Smart-UPS® VT and
XR Battery Enclosure
10-30 kVA
208/220 V
Operation Manual
Smart-UPS® VT and XR Battery
Enclosure10-30 kVA 208/220 V
Operation Manual
IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS
This manual contains important instructions for the SUVT series that should be
followed during installation and maintenance of the UPS and Batteries
S m ar t- U P S ® VT an d XR Bat t e ry E n cl o s ur e 10 - 3 0k VA , 20 8V O p e r a t i o n G u i d e – 99 0 - 15 99 1
Contents
Safety ......................................................................1
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . 1
Symbols used in this guide . . . . . . . . . . . . . . . . . . . . . . . . . 1
Environmental symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
General safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Operation ................................................................3
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
The Smart-UPS VT Family Range . . . . . . . . . . . . . . . . . . . . . . . . 4
13.85 in/352 mm Enclosures . . . . . . . . . . . . . . . . . . . . . . . . 4
20.59 in/523 mm Enclosures . . . . . . . . . . . . . . . . . . . . . . . . 4
Serial number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Type label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Operation Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Normal operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Battery operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Bypass operation (or static bypass operation) utility . . . . . . . . 6
Mechanical bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wrap-around maintenance bypass . . . . . . . . . . . . . . . . . . . . 7
The Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Menu-driven user functions . . . . . . . . . . . . . . . . . . . . . . . . . 9
Basic display navigation principles . . . . . . . . . . . . . . . . . . . 10
Control functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Status views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Clock set-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Alarm threshold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Display setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Diagnostics screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual i
Display Messages/Troubleshooting . . . . . . . . . . . . . . . . . . . . . 17
Display messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Front Panel Removal/Installation . . . . . . . . . . . . . . . . . . . . . . . 20
Front Panel removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Total-Power-Off Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Restart Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Power application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Voltage confirmation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Mechanical Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Mechanical Bypass Lever . . . . . . . . . . . . . . . . . . . . . . . . . 25
Turn into mechanical bypass . . . . . . . . . . . . . . . . . . . . . . . 25
Switch into normal operation (from mechanical
bypass operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Network Management Card with Environmental Monitor . . . . . 27
Network Management Card replacement . . . . . . . . . . . . . . 27
Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
General safety prior to module replacement . . . . . . . . . . . . 28
Battery Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Removal and installation of Battery Locks (if applicable) . . . . 29
Battery Module removal . . . . . . . . . . . . . . . . . . . . . . . . . . 30
How to install a Battery Module . . . . . . . . . . . . . . . . . . . . 30
How to Obtain Replacement Parts . . . . . . . . . . . . . . . . . . . . . . 32
Orderable parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Maintenance Bypass Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Operation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
ii Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Warranty ...............................................................34
LIMITED FACTORY WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . 34
APC product covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Terms of warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Non-transferable warranty extends to first purchaser for use . 34
Assignment of warranties . . . . . . . . . . . . . . . . . . . . . . . . . 35
Drawings, descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Warranty claims procedure . . . . . . . . . . . . . . . . . . . . . . . . 35
Exclusions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Appendix ...............................................................37
UPS Components and Options. . . . . . . . . . . . . . . . . . . . . . . . . 37
13.85 in/352 mm Enclosures . . . . . . . . . . . . . . . . . . . . . . . 37
20.59 in/523 mm Enclosures . . . . . . . . . . . . . . . . . . . . . . . 37
System sizes, part nos., number of Battery Modules and
weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Part number coding: . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Battery Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
User interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Foot print . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
APC Network Management Card AP9619 (installed in UPS) and
APC Humidity Sensor (Optional) . . . . . . . . . . . . . . . . . . . . 43
Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Battery Securing Bracket and Floor Anchoring . . . . . . . . . . . 44
Extended Run Battery Enclosure (XR Battery Enclosure) . . . . . 45
Part numbers for XR Battery Enclosures . . . . . . . . . . . . . . . . 46
Part number for Battery Module . . . . . . . . . . . . . . . . . . . . . 46
Maintenance Bypass Panels with Power Distribution Capability 47
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual iii
Safety
IMPORTANT SAFETY INSTRUCTIONS
This guide contains important instructions that should be followed when handling the UPS, Battery
Enclosures, and Batteries.
