Ariston Aco 27 MFFI User guide

SERIES
Installation and Servicing Instructions Type C Boilers
G.C.N: 47-116-34 G.C.N: 47-116-35 G.C.N: 47-116-09 G.C.N: 47-116-10
LEAVE THESE INSTRUCTIONS WITH THE END-USER
Country of destination: GB/IE
TABLE OF CONTENTS
1. GENERAL INFORMATION
1.1. GENERAL INFORMATION
1.2. TECHNICAL INFORMATION
1.3. OVERALL VIEW
2. INSTALLATION
2.1. REFERENCE STANDARDS
2.2. SITING
2.3. OVERALL DIMENSIONS
2.4. MINIMUM CLEARANCES
2.5. MOUNTING
2.6. ELECTRICAL CONNECTION
2.7. GAS CONNECTION
2.8. WA
2.9.
LUE CONNECTIONS
F
2.10. ACCESSORY CONNECTION
2.11.
LECTRICAL
E
2.12. WATER CIRCUIT DIAGRAM
COMMISSIONING
3.
3.1. INITIAL PREPARATION
3.2. REMOVING THE CASING
3.3. CONTROL PANEL
3.4. INITIAL STA RT-UP
3.5. DISPLAY:MESSA NORMAL OPERA
3.6. OPERATING PARAMETERS
3.6.1. REGULATION MENU TABLE
3.6.2. SETTINGS DISPLA
3.6.3. GAS REGULATION CHECK
3.6.4. IGNITION DELAY ADJUSTMENT
3.6.5. ADJUSTING THE MAXIMUM HEATING POWER
3.6.6. SOFT LIGHT ADJUSTMENT
3.7. CHANGING THE TYPE OF GAS
3.8. BOILER SAFETY SYSTEMS
3.9. COMBUSTION ANALYSIS
3.10. COMPLETION
3.11. DRAINING
THE
CONNECTIONS
TER
APPLIANCE
THE
DIAGRAM
APPLIANCE
SHOWNDURING
GES
TION
Y
6. SERVICING INSTRUCTIONS
6.1. REPLA
CEMENT OF
6.2. TO GAIN GENERAL ACCESS
6.3. ACCESS TO THE COMBUSTION CHAMBER
6.3.1. REMOVING THE FAN
6.3.2.
6.3.3.
6.3.4.
6.3.5. REMO
6.3.6. REMO
6.3.7. R
6.4. ACCESS
6.4.1. REMO
6.4.2. REMO
6.5. ACCESS
6.5.1.
EMOVING THE AIR PRESSURE SWITCH
R
EMOVING THE BURNER
R
EMOVING THE ELECTRODES
R
VING THE
VING THE
EMO
VING THE
TO THE
VING THE
VING THESPARK
TO THEWATER
R
VING THE
EMO
(S
ECOND
ARY
6.5.2. REMOVING THE SAFETY VALVE
6.5.3. REMOVING THE AUTOMATIC AIR VENT
6.5.4. REMOVING THE DIVERTER VALVE ACTUATOR
6.5.5. REMOVING THE DHW FLOW SWITCH (MFFI ONLY) R
6.5.6.
EMO
VING
6.5.7. REMOVING THE PRESSURE GAUGE
6.5.8. REMO
6.5.9. REMO
6.5.10. R
VING THE
VING THE
PR
(N.T.C. - MFFI ONLY)
OBE
EMOVING THE C.H. FLOW TEMPERATURE
PROBE (N.T.C.)
6.5.11. R
EMO
VING THE
PROBE (N.T.C.)
6.6. A
CCESS TO THE CONTROL SYSTEM
6.6.1. CHECKING THE FUSES
6.6.2. REMOVING THE PRINTED CIRCUIT BOARDS
6.6.3. REMOVING THE TIME CLOCK
PAR
TS
HEATEXCHANGER CONDENSATETRAP (TUBE) CONDENSATETRAP
GAS VAL
GAS VAL
GENERA
.H.W.
D
) EXCHANGER
THE PUMP
EXP
ANSION
D.H.W. TEMPERA
C.H. RETURN TEMPERA
7. FAULT FINDING
7.1 FAULT FINDING GUIDE (FLOW-CHARTS)
VE
VE
TOR
CIRCUIT
VESSEL
TURE
TURE
4. ZONE VALVES
5. MAINTENANCE
5.1.
5.2. CLEANING THE PRIMARY EXCHANGER
5.3. CLEANING THE CONDENSATE TRAP
5.4.
G
ENERAL REMARKS
O
TIONAL
PERA
TEST
8. SHORT SPARES PARTS LIST
8.1. ACO 27 MFFI
2
1. GENERAL INFORMATION
1.1. GENERAL INFORMATION
This man should be kept with the appliance so that it can be consulted by the user and our author
Please carefully read the instructions and notices about the unit contained in this manual, as they provide important information regarding the safe installation, use and maintenance of the product.
For operating instructions please consult the separate Users Manual.
ual is an integral and essential part of the product. It
ised personnel.
Read the instructions and recommendations in these Installation and Ser use and maintenance of the appliance.
Keep this manual in a safe place. You may need it for your own reference while Servicing Technicians or your installer may need to consult it in the future.
This is a combined appliance for the production of central heating (C.H.) and domestic hot water (D.H.W.).
This appliance designed. The manufacturer declines all liability for damage caused by improper or negligent use.
No asbestos or other hazardous mater the fabrication of this product.
Before connecting the appliance, check that the information shown on the data plate and the table in section 7 comply with the electric, water and gas mains of the property.You will find the data plate on the reverse of the control panel. The gas with which this appliance operates is also shown on the label at the bottom of the boiler.
Do not install this appliance in a damp environment or close to equipment which spray water or other liquids.
Do not place objects on the appliance. Do not allow children or inexperienced persons to use the
appliance without supervision. If you smell gas in the room,
switches, use the telephone or any other object which might cause sparks. Open doors and windows immediately to ventilate the room. Shut the gas mains tap (at or adjacent to the gas meter) or the valve of the gas cylinder and call your Gas Supplier immediately. If you are going away for a long period of time, remember to shut the mains gas tap or the gas cylinder valve.
Always disconnect the appliance either by unplugging it from the mains or turning off the mains switch before cleaning the appliance or carrying out maintenance.
In the case of faults or failure, s turn off the gas tap. Do not tamper with the appliance. F request the use of or contact MTS (GB) Limited.
vicing Instructions carefully to ensure proper installation,
must be used only for the purpose for which it is
ials have been used in
do not turn on or off light
witch off the appliance and
or repairs
, call y
our local A
iginal spare par
uthorised Servicing Agent and
ts. For in-guarantee repairs
3
1.2. TECHNICAL INFORMATION
Name CE Cer
tification
Flue Type
General Info
Heat Input max/min (Central Heating) kW Heat Input max (Domestic Hot Water) kW Heat Output max/min kW Efficiency of Nominal Heat Input (60/80 Efficiency of Nominal Heat Input (30/50°C) % Efficiency at 30% of Nominal Heat Input (47°C) % Efficiency at 30% of Nominal Heat Input (30°C) % Efficiency at Minum Input % Efficiency (Dir. 92/42/EEC)** SEDBUK Rating Band
Energy Performance
Heat Loss to the Casing (∆T=50°C) % Flue Heat Loss with Burner Operating % Flue Heat Loss with Burner Off %
Max Discharge of Products of Combustion (G20) Kg/h Residual Discharge Head mbar Temp. of exhaust fumes at nominal capacity °C
2 Content %
CO O2 Content %
Emissions
CO Content ppm Nox Class
°C) %
CO 27 MFFI
A
0085BP0229
C13-C33-C43-C53-C83-B23-B33
25,5 / 8,9
27,0
22,5 / 7,7
88,2 88,2 92,9 92,9 86,7
A 0,5 2,6 0,4
35,3 0,61
72 9,1 4,3
109
5
CO 27 RFFI SYSTEM
A
0085BP0229
C13-C33-C43-C53-C83-B23-B33
25,5 / 8,9
-----
22,5 / 7,7
88,2 88,2 92,9 92,9 86,7
A 0,5 2,6 0,4
35,3 0,61
72 9,1 4,3
109
5
Head Loss on Water Side (max) (T=20°C) mbar Residual Head of System bar Expansion Vessel Pre-load Pressure bar Maximum Heating Pressure bar Expansion Vessel Capacity l Maximum Water Content of System l Heating Temperature max/min (High temperature) °C
Central Heating
Heating Temperature max/min (Low Temperature) °C
Domestic Hot
ater W
Specific Flow Rate (10 minutes/DT 30°C) l/min
.H.W. Flow Rate T=25°C l/min
D
.
.H.W
D
Water Temperature (approx) max/min °C
w Rate ∆T=35°C l/min
Flo D.H.W. Minimum Flow Rate l/min Pressure of Domestic Hot Water max/min bar
Domestic Hot
Condensate produced l/h
Max. PH of condensate W
Nominal Pressure Natural Gas (G20) mbar Consumption at Nominal Capacity(G20) m3/h
Gas
Gas Consumption after 10 Minutes* m
Electrical Supply V/Hz
er Consumption W
w
o
P
ature
emper
Minim
um Ambient
T
Protection Grade of Electrical System IP
nal Fuse Rating
Inter
Elettrical Data
200
0,2 0,7
3 7
130 82 / 42 75 / 20
200
0,2 0,7
3 7
130 82 / 42 75 / 20
56 / 36
12,6 15,2 10,8
2,5
6 / 0,2
1,5
4
20
2,43
3
0,85
230/50
118
C
°
+5
24D
1,5
4
20 2,43 0,85
230/50
118
+5 24D
eight
W Dimensions (W/D/H)
G.C. Number
* Calculated at 70% maximum output ** Calculated on Upper calorific value
4
Kg mm
40
280/450/750
47-116-34
40
280/450/750
47-116-09
Name CE Cer
tification
Flue Type
General Info
Heat Input max/min (Central Heating) kW Heat Input max (Domestic Hot Heat Output max/min kW Efficiency of Nominal Heat Input (60/80°C) % Efficiency of Nominal Heat Input (30/50°C) % Efficiency at 30% of Nominal Heat Input (47°C) % Efficiency at 30% of Nominal Heat Input (30°C) % Efficiency at Minum Input % Efficiency (Dir. 92/42/EEC)** SEDBUK Rating Band
Energy Performance
Heat Loss to the Casing (∆T=50°C) % Flue Heat Loss with Burner Operating % Flue Heat Loss with Burner Off %
Water) kW
ACO 32 MFFI
0085BP0229
C13-C33-C43-C53-C83-B23-B33
31,6 /10,5
32,0
28 / 9,5
97,3 88,5 91,2 97,1 89,7
A 0,5 2,7 0,4
ACO 32 RFFI SYSTEM
0085BP0229
C13-C33-C43-C53-C83-B23-B33
31,6 /10,5
----------­28 / 9,5
97,3 88,5 91,2 97,1 89,7
A 0,5 2,7 0,4
Max Discharge of Products of Combustion (G20) Kg/h Residual Discharge Head mbar Temp. of exhaust fumes at nominal capacity °C CO2 Content % O
2 Content
Emissions
CO Content ppm Nox Class
Head Loss on Water Side (max) (T=20°C) mbar Residual Head of System bar Expansion Vessel Pre-load Pressure bar Maximum Heating Pressure bar Expansion Vessel Capacity l Maximum Water Content of System l Heating Temperature max/min (High temperature) °C
Central Heating
Heating Temperature max/min (Low Temperature) °C
Domestic Hot Water Temperature (approx) max/min °C Specific Flow Rate (10 minutes/DT 30°C) l/min
w Rate ∆T=25°C l/min
Flo
.
