (SIT SIGMA Gas
Valve)
Disconnect ignition leads “S” by pulling upward
1.
(FIG. 6.27A);
2. Remove the screw “T” (FIG. 6.28A);
3. Remove the spark generator by pulling forward from the
gas valve (FIG. 6.29A).
S
FIG. 6.27A
6.4.2. Removing the spark generator (HONEYWELL
Gas Valve)
Disconnect ignition leads “S” by pulling upward
1.
(FIG. 6.27B);
2. Remove the screw “T” (FIG. 6.28B);
3. Remove the spark generator by pulling forward from the
gas valve (FIG. 6.29B).
S
FIG. 6.27B
T
FIG. 6.28A
FIG. 6.29A
T
FIG. 6.28B
FIG. 6.29B
36
6.4.3 Removing the gas valve (SIT SIGMA)
6.4.4 Removing the gas valve (HONEYWELL)
tant! Before removing the gas valve, ensure the gas
Impor
supply is turned off.
1. Disconnect all the cables from the solenoid and
modureg;
2. Remove the spark generator (see previous section);
3. Release the nuts “U” (FIG. 6.30A);
4. Remove the screws “V” from the bottom of the gas valve
(FIG. 6.31A);
5. Remove the gas valve (FIG. 6.32A).
U
tant! Before removing the gas valve, ensure the gas
Impor
supply is turned off.
1. Disconnect all the cables from the solenoid and
modureg;
2. Remove the spark generator (see previous section);
3. Release the nuts “U” (FIG. 6.30B);
4. Remove the screws “V” from the bottom of the gas valve
(FIG. 6.31B);
5. Remove the gas valve (FIG. 6.32B).
U
U
FIG. 6.30A
V
V
FIG. 6.31A
U
FIG. 6.30B
V
V
FIG. 6.31B
FIG. 6.32A
FIG. 6.32B
37
6.5ACCESS TO THE WATER CIRCUIT
Important! Before any component is removed, the boiler
must be drained of all water.
6.5.1 Removing the pump pressure switch
1.Remove the pump pressure switch electrical connections
“W” (FIG 6.33);
2.Unscrew the pump pressure switch by
the nut;
3.Remove the pump pressure switch.
W
using
a spanner on
6.5.3 Removing the automatic air vent
Unscrew valve top “Y” (FIG. 6.35);
1.
2. Remove valve complete with float (FIG 6.36).
Y
FIG. 6.35
FIG. 6.33
6.5.2 Removing the safety valve
Disconnect the discharge pipe work from below the
1.
boiler;
2. Unscrew and remove the valve “X” (FIG. 6.34).
X
FIG. 6.36
38
FIG. 6.34
6.5.4 Removing the pump
Remove the U-clip “ Z” (FIG. 6.37);
1.
2. Remove the retaining clip “A1” (FIG. 6.38);
3. Release the nut “C1” (FIG. 6.39);
4. Remove the pipe “D1” (FIG. 6.40);
5. Remove the screws “E1” (FIG. 6.41);
6. Remove the pump.
Z
Z
C1
FIG. 6.39
A1
FIG. 6.37
D1
E1
FIG. 6.40
E1
FIG. 6.38
FIG. 6.41
39
6.5.5 Removing the pressure gauge
6.5.6 Removing the expansion vessel
Remove the U-clip “F1” (FIG. 6.42)
1.
2. Remove the pressure gauge coupling (FIG. 6.42);
3. Push the pressure gauge through the control panel
from the rear (F
IG. 6.43).
F1
FIG. 6.42
Release nuts “G1” and remove the gas pipe (FIG. 6.44);
1.
2. Release nut “H1” (FIG. 6.45);
3. Remove back-nut “I1” (FIG. 6.46);
4. Remove the expansion vessel (FIG. 6.47).
G1
G1
FIG. 6.44
FIG. 6.43
H1
FIG. 6.45
I1
FIG. 6.46
40
FIG. 6.47
6.5.7 Removing the overheat thermostat
Disconnect the overheat thermostat electrical
1.
connections “J1” (FIG. 6.48);
2. Then remove the thermostat from its mounting by
releasing the securing clip (F
IG. 6.49 /6.50).
