Ariston ACO 35 Installation and Servicing Instructions

Page 1
Country of destination: GB/IE
Installation and Servicing Instructions Type C Boilers
ACO 35 MFFIG.C.N: 47-116-35
LEAVE THESE INSTRUCTIONS WITH THE END USER
SERIES
Page 2
2
TABLE OF CONTENTS
1. GENERAL INFORMATION
1.1. GENERAL INFORMATION 3
1.2. T
ECHNICAL INFORMATION 4
1.3. O
VERALL VIEW 6
2. INSTALLATION
2.1. REFERENCE STANDARDS 7
2.2. S
ITING THE APPLIANCE 7
2.3. O
VERALL DIMENSIONS 8
2.4. M
INIMUM CLEARANCES 8
2.5. M
OUNTING THE APPLIANCE 9
2.6. E
LECTRICAL CONNECTION 9
2.7. G
AS CONNECTION 9
2.8. W
ATE R CONNECTIONS 10
2.9. F
LUE CONNECTIONS 13
2.9.1 F
ITTING THE COAXIAL FLUE
(Ø 60 / 100 HORIZONTAL)14
2.9.2 F
ITTING THE 5” FLUE
(Ø 80 / 125 Horizontal/Vertical) 15
2.9.3 F
ITTING THE COAXIAL FLUE
(Ø 60 / 100 VERTICAL) 16
2.9.4 F
ITTING THE TWIN PIPE (Ø80 / 80) 17
2.10. F
ITTING THE MECHANICAL/DIGITAL
TIME CLOCK 20
2.11. S
ETTING THE MECHANICAL TIME CLOCK 22
2.11.1. S
ETTING THE DIGITAL TIME CLOCK 22
2.12. A
CCESSORY CONNECTION 24
2.13. E
LECTRICAL DIAGRAM 26
2.14. W
ATE R CIRCUIT DIAGRAM 28
3. COMMISSIONING
3.1. INITIAL PREPARATION 30
3.2. R
EMOVING THE CASING 32
3.3. C
ONTROL PANEL 33
3.4. I
NITIAL START-UP 35
3.5. D
ISPLAY: MESSAGES SHOWN DURING
NORMAL OPERATION 36
3.6. O
PERATING PARAMETERS 37
3.6.1. R
EGULATION MENU TABLE 37
3.6.2. S
ETTINGS DISPLAY 43
3.6.3. G
AS REGULATION CHECK 44
3.6.4. I
GNITION DELAY ADJUSTMENT 45
3.6.5. A
DJUSTING THE MAXIMUM HEATING
POWER 45
3.6.6. S
OFT LIGHT ADJUSTMENT 45
3.7. C
HANGING THE TYPE OF GAS 45
3.8. A
DJUSTING THE DOMESTIC HOT
WATER FLOW RAT E 45
3.9. B
ALANCING THE CENTRAL
HEATING SYSTEM 45
3.10. B
OILER SAFETY SYSTEMS 46
3.11. C
OMPLETION 47
3.12. D
RAINING 47
4. ZONE VALVES 48
5. SEQUENCE OF OPERATION 51
5.1 CENTRAL HEATING MODE 51
5.2 D
OMESTIC HOT WATE R MODE 51
6. MAINTENANCE 52
6.1. GENERAL REMARKS 52
6.2. C
LEANING THE PRIMARY EXCHANGER 52
6.3. C
LEANING THE CONDENSATE TRAP 52
6.4. O
PERATIONAL TEST 52
7. SERVICING INSTRUCTIONS 53
7.1. REPLACEMENT OF PARTS 53
7.2. T
O GAIN GENERAL ACCESS 53
7.3. A
CCESS TO THE COMBUSTION
CHAMBER 54
7.3.1. R
EMOVING THE FAN 54
7.3.2. R
EMOVING THE AIR PRESSURE SWITCH 55
7.3.3. R
EMOVING THE BURNER 55
7.3.4. R
EMOVING THE ELECTRODES 56
7.3.5. R
EMOVING THE HEAT EXCHANGER 56
7.3.6. R
EMOVING THE CONDENSATE
TRAP (TUBE)58
7.3.7. R
EMOVING THE CONDENSATE TRAP 58
7.4. A
CCESS TO THE GAS VALVE 59
7.4.1. R
EMOVING THE GAS VALVE 59
7.4.2. R
EMOVING THE SPARK GENERATOR 60
7.5. A
CCESS TO THE WATER CIRCUIT 60
7.5.1. R
EMOVING THE D.H.W.
(S
ECONDARY) EXCHANGER 60
7.5.2. R
EMOVING THE SAFETY VALVE 61
7.5.3. R
EMOVING THE AUTOMATIC AIR VENT 61
7.5.4. R
EMOVING THE DIVERTER VALVE
ACTUATOR 62
7.5.5. R
EMOVING THE DHW FLOW SWITCH
(MFFI ONLY)62
7.5.6. R
EMOVING THE PUMP 62
7.5.7. R
EMOVING THE PRESSURE GAUGE 63
7.5.8. R
EMOVING THE EXPANSION VESSEL 64
7.5.9. R
EMOVING THE D.H.W. TEMPERATURE
PROBE (N.T.C. - MFFI ONLY)64
7.5.10. R
EMOVING THE C.H. FLOW
TEMPERATURE PROBE (N.T.C.) 65
7.5.11. R
EMOVING THE C.H. RETURN
TEMPERATURE PROBE (N.T.C.) 65
7.6. A
CCESS TO THE CONTROL SYSTEM 66
7.6.1. C
HECKING THE FUSES 66
7.6.2. R
EMOVING THE PRINTED CIRCUIT
BOARDS 66
7.6.3. R
EMOVING THE TIME CLOCK 67
8. FAULT FINDING 68
8.1 FAULT FINDING GUIDE (FLOW-CHARTS)68
9. SHORT SPARES PARTS LIST 72
10. ANNUAL MAINTENANCE CHECKLIST 76
11. BENCHMARK COMMISSIONING CHECKLIST 78
12. SERVICE INTERVAL RECORD 79
PAGE PAGE
Page 3
3
This manual is an integral and essential part of the product. It should be kept with the appliance so that it can be consulted by the user and our authorised personnel.
Please carefully read the instructions and notices about the unit contained in this manual, as they provide important information regarding the safe installation, use and maintenance of the product.
For operating instructions please consult the separate Users Manual.
1. GENERAL INFORMATION
Read the instructions and recommendations in these Installation and Servicing Instructions carefully to ensure proper installation, use and maintenance of the appliance.
Keep this manual in a safe place. You may need it for your own reference while Servicing Technicians or your installer may need to consult it in the future.
The ACO 35 MFFI is a combined appliance for the production of central heating (C.H.) and domestic hot water (D.H.W.) and is designed for domestic use only..
This appliance must be used only for the purpose for which it is designed.
The manufacturer declines all liability for damage caused by improper or negligent use.
No asbestos or other hazardous materials have been used in the fabrication of this product.
MTS recommends the use of protective clothing when installing and working on the appliance i.e. gloves.
Before connecting the appliance, check that the information shown on the data plate and the table in Section 1.2 (page 4) comply with the electric, water and gas mains of the property. You will find the data plate on the inside of the casing. The gas with which this appliance operates is also shown on the label at the bottom of the boiler.
Do not install this appliance in a damp environment or close to equipment which spray water or other liquids.
Do not place objects on the appliance. Do not allow children or inexperienced persons to use the
appliance without supervision.
If you smell gas in the room, do not turn on or off light switches, use the telephone or any other object which might cause sparks. Open doors and windows immediately to ventilate the room. Shut the gas mains tap (at or adjacent to the gas meter) or the valve of the gas cylinder and call your Gas Supplier immediately.
Always disconnect the appliance either by unplugging it from the mains or turning off the mains switch before cleaning the appliance or carrying out maintenance.
In the case of faults or failure, switch off the appliance and turn off the gas tap. Do not tamper with the appliance. For repairs, call your local Authorised Servicing Agent and request the use of original spare parts. For in-guarantee repairs contact MTS (GB) Limited.
1.1. GENERAL INFORMATION
Page 4
4
Name CE Certification Flue Type
Heat Input max (Domestic Hot Water) kW Heat Input max/min (Central Heating) kW Heat Output max/min (Central Heating) kW Heat Output max/min (Domestic Hot Water) kW Efficiency of Nominal Heat Input (60/80°C) % Efficiency of Nominal Heat Input (30/50°C) % Efficiency at 30% of Nominal Heat Input (47°C) % Efficiency at 30% of Nominal Heat Input (30°C) % Efficiency at Minimum Input % Efficiency (Dir. 92/42/EEC)** SEDBUK Rating Band / % Heat Loss to the Casing (T=50°C) % Flue Heat Loss with Burner Operating %
General Info
Energy Performance
Max Discharge of Products of Combustion (G20) Kg/h Temp. of exhaust fumes at nominal capacity °C CO2 Content % O
2 Content %
CO Content ppm Nox Class
Emissions
Head Loss on Water Side (max) (T=20°C) mbar Residual Head of System bar Expansion Vessel Pre-load Pressure bar Maximum Heating Pressure bar Expansion Vessel Capacity l Maximum Water Content of System l Heating Temperature max/min (High temperature) °C Heating Temperature max/min (Low Temperature) °C
Central Heating
Domestic Hot Water Temperature (approx) max/min °C Specific Flow Rate (10 minutes/T 30°C) l/min D.H.W. Flow Rate ∆T=25°C l/min D.H.W. Flow Rate ∆T=35°C l/min D.H.W. Minimum Flow Rate l/min Pressure of Domestic Hot Water max/min bar
Domestic Hot Water
Nominal Pressure Natural Gas (G20) mbar Consumption at Nominal Capacity(G20) m3/h Gas Consumption after 10 Minutes* m
3
Gas
Electrical Supply V/Hz Power Consumption W Minimum Ambient Temperature °C Protection Grade of Electrical System IP Internal Fuse Rating
Electrical Data
Weight Kg Casing Dimensions (D/W/H) mm
G.C. Number
ACO 35 MFFI
1312BQ4461
C13-C33-C43-C53-C83-B23-B33
44.6 62
9.4
3.8
109
5 (70 mg/kW/h)
200
0.2
0.7 3 7
130 82 / 46 75 / 25
56 / 36
16
18.84
13.5
2.5
6 / 0.2
20
3.17
0.37
3 4
230/50
145
+5
24D
2A Fast Fuse
43
310/450/750
47-116-35
* Calculated at 70% maximum output ** Calculated on Upper calorific value
Max. Condensate produced l/h PH of condensate PH
1.2. TECHNICAL INFORMATION
37.2
33.3 / 7.4
29.4 / 6.5
33.3 / 7.4
88.2
94.6
92.5
97.4
87.3
A / 90.2
0.4
1.7
Page 5
5
LEGEND:
1. Air Release Valve
2. Main Heat Exchanger (Stainless Steel)
3. Detection Electrode
4. Central Heating Flow Temperature Probe
5. Overheat Thermostat
6. Central Heating Return Temperature Probe
7. Air / Gas Mixer
8. Gas Valve
9. P.C.B. Box
10. Diverter Valve
11. Condensate Discharge
12. Condensate Trap
13. Low Water Pressure Switch
14. Domestic Hot Water Temperature Probe
1.3. OVERALL VIEW
FIG. 1.0
15. Secondary Heat Exchanger
16. Domestic Hot Water Flow Switch
17. Circulation Pump with Automatic Air Release Valve
18. Safety Valve (3 bar)
19. Automatic By-pass
20. Fan
21. Ignition Electrode
22. Silencer
23. Spark Generator
24. Expansion Vessel
25. Combustion Analysis Test Point
26. Flue Connector
26 25
1
24
23
22
2
21
3
4
5 6
20
7
8
19
9
18
10
11 1312 14 15 16
17
11
Page 6
6
The technical information and instructions provided herein below are intended for the installer / Servicing Technician so that the unit may be installed and serviced correctly and safely.
In the United Kingdom the installation and initial start up of the boiler must be by a CORGI Registered Installer in accordance with the installation standards currently in effect, as well as with any and all local health and safety standards i.e. CORGI.
In the Republic of Ireland the installation and initial start up of the appliance must be carried out by a Competent Person in accordance with the current edition of I.S.813 “Domestic Gas Installations”, the current Building Regulations, reference should also be made to the current ETCI rules for electrical installation.
This appliance must be installed by a competent installer in accordance with current Gas Safety (installation & use) Regulations.
The installation of this appliance must be in accordance with the relevant requirements of the Local Building Regulations, the current I.E.E. Wiring Regulations, the byelaws of the local water authority, in Scotland, in accordance with the Building Standards (Scotland) Regulation and Health and Safety document No. 635 “Electricity at work regulations 1989” and in the Republic of Ireland with the current edition of I.S. 813, the Local Building Regulations (IE).
C.O.S.H.H.
Materials used in the manufacture of this appliance are non­hazardous and no special precautions are required when servicing.
Installation should also comply with the following British Standard Codes of Practice:
and in the Republic of Ireland in accordance with the following Codes of Practice:
2. INSTALLATION
2.1. REFERENCE STANDARDS
BS 7593:1992 Treatment of water in domestic hot water
central heating systems
BS 5546:1990 Installation of hot water supplies for
domestic purposes BS 5440-1:2000 Flues BS 5440-2:2000 Air supply BS 5449:1990 Forced circulation hot water systems BS 6798:2000 Installation of gas fired hot water boilers
of rated input not exceeding 70kW BS 6891:2005 Installation of low pressure gas pipe up to
28mm BS 7671:2001 IEE wiring regulations BS 4814:1990 Specification for expansion vessels BS 5482:1994 Installation of L.P.G.