.H.W
D D.H.W. Flow Rate T=35°C l/min D.H.W. Minimum Flow Rate l/min
ater max/min
Pressure of Domestic Hot
Domestic Hot Water
W
Max. Condensate produced l/h PH of condensate W
%
bar
45,7
1
76,4
8,7
5
71
5
200
0,2 0,7
3 7
130 82 / 42 75 / 20
56 / 36
15,3 18,3 13,1
2,5
6 / 0,2
1,8
4
45,7
1
76,4
8,7
5
71
5
200
0,2 0,7
3 7
130 82 / 42 75 / 20
1,8
4
Nominal Pressure Natural Gas (G20) mbar Consumption at Nominal Capacity(G20) m3/h
Gas
Gas Consumption after 10 Minutes* m
Electrical Supply V/Hz Power Consumption W Minimum Ambient Temperature °C Protection Grade of Electrical System IP Internal Fuse Rating
Elettrical Data
eight
W Dimensions (W/D/H) mm
Number
G.C.
* Calculated at 70% maxim ** Calculated on Upper calorific value
um output
Kg
20
3,01
3
0,35
230/50
118
+5
24D
42
280/450/750
47-116-35
20 3,01 0,35
230/50
118
+5 24D
40
280/450/750
47-116-10
5
1.2. OVERALL VIEW
9
8
1
3
5
7
12 13 14 15 16
19
21
24
25
6
4
26
20
17
18
23
2
22
9
9
8
8
1
1
3
3
5
5
7
7
10
12 14 15 16
19
24
25
6
6
4
4
26
20
17
18
23
2
2
22
27/32 MFFI
27/32 RFFI SYSTEM
FIG. 1.0
LEGEND:
1. Flue connector
2. Mixer an
F
3.
4. Spark generator
5. Burner
Ignition and detection electrode
6.
7. Air release valve
Main heat e
8.
9. Central Heating flow temperature probe
10. Automatic by-pass
11. Domestic Hot Water temperature probe
ety v
Saf
12.
13. Secondary heat exchanger
14. Gas valve
Condensate discharge
15.
16. Condensate trap inspection cap
ain valve
Dr
17.
18. Domestic Hot Water flow switch
19. Circulation pump with automatic air release valve
20. Condensate trap
er
Div
21.
22. Condensate trap (tube)
23. Central Heating return temperature probe
24. Expansion vessel
25. Air pressure switch
Combustion analysis test point
26.
xchanger (aluminium)
e (3 bar)
alv
alve
ter v
6
2. INSTALLATION
2.1. REFERENCE ST
The technical information and instructions provided herein below are intended for the installer / Servicing Technician so that the unit may be installed and serviced correctly and safely.
In the United Kingdom the installation and initial start up of the boiler must be by a CORGI Registered Installer in accordance with the installation standards currently in effect, as well as with any and all local health and safety standards i.e. CORGI.
In the Republic of Ireland the installation and initial start up of the appliance must be carried out by a Competent Person in accordance with the current edition of I.S.813 “Domestic Gas Installations”, the current Building Regulations, reference should also be made to the current ETCI rules for electrical installation.
This appliance must be installed by a competent installer in accordance with current Gas Safety (installation & use) Regulations.
The installation of this appliance must be in accordance with the relevant requirements of the Local Building Regulations, the current I.E.E. Wiring Regulations, the bylaws of the local water authority, in Scotland, in accordance with the Building Standards (Scotland) Regulation and Health and Safety document No. 635 “Electricity at work regulations 1989” and in the Republic of Ireland with the current edition of I.S. 813, the Local Building Regulations (IE).
ANDARDS
2.2. SITING THE APPLIANCE
The appliance may be installed in any room or indoor area, although particular attention is drawn to the requirements of the current I.E.E. Wiring Regulations, and in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the combined appliance in a room containing a bath or sho room containing a bath or shower should only be considered if there is no alter
Where a room-sealed appliance is installed in a room containing a bath or shower the appliance and any electrical s electricity should be situated so that it cannot be touched by a person using the bath or shower, specifically in accordance with current IEE Wiring Regulations.
The location must permit adequate space for servicing and air circulation around the appliance as indicated in Section 2.4. The location must permit the provision of an adequate flue and termination. For unusual locations special procedures may be necessary. BS 6798-1987 gives detailed guidance on this aspect. A compartment used to enclose the appliance must be designed specifically for this purpose. No specific ventilation requirements are needed for the installation within a cupboard. This appliance is not suitable for outdoor installation.
The type C appliances (in which the combustion circuit, air vent intake and combustion chamber are air-tight with respect to the room in which the appliance is installed) can be installed in any type of room.
native.
witch or appliance control, utilising mains
wer, the location of the boiler in a
C.O.S.H.H.
Materials used in the manufacture of this appliance are non­hazardous and no special precautions are required when servicing.
Installation should also comply with the following British Standard Codes of Practice:
BS 7593:1992
BS 5546:1990
BS 5440-1:2000 Flues BS 5440-2:2000 Air supply BS 5449:1990 BS 6798:1987
BS 6891:1989 Installation of low pressure gas pipe up to
BS 7671:2001 BS 4814:1990 Specification for expansion vessels BS 5482:1994 Installation of L.P.G.
and in the Repub Codes of Pr
Treatment of water in domestic hot water central heating systems Installation of hot water supplies f domestic purposes
culation hot water systems
ced cir
For Installation of gas fired hot water boiler of rated input not exceeding 60kW
28mm IEE wiring regulations
lic of Ireland in accordance with the f
actice:
or
ollo
s
wing
Secondary ventilation is not required with this boiler. The boiler must be installed on a solid, non-combustible, permanent wall to prevent access from the rear.
813
I.S.
The appliance may be installed in any room or indoor area, although particular attention is drawn to the requirements of the current I.E.E. Wiring Regulations, and in Scotland, the electrical
visions of the Building Regulations applicab
pro
Domestic Gas Installations
le in Scotland,
7
2.3. OVERALL DIMENSIONS
93 65
450 143
118 123
750
5
45
50
35
67 67 65 93
acqua gas
280
225 225
130 130
F
785
280
450
300
300
450
20
20
93
450
143
118 123
750
5
45
50
35
132132 93
acqua gas
280
225 225
130 130
F
27/32 RFFI SYSTEM
FIG. 2.1
FIG. 2.0
LEGEND:
A = Central Heating Flow (3/4”) B = Domestic Hot Water Outlet (1/2”) C = Gas Inlet (3/4”) D = Domestic Cold Water Inlet (1/2”) E = Central Heating Return (3/4”) F = Condensate discharge
27/32 MFFI
2.4. MINIMUM CLEARANCES
In order to allow access to the interior of the boiler for maintenance purposes, the boiler must be installed in compliance with the clearance requirements indicated in the diagram below.
27/32 MFFI
8
IG. 2.1
F
FIG. 2.2
85 mm
220 mm
300
27/32 RFFI SYSTEM
2.6. ELECTRICAL CONNECTION
The boiler oper technical data table (Section 1.2), where the maximum absorbed
wer is also indicated. Make sure that the connections for the
po neutral and live wires correspond to the indications in the
ram. The appliance electrical connections are situated on
diag the reverse of the control panel (see the Servicing Instructions for further information Section 6).
IMPOR
TANT
In the event that the power supply cable must be changed, replace it with one with the same specifications. Make the connections to the terminal board located within the control panel, as follows:
- The yellow-green wire should be connected to the terminal ked with the earth symbol; make sure to re-use the ferrule
mar mounted on the other supply cable;
- The blue wire should be connected to the terminal marked “N”;
- The brown wire should be connected to the terminal marked “L”.
ates with alternating current, as indicated in the
!
FIG. 2.2
2.5. MOUNTING THE APPLIANCE
Fasten the boiler in place using the template and anchors supplied with the unit. It is highly recommended that a spirit level be used to position the boiler so that it is perfectly level. For additional information, please consult the instructions contained in the connection kit and the flue kit. For safety purposes, have a competent person carefully check the electrical system in the property, as the manufacturer will not be held liable for damage caused by the failure to earth the appliance properly or by anomalies in the supply of power. Make sure that the residential electrical system is adequate for the maximum power absorbed by the unit, which is indicated on the rating plate. In addition, check that the section of cabling is appropriate for the power absorbed by the boiler.
FIG. 2.3
Note: The diagrams for the electrical system are indicated in section 2.11.
Warning, this appliance must be earthed.
External wiring to the appliance must be carried out by a competent person and be in accordance with the current I.E.E. Regulations and applicable local regulations. The appliance is supplied with a fly-lead already connected, this must be connected to a 240v supply fused at 3A and must facilitate complete electrical isolation of the appliance, by the use of a fused double pole isolator having a contact separation
means of a 3
ely, by
of at least 3 mm in all poles or alter fused three pin plug and unswitched shuttered socket outlet both complying with BS 1363. The point of connection to the Electricity supply must be readily accessible and adjacent to the appliance unless the appliance is installed in a bathroom when this must be sited outside the bathroom (see section 2.2). Should external controls be required, the design of the external electrical circuits should be undertaken by a competent person, see Section 2.10 for further information.
nativ
2.7. GAS CONNECTION
The local gas region contr service pipe. If the gas supply f that an adequate supply is a other appliances when the Pipe work must be of an adequate size. Pipes of a smaller size than the boiler inlet connection should not be used.
or the boiler ser
actor connects the gas meter to the
es other appliances ensure
v le both to the boiler and the
ailab
v
y are in use at the same time.
A
9
2.8. WATER CONNECTIONS
FIG. 2.4
VIEW
OF THE
BOILER CONNECTIONS
27/32 MFFI
I
A
CB
H
27/32 RFFI SYSTEM
I
A
C E
H
D
end:
Leg A = Central Heating Flow
B = Domestic Hot Water Outlet C = Gas Inlet D = Domestic Cold Water Inlet E = Central Heating Return
= Condensate discharge
H I = Safety valve discharge
= Drain valve
J
E
J
Central Heating
Detailed recommendations are giv 5449-1:1990, the f
PIPE WORK:
Copper tubing to BS EN 1057:1996 is recommended for water pipes. Jointing should be either with capillary soldered or compression fittings. Where possible pipes should have a gradient to ensure air is carried naturally to air release points and water flows naturally to drain taps. The appliance has a built-in automatic air release valve, however it should be ensured as far as possible that the appliance heat exchanger is not a natural collecting point for air. Except where providing useful heat, pipes should be insulated to prevent heat loss and avoid freezing. Particular attention should be paid to pipes passing through ventilated spaces in roofs and under floors.