J1
FIG. 6.48
6.5.9 Removing the D.H.W. temperature sensor
(N.T.C.)
Pull off the electrical connector and unscrew the sensor
1.
probe using a suitable spanner (FIG. 6.52).
FIG. 6.49
FIG. 6.50
6.5.8 Removing the heating temperature sensor
(N.T.C.)
Pull off the electrical connector and unscrew the sensor
1.
probe using a suitable spanner (FIG. 6.51).
FIG. 1.52
FIG. 6.51
41
6.5.10 Removing the D.H.W. flow switch
Unplug the electrical connector “M1” (FIG. 6.53);
1.
2. Release nut “N1” (FIG. 6.53a);
3. Release the nut “O1” (FIG. 6.53b) and remove the
D.H.W. flow switch.
M1
6.6ACCESS TO THE CONTROL SYSTEM
Important! Isolate the electrical supply to the boiler before
accessing the control panel.
6.6.1 Checking the fuses
Remove the inspection cover on the reverse of the
1.
control panel (FIG. 6.54);
2. Remove the fuses (FIG. 6.55).
N1
FIG. 6.53
FIG. 6.54
FIG. 6.55
FIG. 6.53a
42
O1
FIG. 6.53b
6.6.2 Removing the time clock
6.6.3 Removing the P.C.B.
Disconnect the electrical connections “P1” from the
1.
clock (FIG. 6.56);
2. Remove screws “Q1” (FIG. 6.57);
3. Lift out the time clock from the control panel (FIG. 6.58).
P1
FIG. 6.56
Isolate electricity;
1.
2. Remove the inspection cover from the reverse of the
control panel;
3. Unplug all electrical connections from the P.C.B.
4. Remove the screws “R1” (FIG. 6.59);
5. Separate the facia panel from the rear of the control
panel ;
7. Remove the screws “S1” and remove the P.C.B.
(FIG. 6.60).
R1
R1
R1
Q1
Q1
FIG. 6.57
S1
FIG. 6.59
S1
FIG. 6.60
FIG. 6.58
43
7.FAULT FINDING
7.1FAULT FINDING GUIDE
(FLOW-CHARTS)
These fault finding guides are not exhaustive. However, it is possible to
detect and correct many defects by using the standard fault finding
diagrams described in this chapter, ensure these guides are carried out in
the set order.
To ensure that the external controls do not interfere with the fault finding,
disconnect the wires from the terminal block on the rear of the control panel
and provide a solid link between the terminals.
Expansion vessel
Gasket 3/8"
Gasket 1/2"
Safety valve (1/4" 3 bar)
Gasket 1/4"
Pump pressure switch
Return group
Pump
Pump
Time clock
P.C.B. (T2 MFFI)
P.C.B. (27 MFFI)
Pressure gauge
Air pressure switch
Air pressure switch
Gasket (Fan)
Fan (23 kW)
Fan (27 kW)
Temperature probe
Exchanger
Burner 12 ramp (natural gas)
Burner 13 ramp (natural gas)
D.H.W. Flow Switch
O-ring
Gasket
Spark Generator
Spark Generator
Gas valve (SIT 845 SIGMA)
Gas valve (HONEYWELL)
Gasket 3/4"
Burner jet (natural gas 1.30)
Gasket
Electrode (ignition R.H.)
Electrode (ignition R.H.)
Electrode (ignition L.H.)
Electrode (ignition L.H.)