I.S. 813 Domestic Gas Installations
2.2. SITING THE APPLIANCE
The appliance may be installed in any room or indoor area, although particular attention is drawn to the requirements of the current I.E.E. Wiring Regulations, and in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the combined appliance in a room containing a bath or shower, the location of the boiler in a room containing a bath or shower should only be considered if there is no alternative.
Where a room-sealed appliance is installed in a room containing a bath or shower the appliance and any electrical switch or appliance control, utilising mains electricity should be situated so that it cannot be touched by a person using the bath or shower, specifically in accordance with current IEE Wiring Regulations.
The location must permit adequate space for servicing and air circulation around the appliance as indicated in Section 2.4. The location must permit the provision of an adequate flue and termination. For unusual locations special procedures may be necessary. BS 6798-2000 gives detailed guidance on this aspect. A compartment used to enclose the appliance must be designed specifically for this purpose. No specific ventilation requirements are needed for the installation within a cupboard. This appliance is not suitable for outdoor installation.
The type C appliances (in which the combustion circuit, air vent intake and combustion chamber are air-tight with respect to the room in which the appliance is installed) can be installed in any type of room.
Secondary ventilation is not required with this boiler. The boiler must be installed on a solid, non-combustible, permanent wall to prevent access from the rear.
Page 7
7
2.3. OVERALL DIMENSIONS
In order to allow access to the interior of the boiler for maintenance purposes, the boiler must be installed in compliance with the clearance requirements indicated in the diagram below.
2.4. MINIMUM CLEARANCES
LEGEND:
A = Central Heating Flow (3/4”) (22mm Copper Tail) B = Domestic Hot Water Outlet (1/2”) (15 mm Copper Tail) C = Gas Inlet (3/4”) ( 22mm Copper Tail) D = Domestic Cold Water Inlet (1/2”) (15mm Copper Tail) E = Central Heating Return (3/4”) (22mm Copper Tail) SV outlet = 1/2” Female BSP (Not Shown)
FIG. 2.0
FIG. 2.1
F
IG. 2.2
After removing the boiler from its packaging, remove the template from the separate box containing the connection kit. N
OTE: Pay particular attention to any test water that may spill
from the appliance.
Place the template in the position the appliance is to be mounted and after ensuring it is hanging squarely, use it to mark the holes for the hanging bracket, connection kit and flue pipe(s) NB: For further information relating to the flue installation please refer to Section 2.9 F
LUE CONNECTION. (If the appliance is to be
fitted on a wall of combustible material, the wall must
be protected by a sheet of fireproof material). If the appliance is to be fitted into a timber framed building, guidance should be sought from the Institute of Gas Engineers document REF: IGE/UP/7.
2.5.1. Drill the wall and plug using those supplied with the
connections kit, position the hanging bracket and secure with the wall screws supplied, assemble the connection kit and secure to the wall. N
OTE: It is highly
recommended that a spirit level be used to position the appliance to ensure that it is perfectly level.
2.5.2. Position the appliance on the hanging bracket and
connect the connection kit to the boiler connections. (see also Sections 2.7 Gas Connections, 2.8 Water Connections & F
IG. 2.4).
For safety purposes, have a competent person carefully check the electrical system in the property, as the manufacturer will not be held liable for damage caused by the failure to earth the appliance properly or by anomalies in the supply of power. Make sure that the residential electrical system is adequate for the maximum power absorbed by the unit, which is indicated on the rating plate. In addition, check that the section of cabling is appropriate for the power absorbed by the boiler.
2.5.
MOUNTING THE APPLIANCE
785
310
450
450
130 130
225 225
143
750 35
93 65
F
67 67 65 93
100
120
water gas
323
310
5
45
50
Page 8
8
2.8. WATER CONNECTIONS
Legend:
A = Central Heating Flow B = Domestic Hot Water Outlet C = Gas Inlet D = Domestic Cold Water Inlet E = Central Heating Return H = Condensate discharge G = Condensate trap F = Safety valve discharge
Central Heating
Detailed recommendations are given in BS 6798:2000 and BS 5449-1:1990, the following notes are given for general guidance.
P
IPEWORK
:
Copper tubing to BS EN 1057:1996 is recommended for water pipes. Jointing should be either with capillary soldered or compression fittings. Where possible pipes should have a gradient to ensure air is carried naturally to air release points and water flows naturally to drain taps. The appliance has a built-in automatic air release valve, however it should be ensured as far as possible that the appliance heat exchanger is not a natural collecting point for air. Except where providing useful heat, pipes should be insulated to prevent heat loss and avoid freezing. Particular attention should be paid to pipes passing through ventilated spaces in roofs and under floors.
BY-
PASS
:
The appliance includes an automatic by-pass valve, which protects the main heat exchanger in case of reduced or interrupted water circulation through the heating system, due to the closing of thermostatic valves or cock-type valves within the system.
S
YSTEMDESIGN
:
This boiler is suitable only for sealed systems.
D
RAINCOCKS
:
These must be located in accessible positions to permit the draining of the whole system. The taps must be at least 15mm nominal size and manufactured in accordance with BS 2870:1980.
VIEW OF THE BOILER CONNECTIONS
G
H
FIG. 2.4
2.6. ELECTRICAL CONNECTION
The boiler operates with alternating current, as indicated in the technical data table (Section 1.2), where the maximum absorbed power is also indicated. Make sure that the connections for the neutral and live wires correspond to those indicated in Fig.2.3). The appliance electrical connections are situated inside the electrical box (see Section 2.12).
I
MPORTANT
!
In the event that the power supply cable must be changed, replace it with one with the same specifications. Make the connections to the terminal board located within the control panel, as follows:
- The yellow-green wire should be connected to the terminal marked with the earth symbol; make sure to re-use the ferrule mounted on the other supply cable;
- The blue wire should be connected to the terminal marked “N”;
- The brown wire should be connected to the terminal marked “L”.
FIG. 2.3
2.7. GAS CONNECTION
The local gas region contractor connects the gas meter to the service pipe. If the gas supply for the boiler serves other appliances ensure that an adequate supply is available both to the boiler and the other appliances when they are in use at the same time. Pipe work must be of an adequate size. Pipes of a smaller size than the boiler inlet connection must not be used.
Note: The diagrams for the electrical system are indicated in Sections 2.12 and 2.13 (pages 22-24).
Warning, this appliance must be earthed.
External wiring to the appliance must be carried out by a competent person and be in accordance with the current I.E.E. Regulations and applicable local regulations. The appliance is supplied with a fly-lead already connected, this must be connected to a 240v supply fused at 3A and must facilitate complete electrical isolation of the appliance, by the use of a fused double pole isolator having a contact separation of at least 3 mm in all poles or alternatively, by means of a 3 A fused three pin plug and unswitched shuttered socket outlet both complying with BS 1363. The point of connection to the Electricity supply must be readily accessible and adjacent to the appliance unless the appliance is installed in a bathroom when this must be sited outside the bathroom (see Section 2.2). Should external controls be required, the design of the external electrical circuits should be undertaken by a competent person, see Sections 2.12 for further information.
F
Page 9
9
RESIDUAL HEAD OF THE BOILER∆T20°C
FIG. 2.5
S
AFETYVALVEDISCHARGE
:
The discharge should terminate facing downwards on the exterior of the building in a position where discharging (possibly boiling water & steam) will not create danger or nuisance, but in an easily visible position, and not cause damage to electrical components and wiring. The discharge must not be over an entrance or a window or any other type of public access.
C
ONDENSATEDISCHARGE
:
A flexible hose is supplied for connection to the condensate discharge point H (Fig. 2.4). The condensate discharge hose from the boiler must have a continuous fall of 2.5° and must be inserted by at least 50 mm into a suitable acid resistant tundish / pipe - e.g. plastic waste or overflow pipe. The condensate discharge pipe must have a continuous fall and preferably be installed and terminated within the building to prevent freezing.
N
OTE:THE FLEXIBLE CONDENSE HOSE SUPPLIED WITH THE
APPLIANCE CAN BE EXTENDED BY PULLING THE TUBE OPENING THE
RIBBED PIPE
.
The discharge pipe must be terminated in a suitable position:
i) Connecting in to an internal soil stack (at least 450 mm
above the invert of the stack). A trap giving a water seal of at least 75 mm must be incorporated into the pipe run, there also must be an air break upstream of the trap.
ii) Connecting into the waste system of the building such as
a washing machine or sink trap. The connection must be upstream of the washing machine/sink (If the connection is down stream of the waste trap then an additional trap giving a minimum water seal of 75 mm and an air break must be incorporated in the pipe run, as above.
iii) Terminating into a gully, below the grid level but above the
water level.
iv) Into a soakway.
N
OTE: If any condensate pipe work is to be installed externally,
then it should be kept to a minimum and be insulated with a waterproof insulation and have a continuous fall.
Some examples of the type of condensate drains can be seen on this page.
2. External termination of condensate drainage pipe via internal discharge branch (e.g. sink waste) and condensate siphon
3. External termination of condensate drainage pipe via internal discharge branch (e.g. sink waste - proprietary fitting).
1. Internal termination of condensate drainage pipe to internal stack
800
700
600
500
400
[mbar]
300
200
100
0
0 200 400 600 800 1000 1200 1400 1600
[l/h]
Page 10
10
4. External termination of condensate drainage pipe via condensate siphon
AIRR
ELEASEPOINTS
:
These must be fitted at all high points where air naturally collects and must be sited to facilitate complete filling of the system. The appliance has an integral sealed expansion vessel to accommodate the increase of water value when the system is heated. It can accept up to 7 l (1.5 gal) of expansion water. If the heating circuit has an unusually high water content, calculate the total expansion and add an additional sealed expansion vessel with adequate capacity.
M
AINSWATE RFEED
- C
ENTRALHEATING
:
There must be no direct connection to the mains water supply even through a non-return valve, without the approval of the Local Water Authority.
F
ILLING
:
A method for initially filling the heating system is supplied with the connection kit. The filling loop is connected between the cold water inlet and the central heating flow connections, and incorporates a non-return valve. To operate the filling loop, it is necessary to open both quarter turn handles, once the required pressure has been achieved, close both handles and disconnect the hose in accordance with water regulations. N
OTE: The installer should ensure that there are
no leaks as frequent filling of the heating system can lead to premature scaling of the main exchanger and failure of hydraulic components.
D
OMESTICWATE R
The domestic water must be in accordance with the relevant recommendation of BS 5546:1990. Copper tubing to BS EN 1057:1996 is recommended for water carrying pipe work and must be used for pipe work carrying drinking water, a scale reducer should also be used to reduce the risk of scale forming in the domestic side of the heat exchanger.
U
NDERFLOORHEATINGSYSTEMS
:
In the event of an under floor heating system, fit a safety thermostat on the boiler flow (instructions for wiring the thermostat to connection SP on the PCB can be found in Section 2.12). This thermostat should be positioned at a safe distance from the boiler to ensure the correct operation of the same. If the thermostat is positioned too close to the boiler, the water remaining in the boiler after domestic hot water has been drawn will flow into the central heating system and may cause the thermostat contact to open without there being any real danger of the system being damaged, this would lead to a boiler shutdown both in D.H.W. mode and C.H. mode, and the error code “E08” would be displayed; boiler operation resumes automatically when the thermostat contact closes on cooling. Should the thermostat fail to be installed as recommended, the under floor heating system can be protected by installing a thermostatic valve upstream from the thermostat in order to prevent the flow of excessively hot water towards the system.
WATER TREATMENT
The boiler is equipped with a stainless steel heat exchanger.
The detailed recommendations for water treatment are given in BS 7593:1992 (Treatment of water in domestic hot water central heating systems); the following notes are given for general guidance;
If the boiler is installed on an existing system, any unsuitable additives must be removed.
Under no circumstances should the boiler be fired before the system has been thoroughly flushed; the flushing procedure must be in line with BS7593:1992.
We highly recommend the use of a flushing detergent appropriate for the metals used in the circuit. These include cleansers produced by Fernox and BetzDearborn, whose
Page 11
11
function is to dissolve any foreign matter that may be in the system;
In hard water areas or where large quantities of water are in the system the treatment of the water to prevent premature scaling of the main heat exchanger is necessary.
The formation of scale strongly compromises the efficiency of the thermic exchange because small areas of scale cause a high increase of the temperature of the metallic walls and therefore add to the thermal stress of the heat exchanger.
Demineralised water is more aggressive so in this situation it is necessary to treat the water with an appropriate corrosion inhibitor.
Any treatment of water by additives in the system for frost protection or for corrosion inhibition has to be absolutely suitable for all the metals used in the circuit.
The use of a corrosion inhibitor in the system such as Fernox MB-1, BetzDeaborn Sentinel X100 or Fernox System Inhibitor is recommended to prevent corrosion (sludge) damaging the boiler and system;
If anti-freeze substances are to be used in the system, check carefully that they are compatible with the metals used in the circuit.
MTS suggests the use of suitable anti-freeze products such as Fernox ALPHI 11, which will prevent rust and incrustation taking place.