BY-PASS:
J
The appliance includes an automatic by-pass valve, which protects the main heat exchanger in case of reduced or interrupted water circulation through the heating system, due to the closing of thermostatic valves or cock-type valves within the system.
SYSTEM DESIGN:
This boiler is suitable only for sealed systems.
DRAIN COCKS:
These must be located in accessible positions to permit the dr
aining of the whole system. The taps must be at least 15mm nominal siz 2870:1980.
SAFETY VALVEDISCHARGE:
The discharge should terminate facing downwards on the
ior of the b
xter
e
ly boiling w
(possib
uisance
n damage to electrical components and wiring. The discharge must not be over an entrance or a window or
y other type of pub
an
CONDENSATEDISCHARGE:
The condensate discharge hose from the boiler must have a continuous fall of 2.5° and must be inserted by at least 50 mm into a suitab overflow pipe. The condensate discharge pipe must have a continuous fall and preferably be installed and terminated within the building to prevent freezing. The discharge pipe must be terminated in a suitable position:
Connecting in to an internal soil stack (at least 450 mm
i)
above the invert of the stack). A trap giving a water seal of at least 75 mm must be incorporated into the pipe run, there also must be an air break upstream of the trap.
ollowing notes are given for general guidance.
e and man
uilding in a position where discharging
ater & steam) will not create danger or
, but in an easily visible position, and not cause
lic access
le acid resistant pipe - e
en in BS 6798:1987 and BS
actured in accordance with BS
uf
.
plastic w
.g.
aste or
10
ii) Connecting into the waste system of the building such as
0
100
200
300
400
500
0 200 400 600 800 1000 1200
(mbar)
(l/h)
a washing machine or sink trap. The connection must be upstream of the washing machine/sink (If the connection is down stream of the waste trap then an additional trap giving a minimum water seal of 75 mm and an air break must be incorporated in the pipe run, as above.
iii) Terminating into a gully, below the grid level but above the
water level. Into a soakway.
iv)
O
: If any condensate pipe work is to be installed
N
TE
xternally, then it should be kept to a minimum and be
e insulated with a waterproof insulation and have a continuous
all.
f
AIR RELEASE POINTS:
These m
ust be fitted at all high points where air naturally collects and must be sited to facilitate complete filling of the system. The appliance has an integral sealed expansion vessel to accommodate the increase of water value when the system is heated. It can accept up to 7 l (1.5 gal) of expansion water. If the heating circuit has an unusually high water content, calculate the total expansion and add an additional sealed expansion vessel with adequate capacity.
MAINS WA
FEED - CENTRAL HEA
TER
TING
:
There must be no direct connection to the mains water supply even through a non-return valve, without the approval of the Local Water Authority.
FILLING:
A method for initially filling the heating system is supplied with the connection kit. The filling loop is connected between the cold water inlet and the central heating flow connections, and incorporates a non-return valve. To operate the filling loop, it is necessary to open both quarter turn handles, once the required pressure has been achieved, close both handles and disconnect the hose in accordance with water byelaws. N The installer should ensure that there are no leaks as frequent filling of the heating system can lead to premature scaling of the main exchanger and failure of hydraulic components.
OTE:
DOMESTIC WA
TER
The domestic water must be in accordance with the relevant recommendation of BS 5546:1990. Copper tubing to BS EN 1057:1996 is recommended for water carrying pipe work and must be used for pipe work carrying drinking water, a scale reducer should also be used to reduce the risk of scale forming in the domestic side of the heat exchanger.
UNDER FLOOR HEATING SYSTEMS:
In the e
vent of an under floor heating system, fit a safety
thermostat on the boiler flow (see Section 2.10). This
mostat should be positioned at a safe distance from the
ther boiler to ensure the correct operation of the same. If the
mostat is positioned too close to the boiler, the water
ther remaining in the boiler after domestic hot water has been
awn will flow into the central heating system and may cause
dr the thermostat contact to open without there being any real danger of the system being damaged, this would lead to a boiler shutdown both in D.H.W. mode and C.H. mode, and the error code automatically when the ther
“E08” would be displayed; boiler operation resumes
mostat contact closes on cooling. Should the thermostat fail to be installed as recommended, the under floor heating system can be protected by installing a thermostatic valve upstream from the thermostat in order to prevent the flow of excessively hot water towards the system.
27/32 MFFI
RESIDUAL HEAD OF THE BOILER
FIG. 2.5
27/32 RFFI SYSTEM
11
WA
The boiler is equipped with an aluminium allo exchanger. The detailed recommendations f BS 7593:1992 (Treatment of water in domestic hot water central heating systems); the following notes are given for general guidance:
- If the boiler is installed in an existing system, any
- Under no circumstances should the boiler be fired before
- Any treatment of water by additives in the system for frost
- If anti-freeze substances are to be used in the system, check
- In under-floor systems, the use of plastic pipes without
TREA
TER
unsuitableadditives must be removed;
thesystem has been thoroughly flushed; the flushing procedure m We highly recommend the use of a flushing detergent appropriate for the metals used in the aluminium alloy circuit. These include (Fernox Superfloc, BetzDearborn Sentinel X300 or X400 or Salamander System Cleanser), whose function is to dissolve any foreign matter that may be in the system; In hard w the system the treatment of the water to prevent premature scaling of the main heat exchanger is necessary.
The formation of scale strongly compromises the efficiency of the thermic exchange because small areas of scale cause a high increase of the temperature of the metallic walls and therefore add to the thermal stress of the heat exchanger. Demineralized water is more aggressive so in this situation it is necessary to treat the water with an appropriate corrosion inhibitor.
protection or for corrosion inhibition has to be absolutely suitable for all the metals used in the circuit including the aluminium alloys. The use of a corrosion inhibitor in the system such as Fernox MB-1, BetzDeaborn Sentinel X100 or Copal Salamander System Inhibitor is recommended to prevent corrosion (sludge) damaging the boiler and systems;
carefully that they are compatible with the aluminium. In particular, DO NOT USE ordinary ETHYLENE GLYCOL, since it is corrosive in relation to aluminium and its alloy, as well being toxic. MTS suggests the use of suitable anti-freeze products such as F taking place. Periodically check the pH of the water/anti-freeze mixture of the boiler circuit and replace it when the amount measured is out of the r DO NOT MIX DIFFERENT TYPES OF ANTI-FREEZE
protection against penetration of oxygen through the walls can cause corrosion of the system’s metal parts ( metal piping, boiler, etc), through the formation of oxides and bacterial agents. To prevent this problem, it is necessary to use pipes with an “oxygen-proof barrier”, in accordance with standards DIN
4726/4729. If pipes of this kind are not used, keep the system separate byinstalling heat exchanger
with a specific system water treatment.
TMENT
y main heat
or water treatment are given in
ust be in line with BS7593:1992.
ater areas or where large quantities of water are in
ernox ALPHI 11, which will prevent rust and incrustation
ange stipulated by the manufacturer ( 7 < pH < 8).
s of those
12
IMPORTANT Failure to carry out the water treatment procedure may invalidate the appliance warranty
2.9. FLUE CONNECTIONS
IMPORTANT!!
BEFORE CONNECTING THE FLUE, ENSURE THAT 1 LITRE OF
WATER HAS BEEN POURED INTO THE EXHAUST CONNECTION TO
FILL THE CONDENSATE TRAP
EMPTY
THERE IS A RISK OF FLUE GASSES ESCAPING INTO THE
ROOM.
(FIG.2.6). SHOULD THE TRAP BE
FIG. 2.6
FLUE SYSTEM
The provision for satisfactory flue termination must be made as descr
ibed in BS 5440-1. The appliance must be installed so that the flue terminal is exposed to outdoor air. The terminal must not discharge into another room or space such as an outhouse or lean-to. It is important that the position of the terminal allows a free passage of air across it at all times. The ter
minal should be located with due regard for the damage or discolouration that might occur on buildings in the vicinity. In cold or humid weather water vapour may condense on leaving the flue terminal. The effect of such “steaming” must be considered. If the terminal is less than 2 metres above a balcony, above ground or above a flat roof to which people have access, then a suitable terminal guard must be fitted. When ordering a terminal guard, quote the appliance model number.
A suitable terminal guard is available from:
TOWER FLUE COMPONENTS Morley Road Tonbridge Kent TN9 1RA
The minimum acceptable spacing from the terminal to obstructions and ventilation openings are specified in Fig. 2.7.
FIG. 2.7
27 MFFI
Coaxial
Systems
TERMINAL POSITION mm
A - Directly below an open window or other opening 300 B - Below gutters, solid pipes or drain pipes 75 C - Below eaves 200 D - Below balconies or car-port roof 200 E - From vertical drain pipes and soil pipes 75 F - From internal or external corners 300 G - Above ground or below balcony level 300 H - From a surface facing a terminal 600
I - From a terminal facing a terminal 1200
J - From an opening in the car port
(e.g. door, window) into dwelling 1200 K - Vertically from a terminal in the same wall 1500 L - Horizontally from a terminal in the same wall 300 M -
Horizontally from an opening window 300 N - Fixed by vertical flue terminal
ype
Exhaust
T
Maximum Extension
Exhaust/Air
(m)
13
C
4
Diameter
of Pipes
(mm)
Ø 60/100
win Pipe
T
Systems
C13, C33, C
53,C83
C
43
20 (S1=S2)
1+39 (S1+S2)
Ø 80/80
Ø 80/80
13
32 MFFI
Exhaust Type
Maximum Extension
Exhaust/Air
(m)
Diameter
of Pipes
(mm)
FIG. 2.8
Coaxial
Systems
Twin Pipe
Systems
13
C
C13, C33, C
C
In FIG. 2.8 (PAG E 11), several different types of flue systems are shown. For additional information regarding the flue accessories, please consult the Flue Pipe Accessories manual.
43
53,C83
4
24 (S1=S2)
1+48 (S1+S2)
Ø 60/100
Ø 80/80
Ø 80/80
14
2.10. ACCESSORY CONNECTION
CN6
CR SE
US
FIG. 2.9
IMPORTANT!! Before carrying out any repairs to the appliance always ensure that the e The boiler will remain live even when the ON/OFF knob is
“O”(off) position.
in the
xternal power supply has been isolated.
SP
TA
FIG. 2.10
IMPORTANT!!
Only remove the links from SP and TA if they are to be connected to external controls.