Detection electrode
Thermostat (overheat)
Burner jet 1.30 full kit (natural gas)
Burner jet 0.77 full kit (LPG)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
50
NOTES
51
9.TECHNICAL INFORMATION
CE Certification
Heat Input max/min kW
Heat Outputmax/min kW
Efficiency of Nominal Heat Input%
Efficiency at 30% of Nominal Heat Input%
Heat Loss to the Casing (∆T=50°C)%
Flue Heat Loss with Burner Operating%
Flue Heat Loss with Burner Off%
Max Discharge of Products of Combustion
(G20)Kg/h
Residual Discharge Headmbar
Consumption at Nominal Capacity(G20)m
Gas Consumption after 10 Minutes*m
3
/h
3
(15°C, 1013 mbar) (G30-G31)Kg/h
Temp. of exhaust fumes at nominal capacity °C
2
CO
Content%
2
O
Content%
CO Contentppm
Minimum Ambient Temperature°C
Head Loss on Water Side (max) (∆T=20°C)mbar
Residual Head of Systembar
Heating Temperature max/min °C
Domestic Hot Water Temperature (approx)max/min °C
D.H.W. Flow Rate ∆T=35°Cl/min
D.H.W. Minimum Flow Ratel/min
Pressure of Domestic Hot Watermax/min bar
Expansion Vessel Capacityl
Expansion Vessel Pre-load Pressurebar
Maximum Water Content of Systeml
Maximum Heating Pressurebar
Nominal PressureNatural Gas (G20) mbar
LPG (G30-G31)mbar
Electrical SupplyV/Hz
Power ConsumptionW
Protection Grade of Electrical SystemIP
Internal Fuse Rating
WeightKg
23 MFFI
63AU4547
25.6/11.0
23.7/9.6
92.5
90.5
1.0
6.5
0.4
51
0.96
2.72
0.32
2.02/2.00
126
7.0
8.0
38
+5
200
0.25
82/42
54/36
9.7
2.5
6/0.2
6
1
130
3
20
30-37
230 / 50
135
X4D
FAST 2 AT
39
27 MFFI
0694BM3512
29.3/11.0
27/9.3
92
88.8
1.3
6.7
0.4
57.7
1.41
3.10
0.36
2.31/2.27
148.5
7.1
8.0
53
+5
200
0.25
82/42
56/36
11.0
2.5
6/0.2
6
1
130
3
20
28-37
230/50
155
X4D
FAST 2 AT
41
G.C. Number47-116-1647-116-24
*Calculated at 70% maximum output
Manufacturer:Merloni TermoSanitari SpA - Italy
Commercial subsidiary: MTS (GB) LIMITED
MTS Building
Hughenden Avenue
High Wycombe
Bucks HP13 5FT
Thank you for choosing an ARISTON boiler.
We guarantee that your boiler is a reliable and technically sound product.
This manual provides detailed instructions and recommendations
for proper installation, use and maintenance.
Remember to keep this manual in a safe place for future reference
i.e. by the gas meter.
Your local MTS Servicing Centre is at your complete
disposal for all requirements.
The guarantee on this appliance is valid for 12 months from the first day of installation.
Repairs to the electric, hydraulic or gas circuits may be carried out only by your local
authorised MTS Servicing Centre.
Every attempt has been made to avoid errors of any kind
in this manual, the Management invites customers to inform
of any inaccuracies which they may find.
This will help to improve our service
TABLE OF CONTENTS
1.GENERAL INFORMATIONpage 3
Technical Informationpage 3
Control Panelpage 4
2.OPERATING INSTRUCTIONSpage 4
3.USEFUL INFORMATION AND TROUBLESHOOTINGpage 6
4.MAINTENANCEpage 7
5.CHANGE OF GAS TYPEpage 7
6.TIME CLOCKpage 7
IMPORTANT!
Please read this manual carefully.
For additional information, please consult the “Installation and Servicing Instructions.”
Make sure to keep the manuals provided with the appliance so that they can be used by
the end-user, installer or local service agent.