Periodically check the pH of the water/anti-freeze mixture of the boiler circuit and replace it when the amount measured is out of the range stipulated by the manufacturer ( 7 < pH < 8). DO NOT MIX DIFFERENT TYPES OF ANTI-FREEZE
In under-floor systems, the use of plastic pipes without protection against penetration of oxygen through the walls can cause corrosion of the systems metal parts (metal piping, boiler, etc), through the formation of oxides and bacterial agents.
To prevent this problem, it is necessary to use pipes with an “oxygen-proof barrier”, in accordance with standards DIN 4726/4729. If pipes of this kind are not used, keep the
system separate by installing heat exchanger
s of those
with a specific system water treatment.
IMPORTANT Failure to carry out the water treatment procedure will invalidate the appliance warranty.
Page 12
12
2.9. CONNECTING THE FLUE
IMPORTANT!!
BEFORE CONNECTING THE FLUE, ENSURE THAT 1 LITRE OF
WATER HAS BEEN POURED INTO THE EXHAUST CONNECTION
TO FILL THE CONDENSATE TRAP
(FIG.2.7). SHOULD THE TRAP
BE EMPTY THERE IS A TEMPORARY RISK OF FLUE GASSES ESCAPING INTO THE ROOM.
FIG. 2.7
Ø 60/100 mm
Fig. 2.9
FIG. 2.9
TERMINAL POSITION mm
A - Directly below an open window or other opening 300 B - Below gutters, solid pipes or drain pipes 75 C - Below eaves 200 D - From vertical drain pipes and soil pipes 75 E - From internal or external corners 300 F - Above ground on a public walkway or patio 2100 G - From a surface facing a terminal 2500 H - From a terminal facing a terminal 2500
I - Vertically from a terminal in the same wall 1500 J - Horizontally from a terminal in the same wall 300 K - Horizontally from an opening window 300 L - Fixed by vertical flue terminal
F
LUESYSTEM
The provision for satisfactory flue termination must be made
as described in BS 5440-1.
The appliance must be installed so that the flue terminal is
exposed to outdoor air.
The terminal must not discharge into another room or space
such as an outhouse or lean-to.
It is important that the position of the terminal allows a free
passage of air across it at all times.
The terminal should be located with due regard for the
damage or discolouration that might occur on buildings in the
vicinity, it must also be located in a place not likely to cause
nuisance.
In cold or humid weather water vapour may condense on
leaving the flue terminal.
The effect of such “steaming” must be considered.
If the terminal is 2.1 metres above a balcony, above ground
or above a flat roof to which people have access, then a
suitable stainless steel terminal guard must be fitted.
The minimum acceptable spacing from the terminal to
obstructions and ventilation openings are specified in Fig.
2.9.
E
E
4
120 mm
Page 13
13
Warning
The exhaust gas ducts must not be in contact with or close to inflammable material and must not pass through building structures or walls made of inflammable material. When replacing an old appliance, the flue system must be changed.
Important
Ensure that the flue is not blocked. Ensure that the flue is supported and assembled in accordance with these instructions.
2.9.1 FITTING THE COAXIAL FLUE (Ø 60 / 100 HORIZONTAL)
Installation without extension
Installation with extension
Fig. 2.10
Fig. 2.11
Level
Level
C
ONTENTS
:
1
XSILICONE
O-R
ING
(60mm)
1XE
LBOW
(90O)
2XW
ALLSEALS(INTERNAL&EXTERNAL
)
1
XFLUEPIPE INCLUDINGTERMINAL
(1
METRE
- 60/100)
1XF
LUECLAMP
1XS
CREWS
1x Seal
Once the boiler has been positioned on the wall, insert the elbow into the socket and rotate to the required position.
NOTE: It is possible to rotate the elbow 360
o
on its vertical axis.
Using the flue clamp, seals and screws supplied (Fig 2.12) secure the elbow to the boiler.
The 1 metre horizontal flue kit (3318073) supplied is suitable for an exact X dimension of 815mm.
Measure the distance from the face of the external wall to the face of the flue elbow (X - Fig 2.9), this figure must now be subtracted from 815mm, you now have the total amount to be cut from the plain end of the flue.
Draw a circle around the outer flue and cut the flue to the required length taking care not to cut the inner flue, next cut the inner flue ensuring that the length between the inner and outer flue is maintained. (Fig 2.12).
e.g.
X = 555mm 815-555 = 260mm (Length to be cut from the plain end of the flue).
Once cut to the required length, ensure that the flue is free from burrs and reassemble the flue. If fitting the flue from inside of the building attach the grey outer wall seal to the flue terminal and push the flue through the hole, once the wall seal has passed through the hole, pull the flue back until the seal is flush with the wall. Alternatively, the flue can be installed from outside of the building, the grey outer seal being fitted last.
120
* slope
150 mm
150 mm
* slope 5 mm per metre
Page 14
14
Fig. 2.12
2.9.2 FITTING THE 5” FLUE (Ø 80 / 125 HORIZONTAL/VERTICAL)
Should the flue require extending, the flue connections are push fit, however, one flue bracket should be used to secure each metre of flue.
N
OTE:SEE PAGE 19 FOR MAXIMUM AND MINIMUM FLUE RUNS.
Once the boiler has been positioned on the wall, it is necessary to insert the Ø80/125 adaptor (F
IG. 2.13) for both
horizontal and vertical flue runs into the boiler flue socket (not supplied with flue kit - Part No 3318095).
Push the adaptor onto the boilers flue connection, grease the seals then add extensions or elbows as required, secure the adaptor, using the clamp and screws provided.
To fit extensions or elbows it is first necessary to ensure that the lip seal is fitted correctly into the inner flue, once verified, it is simply necessary to push them together, no clamps are necessary to secure the flue components.
Before proceeding to fit the flue, ensure that the maximum flue length has not been exceeded (See the tables on Page
19) and that all elbows and bends have been taken into consideration, the maximum flue length is 10 metres, for each additional 90
o
elbow 1 metre must be subtracted from the
total flue length, and for each 45o0.5 metres must be subtracted from the total flue length (the height of the
vertical adaptor and a 45obend can be seen in Fig. 2.14 and a 90
o
bend in Fig. 2.15).
N
OTE: DO NOT CUT THE VERTICAL FLUE KIT.
Screws
Clamp
Seal
Fig. 2.13
Fig. 2.14
Fig. 2.15
Page 15
15
NOTE:SEE PAGE 19 FOR MAXIMUM AND MINIMUM FLUE RUNS.
C
ONTENTS
:
1
XSILICONE
O-R
ING
(60mm)
1
XCONICALADAPTOR
(60/100mm)
1XV
ERTICALFLUEKIT
(80/125mm)
3
XSCREWS
The vertical flue kit is supplied with a specially designed weather proof terminal fitted, it can be used either with a flat roof or a pitched roof.
The Vertical flue kits useable lengths with the pitched roof flashings are indicated in Fig. 2.16.
Before proceeding to fit the flue, ensure that the maximum flue length has not been exceeded (See the tables on Page
19) and that all elbows and bends have been taken into consideration, the maximum flue length is 4 metres, for each additional 90
o
elbow 1 metre must be subtracted from the
total flue length, and for each 45
o
0.5 metres must be
subtracted from the total flue length (the height of the
vertical adaptor and a 45
o
bend can be seen in Fig. 2.17).
Mark the position of the flue hole in the ceiling and/or roof (see Fig. 2.15 for distance from wall to the centre of the flue).
Cut a 120mm diameter hole through the ceiling and/or roof and fit the flashing plate to the roof.
DO
NOT
cut the vertical flue kit.
To connect the vertical flue kit directly to the boiler, place the vertical starter kit (Part No. 3318079) (see Fig. 2.16) onto the exhaust manifold and secure with the clamp, fit the vertical adaptor onto the vertical starter kit (note: there is no need to use a clamp to secure this as it is a push fit connection), the vertical flue kit must then be inserted through the roof flashing, this will ensure that the correct clearance above the roof is provided as the terminal is a fixed height.
Should extensions be required, they are available in 1 metre (Part No. 3318077), 500mm (Part No. 3318078) and 160mm lengths, they must be connected directly to the vertical starter kit before connecting the adaptor to allow the vertical flue kit to be fitted. In the event that extension pieces need to be shortened, they
must
only be cut at the male end and it must
be ensured that the inner and outer flue remain flush (Fig.
2.12)
When utilising the vertical flue system, action must be taken to ensure that the flue is supported adequately to prevent the weight being transferred to the appliance flue connection by using 1 flue bracket per extension.
When the flue passes through a ceiling or wooden floor, there must be an air gap of 25mm between any part of the flue system and any combustible material. The use of a ceiling plate will facilitate this. Also when the flue passes from one room to another a fire stop must be fitted to prevent the passage of smoke or fire, irrespective of the structural material through which the flue passes.
2.9.3. FITTING THE COAXIAL FLUE (Ø 60 / 100 VERTICAL)
Fig. 2.16
Fig. 2.17
Page 16
16
2.9.4. FITTING THE TWIN PIPE (Ø80 / 80)
NOTE:SEE PAGE 19 FOR MAXIMUM AND MINIMUM FLUE RUNS.
Where it is not possible to terminate the flue within the distance permitted for coaxial flues, the twin flue pipe can be used by fitting a special adaptor to the flue connector and using the aperture for the air intake located on top of the combustion chamber.
Always ensure that the flue is adequately supported, using one flue bracket per extension and avoiding low points. (MTS supply suitable clamps as Part No. 705778). To utilise the air intake it is necessary to:
1) Take the air intake cover off the top of the appliance
2) Assemble the flange on the header supplied with the boiler
3) Insert the header on the tube or the elbow up until the lower stop (you do not have to use the washer).
4) Insert the elbow/header in the boiler air intake hole and fasten it with screws.
The twin flue pipes can be fitted with or without additional elbows and need no clamps, simply ensure that the red o-ring is inserted in the female end of the flue pipe and push the extension piece fully into the previous section of flue pipe or elbow, check that the o-ring is not dislodged when assembling the flue (greasing the seal will aid assembly).
Twin pipe can also be converted back to Coaxial flue to enable vertical termination with a coaxial kit by using the pipe bridge (Twin - Coaxial Adaptor - Part No. 3318089). When running the twin flue pipe vertically.
It is not possible to terminate concentrically horizontally. Termination is only possible with separate air and exhaust terminals.
When siting the twin flue pipe, the air intake and exhaust terminals must terminate on the same wall, the centres of the terminals must
be a minimum of 280 mm apart and the air
intake must
not be sited above the exhaust terminal (refer to Fig. 2.20). The air intake pipe can be run horizontally, however, the terminal and the final 1 metre of flue must be installed either horizontally or with a slight fall away from the boiler to avoid rain ingress.
It is also strongly recommended that the air intake pipe run be constructed of insulated pipe to prevent condense forming on the outside of the tube.
The maximum permissible flue length for twin flue is dependent on the type of run used. For flue runs with the intake and exhaust pipes under the same atmospheric conditions (T
YPE 4) the maximum length is
38 metres (27kW) and 48 metres (32kW), for runs with the terminals under different atmospheric conditions (T
YPE 5) the
exhaust terminal must
extend 0.5 metres above the ridge of the roof (this is not obligatory if the exhaust and air intake pipes are located on the same side of the building). For T
YPE
5 also, the maximum permissible combined length is 51 metres (27kW) and 49 metres (32kW).
The maximum length is reached by combining the total lengths of both the air intake and exhaust pipes. Therefore a maximum length of 40 metres for example, will allow a flue run of 20 metres for the air intake and 20 metres for the exhaust pipes, also for each 90
o
elbow 2.2 metres must be
subtracted from the total length and for each 45
o
elbow 1.4
metres must be subtracted from the total flue length.
Some of the acceptable flue configurations are detailed on page 20.
For further information relating to flue runs not illustrated, please contact the Technical Department on 0870 241 8180.
Page 17
17
Fig. 2.18
In the event that twin flue pipes are used, and the boiler has a side clearance of less than 60mm from the wall, it is necessary to cut a larger diameter hole for the flue pipe, this should be ø10 cm, this will then allow for easier assembly of the air intake elbow and the tube outside the wall (see Fig.
2.19).
Fig. 2.19
In the event that the air intake and exhaust are run to the left, it will be necessary to reduce the height of the air intake by cutting 20mm from the base of the air intake elbow (see Fig.
2.18)
Coaxial
Systems
Twin Pipe
Systems
Exhaust Type
Type 1 Type 1
Types 2 & 3
Type 4
Type 5
Maximum Extension
Exhaust/Air
(m)
4 (Horizontal)
16 (Horizontal)
4 (Vertical)
16 (Vertical)
54
(Air Intake & Exhaust
Equal Lengths (27
and 27 metres)
1+56 (Air Intake 1
Metre and Exhaust 56
Metres)
Diameter
of Pipes
(mm)
Ø 60/100 Ø 80/125
Ø 60/100 Ø 80/125
Ø 80/80
Ø 80/80
Reduction
45
o
(m)
0.5
0.5
0.5
0.5
0.25
0.25
Reduction
90
o
(m)
1 1
1 1
0.5
0.5
ø 100
60 mm
Page 18
18
Fig. 2.20
NOTE: DRAWINGS ARE INDICATIVE OF FLUEING OPTIONS ONLY.