In order to gain access to the e first necessary to remove the casing (as shown in Section 3.2) then proceed as follows:
1. Remove the cover of the main PCB box
2. Access can now be gained to the following connector (see Section 2.11): CN10 - Saf CN 9 - Room Thermostat CN CN 6 - Interface PCB
CONNECTION OF ROOM THERMOSTAT OR EXTERNAL
TIME CLOCK
- Insert the thermostat cable through the cable grommet and
a.
fasten it by means of the cable-clamp provided. b.- Connect the thermostat wires to the terminal block
c.- If a remote time clock is to be fitted, disconnect the
d. - Using a volt-free switching time clock, connect the
e. - If using an external time clock and room thermostat,
ety thermostat for underfoor heating
11 - Time clock
(Fig. 2.12 - Diagram A).
CN9
integral time clock from the P.C.B. CN11
switching wires from the time clock following points 1-4
(Fig. 2.12 - Diagram B).
above
these must be connected in series as points 1-7 above
(Fig. 2.12 - Diagram C).
xternal control connections, it is
(FIG 2.9).
FIG.
2.11
CONNECTION OF INTERFACE PCB (optional)
The Interface PCB allows for the connection of: REMOTE CONTROL - Clima Manager External sensor Secondaty outlet (*)
(*) = The secondary outlet can be used for the connection of the
following accessories:
- Zone valve
- LPG valve
- Secondar When connecting one of the abo necessar Menu (see Section 3.6.1)
y Pump
y to modify the
E
E
ameter on the P
par
e accessor
v
ies it is
arameter
FIG. 2.12
15
2.11. ELECTRICAL DIAGRAM
P
r
o
g
.
h
m
Day
7
8 9
10 1112
1
1
CN7
CN12
CN8
CN11
CN9
CN10
1
1
FLOOR
ROOM
TIMER
FUSE
FUSE
N
N
L
L
1
CN16
CN4
2
1 2 1
1
2
3 4
2
123456789
1011
12
1
MV
Az
Bl
Mr
Rs
R/N
Mr
Mr
Nr
Nr
Nr
Bn
Bn
Gr
Gr
Gr
Gr
Gr
Gr
Bn
Bn
Bl
Bl
Bl
Bl
Rs
Bn
Mr Nr
CN1 CN12CN5
7
8 9
10 1112
FS PA
TA TS
NTC1
NTC2
NTC3
CN8 CN11
123456789
101112
12345
6
CN6
CN9 CN10
CN5
CN1
CN2
CN3
CN6
CI
AC WFS
VG
O
P
C
L
K
E
F
A
B
H
I
CR
SE
US
N
D
N
M
The P.C.B. is fitted with 2 fuses, on the live and the
al.
neutr The fuse holder contains:
- 5 x 20mm
“3.15A Slow” glass fuses
FIG. 2.13
16
Legend:
A-ON/OFF button B-Multifunction display C-RESET b D-Green led (indicates burner on) E-Comfort function yellow LED
-
F
Red LED
G-COMFORT button H-Programming key +
-
I
Prog
J-Menù button K-Central Heating temperature adjustment
-
L
Domestic Hot
M-Eepron N-Interface PCB (optional)
FS - Domestic hot water flow switch NTC1 - Central Heating flow temperature probe NTC2 - Central Heating return temperature probe NTC3 - Domestic Hot Water temperature probe
- Connection for boiler thermostat
OP - Time clock VG - Gas valve M - Diverter valve (mod. 27/32 MFFI)
- Connection for external diverter valve
CI - Circulation pump with automatic air release valve MV - Fan AC - Spark generator PA-Air pressure switch TA - Room Thermostat (optional) TS - Underfloor Heating Safety Thermostat (optional) CR - Remote Control (optional) SE - External sensor (optional) US - Secondary outlet (optional)
utton
(indicates lockout)
ramming key -
Water temperature adjustment
(mod. 27/32 MFFI)
(mod. 27/32 RFFI SYSTEM)
(mod. 27/32 RFFI SYSTEM)
CN1 = FAN
1: Start of coil (black) 2: End of coil (brown) 3: “Hall” sensor power supply 12V (red) 4: “Hall” sensor input (white) 5: “Hall” sensor neutral (blue) 6: Not used
CN2 = FLAME SENSOR
CN3 = Earth
CN4 =
1: Live (brown) 2: Neutral (blue)
CN5 = EQUIPMENT
WER SUPPLY
PO
CONNECTIONS
1: Gas valve neutral (blue) 2: Gas valve live (brown) 3: Not used 4: Pump (V1) live (red)
Pump (V2) live (black)
5:
Pump (ON/OFF) live (brown)
6: 7:
Pump neutral (blue)
8: 3-way valve (D. H.W.) (brown) 9: 3-way valve (C. H.)(red/black) 10:
3-way valve Neutral (blue)
11: Spark generator Neutral (blue) 12: Spark generator live (black)
CN6 = INTERFACE PCB
(OPTIONAL - see paragraph 2.10)
Accessories: External sensor Remote Control CLIMA MANAGER Secondary outlet (see Section. 2.10)
CN7 = DISPLAY
1: Power 5V 2: Display return 3: Display transmission 4: Earth
CN8 = SENSOR CONNECTOR
1: Central Heating flow sensor (white) 2: Central Heating return sensor (white) 3: Not used
y)
witch (g
DHW flo
4:
DHW sensor (g
5:
Not used
6: 7: Not used
DHW flo
8:
DHW sensor
9:
C
10: 11: C.H. return sensor earth (white) 12: Not used
CN9 = ROOM THERMOSTAT (OPTIONAL - see paragraph 2.10)
CN10 =
CN11 = TIME CLOCK
w s
witch
w s
.H. flow sensor earth (white)
UNDERFLOOR HEA SAFETY (OPTIONAL - see paragraph 2.10)
see para
re
y)
re
rey)
th (g
ear
y)
re
th (g
ear
THERMOSTAT
graph 2.10
TING
17
2.12. WATER CIRCUIT DIAGRAM
AB C DE
2 3
5
6
7
8 9
10
11
12
13
14
15
16
17
18
19
4
1
20
27/32 MFFI
FIG. 2.14
LEGEND:
1- Fan
ner
Bur
-
2
Ignition/detection electrode
-
3 4 - Air release valve 5 - Main heat exchanger
al heating flo
Centr
-
6
Condensate
-
7
- Gas valve
8 9 - Pressure gauge
alv
ety v
Saf
-
10
Secondar
-
11
- Domestic hot water temperature probe
12 13 - Drain valve
y heat exchanger
w temper
Tr ap
e
ature probe
14 - Domestic hot water flow switch
-
15
-
16 17 - Circulation pump with automatic
-
18
-
19
- Air pressure switch
20
e
alv
ised v
Motor Automatic By-pass
air release valve Expansion v Centr
essel
al heating return temperature probe
18
C
2 3
5
6
7
8 9
10
17
16
18
19
20
4
1
21
A
B
D
E
15
11
12 13
14
27/32 RFFI SYSTEM
2.14
FIG.
LEGEND:
1- Fan 2 3
ner
Bur
­Ignition/detection electrode
-
4 - Air release valve 5 - Main heat exchanger
-
6
-
7
- Gas valve
8
al heating flo
Centr Condensate
Tr ap
w temper
ature probe
15 - Expansion relief valve
e
alv
ain v
Dr
-
16
Automatic By-pass
-
17 18 - Circulation pump with automatic
air release valve Expansion v
-
19
Centr
-
20
- Air pressure switch
21
essel
al heating return temperature probe
9 - Pressure gauge
e
alv
ety v
Saf
-
10
.H.W. priority valve (Optional extra)
D
-
11
- Non-return valve (integral to Jig Kit)
12 13 - Filling loop (integral to Jig Kit) 14 - Indirect cylinder expansion vessel
19
3. COMMISSIONING
3.1. INITIAL PREPARATION
MTS (GB) Limited suppor information pack you will find a copy of the Log Book. It is important that this is completed in the presence of your customer, they are shown how to use it, and it is signed by them. Please instr
engineer or us Preliminary electrical system checks to ensure electrical safety
ust be carried out by a competent person i.e. polarity, earth
m continuity, resistance to earth and short circuit.
FILLING THE HEATING SYSTEM:
Remove the panels of the case and lower the control panel (see section 3.2. for further information). Open the central heating flow and return cocks supplied with the connection kit. Unscrew the cap on the automatic air release valve one full turn and leave open permanently. Close all air release valves on the central heating system. Gradually open valve(s) at the filling point (filling-loop) connection to the central heating system until water is heard to flow, do not open fully. Open each air release tap starting with the lowest point and close it only when clear water, free of air, is visible.
Purge the air from the pump by unscrewing the pump plug and also manually rotate the pump shaft in the direction indicated by the pump label to ensure the pump is free.
Close the pump plug. Continue filling the system until at least 1 bar registers on the pressure gauge. Inspect the system for water soundness and remedy any leaks discovered.
uct your customer that they must have their
Log Book with them whenever they contact a service
.
t the initiative. Within the
FILLING OF THE D.H.W. SYSTEM:
Close all hot water draw-off taps. Open the cold water inlet cock supplied with the connection kit. Open slowly each draw-off tap and close it only when clear water, free of bubbles, is visible
GAS SUPPLY:
or
Inspect the entire installation including the gas meter soundness and purge, all as described in BS 6891:1988. Open the gas coc appliance and chec
.
leaks
k (supplied with the connection kit) to the
k the gas connector on the appliance f
, test f
or
Water Treatment
The boiler is equipped with an aluminium alloy main heat exchanger. The detailed recommendations for water treatment are given in BS 7593:1992 (Treatment of water in domestic hot water central heating systems); the following notes are given for general guidance:
If the boiler is installed in an e
­unsuitableadditives must be removed;
- Under no circumstances should the boiler be fired before thesystem has been thoroughly flushed; procedure m We highly recommend the use of a flushing detergent appropriate for the metals used in the aluminium alloy circuit. These include (F X300 or X400 or Salamander System Cleanser), whose function is to dissolv system; In hard w
ust be in line with BS7593:1992.
x Superfloc
no
er
e any foreign matter that may be in the
ater areas or where large quantities of w
xisting system, an
the flushing
, BetzDearbor
n Sentinel
ater are in
y
20
the system the treatment of the water to prevent premature scaling of the main heat exchanger is necessary.
