IMPORTANT: Cut the strap securing the compressor shipping
support bracket and remove the strap, shipping bracket screws,
and bracket� See FIGURE 1�
FIGURE 1 – REMOVE SHIPPING BRACKET
DISCARD SHIPPING BRACKET
REINSTALL SCREWS (2)
PLASTIC
STRAP
90-2013
2
LOCATION CONSIDERATIONS
FOR PROPER
ELECTRICAL SERVICE ACCESS THIS SIDE
• Allow sufficient clearance for filter removal and
to prevent airflow obstruction
• Electrical service access will require the removal
of the side panel shown� Allow sufficient space
for service on this side of the unit�
FIGURE 2 – FILTER ACCESS CLEARANCE
6" MINIMUM
CLEARANCE
AIR FLOW
6 FT. POWER CORD
TOP VIEW
FILTER
MINIMUM
20"
CLEARANCE
FOR FILTER
(EITHER SIDE)
90-2020
DRAIN INSTALLATION
The drain outlet on the dehumidifier can be hard piped using a 3/4" PVC Slip x 3/4" MNPT fitting and 3/4" nominal drain tubing or the provided 3/4"
MNPT x 3/4" hose barb fitting and 3/4" clear PVC tubing can be used to drain the dehumidifier� Always maintain a constant downward slope from the
dehumidifier to the drain and do not allow soft tubing to curl up which may result in air lock� Note: PTFE thread seal tape is recommended for the
threaded connection and hand tighten only� If hard pipe is used, PVC primer and cement is recommended for the slip fit connection�
A level surface is required to ensure proper drainage from the dehumidifier�
Always install the dehumidifier in a condensate pan when locating in or above a finished space� Adhere to local codes regarding draining of the
condensate pan�
CONDENSATE PUMP AND FLOAT SWITCH
If a condensate pump is needed, install it in the condensate pan if
installed�
Install a condensate overflow safety switch (i�e� float switch) in the
condensate pan, remove the factory installed jumper wire between
the Float Switch terminals on the control and wire the float switch to
the dehumidifier as shown in FIGURE 3� Overflow safety switches on
condensate pumps can be wired to the Float Switch terminals in a
similar fashion�
FIGURE 3 – FLOAT SWITCH WIRING
DH DH
FLOAT
Switch
NORMALLY CLOSED
FLOAT SWITCH
90-1857
3
SETTING THE DESIRED HUMIDITY LEVEL
ON/OFF
SWITCH
1. Plug in dehumidifier and turn on/off switch ON� See FIGURE 4�
2. Press the ON/OFF button to turn the dehumidifier control ON� The display will show the
current setting, and the dehumidifier blower will turn on to start sampling the air�
3. The and buttons allow the humidity level to be set from 40% to 80% relative
humidity� Use the ON/OFF button to turn the dehumidifier ON or OFF�
Set the control at 55%RH when first installed� Allow the dehumidifier to run until it reaches
the setting before deciding if you want to change the setting� See FIGURE 5�
• If you prefer the air to be more dry, decrease the humidity setting�
• If you prefer the air to be less dry, increase the humidity setting�
4. After three (3) minutes of sampling, the measured humidity will be compared to the setting:
a. If the humidity is above the setting, the dehumidifier compressor turns on and “AIR
SAMPLING” will be replaced by “DEHUMIDIFYING”� The compressor remains on until the
measured humidity falls 3% RH below the setting� See FIGURE 6�
b. If the measured humidity is below the setting, the blowers turn off and the display
returns to showing the RH setting�
5. The dehumidifier will sample again every 60 minutes, or at any time if the humidity setting
is lowered�
Your comfort is the best measure of how to adjust your setting� When first installed, your
dehumidifier has to remove all the moisture that is initially in your home� The home acts like
a sponge so the moisture in the materials of your home is at the same level as the air� After
drying the air, the materials of the home will release moisture back into the air until they are
again at the same level� As a result, it is not uncommon for the dehumidifier to operate for an
extended period when first installed�
FIGURE 4 – ON/OFF SWITCH
90-1908
FIGURE 5
Your dehumidifier is equipped with two features that protect against unwanted energy
consumption� Defrost is a normal operating mode that helps to prevent significant ice formation
on the refrigeration system coil� The dehumidifier display will show “DEFROSTING” when
operating in this mode� This mode can occur when there is not enough air moving through the
dehumidifier or if the temperature and/or humidity of the incoming air is too low� The second
protection feature is the E8 code� E8 on the dehumidifier display indicates that the air entering
the dehumidifier is below 50°F or above 104°F, or the dew point of the incoming air is below
40°F� There would be a significant reduction in dehumidifier efficiency if the dehumidifier
operated outside of these conditions� Low dew point conditions can be seen in some basements
or crawl spaces and usually occur in the Winter and Spring months� The dehumidifier continues
to monitor the incoming air and when the conditions are within the operating range, E8 will be
removed from the display and dehumidification will begin as needed�
ENERGY SAVINGS TIPS
Energy Savings Tip #1: Adjust the humidity setting to be as high as is comfortable to
reduce dehumidifier run time� If it feels clammy or “smells musty”, lower the humidity
setting� To save energy, turn the dehumidifier to OFF when you open your windows, just as
you would with air conditioning�
Energy Savings Tip #2: If vacating your home for an extended period in the summer, set
the RH at 55% and set your thermostat as high as you are comfortable setting it to in the
cooling mode� Consult with appropriate professionals regarding the highest temperature
that is safe for your pets or possessions� This will keep the humidity at a controlled level
while minimizing the amount of cooling energy used�
90-1853
FIGURE 6
90-1853
4
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.