2
1. GENERAL INFORMATION
MTS (GB) Limited support the initiative. Your installer will give you, and show
you how to use, a Log Book which will give you important information about your boiler,
and heating system. Please have this Log Book to hand whenever you contact a service
engineer or us.
All CORGI Registered Installers carry a CORGI ID card, and have a registration
number. Both should be recorded in your boiler Logbook. You can check your
installer is CORGI registered by calling CORGI direct on :- (01256) 372300.
This is a combined appliance for the production of Central Heating (C.H.) and Domestic
Hot Water (D.H.W.). This appliance
designed. The manufacturer declines all liability for damage caused by improper or
negligent use.
Do not allow children or inexperienced persons to use the appliance without supervision.
If you smell gas in the room, do not turn light switches on or off, use the telephone or any
other object which might cause sparks.
Open doors and windows immediately to ventilate the room.
Shut the gas mains tap (on the gas meter) or the valve of the gas cylinder and call your
Gas Supplier immediately.
If you are going away for a long period of time, remember to shut the mains gas tap or
the gas cylinder valve. Consult the Installation and Servicing manual when turning off the
boiler for long periods of time.
Before any intervention within the boiler it is first necessary to isolate the electrical
supply by turning the external switch to “OFF”.
TECHNICAL INFORMATION
must be used only for the purpose for which it is
GENERAL DATA
Heating input max-min
Heating output max-min
Efficiency at Maximum Thermal Capacity (see
installation instructions)
CENTRAL HEATING
Operating Temperature max-min
Maximum-Minimum Heating Pressure
Built-in expansion vessel - Total capacity
DOMESTIC HOT WATER
Temperature of Water for Domestic Use (max-min)
Working pressure max-min
Flow rate ∆T 35°C
Minimum flow rate
ELECTRICAL DATA
Electrical Supply/ Frequency
Power Consumption
Protection of Electrical System
CATEGORY
kW
kW
%
°C
bar
litres
°C
bar
l/min
l/min
V/Hz
W
IP
23 kW
25.6-11.0
23.7-9.6
92.5
82-42
3-0.7
6
54-36
6-0.2
9.7
2.5
230/50
135
X4D
27 kW
29.3-11.0
27/9.27
92
82-42
3-0.7
6
56-36
6-0.2
11.0
2.5
230/50
155
X4D
Nominal Pressure Methane Gas (G20)
Nominal Pressure Liquid Gas (G30-G31)
mbar
mbar
20
29-37
20
29-37
3
CONTROL PANEL
LEGEND:
FR019A
2. OPERATING INSTRUCTIONS
D
E
UT009A
A - On/Off button
B - Central heating temperature adjustment
C - Domestic hot water temperature adjustment
D - Heating system pressure gauge
E - Time clock
F - Central heating selector
G - Central heating L.E.D. (green)
H - Flue sensor L.E.D. (yellow)
I - Overheat and/or ignition failure (lockout) L.E.D. (red)
J - Ignition failure (lockout) and/or overheat reset button
K - ON/OFF L.E.D. (green)
CAUTION
In the United Kingdom installation, start-up, adjustments and maintenance must be
performed by a CORGI Registered Installer in accordance with the installation
standards currently in effect, as well as with any and all local health and safety
standards i.e.. CORGI.
In the Republic of Ireland the installation and initial start up of the appliance must
be carried out by a Competent Person in accordance with the current edition of
I.S.813 “Domestic Gas Installations”, the current Building Regulations, reference
should also be made to the current ETCI rules for electrical installation.
HELPFUL SUGGESTIONS
To get the most out of your boiler, we have provided you with some useful advice on
proper use and maintenance:
- Periodically check the system pressure using the pressure gauge “D”, make sure that
the pressure is at 1.5 bar when the system is off and cool. If the pressure is below the
minimum recommended value (1 bar), consult your installer for checking and refilling
the system, an example of how a filling loop should be fitted is shown to the left
“E”.