The formation of scale strongly compromises the efficiency of the thermic exchange because small areas of scale cause a high increase of the temperature of the metallic walls and therefore add to the thermal stress of the heat exchanger. Demineralized water is more aggressive so in this situation it is necessar inhibitor. Any treatment of water by additives in the system for frost
­protection or for corrosion inhibition has to be absolutely suitab aluminium alloys. The use of a corrosion inhibitor in the system such as F MB-1, BetzDeaborn Sentinel X100 or Copal Salamander System Inhibitor is recommended to prevent corrosion (sludge) damaging the boiler and systems;
- If anti-freeze substances are to be used in the system, check carefully that the In particular, DO NOT USE ordinary ETHYLENE GLYCOL, since it is corrosive in relation to aluminium and its alloy, as well being toxic. MTS suggests the use of suitable anti-freeze products such as Fernox ALPHI 11, which will prevent rust and incrustation taking place. Periodically check the pH of the water/anti-freeze mixture of the boiler circuit and replace it when the amount measured is out of the range stipulated by the manufacturer ( 7 < pH < 8). DO NOT MIX DIFFERENT TYPES OF ANTI-FREEZE
- In under-floor systems, the use of plastic pipes without protection against penetration of oxygen through the walls can cause corrosion of the system’s metal parts ( metal piping, boiler, etc), through the formation of oxides and bacterial agents. To prevent this problem, it is necessary to use pipes with an “oxygen-proof barrier”, in accordance with standards DIN
4726/4729. If pipes of this kind are not used, keep the system separate byinstalling heat exchanger
with a specific system water treatment.
y to treat the water with an appropriate corrosion
le for all the metals used in the circuit including the
ernox
y are compatible with the aluminium.
s of those
IMPORTANT Failure to carry out the water treatment procedure
y invalidate the appliance warranty
ma
When the installation and filling are completed turn on the central heating system (Section 3.4) and run it until the
.
ature has reached the boiler oper
temper The system m The flushing procedure must be in line with BS 7593:1992 Code of practice for treatment of water in domestic hot water central heating systems.
ing this oper
Dur heating flushing detergent (Fernox Superfloc or equivalent), whose function is to dissolve any foreign matter that may be in the system.
Substances diff problems to the pump or other components.
The use of an inhibitor in the system such as Fernox MB-1 or equivalent is strongly recommended to prevent corrosion (sludge) damaging the boiler and system.
Failure to carry out this procedure may invalidate the appliance warranty.
ust then be immediately flushed through.
ation, we highly recommend the use of a central
erent fr
om these could create serious
ating temper
ature
21
3.2. REMOVING THE CASING
To remove the front casing panel, follow these steps:
1. Remove the screws “A” (FIG 3.1);
2. Remove the four screws from case hooks (two at the top and two at the bottom) and rotate anti-clockwise (FIG 3.2);
3. Lift and unhook the case panel (FIG 3.3).
A
A
FIG. 3.2
F
IG. 3.1
IG. 3.3
F
22
3.3. CONTROL PANEL
A
B
C
27/32 MFFI
I
H
G
F
E
FIG. 3.4
Button Description
ON/OFF Switch
“COMFORT” Function Push-button
Reset Button/ Flue Test**/ scroll through Functions Menu
Menu Switch
Programming “+” key
Programming “-” key
A
B
C
D
E
F
D
Description
Green LED (illuminated = burner on)
Time cloc
Selector knob f Central Heating Temperature Adjustment Knob
Control Panel Cover
Domestic Hot Water Temperature Adjustment Knob
Heating System Pressure Gauge
k
or Summer/Winter
ANT!!
** IMPOR The Flue Test function will cause the boiler to run continuously on maximum power. This function must only be activated by an authorised engineer
T
.
G
H
“COMFORT” Function L.E.D
Red LED
out)
(illuminated = boiler loc
I
Multi-function Display
k
23
A
B
C
27/32 RFFI SYSTEM
I
H G
F
FIG. 3.4
Button Description
ON/OFF Switch
Heating only
Reset Button/ Flue Test**/ scroll through Functions Menu
u Switch
Men
Programming “+” key
ramming “-” key
Prog
A
B
C
D
F
G
Description
Green LED
ner on)
(illuminated = b
Time clock
Selector knob for Summer/Winter Central Heating Temperature Adjustment Knob
Control Panel Cover
Heating System Pressure Gauge
Heating only L.E.D
ur
D
24
TANT!!
um po
This function m
.
wer
ust onl
y be activ
ated by an
** IMPOR The Flue Test function will cause the boiler to run continuously on maxim authorised engineer.
H
Red LED (illuminated = boiler lockout)
I
Multi-function Display
3.4. INITIAL START-UP
C
FIG. 3.6
1. Make sure that:
- the cap of the automatic air release valve is loosened;
- the system pressure is at least 1 bar on the pressure gauge
- the gas cock is closed (Fig. 3.5);
-
the electrical connection has been carried out in the correct manner.
To allow the air to escape from the system,
proceed as follows:
- push the On/off button and turn the knob “C” (Fig. 3.6) to the “winter” position. The boiler pump will start up and three consecutive attempts will be made to ignite
H
the burner. After the third attempt, the electronic system will shutdown the boiler, because the supply of gas has been cut off. The message “ “H” will illuminate;
- let the pump operate until all the air has escaped from the system;
- repeat the procedure for bleeding the radiators of air;
- draw hot water for a short while;
- check the system pressure and, if it has gone down, fill it with water until it returns to 1 bar.
2. Fill the boiler condensate trap with water, by pouring 1/2 a litre of water into the exhaust flue connector (see fig. 3.7). N.B. In the event of a prolonged period of system shutdown, the condensate trap should be filled bef use. A shortage of water in the trap is dangerous because it could possib
“F” (Fig. 3.4);
FIG. 3.5
A01” will appear on the display and the red LED
ore any renewed
ly lead to a leakage of fumes into the air.
FIG. 3.7
3,
Ensure that the flue is filled correctly.
4. Turn on the gas cock(fig. 3.8) and check the seals on the connections, including the one for the burner, making sure that the meter does not signal the passage of gas. Check the connections with a soap solution and eliminate any leaks.
5. Press the reset button , the boiler will attempt to light. If the burner does not light the first time, repeat the procedure. Note: Should the boiler fail to ignite check that no air is present in the gas pipe.
The boiler is configured in the factory for the gas type in question. To check the air/gas ratio, please refer to section
3.6.4.
6. Complete the Benchmark log book.
Fig. 3.8
25
3.5. DISPLAY:MESSAGES SHOWN DURING NORMAL OPERATION
During operation of the boiler, while it is carrying out its normal operations, the left-hand display shows a series of characters that ref
er to the operations indicated below:
--
Diagnostics phase (precedes the other operations)
0
0
No request for heat
C
C
Heating
c
c
Pump overrun for heating
d
d
Domestic hot water
h
h
Pump o
verrun for domestic hot water
b
b
Storage cylinder(SYSTEM version)
The r
ight-hand display (two-digit) shows:
- in CENTRAL HEATING mode: temperature of the Central Heating system flo
- in DOMESTIC HOT WATER mode: temperature of the Domestic Hot Water (MFFI only).
w;
LEFT RIGHT
FIG. 3.9
26
3.6. OPERATING PARAMETERS
The boiler has been designed to allow easy intervention with regard to the operating parameters.
3.6.1 REGULATION MENU TABLE
Summary of the functions accessed when the RESET button
and the menu button are pushed at the same time for 5 seconds On the display will appear the parameters indicated on table 3A. To modify the parameters push the programming keys and .
TAB.3A
.
left display right display function factory setting
6600
11
22
from
from
00 to999
00 to999
9
Soft light
9
as % of maximun Heating Power
Maximun Heating Power (%)
(ACO 27 MFFI - RFFI SYSTEM)
4433
(ACO 32 MFFI - RFFI SYSTEM)
5555
(ACO 27 MFFI - RFFI SYSTEM)
5522
(ACO 32 MFFI - RFFI SYSTEM)
Fig.
3.10
33
44
55
66
tt
FF
ee
from
SS00 toSS1
from
OO00 to002
from
0000 to003
from
00 to7
7
Ignition delay (minutes)
Central heating maximun temperature
Central heating minimum temperature
pm (Check of the temperature
PT r
erence betw
diff sensors for twelve seconds on initial start-up)
1
2
3
T USED
NO
Boiler types
Secondary outlet function
een the flo
w and return
0000
0022
- ACO 27/32 RFFI SYSTEM
0022
8822
4422
4455
SS00
- ACO 27 /32 MFFI
0000
pp
cc
pp
0011 to1155 orCCO
from
0000 to001
from
UU00 toUU1
from
O
Pump o
1
Comf
Pump speed adjustment (modulating or
1
single speed)
err
v
t function
or
un (Centr
al Heating)
(only model MFFI)
0022
0011
UU11
27
left-hand display right-hand display Function factory setting
rr
pp
pp66
PP55
tt
AA
bb00
0000 to001
from
9900 to991
from
--2200 to++220
from
00__33 to33__0
from
8811
selects low temperature systems
1
or std systems
emperature regulation controlled by
1
T
external sensor
0
Correction of heat curve translation
0
Curve incline
Test Function
Bus Address (Do not modify)
Set-point second heating zone
0011
9900
bb11
bb
bb
bb
bb
bb
bb
2200
30
4400
5500
6600
7700
GSM value
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
T USED
NO
28
Important!! The parameters P5, P6 and P9 are only enabled when the outdoor sensor is connected.
To return to the normal display, press the menu button .
FIG. 3.11
0
5
10
15
20
25
kW
%
Soft light adjustment
The soft light can be adjusted betw (shown on the display as “00”, i.e. 100%) and the minimum
wer (shown on the display as “01”, i.e. 1%). The boiler is
po factory set to a value which is suitable for the ignition with any type of gas (appro The value set expressed as a percentage, can be displayed and adjusted as indicated in Section 3.6.1 (parameter 1)
x. 33%).
11
een the maximum power
FIG. 3.12
Heat input
Maximun Heating Power adjustment
The maximum heating power can be adjusted to between the maximum power allowed by the boiler (24kW) and the minimum power (8kW). The value is factory set to 70% of the maximum power. The value set (expressed as a percentage) canbe displayed and modified as illustrated in Section 3.6.1 (parameter 2). The display shows the value between 100% ("00" on the display) and 1% ("01") of this inter
val.
22
3.13
FIG.
FIG. 3.14
FIG.
3.15
Display
Ignition Delay adjustment
The ignition delay can be adjusted to between 0 and 7 minutes. The delay is factory set to 2 minutes.
alue set can be displayed and modified as illustrated in
The v Section 3.6.1 (parameter 3)
33
Maximun Central Heating temperature
This parameter allows the setting of the maximum temperature for the central heating circuit. The value is factory set at 82°C and can be adjusted as illustr
ated in Section 3.6.1 (par
Minimum Central Heating temperature
This parameter allows the setting of the minimum temperature for the central heating circuit. The value is factory set at 42°C and can be adjusted as illustrated in Section 3.6.1 (parameter 5).
44
ameter 4).
55
29
Boiler types
actory setting:
F
FF
00 - ACO 27 / 32 MFFI (C.H. + D.H.W.)
CO 27 / 32 RFFI SYSTEM(C.H. only)
02 - A THIS
PARAMETER MUST NEVER BE ADJUSTED
.