TYPE 1
TYPE 5
TYPE 4
TYPE 3
TYPE 2
Fig. 2.19
AIR INTAKE MUST NOT BE
FITTED ABOVE THE EXHAUST
AIR INTAKE
EXHAUST
AIR INTAKE
Page 19
19
FIG. 2.22
FIG. 2.21
FIG. 2.23
DIGITAL
MECHANICAL
FIG. 2.20
C2
C2
C2
2.10. FITTING THE MECHANICAL / DIGITAL CLOCK
The ACO MFFI boiler is supplied with a factory fitted mechanical time clock. There is a digital clock available as an optional extra (code: 706348).
To fit the digital clock it is necessary to proceed as follows:-
1. Remove the outer casing
2. Open the control panel (see fig. 2.20);
3. Unplug the electrical connection from the PCB and unscrew the four screws (Fig. 2.21);
4. Remove the time clock (Fig. 2.22).
5. Connect the wires supplied with the clock to the digital time clock as shown in Fig. 2.23;
6. Reassemble in reverse order.
N
OTE:THE MECHANICAL CLOCK HAS FOUR WIRES, THEREFORE THE
HARNESS WILL REQUIRE CHANGING ALSO
.
G
5
3
B
1
2
R
3
1
2
R
B
4
G
Page 20
20
2.11. SETTING THE MECHANICAL TIME CLOCK
2.11.1. SETTING THE DIGITALTIME CLOCK
Fig. 2.24
1. General layout
The mechanical clock covers a 24 hour period. Each tappet represents 15 minutes A (Fig. 2.25). An override switch is
located on the clock B (Fig 2.25).
2. To set the time
To set the time of day, grasp the outer edge of the dial and turn slowly clockwise until the correct time is lined up with the arrow C (Fig. 2.25).
3. To Set the "On" and "Off" times
The clock uses a 24hours system. e.g. 8 = 8.00 am and 18 = 6.00 pm. "ON" periods are set by sliding all tappets between the "ON" time and the "OFF" time to the outer edge of the dial.The tappets remaining at the centre of the dial are the "OFF" periods.
4. For operation
Put the selector switch B to the symbol to control the central heating by the clock. Put the switch B to «I» to select permanent operation or to «0» to turn the central heating off permanently.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
9
6
12
A
C
B
Fig. 2.25
Operating the time switch
The steps marked with the symbol “ ” are necessary to carry out a switching program.
Preparing for Operation
Activate the “Res” switch (=RESET) to reset the time switch to its default setting (activate using a pencil or similar pointed instrument). Do this:
- every time you wish to “reset” the time switch
- to erase all switching times and the current time of day. After approximately two seconds the following display appears: “– – : – –”.
Enter current time and weekday
- Keep the “ ” key pressed down During the summer time period press the +/- 1h key once. Enter the hour using the “h” key Enter the minutes using the “m” key Enter the day using the “Day” key
1 = “Monday”..............7 = Sunday
- Release the “ ” key.
1
12
6
13
24
14
23
15
22
16
21
20
I
19
18
17
2
3
4
5
6
7
9
8
9
10
11
12
Page 21
21
Entering the switching times
You have 20 memory Iocations available. Each switching time takes up one memory location. Keep pressing the “Prog” key until a free memory location is shown in the display “– –:– –”. Programme ON or OFF with the “ ” key: “ ”= OFF; “ ”= ON Enter the hour using “h” Enter the minutes using “m” If a switching command is to be carried out every day (1 2 3 4 5 6 7) then store using the “ ” key, otherwise select the day(s) it is to be carried out by using the “Day” key. When the day seIection is left bIank, the programmed switching instruction operates at the same time every day 1 2 3 4 5 6 = Monday – Saturday 1 2 3 4 5 = Monday – Friday 6 7 =Saturday – Sunday
Selection of single days: 1 = Mon. .............. 2 =Tues.
Save the switching time with the “ ” key. The time switch enters the automatic operating mode and displays the current time of day. Begin any further entry of a switching time with the “Prog” switch. If your entry is incomplete, the segments not yet selected will blink in the display. After programming is completed, and you return the time clock to the current time display with the “ ” key, the time clock will not activate any switching instruction required for the current time. You may need to manually select the desired switching state with the “ ” key. Thereafter, as the unit encounters further switching instructions in the memory in real time, it will correctly activate all subsequent switching instructions.
Manual Override Switch “
With the “ ” you can change the current setting at any time. The switching program already entered is not altered.
Reading the programmed switching times
Pressing the “Prog” key displays the programmed switching times until the first free memory location appears in the display “– – : – –”.
If you now press the “Prog” key once again, the number of free memory Iocations will be displayed, e.g. “18”. If all memory locations are occupied, the display “00” appears.
Changing the programmed switching times
Press the “Prog” key repeatedly until the switching time you want to change is displayed. You can now enter the new data. See point “Entering the switching times”.
Notes on storing switching times:
If you end your entry of the switching times by pressing the “Prog” key, then the switching time you have entered will be stored and the next memory location displayed.
In addition, a complete switching command is stored automatically after around 90 seconds provided no other key is pressed. The time switch then enters the automatic operating mode and displays the current time again.
Deleting individual switching times
Press the “Prog” key repeatedly until the switching time you wish to delete is shown in the display. Then set to “– –” using the “h” or “m” key and keep the “ ” key pressed down for around 3 seconds. The switching time is now erased and the current time is displayed.
AM / PM time display
If you press the “+/-1h” and “h” keys at the same time, the time display switches into the AM/PM mode.
Page 22
22
2.12. ACCESSORY CONNECTION
IMPORTANT!! Before carrying out any repairs to the appliance always ensure that the external power supply has been isolated. The boiler will remain live even when the ON/OFF knob is in the “O”(off) position.
IMPORTANT!!
Only remove the links from SP and TA if they are to be connected to external controls.
TA
SP
FIG. 2.27
F
IG. 2.26
In order to gain access to the external control connections, it is first necessary to remove the casing (as shown in Section 3.2 ­page 39) then proceed as follows:
1. Remove the cover of the main PCB box (Fig 2.26).
2. Access can now be gained to the following connectors (see Section 2.13 - page 24): CN10 - Safety thermostat for underfloor heating (SP) CN 9 - Room Thermostat (TA) CN 11 - Time clock CN 6 - Interface PCB (
FIG. 2.28)
CONNECTION OF ROOM THERMOSTAT OR EXTERNAL
TIME CLOCK
a. - Insert the thermostat cable through the cable grommet
and fasten it by means of the cable-clamp provided.
b. - Connect the thermostat wires to the terminal block
CN9 (Fig. 2.27 - Diagram A).
c.- If a remote time clock is to be fitted, supply 240V from
the same spur as the boiler for the clock motor supply, disconnect the integral time clock from the P.C.B. CN11
d. - Using a volt-free switching time clock, connect the
switching wires from the time clock following points A­C above (Fig. 2.27 - Diagram B).
e. - If using an external time clock and room thermostat,
these must be connected in series as points A-D above (Fig. 2.27 - Diagram C).
N
OTE:ENSURE LOW VOLTAGE AND HIGH VOLTAGE CIRCUITS ARE
CABLED SEPARATELY TO AVOID INDUCED VOLTAGES IN THE LOW
VOLTAGE CIRCUITS
.
Page 23
23
FIG. 2.28
FITTING THE EXTERNAL SENSOR (code. 3318888)
The external sensor is supplied with the interface PCB (Fig. 2.28).
The external sensor should be sited no more than 50 m from the boiler and on an external north facing wall, between 2.5 and 3 metres above the ground. It should also be ensured that the external sensor is positioned out of direct sunlight.
To connect the external sensor, plug the interface PCB into connector CN6 on the main PCB (see Fig. 2.28 and 2.29).
To connect between the interface PCB and the external sensor, it will be necessary to use 2x 0.5mm
2
cable, connected to the
two terminals on the external sensor and to Terminal B
(SE)
(Fig. 2.28) on the interface PCB.
Instructions on the activation and setting of the outdoor sensor are detailed on pages 37 and 38.
Parameter P activates the external sensor, Parameter P 6 modifies the thermal curve and Parameter P 5 selects the specific thermal curve for the type of system installed.
Page 24
24
2.13. ELECTRICAL DIAGRAM
The P.C.B. is fitted with 2 fuses, on the live and the neutral. The fuse holder contains:
- 5 x 20mm “3.15A Slow” glass fuses
FIG. 2.29
C
B
N
F
O
FLOOR
12 1
ROOM
2
34
1
2
TIMER
CN11
CN10
CN9
A
CN6
G
I
L
M
E
H
D
Underfloor
Heating Safety
thermostat
Optional
CN9 CN10
123456789
1
10 11 12
89 7
CN8 CN11
Bl Pnk
Gry Blk
Gry Wh
Rd Bl
Pnk
.
g
o
r
P
Room
thermostat
Day
Optional
D.H.W.
temperature
probe
D.H.W.
flow
C.H. Return
temperature
probe
switch
1
CN12
12345
101112
CN8
6
1
1
CN7
O
123456789
1011
12
2
L
N
L
1
CN5
N
CN16
CN4
Wh Wh AZ
Overheat
thermostat
C.H. Flow
temperature
probe
Az
Low
water
pressure
CN1
switch
BlK
CN2
10 11 12
89 7
Blk Pnk Gry
Wh Bl
Brn Blk
Rd
Spark
generator
Diverter
valve
Circulation
pump
Brn
1
FUSE
Bl
Az
Gas valve
Wh
CN1 CN12CN5
Rd Brn
Blk
Fan
FUSE
CN3
Bi
Page 25
25
Legend:
A-ON/OFF button B-Multifunction display C-Reset button D-Green LED (Indicates burner on) E-Comfort function LED (yellow) F-Red LED (indicates lockout) G-COMFORT button H-Central Heating temperature adjustment I-Programming key + L-Programming key - M-Menu button N-Domestic Hot Water temperature adjustment O-EEPROM key
CN1 = FAN
1:
Start of coil (black)
2: End of coil (brown) 3: “Hall” sensor power supply 12V (red) 4: “Hall” sensor input (white) 5: “Hall” sensor neutral (blue) 6: Not used
CN2 = FLAME SENSOR
CN3 = Earth
CN4 =
POWER SUPPLY
1: Live (brown) 2: Neutral (blue)
CN5 =
EQUIPMENT CONNECTIONS
1: Gas valve neutral (blue) 2: Gas valve live (brown) 3: Not used 4: Pump (V1) live (red) 5:
Pump (V2) live (black)
6:
Pump (ON/OFF) live (brown)
7:
Pump neutral (blue)
8: 3-way valve (C.H.) (red/black) 9: 3-way valve (D.H.W.)(brown) 10:
3-way valve Neutral (blue)
11: Spark generator Neutral (black) 12: Spark generator live (black)
CN6 = INTERFACE PCB
(OPTIONAL - see Section 2.12)
Accessories: External sensor Remote Control CLIMA MANAGER Secondary outlet (see Section. 2.12)
CN7 = DISPLAY
1: Power 5V 2: Display return 3: Display transmission 4: Earth
CN8 = SENSOR CONNECTOR
1: Central Heating flow sensor (white) 2: Central Heating return sensor (white) 3: Not used 4: DHW flow switch (grey) 5: DHW sensor (grey) 6: Not used 7: Not used 8: DHW flow switch earth (grey) 9: DHW sensor earth (grey) 10: C.H. flow sensor earth (white) 11: C.H. return sensor earth (white) 12: Not used
CN9 = ROOM THERMOSTAT (OPTIONAL - see Section 2.12)
CN10 = UNDERFLOOR HEATING
SAFETY THERMOSTAT (OPTIONAL - Section 2.12)
CN11 = TIME CLOCK
(see Section 2.12)
CN12 = SENSOR CONNECTOR
1: Not used 2: Not used 3: Low water pressure switch 4: Low water pressure switch earth 5: Overheat thermostat 6: Overheat thermostat
Page 26
26
2.14. WATER CIRCUIT DIAGRAM
L
EGEND
:
1 - Air release valve 2 - Main heat exchanger 3 - Burner 4 - Fan 5 - Air / Gas Mixer 6 - Gas valve 7 - Overheat thermostat 8 - Central heating flow temperature probe 9 - Secondary heat exchanger 10 - Motorised valve 11 - Low water pressure switch 12 - Domestic hot water temperature probe 13 - Condensate Trap 14 - Drain valve 15 - Automatic By-pass
16 - Domestic hot water flow switch 17 - Pressure gauge 18 - Safety valve 19 - Circulation pump with automatic
air release valve 20 - Central heating return temperature probe 21 - Expansion vessel
A - Central Heating Flow B - DHW Outlet C - Gas Inlet D - Cold Water Inlet E - Central Heating Return F - Safety valve discharge
G - Condensate trap
H - Condensate discharge
FIG. 2.30
1
2
10
11
3
21
4
5
6
20
7
8
9
19
18
17
bar
16
15
14
12
ABC
D
E
F
G
H
13
Page 27
27
3. COMMISSIONING
3.1. INITIAL PREPARATION
MTS (GB) Limited support the initiative. In Sections 11 and 12 of this manual you will find the commissioning checklist (page 70) and the service interval record (Page 71), It is important the commissioning checklist is completed in the presence of your customer, they are shown how to use it, and it is signed by them. Please instruct your customer that they must have this manual with them whenever they contact a service engineer or us. Preliminary electrical system checks to ensure electrical safety must be carried out by a competent person i.e. polarity, earth continuity, resistance to earth and short circuit.