Symbols used in this guide
WARNING!
Risk of electric shock.
CAUTION!
Read this information to avoid equipment damage.
Indicates important information.
Note
Indicates that more information is available on this subject in a different section of this
manual.
Indicates that more information is available on the same subject in a different manual.
Environmental symbols
Temperature Ventilation
Humidity Dust/Fumes Altitude
requirements
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 1
Safety – IMPORTANT SAFETY INSTRUCTIONS
General safety
Two people to lift components weighing between 40 - 70 lbs / 18 - 32 kg.
Indicates that a switch or current protection device is in the ON position.
Indicates that a switch or a breaker is in the OFF position.
WARNING!
Hazardous electrically-charged parts inside the UPS are energized from the battery supply
even when the AC power is disconnected. Follow Total-Power-Off Procedure to
completely de-energize the system.
For configurations including customer-supplied external batteries, refer to manufacturer’s
battery installation and maintenance instructions.
Note
2 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Operation
Introduction
Welcome to the Operation Manual covering the Smart-UPS® VT UPS and the Extended Run Battery
Enclosure (XR Battery Enclosure). This manual provides you with a detailed description of restart,
operation, and troubleshooting.
Separate manuals are available on:
• Receiving and Unpacking part no. 990-1747.
• Site preparation and Installation part no. 990-1598.
For documentation on Maintenance Bypass Panels with/without Power Distribution Unit,
see product-specific manuals.
For more details on APC products and services, visit us at www.apc.com
Note
Note
Note
WARNING!
Only trained person familiar with the construction and operation of the equipment,
including the electrical and mechanical hazards involved, may install and remove
system components.
Details on the UPS sizes, runtime, weight etc. are available in the Appendix under
“System sizes, part nos., number of Battery Modules and weights” on page 38
Most illustrations show 20.59in/523mm Enclosures but apply to both Enclosure sizes.
Any differences between the two Enclosure sizes will be addressed in the manual.
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 3
The Smart-UPS VT Family Range
13.85 in/352 mm Enclosures
H
o
t
l
i
n
e
i
n
U
S
H
/
C
o
a
t
l
n
i
n
a
e
d
a
i
n
/
L
E
A
W
M
M
o
E
:
U
r
A
l
+
n
d
:
1
i
w
t
S
8
+
i
d
e
0
3
e
r
0
5
i
a
3
S
8
l
u
0
9
N
0
p
1
o
p
4
7
o
A
0
r
P
t
2
C
0
n
0
u
0
m
b
A
e
P
r
C
s
:
S
K
w
U
w
w
.
a
p
c
c
.
c
o
m
/
s
u
p
M
p
o
o
d
r
e
t
l
/
s
e
r
v
S
i
c
U
e
V
/
T
g
F
e
1
o
0
m
K
S
B
a
U
2
p
V
F
B
_
T
a
w
1
t
0
t
o
e
K
r
r
F
l
y
d
1
C
.
B
A
d
a
2
P
f
p
S
m
C
a
c
S
i
m
t
y
a
r
t
U
P
@
S
S
U
–
w
V
V
1
/
1
T
A
T
9
2
B
1
1
p
V
0
0
a
p
K
k
t
a
D
t
V
.
F
r
C
A
e
M
2
n
B
2
o
t
2
0
d
/
S
8
u
A
V
l
e
P
E
C
x
R
S
p
a
.
m
A
t
t
e
o
a
c
d
r
t
2
t
i
S
-
I
v
n
U
e
U
p
P
V
P
u
S
T
o
t
1
V
w
C
0
T
u
e
K
r
r
w
1
7
F
r
0
e
/
.
1
2
2
k
n
B
A
V
B
t
4
h
A
a
S
t
R
2
t
S
.
A
0
a
U
M
8
P
t
e
V
V
C
o
d
T
d
S
u
F
O
m
l
1
e
u
0
s
a
t
K
p
r
S
t
u
B
-
U
U
t
4
V
P
C
F
T
S
u
1
w
r
0
V
r
/
K
e
1
T
n
F
B
1
t
2
0
a
B
k
t
1
B
t
4
V
.
