Model 1610 Easy Install™ Media Air Cleaner
Installation Instructions
WARNING
1. High voltage may cause serious
injury from electrical shock.
Disconnect power to the
furnace/air handler before
starting installation.
2. Sharp edges may cause injury
from cuts. Use care when cutting
and handling sheet metal.
1. To prevent component failure, do not install the air cleaner on the warm
air supply or in an area where the temperature may exceed 140°F. This
may include areas above heat exchangers in downflow furnaces or above
exhaust flues in lowboy furnace cold air returns.
2. Installation must be done by a qualified heating and air conditioning
professional. Read instructions thoroughly before beginning installation.
3. Do not install air cleaner downstream of a UV light. UV lamps will cause
degradation of the filtering media.
SPECIFICATIONS
Airflow Capacity: up to 2000 CFM maximum
Replacement Media: Model 410 or 413 with SelfSeal
™
Air Cleaner Operating Environment: Temperature: 0°F – 140°F
DIMENSIONS
CAUTION
FIGURE 1 – Air Cleaner Dimensions
15.7”
17.8”
30.1”
15.5”
10-11479
LOCATING THE AIR CLEANER
1. The air cleaner can be mounted on the right or left side of the HVAC equipment (see Figure 2).
2. The door can be facing the front or rear of the HVAC equipment cabinet (see Figure 2).
3. The door and blanking plate are reversible to allow filter access from the front or rear of the HVAC equipment cabinet
(see Figure 2).
4. Leave sufficient space (29”) for the removal of the filtering media (see Figure 3).
FIGURE 2
The door and blanking
panel are reversible to
allow filter access from
the front or back.
BLANKING
PLATE
10-11481
FIGURE 3
10-11483
29” FOR FILTER
REPLACEMENT
DOOR
EASY TO INSTALL AIR CLEANER FEATURES
The air cleaner has many features to make retrofit easier:
1. The cold air return opening is adjustable between 8” and 10”. This is done by bending up the appropriate tabs. The 8” dimension
can be offset to the right or left by moving the “L” bracket to either side to match up with the location of the return drop.
FIGURE 4 – 8” x 24” OFFSET RIGHT FIGURE 5 – 8” x 24” OFFSET LEFT
BEND UP T
10-11490
2
ABS
L BRACKET
10-11490