FIG. 3.16
FIG. 3.17
Secondary outlet Function
EE
(This parameter can be modified only with the interface PCB connected)
With the interfa ce PCB connected, it is possible to set the boiler to operate with one of the following accessories, (see Section
2.10 for further information). The setting can be varied by pushing the and keys, the following options are available:
0
000
1
001
2
002
3
003
PUMP OVERRUN
The pump overrun may be varied (after the burner has been turned off) by pressing the programming keys and .. The following modes are available:
001
1
003
3
006
6
009
9
112
2
115
5
CCO
O
zone valve - factory setting LPG valve seconday pump NOT USED
PP
ute of pump overrun
1 min 3 minutes of pump overrun - factoy setting 6 minutes of pump overrun 9 minutes of pump overrun 12 minutes of pump overrun 15 minutes of pump overrun Continuous pump overrun
FIG. 3.18
Comfort Function (MFFI model)
The boiler allows the convenience level to be increased in the output of domestic hot water by means of the “COMFORT” function. This function keeps the secondary exchanger warm during the periods in which the boiler is inactive, thereby allowing the initial water drawn to be at a higher temperature. The function may be activated by pressing the
y on the control panel (see section 3.3.). When the function is
e
k
w light
ello
, a y
e
activ
K
D
panel.
t function can be activ
The comf
or
the and keys
0
000
Comfort function deactvated
1
001
Comfort function active for 30 minutes - factory setting.
It is possib
le to deactiv
“K” comes on, again located on the control
ate the comf
CC
COMFORT button
ated or deactivated by pressing
ort function by pressing the button . The yellow LED
NOTE: Dur function, if selected, is temporarily deactivated. The L.E.D. light remains on to indicate that the boiler will return to the “COMFORT” mode once the pump overrun has finished.
Pump Speed Adjustment
By pressing the and k
ation of the pump
oper
“K” will go out.
ing the overrun period of the pump, the “COMFORT”
PP
ys it is possib
e
, the two options are as follows:
le to adust the
FIG. 3.19
30
0
UU0
- Single Speed Pump
1
UU1
- Modulating Pump - f
actor
y setting
+20
20
-20
6
60
100
-20
+20
-20 +20
to in
crea
se
the
cu
rve
in
pa
ral
lel
to
decrea
se
the
cu
rve
in
pa
ral
lel
FIG. 3.20
FIG. 3.21
FIG. 3.25
r
SETTING THE TEMPERATURE FIELD
Using the programming keys and it is possible to make the
ollowing adjustments:
f
000
0
signifies that the flow temperature (which may be set by
means of the knob on the front control panel) may be regulated from 20 to 75°C.
001
1
signifies that the flo
means of the knob on the front control panel) may be regulated from 42 to 82 °C.
w temperature (which also may be set by
r
TEMPERATURE REGULATION CONTROLLED BY THE
P
EXTERNAL SENSOR
(Onl
y enabled when the outdoor sensor is installed)
By pressing the and
adjustments:
990
0
T
emperature regulation controlled by the external sensor is
inactive (not installed).
991
1
Temperature regulation controlled by the external sensor is
active (installed).
Adapting the heat curve “
(Only enabled when an outdoor sensor is installed)
o adapt the heat curve to the system requirements, set
T parameter “P 6” in order to shift the curve in parallel, so that the flow temperature calculated is changed, along with the ambient temperature. When “
P 6” appears on the left-hand display, use the
heating control knob to shift the curve in parallel as illustrated in the figure below. The shift value can be read on the right-hand display, from -20 to +20.
P
it is possible to make the following
PP 6
6
FIG. 3.26
Flow temperature (°C)
Exter
nal temper
ature (
C)
°
31
100
80
3
2,5
2
1,5
1,2
1
0,5 0,3
60
40
20
20 16
temp. esterna [°C]
temp. di mandata della caldaia [°C]
12 8 4 0 -4 --8 --12 --16
FIG. 3.22
3.23
FIG.
WARNING (*) - If curve 0_3 or 0_5 is set, a system safety thermostat must be connected to the main terminal board (see paragraph
2.10)
PP 5
SETTING THE CURVE INCLINE
(Only enabled when an outdoor sensor is installed)
When using an outdoor sensor, the microprocessor-controlled P.C.B. calculates the most suitable flow temperature, taking into account the e
xternal temperature and the type of system. The microprocessor is capable of doing this because it is possible to establish a link between the external temperature and the flow temperature of the Central Heating system water. This link translates into a "thermal curve". The type of curve should be chosen in correspondence with the planned temperature of the system and the nature of the heat loss present in the building.
5
3.24
Fig.
With parameter P 5 it is posslbe to adjust the heat curve setting to those shown in fig. 4.16). Using programming keys
and , the curve setting may be changed. The possibility of setting curves varies according to parameter r: r = 00 (low temperature range) from curve 0_3 to 0_5
systems only)
r = 01 (high temperature range) from curve 1_0 to 3_0.
max power Central Heating
max power DHW
minimum power
32
(underfloor
3.27
FIG.
FIG. 3.28
FIG. 3.29
Flow temperature (°C)
External temperature (°C)
Test Function
The P.C.B. allows the boiler to be forced to the maximum or minimum power. Enable the test function and
ight-hand displa
the r To select operation at maximum power, press the programming
y , tw
e
k
y (see Fig.
displa This function is disab adjustments menu.
o select oper
T
y , two dashes will appear at the bottom of the right-hand
e
k display (see Fig. 3.10). This function is disabled when you press reset key
Note: The boiler can be forced to the maximum and minimum power even without enabling the test function via the adjustments men a - b
b - by pressing the key, the boiler is forced to operate at
“H” to quit the adjustments menu.
y pressing the Reset k automatically forced to test mode and t-- will be displayed, the boiler is now in the test mode for the maximum heating po
wer, to force the boiler to maximum output for hot water it is necessary to press the and keys together, two dashes appear at the top of the right-hand display (see Fig.
3.9). This function is disabled by pressing the reset key .
um po
minim
ight-hand displa
r pressing the reset k
tt
OO will appear on
y (see Fig.
o dashes will appear at the top of the r
3.9). led when y
ation at minim
u:
, tw
er
w
y (Fig.
e
3.8).
ou press reset key to quit the
wer, press the programming
um po
ey for 5 seconds, the boiler is
o dashes appear at the bottom of the
This function is disab
3.10).
.
y
ight-hand
led b
y
3.6.2 SETTINGS DISPLAY
The boiler is designed to monitor some operating variables and settings by means of the display on the front control panel. Keeping, at the same time, the reset and the menu key pressed for over 10 seconds will allo system variables. By pressing the reset button repeatedly after that, it is possib
Indication on the left-hand display
UU//1 UU//2 UU//3 UU//4 UU//5 UU//6
E
E
A
To return to the normal display, press the menu key. The boiler will automatically retun to the normal display after no b
uttons have been pressed for 2 minutes.
NOTE 1: U/1 means that “ NOTE2: the value 100% appears as “
* = Only displated when an external sensor is fitted.
w access to the “readout” function of the main
le to read the following information in sequence:
V
alue read on right-hand display
1 2 3 4 5 6
Flow temperature of the Central Heating circuit (°C) Return temperature of the Central Heating circuit (°C) Domestic Hot Water output temperature (°C) Outdoor temperature (°C)* Exaust Fume temperature Fan speed (% rpm) Last safety shut-off (see section 3.7.) Last shutdown (see section 3.7.)
U
U
1
1
” and “
” blink alternately on the display
000
0
” on the display
33
1 3
2
4
2
4
3
1
3.6.3 GAS REGULATION CHECK
Supply pressure check
1. Loosen screw “1” (Fig. 3.31) and conect the pressure gauge connection pipe into the test point.
2. Turn the boiler on at maximum power, enabling the “flue sweep” function (press the RESET key for 5 seconds and press the programming keys + and - together). The supply pressure should correspond to that shown for the type of gas the boiler is designed for methane gas G20.
and make sure it is
When the check is over, tighten screw “
3.
1
securely in place.
Disable the test mode by pressing the reset key.
4.
FIG. 3.30
SUPPLY PRESSURE
G20 methane 17-25 mbar
AIR/GAS RATIO SETTING
Calibration v CO
2 at maximum power % vol 8,7 ±0.2
alues c
after 4 minutes of operation methane G20
hec
AIR/GAS RATIO CHECK
Air/gas ratio at minimum power
To check the air/gas ratio at minimum power, proceed as follows:
1. Connect the combustion analyser to the analysis point (Fig.
3.30) after removing the cover plate.
2. Turn the boiler on at minimum power via the test function (see paragraph 3.6.1) or by pressing RESET key for 5 seconds and the programming key - on the control panel. Ensure the CO
value indicated in table 4D. If this is not the case, adjust screw
“2” (Fig.3.31) with a screwdriver, after removing the
cap, until you obtain the correct CO reading to become stable for at least 4 minutes.
3. When the check is over, replace the cap on screw “
3.31).
4. Disable operation at minimum power by pressing the RESET key.
Air/gas ratio at maximum power
To check the air/gas ratio at maximum power, proceed as
follows:
1. With the combustion analyser already connected to the
FIG. 3.31
analysis point, set the boiler to maximum power via the test function (see paragraph 3.6.1) or enabling the “flue sweep function” by pressing the RESET key for 5 seconds and the programming keys + and -. Ensure the CO value indicated in table 4D. If this is not the case, adjust
4” with a screwdriver (Fig. 3.31), until you obtain the
screw “ correct CO at least 4 minutes.
2. Disable the test mode by pressing the RESET key. The test mode is automatically disabled after 5 minutes.
3.
Repeat the air/gas ratio at minimum power check (see above).
k
4. Disconnect the analyser, remount the cover plate and check it is securely in place.
value on the analyser corresponds with the
2
reading. Allow the
2
2 value on the analyser corresponds with the
2 reading.
Allow the reading to become stable for
2” (Fig.
AIR/GAS
Calibration v CO
2 at minim
after 4 min methane G20
34
RATIO SETTING
k
um po
hec
wer
alues c
utes of operation
ol 9,2 ±0.2
% v
3.6.4 IGNITION DELAY ADJUSTMENT
The ignition delay can be adjusted to between 0 and 7 minutes. The delay is factory set to 2 minutes. The value set can be displayed and modified as illustrated in paragraph 3.6.1 (parameter 3).
3.6.5 ADJUSTING THE MAXIMUM HEATING POWER
3.6.6 SOFT LIGHT ADJUSTMENT
3.7 CHANGING THE TYPE OF GAS
The maximum heating power can be adjusted to between the maximum power allowed by the boiler (24 kW) and the minimum one (8 kW). The value is factory set to 70% of the maximum
wer.
po The value set (expressed as a percentage) can be displayed and modified as illustrated in paragraph 3.6.1(parameter 2).
The soft light can be adjusted between the maximum power (shown on the display as "00", i.e. 100%) and minimum power (shown on the display as "01", i.e. 1%). The boiler is factory set to a value which is suitable for ignition with any type of gas (approx. 33%). The value set (expressed as a percentage) can be displayed and modified as illustrated in paragraph 3.6.1 (parameter 1).