4
S
a
A
M
.
t
4
t
2
o
A
e
A
0
d
r
h
8
u
y
P
V
l
C
e
C
u
E
S
r
x
m
r
p
e
a
S
.
n
r
t
U
t
t
o
-
V
U
4
T
P
1
S
w
0
K
V
/
2
F
T
B
3
1
B
a
0
t
4
7
k
t
.
S
.
V
2
M
A
A
o
h
2
d
A
0
u
8
P
l
e
V
C
s
S
E
m
x
S
p
a
U
.
r
V
t
t
-
o
U
T
4
1
P
0
S
w
K
V
F
/
3
1
T
4
0
B
B
1
k
1
a
4
0
V
4
t
S
k
A
t
.
.
4
V
S
/
M
8
A
A
U
A
k
h
o
2
W
V
P
d
0
T
C
u
8
F
l
e
V
S
1
s
m
5
E
K
a
x
B
r
p
t
2
.
U
F
t
o
P
S
4
2
V
7
T
.
1
w
1
A
0
2
S
/
4
k
1
U
V
.
B
6
V
A
a
A
T
t
2
h
t
1
.
0
5
M
8
2
K
V
0
o
F
8
d
2
V
u
B
l
e
2
s
S
A
2
P
7
C
.
8
S
A
m
a
r
2
t
8
-
U
.
8
P
A
2
S
h
0
V
8
T
V
w
1
5
/
2
k
S
V
B
U
A
a
V
S
t
2
t
T
.
U
0
2
1
M
8
8
V
5
V
.
o
T
9
K
d
F
A
F
u
1
2
l
5
e
B
K
s
4
B
S
A
4
P
F
C
S
m
a
r
t
-
1
U
S
4
U
P
.
4
S
V
w
A
T
V
/
h
1
2
T
5
B
K
1
a
5
F
t
k
t
3
.
V
B
M
A
4
A
o
S
2
P
d
0
C
u
8
l
e
V
S
s
m
E
a
x
r
p
t
.
U
t
S
o
P
U
S
4
w
V
V
/
T
3
T
1
B
5
1
a
K
5
t
F
k
t
.
V
4
M
B
A
1
o
4
2
4
d
S
A
0
.
u
4
8
P
l
A
e
V
C
h
s
S
E
m
x
p
a
.
r
t
t
-
o
U
4
P
S
V
S
T
U
w
1
V
5
S
/
4
k
T
U
V
2
B
V
2
A
0
a
1
T
K
t
2
.
t
F
6
F
.
0
1
2
A
M
2
8
5
0
A
B
h
V
k
o
K
P
V
4
d
B
A
C
S
u
4
/
l
1
e
S
F
2
s
m
k
a
W
r
t
-
U
P
S
S
w
4
U
V
/
0
2
V
T
.
6
T
B
A
2
2
a
0
2
0
t
k
8
t
K
.
V
.
8
F
M
A
A
A
3
o
2
B
h
P
d
0
4
C
u
8
2
S
l
e
V
0
S
s
8
m
V
E
a
x
r
p
t
-
.
U
t
o
P
4
S
1
4
w
S
.
6
V
/
U
3
A
T
V
B
2
T
a
0
2
t
1
k
t
0
.
4
V
K
M
.
A
4
F
o
A
4
2
2
d
A
B
h
0
0
u
8
P
4
8
l
e
V
S
V
C
s
S
S
E
U
m
x
V
p
a
T
.
r
t
F
t
-
o
U
3
4
0
4
P
K
3
S
S
.
B
U
3
V
4
A
V
T
F
T
w
2
3
2
0
0
/
4
1
k
K
.
V
B
6
F
A
A
a
3
t
B
h
2
t
.
0
4
M
8
S
V
o
A
d
u
P
l
C
e
s
S
m
a
S
r
t
U
-
U
V
2
P
T
0
S
k
3
w
2
V
0
V
8
/
A
K
3
.
T
/
8
F
1
B
A
3
4
6
a
0
B
h
k
t
k
t
4
W
.
V
S
M
A
o
2
d
A
0
u
8
P
l
5
e
V
C
4
s
.
S
2
E
A
m
x
p
a
.
r
V
t
t
-
o
o
U
l
4
t
P
a
S
g
2
e
V
0
&
T
8
5
V
w
3
C
5
2
0
.
/
o
5
4
1
k
n
A
.