NOTE:DO NOT UNDER ANY CIRCUMSTANCES USE THE APPLIANCE WITH THE PRESSURE GAUGE
READING ZERO.
- The outer panels of the unit's case must only be cleaned with a damp cloth. Do not use
abrasive cleaners. The control panel can be wiped with either a damp or dry cloth.
FILL01
Spray polishes must not be used on the control panel surface or knobs. Care must be
taken to prevent any liquid from entering the appliance.
4
PRACTICAL TIPS
F
G
- If the water is very hard, it is recommended that a water softener or in-line scale reducer
be added to the system so as to reduce the formation of limescale in the boiler
exchangers.This will ensure that the efficiency of the unit remains the same over time,
reducing gas consumption and maintenance costs.
- If the boiler should be out of use for a prolonged period, it is recommended that the
electrical power supply be disconnected and that the external gas cock
“F” and “G” be
closed. If low temperatures are expected, the boiler and system pipe work should be
drained in order to prevent frost damage.
- To improve comfort and take full advantage of the heat produced by the boiler, it is
recommended that an external (room) thermostat be installed.
- It is good practice to clean and service the appliance and central heating system every
year. Call a local Service Agent.
IGNITION PROCEDURE
Press button “A”. The green L.E.D. “K” will illuminate indicating that the boiler is ready
K
I
UT002A
G
F
UT003A
B
to operate. The centralised electronic control unit will ignite the burner, upon demand for
either C.H. or D.H.W. If, after approximately 10 seconds, the burner has not ignited, the
boiler safety devices will shut off the gas and the red L.E.D.
ignition system, the reset
“J” must be pressed and released. Should the boiler fail to
“I” illuminates. To reset the
ignite a second time, check that the external gas cock is open. If the problem persists,
contact a local Service Agent.
IMPORTANT!! Always wait 2 minutes before resetting
each time.
WINTER AND SUMMER OPERATING MODES
In the ‘winter operating mode’, the boiler will produce both central heating and domestic
hot water.In the ‘summer operating mode’, the boiler will produce only domestic hot water.
Press “F” button to select winter mode. The green L.E.D. “G” will illuminate.
ADJUSTING THE HEATING
It is possible to set the temperature of the heating system by adjusting the knob “B”.
By positioning the indicator somewhere between 1 and 9, a temperature may be obtained
which varies from approximately 42˚C to about 82˚C.
UT004A
EXTERNAL (ROOM) THERMOSTAT CONTROL
If an external (room) thermostat is installed, it is recommended that the temperature of
the heating system be set by means of the “B” knob, leaving it at 7-8 position in order to
obtain the best performance from the boiler and to allow the regulation of the external
temperature to function efficiently.
C
SETTING THE HOT WATER FOR DOMESTIC USE
Both in the winter and summer mode, the temperature of the domestic hot water may be
adjusted by using the “C” knob. A delivery temperature for the water may be chosen in a
range from 36˚C to about 54˚C, depending on the flow rate of the water and the position
UT005A
of the knob between 1 and 9 settings.
NOTE: Should the Domestic Hot Water not be hot
enough, it may be necessary to slow the flow rate from the hot water outlet being
used.
G
TURNING OFF THE CENTRAL HEATING
F
UT003A
K
To turn off the Central Heating, press the “F” button; the respective green L.E.D.“G” will go off.
The boiler will stay in summer mode, only providing Domestic Hot Water
TURNING OFF THE BOILER
UT002A
To turn the boiler off, press the button “A”; the respective green L.E.D. “K” will go off. Close the
gas cock located under the boiler by inserting a screw driver into the bottom slot (See F & G)
and turning 1/4turn clockwise until it stops (slot horizontal). It is also necessary to turn the
electricity supply switch (located outside the boiler) to the OFF position.
5
3.USEFUL INFORMATION
AND TROUBLESHOOTING
J
I
BOILER SHUTDOWN SITUATIONS
The boiler is equipped with safety devices that intervene in certain situations and shut it
off. Most of these situations are communicated by means of the L.E.D.s and at times the
user may be able to remedy them.