Initially the ACO boiler is only available for use with methane Gas (G20).
35
3.8. BOILER SAFETY SYSTEMS
The boiler is protected from malfunctioning by means of internal checks by the P.C.B., which brings the boiler to a stop if necessary. In the event of the boiler being shut off in this manner, a code appears on the display which refers to the type of shut-off and the reason behind it. There are two types of shut-off:
There follows a list of the shutdown modes and the respective codes shown on the display.
A
A
Shutdown (“ reset the boiler using the appropriate key. If this shutdown occurs frequently, your local Service Agent should be contacted.
DISPLAY CAUSE
AA0011
AA0022
AA0033
AA0077
AA3333
AA9977
AA9988
” type): if such a situation occurs, it is necessary to
Too many attempts to ignite on starting up
No water or no water circulation in central heating system
The heating flow temperature exceeds 105°C during operation
Too many failures to flame in one period during operation
Problem with the fan
Problem with the electronic monitoring
Problem with the electronic monitoring
SAFETY SHUTDO
-
(characterised on the display by the letter “ is automatically remo resolved. As soon as the origin of the shutdown disappears, the boiler starts up again and returns to its normal operation.
SHUTDOWN: (characterised on the display by the letter
-
A
A
”), is not removed unless a manual intervention is made. The boiler may return to operation only if reset by pressing the RESET button located at the centre of the display.
Safety shutdown: In the event that a safety shutdown occurs, it is necessary to contact an Authorised Service Centre.
DISPLAY CAUSE
EE 0044
EE 0055
EE 0066
EE 0077
EE 0088
EE 0099
EE 1100
WN:for this group of errors
E
E
”) the situation
ved as soon as the cause behind it is
Domestic hot water temperature probe in open circuit
Domestic hot water temperature probe in short circuit
Heating flow temperature probe in open circuit
Heating flow temperature probe in short-circuit
Heating return temperature probe in open circuit
Heating return temperature probe in short-circuit
Under floor heating temperature probe in open circuit
lem with the electronic monitor
AA9999
NOTE: When there is no ignition, check that the gas cock is open.
36
Prob
ing
EE 2200
EE 3300
EE 3311
EE 3333
EE 3344
EE 8800
EE 9944
EE 9955
EE 9999
e closed
Flame detected with gas v
Outdoor sensor open circuit
Outdoor sensor in shor
ation sensed with no demand f
an oper
F central heating or domestic hot water
Fan operation but air pressure switch does not close
Remote Control CLIMA MANAGER room sensor in open circuit or short circuit
Problem within the electronic system
Error reading flo
Problem within the electronic system
w or retur
alv
t circuit
n temper
ature probe
or
DAILYTEST.
In order to prevent the shutdown of the components, the boiler carries out a self-diagnosing test every 21 hours: the pump turns on for 15 seconds and the diverter valve moves.
ANTI-FR
The anti-frost function acts on the central heating flow temperature probe, independently from other regulations, when the board is turned ON. If the pr for 2 minutes. After the tw the following: a) if the centr stops; b) if the centr the pump will run for another two minutes; c) if the central heating flow temperature is < 3°C, the burner will fire (heating position) at minimum power until the temperature reaches 33°C, the burner will go out and the pump will continue
un for two minutes.
to r
DEVICE.
OST
imary circuit temperature falls below 8°C the pump will
o minutes of circulation (fixed) the boiler will check
al heating flow temperature is > 8°C, the pump
al heating flow temperature is between 3 and 8°C,
If the flow temperature remains between 3-8°C the pump will continue to run for two minutes for a maximum of 10 times unless a temperature above 8°C is detected in the central heating flow, after this the the burner will fire. If lockout is caused by overheat the burner is kept OFF.
NOTE: In all cases, the circulation takes place in the central
heating system. The anti-frost device activates only when (with the boiler
ating correctly):
oper
- the system pressure is correct;
- the boiler is electr
- there is a supply of gas.
ANTI-SCALE DEVICE.
When producing domestic hot water, the burner shuts off
ver the output temperature of the hot water exceeds
whene 61°C or the flow temperature of the primary circuit exceeds 78°C. It will not turn on if the temperature of the primary circuit is greater than 78°C.
ically powered;
3.9. COMBUSTION ANALYSIS
3.10 COMPLETION
3.11 DRAINING
The boiler is designed to allow for easy analysis of the products of combustion. Using the flue analysis points, it is possible to detect the temperature of the burnt gas, the combustion air, the concentrations of O To access these points, unscrew the front screw and remove the metal plate and seal. The best test conditions, with the maximum heating power, are achieved when the FLUE SWEEP FUNCTION is enabled (press the RESET KEY for 5 seconds and the programming keys + and -). The boiler will return to normal operating conditions automatically after 5 minutes, or if you press the reset key. When you have finished, reposition the metal plate correctly and make sure the seal fits perfectly.
For the Republic of Ireland it is necessary to complete a “Declaration of Conformity” to indicate compliance to I.S. 813. An example of this is given in the current edtion of I.S. 813. In addition it is necessar
The draining of the heating system must be carried out as
ws:
ollo
f
urn off the boiler and the bipolar switch;
T
-
- Loosen the automatic air release valve;
- Open the system's discharge valve and gather the water that comes out in a container Empty out from the lo
­provided).
If the system is to be left active in areas where the room temperature may go below 0°C during winter, it is recommended that anti-freez system in order to avoid the need for repeated draining.
2, CO2, etc.
y to complete the Log Book.
;
west points of the system (where
e liquid be added to the w
ater in the heating
Draining the domestic hot water system
y time that there is a danger of freezing, the domestic hot
er
Ev water system must be drained as follows:
- close the water mains stop-cock;
- open all the hot and cold water outlets; empty out from the lowest points (where provided).
-
37
4. ZONE VALVES
The boiler is capable of managing a heating system that uses zone valves. The electrical connection of these valves is carried out by means of the appropriate terminal board (indicated in the
LECTRICAL CONNECTIONsection).
E
By way of example, two possible types of systems would be:
1. System with 2 v (day and night).
2. System with 1 valve (regulation of the night zone subordinated to that of the day).
A possible set-up for the first type of system is as follows:
alves with independent regulation of the zones
CR = remote control VZ1,2 = zone valve 1 and 2 TA = room thermostat or timer-thermostat
= radiators F,N = electrical connection (live and neutral) RL = relay
A possible set-up for the system with a single zone valve is as follows: This set-up is simpler and more economical because it does not involve the use of the special relay. The night zone, however, may only be heated during the time periods in which the remote control timer gives consent to the heating of the day zone. Example:
day zone programming (remote control): 8:00 - 22:00
night zone programming (timer-thermostat): 20:00 - 22:00
38
5. MAINTENANCE
5.1. GENERAL REMARKS
IMPORTANT!!
Every time that the combustion chamber cover or the primary heat exchanger is removed from the boiler, the combustion chamber seal must be replaced (code:
65102217). gasket must be spread around the area the gasket fits to ensure an airtight seal.
Only the grease provided must be used, however, should more grease be needed it must have a temperature range of between –40 deg C and +200 deg C”
The silicone grease provided with the
It is recommended that the following inspections be carried out on the boiler at least once a year:
1. Check the seals in the water group and, if necessary, replace the gaskets and restore the seal to perfect working order.
2. Check the seals in the gas group and, if necessary, replace the gaskets and restore the seal to perfect working order.
3. Visually check the overall state of the boiler.
4. Visually check the combustion and, if necessary,
disassemb
5. Following inspection 3, disassemble and clean the comb
6. Following inspection 4, disassemble and clean the injector, if necessar
7. Clean the primary heat exchanger (see section 6.2)
8. Regulate the correct r
ignition, partially loaded and at maximum load.
9. Check the correct functioning of the heating safety devices:
- temperature limit safety device.
10. Check the correct functioning of the gas group safety
vices:
de
- absence of gas or flame safety device (Ionisation).
11. Check that the electrical connections are correct (in conformity with the instructions manual).
12. Check the efficiency of the production of domestic hot water (test the rate of flow and temperature).
13. Carry out a general inspection of the functioning of the boiler.
14. Check the characteristics for expulsion of the products of
combustion.
15. Remove the oxide from the detection electrode by means of an emery cloth.
le and clean the burner.
ustion chamber, if necessary.
y.
ate of flow of the gas: rate of flow on
5.2. CLEANING THE PRIMARY EXCHANGER
IMPORTANT!!
Every time that the combustion chamber cover or the primary heat exchanger is removed from the boiler, the combustion chamber seal must be replaced (code:
65102217). The silicone grease provided with the gasket must be spread around the area the gasket fits to ensure an airtight seal.
Only the grease provided must be used, however, should more grease be needed it must have a temperature range of between –40 deg C and +200 deg C”
5.3. CLEANING THE CONDENSATE TRAP
NB: if the boiler is not to be used for a prolonged period, the condensate trap should be filled before igniting it again. A shor
isk of e
r
tage of w
ater in the tr
xhaust fumes escaping into the air
ap is dangerous because there is the
.
CLEANING THE EXHAUST SIDE Remove the combustion chamber inspection hatch (see section
6.3.5). Check that the exhaust passages between the blades of
the block are free; if there are deposits present, wash the blades with compressed air, water or a vinegar-based detergent. NOTE: it is possible to use a brush in order to mechanically remove the residues. Use of detergents:
- soak the blades well
- allow the detergent to act for about 20 minutes
- rinse with a strong jet of water to remove the deposits (the control panel must be kept closed)
- make sure that there are no traces of detergents in the exchanger.
CLEANING THE WATER SIDE Use detergents that dissolve CaCO3. Leave to act for a short time (in order not to damage the alumin
e sure that the detergent does not remain inside the
Mak exchanger.
t of the condensate tr
er par
Unscre Lastly
w the lo
, fill it with w
w
ater and replace the stopper.
um) and then r
ap and clean it.
inse
.
5.4. OPERATIONAL TEST
, fill the
After ha heating circuit to a pressure of appro air from the system. Also fill the domestic hot water system.
-
-
-
- Check the seal and the correct functioning of the system for
- Check that the boiler ignites properly and carry out a visual
ving carr
Place the boiler in oper If necessar Check the settings and the correct functioning of all the control, regulation and monitoring parts.
xpelling fumes/dr
e
check on the burner flame.
ied out the maintenance oper
x. 1.5 bar and release the
ation.
, release the air again from the heating system.
y
wing of comb
a
ustion air.
ations
39
TABLE I and II
YES
YES
YESYES
YESYES
NONO
NONO
IS THE
DISPLAY ON?
DOES AN ERROR CODE
APPEAR ON THE DISPLAY?
1. Check the fuses
2. Check the power supply to the control panel
3. Check/replace the ON/OFF button
4.