V
A
B
6
n
A
C
A
a
e
t
h
2
c
t
I
.
0
n
t
i
M
8
p
o
V
u
n
o
d
t
2
T
u
0
y
l
e
8
p
s
V
e
s
2
0
8
Y
/
1
2
2
8
0
.
8
V
3
A
0
5
4
h
k
7
W
V
A
.
A
7
+
C
A
/
G
2
O
4
N
k
u
D
W
t
p
6
u
0
t
H
z
8
1
.
3
A
2
0
8
D
Y
C
/
1
B
2
I
n
a
0
2
p
t
V
0
t
u
D
e
8
4
t
r
a
V
W
i
t
e
e
s
+
G
N
8
D
3
.
6
3
i
0
A
n
H
s
D
t
z
a
a
l
t
l
e
e
d
f
+
o
/
2
r
0
1
1
8
.
9
V
2
R
V
e
p
l
D
a
c
a
e
t
e
m
8
f
6
S
e
o
.
n
r
6
E
t
A
2
E
.
R
I
N
e
p
S
l
a
T
c
A
e
m
L
L
e
n
A
B
t
T
E
I
O
F
O
N
R
I
N
E
S
C
T
O
R
N
U
N
S
C
U
E
T
C
P
I
O
P
T
N
I
L
N
Y
S
G
T
O
T
H
T
E
H
I
S
R
E
A
R
C
O
P
V
L
E
A
R
C
E
M
D
U
O
S
T
N
B
U
E
P
S
8
8
5
-
2
3
2
1
C
_
r
e
v
0
4
Front Rear Front without front panel
!
Out
put
Pw
r
Z
one
P
rob
e
10/100
Ba
s
e-
T
R
e
s
e
t
A
10
P
9
/100
6
1
9
N
e
t
w
o
r
k
M
a
n
a
g
e
m
e
n
t
C
a
r
d
E
M
Se
ria
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
ria
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
S
e
r
ia
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
er
ial
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
er
ial
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
Se
ria
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
Se
ri
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
ia
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
10-15 kVA
20.59 in/523 mm Enclosures
H
o
t
li
n
e
i
n
U
H
S
o
/
C
t
l
a
in
n
e
a
d
i
n
a
/
W
E
L
U
M
A
o
n
E
r
M
it
l
A
d
S
:
w
:
e
+
r
i
ia
1
d
+
e
l
3
8
N
5
0
S
o
3
0
u
p
9
8
1
0
p
0
o
7
r
0
4
t
A
2
n
P
0
u
0
C
m
A
0
P
b
C
e
S
r
s
K
:
U
w
w
w
.
a
p
c
c
.c
o
m
/s
M
u
o
p
d
p
S
e
o
U
l
r
V
t
T
/s
F
e
1
r
0
v
K
i
c
B
S
e
2
U
/
F
g
V
e
T
o
10
m
K
a
F1
B
a
B
tte
A
2
P
S
ry
C
C
S
a
m
p
ar
a
c
t-U
S
ity
U
P
V
w
S
T
/
V
1
@
1 B
0
T
K
–
1
1
a
F2
tt. M
0
9
kV
B
2
2S
V
A
o
D
20
A
du
C
P
le
8V
C
E
S
xp
m
S
a
. to
U
r
t-U
V
2
T
P
10
S
K
V
F1
T
w
1
B
S
/2
0
4S
U
B
kV
V
7
a
T
.2
A
A
tt.
F
P
2
A
1
C
M
h
0
0K
S
8
o
V
du
B
m
S
4
U
a
le
F
r
V
s
t-U
T
1
P
0
w
S
K
/1
V
F2
B
T
B
10
a
4S
tt.
kV
M
A
A
1
o
P
2
4
d
C
.4
u
0
le
S
8
A
V
S
E
h
m
U
xp
a
V
rt-U
T
. to
10
P
4
w
K
S
/
F3
V
2
B
B
T
att.
4S
1
0
M
k
V
A
A
o
7
P
du
.2
2
C
0
A
le
8
h
S
S
s
V
U
m
E
V
a
x
T
r
p.
t-U
10
to
P
K
w
4
S
F4
/3
V
B
S
B
T
4
U
a
1
S
V
tt. M
0
T
kV
F
1
1
A
4
A
o
5K
.