F
ILLING THEHEATINGSYSTEM
:
Remove the case and lower the control panel (see section 3.2. for further information). Open the central heating flow and return cocks supplied with the connection kit. Unscrew the cap on the automatic air release valve one full turn and leave open permanently. Close all air release valves on the central heating system. Gradually open valve(s) at the filling point (filling-loop) connection to the central heating system until water is heard to flow, do not open fully. Open each air release tap starting with the lowest point and close it only when clear water, free of air, is visible.
Purge the air from the pump by unscrewing the pump plug and also manually rotate the pump shaft in the direction indicated by the pump label to ensure the pump is free.
I
MPORTANT!!
O
PEN THE MANUAL AIR VENT AND ENSURE THAT THE PRIMARY
EXCHANGER IS FREE OF AIR. (See FIG. 3.0)
Refit the pump plug. Continue filling the system until at least 1 bar registers on the pressure gauge. Inspect the system for water soundness and remedy any leaks discovered.
F
ILLING OF THE
D.H.W. S
YSTEM
:
Close all hot water draw-off taps. Open the cold water inlet cock supplied with the connection kit. Open slowly each draw-off tap and close it only when clear water, free of bubbles, is visible
GASS
UPPLY
:
Inspect the entire installation including the gas meter, test for soundness and purge, all as described in BS 6891:2005. Open the gas cock (supplied with the connection kit) to the appliance and check the gas connector on the appliance for leaks.
W
ATE RTREATMENT
:
The boiler is equipped with a stainless steel heat exchanger.
The detailed recommendations for water treatment are given in BS 7593:1992 (Treatment of water in domestic hot water central heating systems); the following notes are given for general guidance;
If the boiler is installed on an existing system, any unsuitable additives must be removed.
Under no circumstances should the boiler be fired before the system has been thoroughly flushed; the flushing procedure
Manual Air Vent
FIG. 3.0
Page 28
28
must be in line with BS7593:1992. We highly recommend the use of a flushing detergent appropriate for the metals used in the circuit. These include cleansers produced by Fernox and BetzDearborn, whose function is to dissolve any foreign matter that may be in the system; In hard water areas or where large quantities of water are in the system the treatment of the water to prevent premature scaling of the main heat exchanger is necessary.
The formation of scale strongly compromises the efficiency of the thermic exchange because small areas of scale cause a high increase of the temperature of the metallic walls and therefore add to the thermal stress of the heat exchanger.
Demineralised water is more aggressive so in this situation it is necessary to treat the water with an appropriate corrosion inhibitor.
Any treatment of water by additives in the system for frost protection or for corrosion inhibition has to be absolutely suitable for all the metals used in the circuit.
The use of a corrosion inhibitor in the system such as Fernox MB-1, BetzDeaborn Sentinel X100 or Fernox System Inhibitor is recommended to prevent corrosion (sludge) damaging the boiler and system;
If anti-freeze substances are to be used in the system, check carefully that they are compatible with the metals used in the circuit.
MTS suggests the use of suitable anti-freeze products such as Fernox ALPHI 11, which will prevent rust and incrustation taking place.
Periodically check the pH of the water/anti-freeze mixture of the boiler circuit and replace it when the amount measured is out of the range stipulated by the manufacturer ( 7 < pH < 8). DO NOT MIX DIFFERENT TYPES OF ANTI-FREEZE
In under-floor systems, the use of plastic pipes without protection against penetration of oxygen through the walls can cause corrosion of the systems metal parts (metal piping, boiler, etc), through the formation of oxides and bacterial agents.
To prevent this problem, it is necessary to use pipes with an “oxygen-proof barrier”, in accordance with standards DIN 4726/4729. If pipes of this kind are not used, keep the
system separate by installing heat exchanger
s of those
with a specific system water treatment.
IMPORTANT Failure to carry out the water treatment procedure
will invalidate the appliance warranty.
Page 29
29
3.2. REMOVING THE CASING
To remove the front casing panel, follow these steps:
1. Remove the screws “A” (F
IG 3.1);
2. Remove the four screws from the case hooks (two at the top and two at the bottom) and rotate (F
IG 3.2);
3. Lift and unhook the case panel (F
IG 3.3).
FIG. 3.2
F
IG. 3.3
F
IG. 3.1
A
A
Page 30
30
3.3. CONTROL PANEL
FIG. 3.4
A
D
E
F
G
H
I
C
B
** IMPORTANT!! The Flue Test function will cause the boiler to run continuously on maximum power. This function must only be activated by an authorised engineer.
Button Description
ON/OFF Button
“COMFORT” Function Push-button
Reset Button/ Flue Test**/ scroll through Functions Menu
Menu Button
Programming “+” key
Programming “-” key
Description
A
Green LED (illuminated = burner on)
B
Time clock
C
Selector knob for Summer/Winter Central Heating Temperature Adjustment Knob
D
Control Panel Cover
E
Domestic Hot Water Temperature Adjustment Knob
F
Heating System Pressure Gauge
G
“COMFORT” Function L.E.D
H
Red LED (illuminated = boiler lockout)
I
Multi-function Display
35 MFFI (Combi)
Page 31
31
3.4. INITIAL START-UP
1. Make sure that:
- the cap of the automatic air release valve is loosened;
- the system pressure is at least 1 bar on the pressure gauge “F” (Fig. 3.4);
- the gas cock is closed (Fig. 3.7);
- the electrical connection has been carried out in the correct manner.
To allow the air to escape from the system,
proceed as follows:
- push the On/off button and turn the knob “C” (Fig. 3.5) to the “winter” position. The boiler pump will start up and three consecutive attempts will be made to ignite the burner. After the third attempt, the electronic system will shutdown the boiler, because the supply of gas has been cut off.
The message “A01” will appear on the display and the red LED “H” will illuminate;
- let the pump operate until all the air has escaped from the system;
- repeat the procedure for bleeding the radiators of air;
- draw hot water for a short while;
- check the system pressure and, if it has gone down, fill it with water until it returns to 1 bar.
2. Fill the boiler condensate trap with water (Fig. 3.6). N.B. In the event of a prolonged period of system shutdown, the condensate trap should be filled before any renewed use. A shortage of water in the trap could temporarily lead to a small leakage of fumes into the air.
3, Ensure that the flue is fitted correctly.
4. Turn on the gas cock (Fig. 3.8) and check
the seals on the connections, including the one for the burner, making sure that the meter does not signal the passage of gas. Check the connections with a soap solution and eliminate any leaks.
5. Press the reset button , the boiler will attempt to light. If the burner does not light the first time, repeat the procedure. Note: Should the boiler fail to ignite check that no air is present in the gas pipe.
The boiler is configured in the factory for the gas type in question. To check the CO
2 setting, please refer to Section
3.6.3 (page 41).
6. Run the appliance in the DHW mode and check the correct
operation of the thermostat control.
7. Complete the commissioning checklist (page 70).
FIG. 3.5
C
H
FIG. 3.7
Fig. 3.8
FIG. 3.6
Page 32
32
3.5. DISPLAY: MESSAGES SHOWN DURING NORMAL OPERATION
During operation of the boiler, while it is carrying out its normal operations, the left-hand display shows a series of characters that refer to the operations indicated below:
0 No request for heat C Heating c Pump overrun for heating d Domestic hot water h Pump overrun for domestic hot water F Frost Protection
The right-hand display (two-digit) shows:
- in CENTRAL HEATING mode: temperature of the Central Heating system flow;
- in DOMESTIC HOT WATER mode: temperature of the Domestic Hot Water.
FIG. 3.9
LEFT RIGHT
Page 33
33
3.6. OPERATING PARAMETERS
The boiler has been designed to allow easy use of the operating parameters.
3.6.1 REGULATION MENU TABLE
Summary of the functions accessed when the RESET button
and the menu button are pushed at the same time for 5 seconds. On the display will appear the parameters indicated in table 3A. To switch between the different parameters press the button. To modify the parameters push the programming keys and .
Fig. 3.10
Parameter Function Range Factory setting
1
Soft light as % of maximum Heating Power (NG)
from 00 to 99
(step: 1%)
58
2
Maximum Heating Power (%)
from 00 to 99
(step: 1%)
60
3
Ignition delay (minutes)
from 00 to 07
(step: 1 minute)
02
4
Central heating minimum temperature
25°C if parameter r = 00 42°C if parameter r = 01
42
5
Central heating maximum temperature
75°C if parameter r = 00 82°C if parameter r = 01
82
6
PT rpm (Check of the temperature difference between the flow and return sensors for twelve seconds on initial start-up - D
O NOT ADJUST)
45
t/S
NOT USED
F
Boiler types
from O0 to 02
00
e
Secondary outlet function
from 00 to 03
00
p
Pump overrun (Central Heating ­mins)
from 01 to 15 or CO
02
c
Comfort function
from 00 to 01
00
p
Pump speed adjustment (modulating or single speed)
U0 (single speed)
U1 (modulating)
U1
TABLE. 3A
Page 34
34
Important!! The parameters P5 and P6 are only enabled when the outdoor sensor is activated (Parameter P - page 37-
38).
To return to the normal display, press the menu button .
Parameter Function Range Factory setting
r
selects low temperature systems or standard systems
00 (Low temperature) 01 (Standard System)
01
p9
Temperature regulation controlled by external sensor
90 (Disabled)
91 (Enabled)
90
p6
Correction of heat curve translation
from -20 to +20
P5
Curve incline
from 0_1 to 5_0
0_9
t
Test Function
A
Bus Address (Do not modify)
b 0
Set-point second heating zone
from 25 to 82
75
b 1
GSM value (Do not modify)
b 2
Heating delay after commutation in DHW (from 0 to 30 minutes)
from 00 to 30
(step: 1 minute)
00
b 3
Post-ventilation in Heating mode
0 (Disabled)
1 (Enabled)
1
b 4
NOT USED
b 5
NOT USED
b 7
NOT USED
b 8
NOT USED
Page 35
35
FIG. 3.11
Soft Light adjustment 1
The soft light can be adjusted between the maximum power (shown on the display as “99”) and the minimum power (shown on the display as “00”). The boiler is factory set to a value which is suitable for the ignition with any type of gas. The value set expressed as a percentage, can be displayed and adjusted as indicated in
Section 3.6.1 (parameter 1)
FIG. 3.12
Maximum Heating Power adjustment 2
The maximum heating power can be adjusted between the maximum power allowed by the boiler (29.4kW) and the minimum recommended power (6.5 kW) indicated in the graph below. The value is factory set to 70% of the maximum power. The value set (expressed as a percentage) can be displayed and modified as illustrated in Section 3.6.1 (parameter 2). The display shows the value between 100% ("99" on the display) and 1% ("00").
Use the graph below as a guide to set the boiler heating power to suit the system load.
Display
Heat Output
Ignition Delay adjustment 3
The re-ignition delay for Central Heating can be adjusted to between 0 and 7 minutes. The delay is factory set to 2 minutes. The value set can be displayed and modified as illustrated in Section 3.6.1 (parameter 3)
FIG. 3.13
6.5
29.4
Page 36
Secondary outlet Function E (This parameter can be modified only with the interface PCB connected)
With the interface PCB connected, it is possible to set the boiler to operate with one of the following accessories, (see Section
2.12 for further information). The setting can be varied by pushing the and keys, the following options are available:
00 zone valve -
factory setting -
(NOT USED IN UK)
01 N
OT USED
02 NOT USED 03 NOT USED
36
PUMP OVERRUN P
The pump overrun time may be adjusted (after the burner has been turned off) by pressing the programming keys and . The following modes are available:
01 1 minute of pump overrun 02 2 minutes of pump overrun - factory setting 03 3 minutes of pump overrun 04 4 minutes of pump overrun
..... .............................
15 15 minutes of pump overrun
FIG. 3.17
FIG. 3.16
Boiler types F
Factory setting: 00 - ACO 35 MFFI (COMBI)
T
HIS PARAMETER MUST NEVER BE ADJUSTED.
Maximum Central Heating temperature 5
This parameter allows the setting of the maximum temperature for the central heating circuit. The value is factory set at 82°C and can be adjusted as illustrated in Section 3.6.1 (parameter 5).
Minimum Central Heating temperature 4
This parameter allows the setting of the minimum temperature for the central heating circuit. The value is factory set at 46°C and can be adjusted as illustrated in Section 3.6.1 (parameter 4).
FIG. 3.15
FIG. 3.14
Page 37
37
Pump Speed Adjustment P
By pressing the and keys it is possible to adust the operation of the pump, the two options are as follows:
U0- Single Speed Pump U1- Modulating Pump -
factory setting
FIG. 3.19
FIG. 3.18
Comfort Function (MFFI model - Combi only)
C
The boiler allows the convenience level to be increased in the output of domestic hot water by means of the “COMFORT” function. This function keeps the secondary exchanger warm during the periods in which the boiler is inactive, thereby allowing the initial water drawn to be at a higher temperature. The function may be activated by pressing the key on the control panel (see Section 3.3). When the function is active, a yellow light “G” comes on, again located on the control panel.
The comfort function can be activated or deactivated by pressing the and keys
00 Comfort function deactivated 01 Comfort function active for 30 minutes - factory setting.
It is possible to deactivate the comfort function by pressing the
button.
The yellow LED “G” will go out.
NOTE: During the overrun period of the pump, the “COMFORT” function, if selected, is temporarily deactivated. The L.E.D. light remains on to indicate that the boiler will return to the “COMFORT” mode once the pump overrun has finished.