Check the connection between
the main and displa
y P.C.B.s
5. Check/replace the main and display P.C.B.s
NO
NO
PRESS THE ON/OFF BUTTON
TO THE ON POSITION
MAKE SURE THAT:
1. There is sufficient water in the system
2. The gas is turned on
3. The electrical supply is turned on
SUMMERSUMMER
WINTERWINTER
COMFORT
SELECTOR ON/OFF:
yellow L.E.D
. on
YES:
COMFORT ONYES: COMFORT ON
YES: COMFORT ONYES: COMFORT ON
Flow
temperature
<36C
COMFORT
SELECTOR ON/OFF:
yellow L.E.D
. on
Flow
temperature
>42C
Flow
temperature
<36C
Flow
temperature
>42C
NO: NO:
COMFOR
T OFFCOMFORT OFF
NO: NO:
COMFOR
T OFFCOMFORT OFF
YESYES
NONO
YESYES
NONO
NONO
YESYES
NONO
YESYES
YESYES
YESYES
D.H.W.
IS BEING
DRAWN?
D.H.W.
IS BEING
DRAWN?
YESYES
NONO
IS THE
THE TIME CLOCK
AND/OR ROOM THERMOSTAT
BE ACTIVATED?
NONO
NONO
BUILT-IN
ELECTRONIC
ANTI-FROST DEVICE:
Is there a condition for it to be active?
(flow temp between 3C & 8C)
- PC0 continuous pump operation selected on menu
THERE IS NO CALL FOR PUMP OPERATION
THERE IS NO CALL FOR PUMP OPERATION
A
NO
BUILT-IN
ELECTRONIC
ANTI-FROST DEVICE:
Is there a condition for it to be active?
(flow temp between 3C & 8C)
- PC0 continuous pump operation selected on menu
7. FAULT FINDING
7.1. FA
ULT
FINDING GUIDE
(FLOW-CHARTS)
Model 27/32 MFFI
It is possib
le to detect and correct any defect by using the standard fault
finding diagrams described in this chapter.
55
TABLE I and II
YES
YES
YESYES
YESYES
NONO
NONO
IS THE
DISPLAY ON?
DOES AN ERROR CODE
APPEAR ON THE DISPLAY?
1. Check the fuses
2. Check the power supply to the control panel
3. Check/replace the ON/OFF button
4.
Check the connection between
the main and display P.C.B.s
5. Check/replace the main and displa
y P.C.B.s
NONO
PRESS THE ON/OFF BUTTON
TO THE ON POSITION
MAKE SURE THAT:
1. There is sufficient water in the system
2. The gas is turned on
3.
The electrical supply is turned on
SUMMERSUMMER
WINTERWINTER
COMFORT
SELECTOR ON/OFF:
yellow L.E.D
. on
YES: COMFORT ONYES: COMFORT ON
YES: COMFORT ONYES: COMFORT ON
Flow
temperature
<36C
COMFOR
T
SELECTOR ON/OFF:
yellow L.E.D
. on
Flow
temperature
>42C
Flow
temperature
<36C
Flow
temperature
>42C
NO: NO:
COMFORT OFFCOMFORT OFF
NO: NO:
COMFORT OFFCOMFORT OFF
YESYES
NONO
YESYES
NO
NO
NO
NO
YES
YES
NONO
YESYES
YESYES
YESYES
D.H.W.
IS BEING
DRAWN?
D.H.W.
IS BEING
DRAWN?
YESYES
NONO
IS THE
THE TIME CLOCK
AND/OR ROOM THERMOSTAT
BE ACTIVATED?
NONO
NONO
BUILT-IN
ELECTRONIC
ANTI-FROST DEVICE:
Is there a condition for it to be active?
(flow temp between 3C & 8C)
- PC0 continuous pump operation selected on menu
THERE IS NO CALL FOR PUMP OPERATION
THERE IS NO CALL FOR PUMP OPERATION
A
NO
BUILT-IN
ELECTRONIC
ANTI-FROST DEVICE:
Is there a condition for it to be active?
(flow temp between 3C & 8C)
- PC0 continuous pump operation selected on menu
Model 27/32 RFFI SYSTEM
56
YESYES
YESYES
NONO
NONO
YESYES
IS THE
PUMP RUNNING?
WAS THE
PL
AUSIBILITY TEST OK? (
E95: test failed
)
1. Check the pump cable
2. Check/replace the pump
3. Check/replace the NTC probes
4. Replace the main P.C.B.
P
OWER TO
THE PUMP?
NONO
A
B
Release/Replace pump
1. Check/replace pump cable
57
1. Check the fan cable
2.
Replace the fan
3. Replace the main P.C.B.
1. Check/replace ignition electrode
2. Check ignition cable
3. Check/replace the main P.C.B.
Replace
the main P
.C.B.
IS THE F
AN
RUNNING?
DOES CODE
A33 APPEAR?
ARE IGNITION
SPARKS GENERATED
REGULARLY?
DOES THE
AIR PRESSURE SWITCH
CLOSE? (E33)
YES
YES
YESYES
NONO
NONO
NONO
YESYES
YESYES
NONO
1. Check the power supply of the gas valve.
2. Check for an air pressure signal
3. Check the gas pressure on the burner
4. Check the soft-light adjustment
5. Replace the gas valve
6. Check/replace the main P.C.B.
1. Table II
2. Press RESET
1. Table III
IS THE BURNER
ALIGHT?
BOILER HAS SHUTDOWN?
YESYES
YESYES
NONO
WAS THE FLOW TEST
SUCCESSFULL?
(A02 TEST FAILED)
YESYES
NONO
NONO
IS
THERE STILL
A PROBLEM?
NORMAL
OPERATION
NONO
YESYES
B
1. Check pump cable
2. Check/replace the pump
3. Check NTC probes cables
4. Check/replace NTC probes
5. Check/replace main P.C.B.
1. Check the exhaust flue duct
2. Check the APS cable
3. Check if there is condensate in the silicone pipes
4.
Check/Replace the APS
5. Check/Replace the main P.C.B.
58
8. SHORT SPARE PART LIST
49
15
16
17
64
63
137
31
87
26
85
47
48
83
84
3427 302925
19
3736 38 41 423935
43
44
45
46
82
104
98
103
97
102
98
100
99
36
101
97
96
11
77
76
78
74
RESET
CONFORT
ON/OFF
68
79
82
51
50
47
48
89
88
92
90
91
61 60
22
23
24
20
19
21
86
28
94 95
93
110
32 33 40
72
70
69
73
80
71
81
14
13
7
6
1
12
8
7
8
6
9
10
62
4
3
5
58 575
63
6
64
4
2
54 5253
111
109
112
113
88
134
122
128
136
126
121
121
124
133
107
108
108
106
105
88
91
90
118
117
67
66
65
123
122
119
120
130
132
131
129
135
59
59
56 55
125
125
116 115 114
18
88
127
75
6
205
ON/
OFF
CON
FOR
T
RE
S
ET
M
208
207
210
215
216
202
201
205
204
203
212
213
214
206
211
209
cod. 65102191
27/32 MFFI
59
Key
no.
G.C. part
no.
Description
ON
ARIST
Part. No.
1 Flue restrictor 65102197 10 Spark generator 65102177 14 Main P.C.B. 65102236 18 Secondary heat exchanger 990685 21 Temperature probe (DHW) 998458 22 Manifold (CH Return) 990384 29 Safety valve (3bar) 997088 31 Pressure gauge 65102220 32 Gas valve 65102247 35 Flow switch (DHW) 995948 37 Motor (3-way valve) 997147 42 Pump 65102253 46 Automatic air vent 995865 54 Expansion vessel 995940 55 Air pressure switch 65102232 75 Hose clip 990632 90 Retaining clip (NTC CH) 65101007 91 NTC (CH) 990405
101 Repair kit (3-way valve) 65101288 107 Main exchanger (27 KW) 65102233 107 Main exchanger (32 KW) 65102260 126 Ignition electrode 65102198 130 Detection electrode 65102199 132 Fan 65102248 136 Burner (27kW) 65102181 136 Burner (32kW) 65102180 203 Cable (Time Clock) 65102188 204 Time Clock 999599 215 Display P.C.B. 65102235 216 Cable (Display P.C.B.) 65102185
60
47
16
17
18
62
61
123
28
83
23
81
45
46
79
80
24 272622 36 39 4037
41
42
43
44
34
90
33
11
75
74
76
73
RES
ET
ON/
OFF
66
77
48
45
46
84
85
86
59 58
19
20
21
82
25
87 88
96
31 38
70
68
67
71
78
69
14
13
7
6
1
12
8
7
8
6
9
10
60
4
3
5
56 555
61
6
62
4
2
52 5051
97
95
98
99
29
120
108
114
122
112
107
107
110
119
93
94
94
92
91
29
86
85
104
103
65
64
63
109
108
105
106
116
118
117
115
121
57
57
54 53
111
111
102 101 100
29
113
72
6
353433
89
3029 32
15
49
205
ON/
OFF
RE
S
ET
M
208 207
211
216
217
202
201
205
204
203
213
214
215
206
212
210
code 65102299
209
27/32 RFFI SYSTEM
61
Key
no.
G.C. part
no.
Description
ARISTON
art. No.
P
1 Flue restrictor 65102196 10 Spark generator 65102177 14 Main P.C.B. 65102236 42 Manifold (CH Return) 65102305 26 Safety valve (3bar) 997088 28 Pressure gauge 65102220 31 Gas valve 65102247 40 Pump 65102253 44 Automatic air vent 995865 52 Expansion vessel 995940 53 Air pressure switch 65102232 75 Hose clip 990632 85 Retaining clip (NTC CH) 65101007 86 NTC (CH) 990405 93 Main exchanger (27 KW) 65102233 93 Main exchanger (32 KW) 65102260
112 Ignition electrode 65102198 116 Detection electrode 65102199 118 Fan 65102248 122 Burner (27kW) 65102181 122 Burner (32kW) 65102180 203 Cable (Time Clock) 65102188 204 Time Clock 999599 216 Display P.C.B. 65102235 217 Cable (Display P.C.B.) 65102185
62
63
Manufacturer: Merloni TermoSanitari SpA - Italy Commercial subsidiaries: MTS (GB) LIMITED MTS Heating Limited
MTS Building Damastown Industrial Park Hughenden Avenue Damastown Avenue
ycombe
W
High Bucks HP13 5FT Dublin 15
elephone:
T
ax:
F Internet: www.mtsgroup.com/uk Internet: www.mtsgroup.com/ie E-mail:
Technical Advice: 0870 241 8180 Technical Advice: (01) 437 0121
Customer Ser
(01494) 755600
(01494) 459775 Fax: (01) 810 3727
.com
o@uk.mtsg
inf
roup
0870 600 9888
vice:
Mulhuddart
elephone:
T
E-mail:inf
Customer Ser
(01) 810 3723
o@ie.mtsgroup.com
vice:
(01)
437 0121
099841832211
Loading...