P
du
2
4A
C
0
B
le
h
8
2
S
s E
V
F
m
a
x
rt-U
p
.
to
P
4
S
S
V
U
T
w
V
1
/
T
4
0
15
B
kV
2
1
at
K
A
.6
F
t. M
2
A
2
0
B
h
8
o
2
V
d
S
u
le
A
s
P
C
S
m
a
rt
-U
2
P
8
.8
S
V
A
S
S
h
T
w
U
U
1
/2
V
V
5
T
B
T
kV
15
F
a
1
A
tt
K
5
2
.
F2
M
K
0
B
8
od
B
4
V
4
F
u
S
le
s
S
A
U
P
V
C
T
S
15
1
m
4
K
a
.
F3
4A
rt
-U
B
h
4
P
w
S
S
/
V
2
B
T
a
1
tt.
5
M
kV
A
S
P
U
A
o
C
d
2
V
u
T
S
0
le
15
8V
m
s
a
E
K
r
F4
t-
xp
U
B
.
P
to
w
4
S
S
/3
4
V
B
T
1
a
15
4
tt.
.4
M
k
A
V
h
A
A
od
P
20
u
C
les
8
S
S
S
V
m
E
U
U
ar
V
x
V
p
T
TF
t-
.
2
U
to 4
0
2
P
K
0
S
F
K
V
2
B
B
2
T
4
w
4
1
F
1
/4
S
.6A
5
B
k
V
h
a
A
tt.
2
A
M
P
0
S
8
C
o
V
U
d
S
u
V
m
le
T
a
s
2
rt-U
0
K
F
P
3
w
S
B
28
/
V
2
4
B
S
.8
T
att.
2
A
h
0
M
k
A
V
P
A
o
C
du
2
S
U
S
0
le
8
m
V
s
V
T
a
E
2
rt-U
x
0
p.
K
P
F
to
w
4
S
/3
B
S
4
V
1
4
U
4
B
T
S
.4
V
a
20
T
A
tt.
F
h
M
k
3
V
0
A
A
o
K
P
du
2
B
S
C
0
4
le
U
8
F
S
s
V
V
m
E
T
a
3
x
r
0
p.
t-U
K
to
F3
P
4
S
B
2
V
4
1
S
.6
T
w
2
A
/4
h
0
B
kV
a
A
tt.
2
SU
M
0
A
8
V
o
P
V
d
T
C
u
3
S
le
0
K
s
m
F
a
4B
rt-U
2
4
8
S
.
P
8
w
S
A
/3
V
h
B
T
a
3
tt.
0
V
M
k
V
o
A
A
o
lta
P
d
2
u
C
0
g
le
S
8
e
s
V
m
&
E
C
ar
x
A
p
t-U
o
C
.
n
to 4
In
n
P
ec
S
p
2
V
u
1
t
io
t
.6
T
w
n
3
A
/4
T
h
0
B
k
y
V
p
a
2
A
e
tt.
0
2
s
8
M
Y
0
8
/1
o
V
du
2
0
le
V
s
4
W
+
2
G
8
A
.
N
C
8
A
D
O
h
6
u
0
t
H
p
u
z
t
20
8
Y
/1
D
2
C
0
V
In
4
p
B
W
u
a
D
+
t
t
G
te
a
te
N
ri
D
es
6
0
H
in
z
s
ta
D
lled
a
+
te
/-
1
fo
9
r
2
V
1
.
R
e
p
la
c
e
m
en
t
Front
!
O
u
t
p
u
t
P
w
r
Z
o
n
e
P
r
o
b
e
1
Re
0
/
1
se
0
0
t
B
a
s
e
T
A
P
96
1
0
19
/
1
0
N
0
etw
o
rk
M
an
a
gem
en
t
C
ard
E
M
!
