Aprilaire 1872 User Manual

Model 1872 Dehumidifier
Installation and Operating Manual
SAFETY INSTRUCTIONS
WARNING
1. 120 Volts may cause serious injury from electric shock. Disconnect electrical power before starting installation or servicing. Leave power
disconnected until installation/service is completed.
2. Dropping may cause personal injury or equipment damage. Handle with care and follow installation instructions.
CAUTION
1. Read all instructions before beginning installation.
2. Improper installation may cause property damage or injury. Read instructions before installation, service or maintenance.
3. Do not use in pool applications. Pool chemicals can damage the dehumidifier.
4. Do not use solvents or cleaners on or near the circuit board. Chemicals can damage circuit board components.
5. Wait 24 hours before running the unit if it was not shipped or stored in the upright position
6. Do not use dehumidification to prevent window condensation in the winter. To address window condensation, use ventilation to lower
indoor humidity in the winter.
TABLE OF CONTENTS
SAFETY INSTRUCTIONS � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 1
SPECIFICATIONS � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �2
REMOVE SHIPPING BRACKET � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 2
LOCATION CONSIDERATIONS � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 3
DRAIN INSTALLATION � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 3
Condensate Pump and Float Switch� � � � � � � � � � � � � � � � � � � � � � � � � � � � �3
SETTING THE DESIRED HUMIDITY LEVEL � � � � � � � � � � � � � � � � � � � � � � � � �4
MAINTENANCE� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 5
DUCT COLLAR INSTALLATION� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �6
Control Location� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �6
DUCTING � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 7 Ducting in Basement � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �7 Ducting to Whole Home without an Air Handler� � � � � � � � � � � � � � � � � �8
TROUBLESHOOTING � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �9 Table 1 – Diagnostic Codes � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �9 Table 2 – Troubleshooting Guide � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 10
SERVICE PARTS � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �11
LIMITED WARRANTY � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 12
READ AND SAVE THESE INSTRUCTIONS
1
SPECIFICATIONS
CLIP OFF
REMOVE SCREWS (2)
MODEL 1872
Weight 113 lbs�
Capacity
AHAM DH-1-2008 80°F, 60% RH Conditions
Power 115 VAC, Single Phase, 60Hz
Dehumidifier Inlet Air Conditions
Filter MERV 8, washable
EXTERNAL STATIC PRESSURE ("w.c.) AIRFLOW (CFM)
Airflow
0.7"w.c. is maximum design external static pressure.
Dehumidification: 50°F – 104°F, 40°F dew point minimum
Ventilation: 40°F – 140°F, 0%RH – 99%RH (non-condensing)
0�0 310
0�2 270
0�4 225
0�6 175
130 pints per day @ 310 CFM
8�3A operating current
REMOVE SHIPPING BRACKET
IMPORTANT: Cut the strap securing the compressor shipping support bracket and remove the strap, shipping bracket screws, and bracket� See FIGURE 1
FIGURE 1 – REMOVE SHIPPING BRACKET
DISCARD SHIPPING BRACKET REINSTALL SCREWS (2)
PLASTIC STRAP
90-2013
2
LOCATION CONSIDERATIONS
FOR PROPER
ELECTRICAL SERVICE ACCESS THIS SIDE
• Allow sufficient clearance for filter removal and to prevent airflow obstruction
• Electrical service access will require the removal of the side panel shown� Allow sufficient space for service on this side of the unit�
FIGURE 2 – FILTER ACCESS CLEARANCE
6" MINIMUM
CLEARANCE
AIR FLOW
6 FT. POWER CORD
TOP VIEW
FILTER
MINIMUM
20"
CLEARANCE FOR FILTER (EITHER SIDE)
90-2020
DRAIN INSTALLATION
The drain outlet on the dehumidifier can be hard piped using a 3/4" PVC Slip x 3/4" MNPT fitting and 3/4" nominal drain tubing or the provided 3/4" MNPT x 3/4" hose barb fitting and 3/4" clear PVC tubing can be used to drain the dehumidifier� Always maintain a constant downward slope from the dehumidifier to the drain and do not allow soft tubing to curl up which may result in air lock� Note: PTFE thread seal tape is recommended for the threaded connection and hand tighten only� If hard pipe is used, PVC primer and cement is recommended for the slip fit connection�
A level surface is required to ensure proper drainage from the dehumidifier�
Always install the dehumidifier in a condensate pan when locating in or above a finished space� Adhere to local codes regarding draining of the condensate pan�
CONDENSATE PUMP AND FLOAT SWITCH
If a condensate pump is needed, install it in the condensate pan if installed�
Install a condensate overflow safety switch (i�e� float switch) in the condensate pan, remove the factory installed jumper wire between the Float Switch terminals on the control and wire the float switch to the dehumidifier as shown in FIGURE 3� Overflow safety switches on condensate pumps can be wired to the Float Switch terminals in a similar fashion�
FIGURE 3 – FLOAT SWITCH WIRING
DH DH
FLOAT
Switch
NORMALLY CLOSED
FLOAT SWITCH
90-1857
3
SETTING THE DESIRED HUMIDITY LEVEL
ON/OFF SWITCH
1. Plug in dehumidifier and turn on/off switch ON� See FIGURE 4�
2. Press the ON/OFF button to turn the dehumidifier control ON� The display will show the
current setting, and the dehumidifier blower will turn on to start sampling the air�
3. The and buttons allow the humidity level to be set from 40% to 80% relative humidity� Use the ON/OFF button to turn the dehumidifier ON or OFF�
Set the control at 55%RH when first installed� Allow the dehumidifier to run until it reaches
the setting before deciding if you want to change the setting� See FIGURE 5
If you prefer the air to be more dry, decrease the humidity setting�
If you prefer the air to be less dry, increase the humidity setting�
4. After three (3) minutes of sampling, the measured humidity will be compared to the setting:
a. If the humidity is above the setting, the dehumidifier compressor turns on and “AIR
SAMPLING” will be replaced by “DEHUMIDIFYING”� The compressor remains on until the measured humidity falls 3% RH below the setting� See FIGURE 6
b. If the measured humidity is below the setting, the blowers turn off and the display
returns to showing the RH setting�
5. The dehumidifier will sample again every 60 minutes, or at any time if the humidity setting is lowered�
Your comfort is the best measure of how to adjust your setting� When first installed, your dehumidifier has to remove all the moisture that is initially in your home� The home acts like a sponge so the moisture in the materials of your home is at the same level as the air� After drying the air, the materials of the home will release moisture back into the air until they are again at the same level� As a result, it is not uncommon for the dehumidifier to operate for an extended period when first installed�
FIGURE 4 – ON/OFF SWITCH
90-1908
FIGURE 5
Your dehumidifier is equipped with two features that protect against unwanted energy consumption� Defrost is a normal operating mode that helps to prevent significant ice formation on the refrigeration system coil� The dehumidifier display will show “DEFROSTING” when operating in this mode� This mode can occur when there is not enough air moving through the dehumidifier or if the temperature and/or humidity of the incoming air is too low� The second protection feature is the E8 code� E8 on the dehumidifier display indicates that the air entering the dehumidifier is below 50°F or above 104°F, or the dew point of the incoming air is below 40°F� There would be a significant reduction in dehumidifier efficiency if the dehumidifier operated outside of these conditions� Low dew point conditions can be seen in some basements or crawl spaces and usually occur in the Winter and Spring months� The dehumidifier continues to monitor the incoming air and when the conditions are within the operating range, E8 will be removed from the display and dehumidification will begin as needed�
ENERGY SAVINGS TIPS
Energy Savings Tip #1: Adjust the humidity setting to be as high as is comfortable to reduce dehumidifier run time� If it feels clammy or “smells musty”, lower the humidity setting� To save energy, turn the dehumidifier to OFF when you open your windows, just as you would with air conditioning�
Energy Savings Tip #2: If vacating your home for an extended period in the summer, set the RH at 55% and set your thermostat as high as you are comfortable setting it to in the cooling mode� Consult with appropriate professionals regarding the highest temperature that is safe for your pets or possessions� This will keep the humidity at a controlled level while minimizing the amount of cooling energy used�
90-1853
FIGURE 6
90-1853
4
Loading...
+ 8 hidden pages