G
TEMPERATURE REGULATION CONTROLLED BY THE
EXTERNAL SENSOR
P
By pressing the and it is possible to make the following
adjustments:
90” Temperature regulation controlled by the external sensor is
inactive (not installed).
91” Temperature regulation controlled by the external sensor is
active (installed).
SETTING THE TEMPERATURE FIELD r
Using the programming keys and it is possible to make the
following adjustments:
00” signifies that the flow temperature (which may be set by
means of the knob on the front control panel) may be regulated from 25 to 75°C.
01” signifies that the flow temperature (which also may be set by
means of the knob on the front control panel) may be
FIG. 3.20
FIG. 3.21
Page 38
38
SETTING THE CURVE INCLINE P 5
(Only enabled when an outdoor sensor is installed)
When using an outdoor sensor, the microprocessor-controlled P.C.B. calculates the most suitable flow temperature, taking into account the external temperature and the type of system. The microprocessor is capable of doing this because it is possible to establish a link between the external temperature and the flow temperature of the Central Heating system water. This link translates into a "thermal curve". The type of curve should be chosen in correspondence with the planned temperature of the system and the nature of the heat loss present in the building.
To select the type of curve access the Setting Menu by pressing the
and buttons for 5 seconds and proceed as follows;
1. Press the button four times to access Parameter 5;
2. P 5 will be shown on the left hand display;
3. Choose the curve required for the system from Fig. 3.26 and select by pressing the and buttons.
FIG. 3.25
FIG. 3.24
ADAPTING THE HEAT CURVE P 6
(Only enabled when the outdoor sensor is activated)
Should the external sensor be fitted it will be necessary to set the heating curve (see below) and may be necessary to adjust the parallel shift depending on the performance of the heating system used.
If the temperature in the house is too high, it will be necessary to decrease the parallel shift, whereas if the temperature is too low it will be necessary to increase the parallel shift as described below.
To set up the external sensor proceed as follows;
1. Access the settings menu by pressing the and buttons for five seconds;
2. Press the button 5 times to access Parameter 6
3. P 6 will now appear in the left hand display
4. Adjust the parallel shift by turning the heating control knob clockwise to increase or anti-clockwise to decrease as shown below. The shift value can be read on the right hand display, from
-20 to +20 (Fig. 3.23).
Flow temperature (°C)
External temperature (°C)
FIG. 3.23
FIG. 3.22
100
6
-20 +20
60
20
+20
to increase the curve in parallel
the curve in parallel
to decrease
-20 +20
-20
Page 39
39
Test Function t
The test function is used to enable the engineer/installer to check the combustion rate (see Section 3.6.3). The P.C.B. allows the boiler to be forced to the maximum or minimum power. Enable the test function, two dashes will appear on the right-hand display (see Fig. 3.27).
To select operation at maximum power, press the programming key
, two dashes will appear at the top of the right-hand display (see Fig. 3.29). This function is disabled when you press the reset key to quit the adjustments menu.
To select operation at minimum power, press the programming key
, two dashes will appear at the bottom of the right-hand display
(see Fig. 3.28). This function is disabled when you press the reset key “H” to quit the adjustments menu.
Note: The boiler can be forced to the maximum and minimum power
even without enabling the test function via the adjustments menu:
a - by pressing the Reset key for 5 seconds, the boiler is
automatically forced to test mode and t-- will be displayed, the boiler is now in the test mode for the maximum heating power, to force the boiler to maximum output for hot water it is necessary to press the and keys together, two dashes appear at the top of the right-hand display (see Fig. 3.29). This function is disabled by pressing the reset key .
b - by pressing the key, the boiler is forced to operate at
minimum power, two dashes appear at the bottom of the right­hand display (Fig. 3.28). This function is disabled by pressing the reset key.
max power Central Heating
minimum power
FIG. 3.27
FIG. 3.28
With parameter P5 it is necessary to adjust the heat curve to one of those shown in Fig. 3.26. By using the programming keys
and , the curve may be changed to select the required curve
for the system.
WARNING If a curve is selected for an under-floor heating a system safety thermostat must be connected to the main terminal board (see paragraph 2.12)
Fig. 3.26
max power DHW
FIG. 3.29
Flow temperature (°C)
External temperature (°C)
Page 40
40
The boiler is designed to monitor some operating variables and settings by means of the display on the front control panel. Keeping, at the same time, the reset and the menu key pressed for over 10 seconds will allow access to the “readout” function of the main system variables. By pressing the reset button repeatedly after that, it is possible to read the following information in sequence:
Indication on the left-hand display
U/1 U/2 U/3 U/4 U/6
E
A
Value read on right-hand display
Flow temperature of the Central Heating circuit (°C)
Return temperature of the Central Heating circuit (°C)
Domestic Hot Water output temperature (°C)
Outdoor temperature (°C)*
Fan speed (% rpm)
Last safety shut-off (see section 3.10.)
Last shutdown (see section 3.10.)
3.6.2 SETTINGS DISPLAY
To return to the normal display, press the menu key. The boiler will automatically return to the normal display after no buttons have been pressed for 2 minutes.
N
OTE 1: U/1 means that “U ” and “1” blink alternately on the display
N
OTE 2: the value 100% appears as “99” on the display
* = Only displayed when an external sensor is fitted.
Page 41
41
SUPPLY PRESSURE (WORKING)
G20 methane 20 mbar
LPG 37 mbar
3.6.3 GAS REGULATION CHECK
Supply pressure check
1. Loosen screw “1” (Fig. 3.31) and connect the pressure gauge
connection pipe into the test point.
2. Turn the boiler on at maximum power, enabling the “test”
function (press the key for 5 seconds and then press the programming keys and together ensuring the dashes are at the top of the display (see Fig. 3.29). The supply pressure should correspond to that shown for the type of gas the boiler is designed for (see table below).
3. Disable the test mode by pressing the reset key.
4. When the check is over, tighten screw “1” and test for tightness.
N
OTE:IF THE WORKING PRESSURE IS INSUFFICIENT CHECK THE GAS
METER
, METER GOVERNOR, OR INSTALLATION PIPEWORK FOR
ERROR.
I
MPORTANT
!
D
O NOT PROCEED CHECKING AND ADJUSTING THE
CO
2
SETTINGS
UNLESS THE WORKING PRESSURE IS ADEQUATE
.
N
OTE
: A
LL SETTINGS ARE TO BE MADE WITH A
CO
2
METER WITH THE
PROBE FITTED TO THE FLUE GAS ANALYSIS POINT(FIG
. 3.30).
Setting the CO2 at minimum power
To check the air/gas ratio at minimum power, proceed as follows:
1. Connect the combustion analyser to the analysis point (Fig.
3.30) after removing the screw and cover.
2. Set the boiler to minimum power via the test function (see
paragraph 3.6.1) or by pressing the button for 5 seconds and then pressing the button on the control panel, ensure the dashes are at the bottom of the display (see Fig. 3.28). Ensure the CO
2 value on the analyser corresponds with the
value indicated in table 4D. If this is not the case, adjust screw “2” (Fig.3.31) with a screwdriver in small intervals, allowing the reading to become stable before adjusting further, until you obtain the correct CO2 reading. Allow the reading to become stable for at least 4 minutes.
3. When the check is over, replace the cap on screw “2” (Fig. 3.31).
4. Disable operation at minimum power by pressing the key
or press the key to check the maximum value (dashes at top of display see Fig. 3.29).
While the appliance is operating at maximum power, check the gas rate of the appliance at the gas meter
Setting the CO2 at maximum power
To check the air/gas ratio at maximum power, proceed as follows:
1. With the combustion analyser already connected to the analysis
point, set the boiler to maximum power via the test function (see paragraph 3.6.1) or by pressing the button for 5 seconds and then the programming keys and ensuring the dashes are at the top of the display (see Fig. 3.29). Ensure the CO
2 value on the analyser corresponds with the
value indicated in table 4D. If this is not the case, adjust screw “4” with a screwdriver in small intervals allowing the analyser reading to stabilise before adjusting further (Fig. 3.31), until you obtain the correct CO
2 reading. Allow the reading to become
stable for at least 4 minutes.
2. Disable the test mode by pressing the button.
The test mode is automatically disabled after 5 minutes.
3. Repeat the air/gas ratio at minimum power check (see
above).
4. Disconnect the analyser, remount the cover plate and check it is
securely in place.
While the appliance is operating at minimum power, check the gas rate of the appliance at the gas meter
N
OTE:WHEN MAKING ADJUSTMENTS, ADJUST SMALL AMOUNTS AND
WAIT FOR THE ANALYSER TO STABILISE BEFORE MAKING
FURTHER ADJUSTMENTS
.
CO2 SETTING MAXIMUM VALUE
Calibration values check CO
2 at maximum power G20 % vol 9.4 ±0.2
after 4 minutes of operation
LPG % vol 10.1 ±0.2
CO2 SETTING MINIMUM VALUE
Calibration values check CO
2 at minimum power G20 % vol 8.7 ±0.2
after 4 minutes of operation
LPG % vol 8.6 ±0.2
SETTING THE GAS PRESSURES
FIG. 3.32
FIG. 3.31
TABLE 4D
FIG. 3.30
4
3
2
1
Page 42
42
The soft light can be adjusted between the maximum power (shown on the display as "99", i.e. 100%) and minimum power (shown on the display as "00", i.e. 1%). The boiler is factory set to a value which is suitable for ignition with any type of gas. The value set (expressed as a percentage) can be displayed and modified as illustrated in paragraph 3.6.1 (parameter 1).
The ignition delay can be adjusted to between 0 and 7 minutes. The delay is factory set to 2 minutes. The value set can be displayed and modified as illustrated in paragraph 3.6.1 (parameter 3).
3.6.4 IGNITION DELAY ADJUSTMENT
3.6.5 ADJUSTING THE MAXIMUM HEATING POWER
3.6.6 SOFT LIGHT ADJUSTMENT
The maximum heating power can be adjusted between the maximum power allowed by the boiler (29.4kW) and the minimum power (6.5 kW) indicated in the graph. The value is factory set to 70% of the maximum power. The value set (expressed as a percentage) can be displayed and modified as described in paragraph 3.6.1 (parameter 2) using the graph on Page 35.
3.7 CHANGING THE TYPE OF GAS
The boiler operation can be changed over from methane gas (G20) to Liquid Gas (G31) or vice versa, an operation that must be performed by a CORGI registered Gas Engineer.
To change the type of gas it is necessary to proceed as follows:
1. Before starting ensure both the gas and electrical supplies to the boiler are isolated and the boiler is cool.
2. Remove the casing as indicated in Section 3.2.
3. Remove the silencer
4. Disconnect the electrical connection of gas valve and fan.
5. Remove the three torx screws of the air gas connections (see Fig. 3.32) and loosen the nut under the gas valve (see Fig. 3.33)
5. Remove all the mixer/fan/gas valve group (see Fig. 3.34)
6. Unscrew the four torx screws and disconnect the gas valve (see Fig. 3.35).
7. Insert the diaphram into the gas valve (see Fig. 3.36)
8. Reassemble in reverse order.
9. Replace the gas label.
FIG. 3.32
FIG. 3.33
FIG. 3.34
Page 43
43
3.8 ADJUSTING THE HOT WATER FLOW RATE
To adjust the hot water flow rate, it is necessary to first open the hot water tap with the highest flow rate (normally the bath tap), adjust the cold water inlet valve until the correct temperature rise is achieved at the stated flow rate ( ACO 35 MFFI - ∆T@35°C = 13.5 l/min).
Alternatively, you can advise the customer to restrict the water flow through each individual tap, by opening the tap and slowly closing it until the water reaches the desired temperature.
3.9 BALANCING THE CENTRAL HEATING SYSTEM
To balance the central heating system it is first necessary to close all radiator valves on the system, turn on the central heating, allow the boiler to reach operating temperature and then starting at the radiator furthest from the boiler, open the radiator valves until the radiator becomes hot and move to the next radiator on the circuit, working your way back to the radiator closest to the boiler.
10. Carry out check 3.6.3, verifying the inlet pressure is correct and the CO2 values are as stated in Table 4D (page 41).
11. Check the gas connection for tightness.
12. Check that the ignition operates correctly and visually check the
burner flame.
13. Check that the domestic hot water is being correctly produced by drawing hot water.
14. Check the flow rate and/or temperature of the water, depending on the case.
15. Check that the condensate drips without difficulty into the discharge.
FIG. 3.35
FIG. 3.36
LPG (G31)
Consumption at Nominal Capacity(G31) kg/h 2.33 Gas Consumption after 10 Minutes* kg 0,27
* Calculated at 70% maximum output
Page 44
44
NOTE: When there is no ignition (A01), check that the gas cock is
open and gas is being supplied.
3.10 BOILER SAFETY SYSTEMS
The boiler is protected from malfunctioning by means of internal checks by the P.C.B., which brings the boiler to a stop if necessary. In the event of the boiler being shut off in this manner, a code appears on the display which refers to the type of shut-off and the reason behind it. There are two types of shut-off:
-
SAFETY SHUTDOWN:
for this group of errors (characterised
on the display by the letter “E”) the situation is automatically removed as soon as the cause behind it is resolved. As soon as the origin of the shutdown disappears, the boiler starts up again and returns to its normal operation.