O
u
t
p
u
t
P
w
r
Z
o
n
e
P
r
o
b
e
1
R
0
/
e
1
s
0
e
0
t
B
a
s
e
T
AP9
1
6
0
1
/
1
9 N
0
0
e
tw
o
rk
M
an
ag
em
e
nt C
ard
EM
Blind
plates
cover
empty
battery
bays
p
_
w
o
r
l
d
.
d
fm
A
p
p
a
r
en
t/
R
A
a
c
te
tiv
d
e
In
P
p
o
u
w
t C
e
r
u
r
re
n
t
R
a
ted
O
u
t
p
u
t
C
u
rr
e
n
t
B
a
tt
e
r
y
C
u
rr
e
n
t
1
0
kV
A
/8k
W
2
7
.1
A
2
0
8
V
2
7
.8
A
2
0
8
V
2
8
.9
A
1
5
k
V
A
/1
2
kW
4
0
.
6
A
2
0
8
V
4
1
.6
A
2
0
8
V
4
3
.3
A
20
kV
A
/1
6
k
W
5
4
.2
A
2
0
8
V
55
.5
A
2
08
V
3
0
k
V
A
/2
4
5
kW
7
.7
A
8
1
.3A
2
0
8
V
8
3
.3
A
2
0
8
D
V
a
te
fo
r 2
S
E
.
R
8
E
e
6
p
.6
I
la
N
A
c
S
e
m
T
A
e
n
L
t
L
B
A
E
T
F
I
O
O
R
N
E
I
N
C
S
O
T
S
N
R
U
N
U
P
E
C
P
C
T
L
T
I
Y
O
I
N
N
G
S
T
O
T
T
H
H
I
S
E
R
E
A
R
C
P
O
L
A
V
E
C
R
E
D
M
O
U
N
S
T
U
B
P
E
S
8
8
5
-23
2
1
C
_
re
v
0
4
Rear
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
ia
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
ia
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
Front without
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
S
e
r
i
a
l
:
M
o
d
e
l
:
BA
TT
ER
Y
U
N
IT
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
TE
R
Y
U
N
IT
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
TE
R
Y
U
N
IT
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
TE
R
Y
U
N
IT
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
TT
ER
Y
U
N
IT
S
e
r
ia
l
:
M
o
d
e
l:
B
A
T
T
E
R
Y
U
N
IT
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
TT
E
RY
U
N
IT
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
TT
ER
Y
U
N
IT
S
e
ri
a
l
:
M
o
d
e
l:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
AT
TE
R
Y
U
NIT
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
TT
E
RY
U
N
IT
S
e
r
ia
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
front panel 10-15 kVA
Front without
front panel 20-30 kVA
4 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Operation – The Smart-UPS VT Family Range
Serial number
The serial number is available on the type label on the rear side of the UPS.
Type label
Hotline in US/Canada/LAM: +1 800 800 4APC
Hotline in EMEA: +353 91 70 2000
Worldwide Support numbers: www.apcc.com/support/service/geomap_world.dfm
Unit Serial No
SUVTF10KB2F
SUVTF10KB4F
SUVTF15KB2F
APC SKU
SUVT10KF1B2S
SUVT10KF2B2S
SUVT10KF1B4S
SUVT10KF2B4S
SUVT10KF3B4S
SUVT10KF4B4S
SUVT15KF2B2S
Model
APC Smart-UPS VT 10kVA 208V
w/1 Batt. Module Exp. to 2
APC Smart-UPS VT 10kVA 208V
w/2 Batt. Modules
APC Smart-UPS VT 10kVA 208V
w/1 Batt. Module Exp. to 4
APC Smart-UPS VT 10kVA 208V
w/2 Batt. Modules Exp. to 4
APC Smart-UPS VT 10kVA 208V
w/3 Batt. Modules Exp. to 4
APC Smart-UPS VT 10kVA 208V
w/4 Batt. Modules
APC Smart-UPS VT 15kVA 208V
w/2 Batt. Modules
Battery Capacity
@– 192V DC
7.2Ah
14.4Ah
7.2Ah
14.4Ah
21.6Ah
28.8Ah
14.4Ah
Apparent/
Active Power
10kVA/8kW
Rated Input Current
27.1A
208V
Rated Output Current
27.8A
208V
Battery Current
28.9A
SUVT15KF2B4S
SUVTF15KB4F
SUVTF20KB4F
SUVTF30KB4F
Voltage & Connection Types
AC Input
208Y/120V 4W+GND 60Hz
SUVT15KF3B4S
SUVT15KF4B4S
SUVT20KF2B4S
SUVT20KF3B4S
SUVT20KF4B4S
SUVT30KF3B4S
SUVT30KF4B4S
AC Output
208Y/120V 4W+GND 60Hz
APC Smart-UPS VT 15kVA 208V
w/2 Batt. Modules Exp. to 4
APC Smart-UPS VT 15kVA 208V
w/3 Batt. Modules Exp. to 4
APC Smart-UPS VT 15kVA 208V
w/4 Batt. Modules
APC Smart-UPS VT 20kVA 208V
w/2 Batt. Modules Exp. to 4
APC Smart-UPS VT 20kVA 208V
w/3 Batt. Modules Exp. to 4
APC Smart-UPS VT 20kVA 208V
w/4 Batt. Modules
APC Smart-UPS VT 30kVA 208V
w/3 Batt. Modules Exp. to 4
APC Smart-UPS VT 30kVA 208V
w/4 Batt. Modules
DC Input
+/- 192V
Date
installed
14.4Ah
21.6Ah
28.8Ah
14.4Ah
21.6Ah
28.8Ah
21.6Ah
28.8Ah
Batteries
Date for 1.