SHUTDOWN DUE TO IGNITION FAILURE
In the event that the automatic ignition of the burner has failed, the red L.E.D. “I” will
illuminate. In order to reset the ignition, the button “J” must be pressed and released.
Should the boiler fail to ignite a second time, check that the external gas cock is open. If
the problem persists, contact a local Service Agent.
before resetting each time.
IMPORTANT!! Always wait 2 minutes
J
In the event that the safety limit is exceeded for the temperature of the water in the boilers
I
exchanger, the thermostat shuts off the boiler and the red L.E.D. “I” illuminates.
To remedy this situation, wait a few minutes to allow the exchanger to cool down, then
press and release the reset button
If this situation occurs frequently, contact a local Service Agent.
SHUTDOWN DUE TO OVERHEATING
“J”.
SHUTDOWN DUE TO INSUFFICIENT WATER CIRCULATION
D
UT001A
H
If the boiler is off, one possible cause for this state is an insufficient pressure of water in
the system.
Check the system pressure on the pressure gauge
pressurise the system as instructed by your installer, should you be unsure some basic
instructions are provided hereafter;
Ensure that the filling loop hose is connected to the cold water inlet pipe and to either
the Central Heating flow or return
Open the handle/s or tap/s to allow water into the Central Heating system
Once the needle on the pressure gauge reaches 1 Bar, close the handle/s or tap/s and
disconnect the filling loop hose
Should it still be unclear how to proceed, please consult your installer.
If the boiler does not start up again, contact a local Service Agent.
If there are frequent drops in pressure within the system, have a plumber check the
heating system for possible water leaks.
“D” and if it is less than 0.5 bar, re-
4. MAINTENANCE
5. CHANGE OF GAS TYPE
6
TEMPORARY SHUTDOWN DUE TO DEFECTIVE DISCHARGE OF EXHAUST PRODUTS
The boiler is fitted with safety devices, which in the event of a defective discharge of
exhaust products, automatically interrupts the gas supply, thereby shutting off the boiler.
The shut-off of the boiler is temporary and is indicated by the illumination of the yellow
“H” for a period of about 15 minutes.
L.E.D.
Once this time period has passed and the discharge state of exhaust system has
returned to normal, the boiler automatically turns back on.
IMPORTANT!
If this situation occurs frequently, contact a local Service Agent so that they may check
that the exhaust fumes are being expelled correctly, that the flue is installed correctly and
that the area is ventilated properly.
Schedule an annual maintenance check-up for the boiler with a competent person.
Correct maintenance always results in savings in the cost of running the system.
Our boilers are designed to function either with Natural Gas (methane) or LPG gas. If you need
to changeover from one gas to the other, one of our local Service Agents should be contacted.
6.TIME CLOCK
UT014A
UT011Ap
NOTE: the time clock is for Central Heating control only.
The time clock is provided with 96 switches, called riders, each of which covers a time
interval of 15 minutes (four per hour).
When a rider is switched from the inside (off setting) to the outside of the clock border (on
setting), the circuit is closed (switch on) for a period of 15 minutes and then the boiler
starts if the room thermostat (if installed) or the heating thermostat require heat (heating
function on).
EXAMPLE
To set the heating of your home in the time interval from 7.00 am to 9.30 am and from
7.00 pm to 10.00 pm every day:
- rotate the outer ring of the clock in a clockwise direction until the correct time of day
(24h) lines up with the arrow on the clock (at approx. 2 o’clock position);
under no circumstances should the minute hand be moved manually;
-
- make sure all the switches, i.e. the riders, are placed on the inside of the clock border;
- pull outward the riders for 7.00 am and 9.30 am, and then all riders between these two;
- repeat this for 7.00 pm and 10.00 pm.
Other heating intervals may be set in the same way.