-
SHUTDOWN:
(characterised on the display by the letter “A ”), is
not removed unless a manual intervention is made. The boiler may return to operation only if reset, press the
button. There follows a list of the shutdown modes and the respective codes shown on the display.
Shutdown (“A ” type): if such a situation occurs, it is necessary to reset the boiler using the appropriate key. If this shutdown occurs frequently, your local Service Agent should be contacted.
Safety shutdown: In the event that a safety shutdown occurs, it is necessary to contact an Authorised Service Centre.
DISPLAY CAUSE
A 01
Too many attempts to ignite on start up
A 03
The heating flow temperature exceeds 105°C during operation
A 07
Too many failures to ignite in one period during operation
A 33
Problem with the fan
A 97
Problem with the electronic monitoring
A 98
Problem with the electronic monitoring
A 99
Problem with the electronic monitoring
DISPLAY CAUSE
E 02
No water or no water circulation in central heating system (for 40 sec.)
E 06
Heating flow temperature probe in open circuit
E 07
Heating flow temperature probe in short-circuit
E 08
Heating return temperature probe in open circuit
E 09
Heating return temperature probe in short-circuit
E 10
Under floor heating temperature probe in open circuit
E 20
Flame detected with gas valve closed
E 94
Problem within the electronic system
E 99
Problem within the electronic system
DISPLAY CAUSE
S 01
Ignition failure on 1st attempt
S 02
Ignition failure on 2nd attempt
S 04
Domestic hot water temperature probe in open circuit
S 05
Domestic hot water temperature probe in short circuit
S 06
Problem with rectification probe
S 30
Outdoor sensor open circuit
S 31
Outdoor sensor in short circuit
S 80
Remote Control CLIMA MANAGER room sensor in open circuit or short circuit
Page 45
45
The draining of the heating system must be carried out as follows:
- Turn off the boiler and isolate the electrical supply;
- Loosen the automatic air release valve;
- Open the system's discharge valve
- Empty out from the lowest points of the system (where provided).
If the system is to be left active in areas where the room temperature may go below 0°C during winter, it is recommended that anti-freeze liquid be added to the water in the heating system in order to avoid the need for repeated draining.
Draining the domestic hot water system Every time that there is a danger of freezing, the domestic hot water system must be drained as follows:
- close the water mains stop-cock;
- open all the hot and cold water outlets;
- empty out from the lowest points (where provided).
3.12 DRAINING
3.11 COMPLETION
D
AILYTEST
. In order to prevent sticking components, the boiler carries out a self­diagnosing test every 21 hours: the pump runs for 15 seconds and the diverter valve moves once.
A
NTI-FROSTDEVICE
. The anti-frost function acts on the central heating flow temperature probe, independently from other regulations, when the electrical supply is turned on. If the primary circuit temperature falls below 8°C the pump will run for 2 minutes. After the two minutes of circulation (fixed) the boiler will check the following: a) if the central heating flow temperature is > 8°C, the pump stops; b) if the central heating flow temperature is between 3 and 8°C, the pump will run for another two minutes; c) if the central heating flow temperature is < 3°C, the burner will fire (heating position) at minimum power until the temperature reaches 33°C, the burner will go out and the pump will continue to run for two minutes. If the flow temperature remains between 3-8°C the pump will continue to run for two minutes for a maximum of 10 times unless a temperature above 8°C is detected in the central heating flow, after this the the burner will fire. If lockout is caused by overheat the burner is kept OFF.
N
OTE: In all cases, the circulation takes place in the central
heating system. The anti-frost device activates only when (with the boiler operating correctly):
- the system pressure is correct;
- the boiler is electrically powered;
- there is a supply of gas.
A
NTI-SCALEDEVICE
.
When producing domestic hot water, the burner shuts off whenever the output temperature of the hot water exceeds 61°C or the flow temperature of the primary circuit exceeds 78°C. It will not turn on if the temperature of the primary circuit is greater than 78°C.
For the Republic of Ireland it is necessary to complete a “Declaration of Conformity” to indicate compliance to I.S. 813. An example of this is given in the current edition of I.S. 813. In addition it is necessary to complete the commissioning checklist (Section 11, page 70).
Page 46
46
5. SEQUENCE OF OPERATION
Activation of the time clock and/or room thermostat starts the boiler. The letter C is shown in the display followed by the flow
temperature.
With the boiler in rest, the diverter valve is in the domestic hot water position, activation of the central heating changes the position of the motorised valve head, moving the diverter valve into the central heating position.
The start of the pump is delayed for 7 seconds to allow the movement of the diverter valve. The pump starts at speed 2, after the low water pressure switch verfies water is present. If the low water pressure switch does not verify water is present
after 40 seconds, error code E02, the boiler will resume operation
once the problem has been resolved.
Following the satisfaction of the low water pressure switch check the fan starts and an ignition attempt is then made for 3 seconds after the fan starts. The gas valve is energised and gas is delivered to the burner fixed in relation to the fan. The ignition gas pressure (soft light) is adjusted at Step 1 in the parameter adjustment mode (see Section 3.6.1). This value is factory set. (1= minimum fan speed and 00 = maximum fan speed). Soft light takes 4 seconds, the electronics check for flame ionisation three times consecutively.
Failure on ignition results in the error code A01.
The boiler will modulate the burner according to the central heating output. The burner can activate up to a maximum of the set point at +4
o
C. Reignition of the burner occurs once it has thermostatically turned off can be time delayed between 0 and 7 minutes, adjustable in Step 3 (Section 3.6.1), the factory setting is 2 minutes.
Overheat safety is provided by a Klixon thermostat, the temperature is set to 105 ±1
o
C, this thermostat remains active even when the burner is off. In the event that the Klixon thermostat reads a temperature value above 105 ±1oC the boiler will shut down and the
display will show A03, the fan will continue to run for 20 seconds.
After correct operation is proven the pump speed changes to speed 3 (if the system is cold), if the system is warm the pump remains at speed 2.
5.1 CENTRAL HEATING MODE
5.2 DOMESTIC HOT WATER MODE
When a hot water tap is turned on the domestic hot water flow switch is operated (if the diverter valve is in the central heating position it will motor into the domestic hot water position and the
boiler starts. The letter d is shown in the display followed by the temperature of the domestic hot water leaving the appliance.
The appliance will then follow the same operating logic as described in Central Heating Mode.
In domestic hot water mode NTC1 limits the maximum temperature to 78oC, reignition will occur at 74oC. The domestic hot water temperature is limited to 61
o
C, reignition will occur at 60oC.
Page 47
47
6. MAINTENANCE
6.1. GENERAL REMARKS
To ensure the validity of the 5 Year Guarantee, the boiler must be serviced annually by a CORGI registered gas engineer.
MTS (GB) Limited will write to the householder as the boiler becomes due for it’s annual service.
With the letter will also be sent a ‘Service Pack’, this will include the annual maintenance checklist to be completed and signed by the CORGI registered engineer, also included in this pack may be a component which must be replaced and the old one returned with all documentation included in the ‘Service Pack’ to MTS (GB) Ltd.
See Section 10 for annual maintenance requirements.
N
OTE:FAILURE TO COMPLY WITH THE ANNUAL SERVICE
REQUIREMENTS WILL RESULT IN THE
5 YEAR GUARANTEE
BECOMING VOID.
CLEANING THE EXHAUST SIDE Access the combustion chamber (see section 7.3). Check that the exhaust passages are clear; if there are deposits present, wash the exchanger with compressed air, water or a vinegar-based detergent. NOTE: it is possible to use a brush in order to mechanically remove the residues.
Use of detergents:
- soak the blades well
- allow the detergent to act for about 20 minutes
- rinse with a strong jet of water to remove the deposits (the
control panel must be kept closed)
- make sure that there are no traces of detergents in the
exchanger.
CLEANING THE WATER SIDE Use detergents that dissolve CaCO3. Leave to act for a short time and then rinse. Make sure that the detergent does not remain inside the exchanger.
To clean the condensate trap it is simply necessary to unscrew the lower part of the condensate trap and clean it. Lastly, fill it with water and replace the stopper.
6.2. CLEANING THE PRIMARY EXCHANGER
6.3. CLEANING THE CONDENSATE TRAP
6.4. OPERATIONAL TEST
After having carried out the maintenance operations, fill the heating circuit to a pressure of approx. 1.5 bar and release the air from the system. Also fill the domestic hot water system.
- Place the boiler in operation;
- If necessary, release the air again from the heating system.
- Check the settings and the correct functioning of all the
control, regulation and monitoring parts;
- Check the seal and the correct functioning of the system for
expelling fumes/drawing of combustion air;
- Check that the boiler ignites properly and carry out a visual
check on the burner flame;
- Check the CO2 values are correct (see Section 3.6.3)
IMPORTANT!!
If the boiler is not to be used for a prolonged period, the condensate trap should be filled before operating the boiler. A shortage of water in the trap will temporarily risk flue gasses escaping into the room.
Page 48
48
FIG. 7.1
7. SERVICING INSTRUCTIONS
The life of individual components vary and they will need servicing or replacing as and when faults develop. The fault finding sequence chart in Section 8 will help to locate which component is the cause of any malfunction, and instructions for removal, inspection and replacement of the individual parts are given in the following pages.
7.1. REPLACEMENT OF PARTS
7.2. TO GAIN GENERAL ACCESS
All testing and maintenance operations on the boiler require the control panel to be lowered. This will also require the removal of the casing.
To lower the control panel and remove the casing, proceed as follows:
1.
Remove the screws “A” (Fig. 7.1);
2.
Loosen the four screws ‘B’ from the case hooks (two at the top and two at the bottom) and rotate (Fig. 7.2);
3.
Lift and unhook the case panel (Fig. 7.3);
4.
Lower the control panel (Fig. 7.4)
To ensure efficient safe operation, the boiler must be serviced annually by a competent person.
Before starting any servicing work, ensure both the gas and electrical supplies to the boiler are isolated and the boiler is cool.
Before and after servicing, a combustion analysis should be made via the flue sampling point (please refer to Section 3.6.3).
After servicing, preliminary electrical system checks must be carried out to ensure electrical safety (i.e. polarity, earth continuity, resistance to earth and short circuit).
A
A
FIG. 7.3
FIG. 7.2
B
Page 49
49
7.3.1. REMOVING THE AIR/GAS ASSEMBLY
1.
Remove the three torx screws “C” (FIG. 7.5);
2.
Loosen the nut “D“ under the gas valve (FIG. 7.6);
3.
Disconnect electrical connections to gas valve and fan;
4.
Dismount the gas valve/mixer/fan group (FIG. 7.7);
5.
Reassamble in reverse order.
FIG. 7.5
FIG. 7.6
C
D
7.3. ACCESS TO THE COMBUSTION CHAMBER
FIG. 7.4
To gain better acess to certain components, it will be necessary to remove the silencer.
Page 50
50
FIG. 7.7
7.3.2. REMOVING THE BURNER
1.
Remove ther air/gas assembly see section 7.3.1;
2.
Slide the burner from its housing (FIG. 7.8);
3.
Reassemble in reverse order and check all seals are undamaged and the burner is positioned correctly.
FIG. 7.8
FIG. 7.9
FIG. 7.10
FIG. 7.11
7.3.3. REMOVING THE DETECTION ELECTRODE
1.
Remove the two torx screws “E” (FIG. 7.9);
2.
Extract the electrode (FIG. 7.10);
3.
Disconnect the detection electrode cable (FIG. 7.11).
E
Page 51
51
FIG. 7.12
FIG. 7.14
FIG. 7.13
7.3.4. REMOVING THE IGNITION ELECTRODE
1.
Remove the earth cable from the electrode (FIG. 7.12);
2.
Remove the electrode cable from the spark generator (F
IG. 7.13);
3.
Unscrew the two screws “F” (FIG. 7.14).
F
1.
Remove ther air/gas assembly see section 7.3.1;
2.
Disconnect the air/gas connection unscrew the three
screws “G“ (FIG. 7.15);
3.
Remove the mixer by unscrewing the two screws “H” (FIG.
7.16).
4.
Remove the fan (FIG. 7.17).
7.3.5. REMOVING THE FAN
FIG. 7.16
H
H
FIG. 7.15
G
FIG. 7.17
Page 52
52
FIG. 7.20
7.3.6. REMOVING THE HEAT EXCHANGER
1.
Drain the boiler;
2.
Remove the air/gas assembly see section 7.3.1;
3.
Remove the electrodes see section 7.3.3 - 7.3.4;
4.
Remove the condensate trap tube see section 7.3.7;
5.
Unplug the C.H. return and flow temperature probes and the overheat thermostat (F
IG. 7.18);
6.
Unplug the pipe clips (FIG. 7.18);
7.
Loosen the nut “I” and remove the pipe (FIG. 7.19 - 7.20);
8.
Loosen the nut “J” and remove the pipe (FIG. 7.21 - 7.22);
9.
Loosen the nuts “K” and remove the exchanger (FIG. 7.23 - 7.24).
FIG. 7.18
FIG. 7.22
FIG. 7.23
FIG. 7.21
FIG. 7.19
J
I
ATTENTION!!
When removing the heat exchanger, ensure that no water can enter the electrical box containing the PCB!
K
K
K
Page 53
53
7.3.7. REMOVING THE CONDENSATE TRAP (TUBE)
1.
Unplug the clip “L” (FIG. 7.25);
2.
Unscrew the screw “M” (FIG.7.26);
3.
Remove the condensate tube (FIG. 7.27).