Replacement
15kVA/12kW
20kVA/16kW
30kVA/24kW
Date for 2.
Replacement
40.6A
208V
54.2A
208V
81.3A
208V
41.6A
208V
55.5A
208V
83.3A
208V
SEE INSTALLATION INSTRUCTIONS
BEFORE CONNECTING TO THE
SUPPLY
THIS REAR COVER MUST BE
PLACED ON UPS
885-2321C_rev04
43.3A
57.7A
86.6A
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 5
Operation Modes
In a stand-alone installation, the UPS has four different operating modes. If the installation includes a
Maintenance Bypass Panel, bypass mode and test mode will also be available.
Normal operation
During normal operation, the UPS converts utility power to conditioned power for the connected
load.
Battery operation
During battery operation, the UPS provides power to the connected load from its internal and (if
applicable) external batteries for a finite period. The UPS transfers to battery operation if the supply
of utility power fails, or is outside pre-defined limits.
Bypass operation (or static bypass operation) utility
Static bypass operation can either be obtained by user request or automatically, as the UPS will
switch into bypass operation if both the normal and battery operation modes are unavailable. During
static bypass operation, the utility power is sent through internal Radio Frequency Interference (RFI)
filters to the connected load, bypassing the internal power converters. The UPS transfers to bypass
operation following a command received via the user display, or after a short or heavy overload on
the output of the UPS. Battery back-up is not available in bypass operation.
Mechanical bypass
In mechanical bypass, utility power is sent directly to the connected load through a mechanical
breaker, bypassing all internal UPS functions and filters. Mechanical bypass is obtained by the
operation of the mechanical bypass breaker lever located behind the front cover. Mechanical bypass
is a feature designed to keep the load supplied with utility power at maintenance of the power
sections of the UPS. All major maintenance operations can be performed with the UPS running in
mechanical bypass, and with the load being supplied directly with unconditioned utility power.
6 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Operation – Operation Modes
Wrap-around maintenance bypass
The UPS can be connected to an external Maintenance Bypass Panel. When activated, this panel
bypasses the entire UPS Enclosure (only possible with an optional APC Maintenance Bypass Panel),
feeding utility power directly to the load. An activated wrap-around Maintenance Bypass Panel
completely isolates the UPS and allows maintenance to be performed - including a replacement of the
entire UPS.
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 7
The Display
Introduction
CAUTION!
The display provides access to more functions than described in this manual. Those
functions should not be accessed without the assistance of APC Customer Support in
order to avoid unwanted load impacts. For APC World-wide Customer Support, refer to
rear cover of this manual.
Four Light Emitting Diode (LED)
indicators report the operational
status of the UPS.
Liquid Crystal
Display (LCD)
Screen
Five navigation keys are used to select
and open menu items, to access
information, change system parameters,
and to launch context-sensitive help.
LOAD ON
Chrg 100%
ON BATT
Load 000%
120Vin 000Vout 60Hz
BYPASS
Runtime: 00hr 30m
FAULT
ESC
?
LOAD ON
ON BATT When the yellow LED is on, power to the load flows from the batteries to the
BYPASS When the yellow LED is on, power to the load is supplied through the static
FAULT When the red LED is on, a fault condition exists.