The clock is provided with a selector switch with three positions (see figure):
Position “I” CONSTANT: in this position, the clock circuit is always closed (switch on),
1.
therefore the boiler will constantly be on and will only shut off upon the request of the
room thermostat (if installed) or the heating thermostat;
UT014A
UT014A
TECHNICAL DATA
Ambient
temperature:
Shortest
switching time
Programmable:Every 15 minutes
- 10°C to + 55°C
: 15 minutes
Position “O” HEATING OFF: in this position, the clock circuit is always open (switch off)
2.
and the boiler will therefore never ignite for heating;
3.
“Central” Position
PROGRAMMING ACTIVE: in this position, the programme set by
the user is active.
7
Manufacturer:Merloni TermoSanitari SpA - Italy
Commercial subsidiary:MTS (GB) LIMITED
MTS Building
Hughenden Avenue
High Wycombe
Bucks HP13 5FT
Telephone: (01494) 755600
Fax: (01494) 459775
Internet: www.ariston.co.uk
E-mail: info@uk.mtsgroup.com
Technical Service Hot Line: (01494) 539579
13Flow meter filter installed on the cold water inlet
ER2002211017104001
- 4 -
PART.NOTIFICATION OF CHANGES
Spares listed below are not interchangeable with those in Ed.1, Ed.2 and Ed.3
5995393 - Frame support - replaces code 999594 from serial number: 2320209500001
11995492 - Pivot- replaces code 998569 from serial number: 2320209500001
12998589 - By-pass pipe- replaces code 999923 from serial number: 2320209500001
14998064 - Spring (by-pass pipe)- not listed on original drawing
17996049 - Flow group- replaces code 998612 from serial number: 2320209500001
20995903 - Low water pressure switch- replaces code 998627 from serial number: 2320209500001
22573530 - Lock nut (½")- not listed on original drawing
23996047 - Return group- replaces code 995344 from serial number: 2320209500001
26995364 - Spacer plate (pump)- replaces code 999602 from serial number: 2320209500001
29999968 - Cable (pump)- not listed on original drawing
30998577 - L.E.D. (L=14.2) - replaces code 999593 from serial number: 2320209500001
37995461 - Control panel- replaces code 999384 from serial number: 2320209500001
40999724 - P.C.B. (T2 MFFI)- replaces code 999410 from serial number: 2320209500001
46998635 - Low voltage wiring- replaces code 999387 from serial number: 2320209500001
60999925 - Earth cable (sealed chamber)- not listed on original drawing
61995318 - Cable (fan/sensor)- replaces code 998633 from serial number: 2320209500001
62995319 - Cable (P.C.B./fan)- not listed on original drawing
64995349 - Gasket (fan)- replaces code 995320 from serial number: 2320209500001
68995893 - Panel (combustion chamber (L.H.) - replaces code 998600 from serial number: 2320209500001
72996158 - Burner (12 ramp - N.G.) - replaces code 998618 from serial number: 2320209500001
76996159 - Pipe (cold water inlet)- replaces code 999394 from serial number: 2320209500001
77996072 - D.H.W. flow switch (Bitron)- not listed on original drawing (new design)
79999495 - Cable (D.H.W. flow switch - 15 Ohm) - not listed on original drawing
81999919 - Spark generator - replaces code 998645 from serial number: 2320209500001
90571787 - Terminal board (two pole) - not listed on original drawing
91997745 - Control panel cover (rear)- not listed on original drawing
93996134 - Panel (combustion chamber - front)- replaces code 999151 from serial number: 2320209500001
99996065 - Thermostat (overheat 103°C)- replaces code 997206 from serial number: 2320209500001
100995892 - Panel (combustion chamber - R.H.)- replaces code 998599 from serial number: 2320209500001
102995995 - Panel (insulation - front) - replaces code 995995 from serial number: 2320209500001
106999929 - Cable (P.C.B./air pressure switch) - not listed on original drawing
- 5 -
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.