FIG. 7.27
FIG. 7.24
FIG. 7.25
FIG. 7.26
L
M
Page 54
54
FIG. 7.28
FIG. 7.29
7.3.8. REMOVING THE CONDENSATE TRAP
1.
Remove the condensate trap tube - see section 7.3.7;
2.
Remove the condensate trap glass (FIG. 7.28);
3.
Remove the trap from the boiler (FIG. 7.29).
NOTE: Take care when removing the blanking cap to
place a container under the boiler as this will release the contents of the condensate trap.
7.4 ACCESS TO THE GAS VALVE
FIG. 7.30
FIG. 7.31
1.
Remove the casing and lower the control panel as instructed in Section 7.1.
2.
Press the release button “N” for the control panel (Fig.
7.30) and pull forward to remove from the boiler frame.
3.
Clip the control panel onto the frame of the boiler. (Fig.
7.31).
N
Page 55
55
7.4.1. REMOVING THE GAS VALVE
1.
Remove the air/gas assembly see section 7.3.1;
2.
Remove the screws “O” from the bottom of the gas valve (F
IG. 7.32);
3.
Remove the gas valve;
FIG. 7.32
O
7.4.2. REMOVING THE SPARK GENERATOR
1.
Disconnect the electrical connection from the spark generator (FIG. 7.33);
2.
Remove the screws “P” from the bottom of the spark generator (FIG. 7.34);
4.
Remove the spark generator.
FIG. 7.33
FIG. 7.34
P
P
4.
Reassemble in reverse order;
5.
The gas valve settings will need to be adjusted (see section 3.6.3);
6.
Reinstate the gas supply and test for tightness on reassembly.
Page 56
56
7.5 ACCESS TO THE WATER CIRCUIT
7.5.1. REMOVING THE D.H.W. (SECONDARY) EXCHANGER
1.
Remove the two allen screws “Q” (FIG. 7.35 and 7.36);
2.
Push the exchanger towards the rear of the boiler, lift upwards and remove from the front of the boiler (FIGS.
7.37, 7.38 and 7.39);
3.
Before replacing the exchanger ensure that the O-rings are in good condition and replace if necessary.
Important!
Before any component is removed, the boiler
must be drained of all water.
FIG. 7.35
FIG. 7.37
FIG. 7.38
FIG. 7.39
Q
Q
FIG. 7.36
Page 57
57
7.5.2. REMOVING THE SAFETY VALVE
1.
Loosen the nut “R” and remove the pipe (Fig. 7.40);
2.
Remove the valve (Fig. 7.41).
FIG. 7.40
FIG. 7.41
7.5.3. REMOVING THE AUTOMATIC AIR VENT
1.
Remove the U-clip “S” (FIG. 7.42);
2.
Remove the automatic air vent (FIG. 7.43).
FIG. 7.43
FIG. 7.42
S
R
Page 58
58
7.5.6. REMOVING THE PUMP
1.
Unplug the electrical connection (FIG. 7.48);
2.
Unscrew the four screws “U” (FIG. 7.48);
3.
Remove the pump (FIG. 7.49).
FIG. 7.48
FIG. 7.49
7.5.5. REMOVING THE D.H.W. FLOW SWITCH
1.
Unplug the electrical connector (FIG. 7.46);
2.
Remove the D.H.W. flow switch (FIG. 7.47).
FIG. 7.46
FIG. 7.47
FIG. 7.44
7.5.4. REMOVING THE DIVERTER VALVE ACTUATOR
1.
Unplug the electrical connector and retaining clip “T” (FIG. 7.44);
2.
Remove the diverter valve actuator (FIG. 7.45).
FIG. 7.45
T
T
T
T
T
Page 59
59
7.5.8. REMOVING THE PRESSURE GAUGE
1.
Release U-clip “W” (FIG. 7.53 - 7.54);
2.
Ease the pressure gauge through the control panel from the rear;
3.
Remove the pressure gauge.
FIG. 7.53
FIG. 7.54
W
7.5.7. REMOVING THE LOW WATER PRESSURE SWITCH
1.
Disconnect the electrical connection (FIG. 7.50);
2.
Loosen the nut “V” (FIG 7.51);
3.
Remove the low water pressure switch. (FIG 7.52).
FIG. 7.50
FIG. 7.51
FIG. 7.52
V
Page 60
60
7.5.10 REMOVING THE D.H.W. TEMPERATURE PROBE (N.T.C.)
1.
Remove the electrical connector by pulling off and loosening the nut “Z” (Fig. 7.58);
2.
Remove the D.H.W. temperature probe (FIG. 7.59).
FIG. 7.58
FIG. 7.59
7.5.9. REMOVING THE EXPANSION VESSEL
1.
Unscrew the screw “X” (FIG. 7.55);
2.
Loosen nut “Y” (FIG. 7.56);
3.
Remove the expansion vessel (FIG. 7.57).
X
FIG. 7.55
FIG. 7.56
FIG. 7.57
Y
Z
Page 61
61
FIG. 7.60
7.5.10. Removing the C.H. Flow Temperature Probe (N.T.C.)
1.
Unplug the C.H. Flow temperature probe (Fig. 7.60);
2.
Remove the electrical connection from the C.H. flow temperature probe (FIG. 7.61).
FIG. 7.62
FIG. 7.63
7.5.11. REMOVING THE C.H. RETURN TEMPERATURE
PROBE (N.T.C.)
1.
Unplug the C.H. Return temperature probe (Fig. 7.62);
2.
Remove the electrical connection from the C.H. return temperature probe (F
IG. 7.63).
FIG. 7.61
FIG. 7.64
7.5.10. Removing the Overheat Thermostat
1.
Unplug the overheat thermostat (Fig. 7.64);
2.
Remove the electrical connection from the overheat thermostat (FIG. 7.65).
FIG. 7.65
Page 62
62
7.6.1. CHECKING THE FUSES
1.
Remove the inspection cover of the PCB box (FIG. 7.66
- 7.67);
2.
Loosen the two screws “A1” and slide the PCB forward before removing the screws (FIG. 7.68).
7.6 ACCESS TO THE CONTROL SYSTEM
FIG. 7.66
FIG. 7.67
FIG. 7.68
A1
A1
7.6.2. REMOVING THE P.C.B.S
1.
Remove the inspection cover of the PCB box (FIG.
7.66- SECTION 7.6.7);
2.
Unplug all the electrical connections and loosen the screws “A1” (FIG. 7.68);
4.
Pull forward the main PCB (FIG. 7.69 & 7.70);
5.
Unscrew the screws “A2” (Fig. 7.71);
6.
Remove the cover of the control panel (FIG. 7.72);
7
. Unscrew the display P.C.B. mounting screws “A3” and
disconnect the P.C.B. connection cable “A4” (FIG. 7.73);
8.
Remove the display P.C.B. (FIG. 7.74);
9.
Replace either P.C.B. in reverse order.
FIG. 7.69
FIG. 7.70
FIG. 7.71
A2
A2
A2
Page 63
63
FIG. 7.72
FIG. 7.73
FIG. 7.74
7.6.3. REMOVING THE TIME CLOCK
1.
Open the control panel (see the paragraph “
Removing
the P.C.B.s”);
2.
Unplug the electrical connection from the time clock and unscrew the four screws (FIG. 7.75);
3.
Remove the time clock (FIG. 7.76).
FIG. 7.76
FIG. 7.75
A3
A3
A3
A3
A4
Page 64
64
It is possible to detect and correct defects by using the standard fault finding diagrams described in this chapter.
NOTE:THESE CHECKS ARE NOT EXHAUSTIVE
8.1. FAULT FINDING GUIDE (FLOW-CHARTS)
8. FAULT FINDING
Page 65
65
1. Check if there is air in the system
2. Check the pressure on the water gauge and fill system to 1 bar
Push the RESET button
IS THE
LOW WATER
PRESSURE SWITCH
WORKING CORRECTLY?
E 02:does not close
Page 66
66
Page 67
67
9. SHORT SPARE PART LIST
35 MFFI
615
111
147
101
110
107
401
190
206
616
571
917
589
917 904
564
597
520
548
537
531
502
911
917
917
0101 MAIN EXCHANGER 65103385
BURNER 65103333
0107 0110
ELECTRODE (IGNITION) 65103358 ELECTRODE (DETECTION) 65103359
0111
0147
GASKET D:129.4 61306030 SPARK GENERATOR 65103516
0190
FAN ASSY 61314434
0206 0401
GAS VALVE 65103413
0502 MOTOR (3-WAY VALVE) 997147 0520
TEMPERATURE PROBE (D.H.W.) 998458
0529 PRESSURE GAUGE 65102220
531
AUTO AIR VENT + O-RING 9
0
SAFETY VALVE (1/2 3 BAR) 573172
0537 0538
KIT FOR REAR PUMP ATTACHMENT 65103500
0548
TEMPERATURE PROBE + CLIP 65103502 FLOW DETECTION KIT WITH MAGNET 65100540
0564
0571
LOW WATER PRESSURE SWITCH 995903
0589 SECONDARY EXCHANGER 65103501 0597
THERMOSTAT (OVERHEAT) 996065
P.C.B.(ACO-MCU) 65103508
0615 0616 P.C. B. (DISPLAY) 65102235 0901
FILLING LOOP PIPE 990737
0904 TAP (M/M 3/8 ) 65102016
TAP (M/M 3/8 - C.H. FLOW) 990742
0911
0917
GASKET 3/8 573521
95367
901
529
538
Page 68
68
10. ANNUAL MAINTENANCE CHECKLIST
7.5.3. REMOVING THE AUTOMATIC AIR VENT
1.
Remove the U-clip “S”;
2.
Remove Auto Air Vent.
S
Annual Maintenance Check List
In order to maintain the 5 year manufacturers warranty, a similar sheet to this has been sent to the customer. It must be completed in full by a CORGI registered engineer and returned with a replaced component if requested. Note: These checks are not exhaustive, additional checks may be necessary
The flue has been checked to ensure it is:
Sited in accordance with the manufacturers instructions Installed correctly Is in good condition
The correct operation of the following components has been checked:
Air Pressure Switch Thermostat Controls Safety Valve Ionisation (Flame Detection)
The following has been carried out:
Pressure in expansion vessel checked and corrected where necessary (0.7 bar) Condensate system removed, cleaned and refilled Auto Air Vent replaced and returned (see instructions over leaf) DHW flow switch removed and cleaned (Combi Only) Electrodes removed and cleaned (with emery cloth) Burner and fan removed and cleaned (if necessary) Primary heat exchanger checked and cleaned if necessary All electronic parameters checked and set as required Time clock and room thermostat checked for correct operation Appliance settings made in accordance with manufacturers instructions End user advised on the correct operation of the appliance
Please check the following information:
Gas inlet pressure Gas rate CO
2 setting (min/max)
DHW flow rate
(∆T @ 35 C)
o
CH output Service Interval Record completed in Installation Instruction Manual
Gas working pressure CO
2 ratio
DHW flow rate set to
Page 69
69
11. BENCHMARK COMMISSIONING CHECKLIST
Page 70
70
12. SERVICE INTERVAL RECORD
Page 71
71
Page 72
420010001200- 02/2006
MTS are continuously improving their products and therefore reserve the right to change specifications without prior notice and
accepts no liability for any errors or omission in the information contained in this document.
Manufacturer: Merloni TermoSanitari SpA - Italy
Commercial subsidiary: MTS (GB) Limited, MTS Building, Hughenden Avenue, High Wycombe, Bucks HP13 5FT
Please read these terms and conditions which are in addition to any terms and conditions detailed in this book or any registration card supplied with your appliance.
A charge will be made to the owner of the appliance if:
The reason for any service visit is as a direct result of a failure to install the appliance in accordance with the manufacturer’s instructions.
Your installer does not complete the necessary commissioning process and procedure as detailed in the Installation and Operating Instructions.
Your appliance is not serviced on or before the 12 month anniversary of installation - this only applies to appliances with a 2 and 5 year guarantee.
Our service engineer calls as requested and the failure is a non-manufacturing defect.
Failure to pay an invoice for any such occurence will be assumed by MTS that you accept that your appliance has not been installed correctly and understand that any manufacturer’s guarantee has been withdrawn.
On the 12 month anniversary of the appliance installation, you must have it serviced to continue any guarantee offered into the following year. Failure to do so will invalidate your guarantee and should an MTS engineer be required to attend and no proof of service documentation is made available, then MTS will charge.
As part of the commissioning process, it is a legal requirement to register all boiler installations or replacements with CORGI. Upon registration a “Certification Number” will be issued followed by a “Declaration of Safety” Certificate. MTS (GB) Ltd cannot be called upon to carry out any work under the manufacturer’s guarantee without proof of registration. The registration number must be quoted when requesting a service visit, and the “Declaration of Safety” Certficate subsequently shown to the service engineer. If the certificate is not made available, the engineer will not work on the appliance and a wasted call charge will be made.
TERMS AND CONDITIONS OF GUARANTEE
If you have a problem with commissioning on installation, please contact our
Technical Department on 0870 241 8180
Benchmark completed and customer advised
Customer advised on how to use and repressurise boiler
CORGI contacted for certification
Phone
Internet
Certification Number
CORGI will send Safety Certificate within 10 days to your customer
Date boiler installed
Serial Number
CORGI registration number (installer)
Installer details Name:
Address:
Phone:
For Customer Service please phone 0870 600 9888
Loading...