LCD Screen Displays alarms, status data, instructional help, and configuration items.
UP and DOWN
navigation keys
HELP key Launches context-sensitive help.
ENTER key Opens menu items and input changes to system parameters.
ESC key Returns to previous screen displayed.
When the green LED is on, the UPS provides power to the load equipment.
Power Module.
bypass switch or mechanical bypass.
Selects menu items and accesses information.
8 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Navigation
Menu-driven user functions
If you get beyond the functions described in the menu tree, do not proceed. Press ESC to go back.
Control
Turn load off
UPS into
bypass
Status
Vin Vbyp Vout
Iin lbyp Iout
kVA & kW
Frequencies
Overview
Chrg xxx%
Load xxx%
xxxVin
Runtime
Main Menu
Control
Stat us
Setup
Logging
Display
Diags
Help
Setup
Logging
Display
Diags
Load & Bat
Settings
Logging
Display setup
Diagnostics
Batteries
Alarm
thresholds
Clock
Alarms
Beeper setup
Contrast
Language
View log
View statistics
Faults and
Diagnostics
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 9
Operation – Navigation
Basic display navigation principles
On the display, press ESC until you get to the Overview Screen, which provides you with basic
system status information.
Press UP, DOWN arrows to navigate the selector arrow and view all sub-menu screens.
Chrg 100%
Load 000%
120Vin 000Vout 60Hz
Runtime: 0hr 0m
Overview Screen
Press ENTER to open the Main Menu screen. From here, you command, configure, and monitor the
system.
Control
Status
Setup
Main Menu
Logging
Display
Diags
Help
Control functions
From the Control screen on the Main Menu, you can select the following functions:
• Switch Load OFF/ON
• Switch the UPS into Bypass/out of Bypass
Control
Status
Setup
Main Menu
Logging
Display
Diags
Help
WARNING!
Disconnecting the UPS output to the load, does NOT de-energize the UPS! Always
follow the Total-Power-OFF procedure if you need to de-energize the UPS in
emergency situations!
Switch load OFF (disconnect the UPS output to the load equipment):
• From the Main Menu, select Control and press ENTER
• Use UP/DOWN key to navigate to Turn Load Off , and press ENTER
• Select YES , Turn Load Off
10 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Switch load ON:
• From the Main Menu, select Control and press ENTER
• Use UP/DOWN key to navigate to Turn Load On , and press ENTER
• Select YES, Turn Load On
Switch into bypass:
• From the Main Menu, select Control and press ENTER
• Use UP/DOWN key to navigate to UPS into Bypass and press ENTER
• Use UP/DOWN key to navigate to YES, UPS into bypass , and press ENTER
Switch out of bypass:
• From the Main Menu, select Control and press ENTER
• Select UPS out of Bypass and press ENTER
Operation – Navigation
• Use UP/DOWN key to navigate to YES, UPS out of Byp, and press ENTER
Status views
Select Status on the Main Menu to view the status on the following parameters
Control
Status
Setup
Main Menu
Logging
Display
Diags
Help
Voltage on all phases.
Utility voltage (V), bypass voltage (V), and output voltage (V) for each phase.
Current on all phases.
Utility current (A), bypass current (A), and output current (A) for each phase.
kVA and kW.
Apparent power (kVA) and real power (kW) generated by the UPS to the load.
Frequencies.
Utility frequency, bypass frequency and output frequency in Hertz (Hz).
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 11
Operation – Navigation
Load and batteries.
Load: Percentage of the load in relation to the total UPS capacity.
Bat Voltage: shows either the positive or negative half of the battery voltage (the lower value of the
two will appear).
Bat Cap: Percentage charge on the batteries in relation to the total battery capacity.
Runtime: The predicted runtime at the current load.
Batteries.
Bat AmpHr: Battery capacity, including both external and internal batteries.
UPS Temp: The highest external battery temperature.
Alarm thresholds.
Load: An alarm will be set when the load is above the threshold level.
Runtime: An alarm will be set when the runtime is below the threshold level.
Clock set-up
From the Setup screen on the Main Menu, you can change the date and the clock setting. From the
Settings screen, select Clock, and press ENTER. A date and a time line will appear.
Control
Status
Setup
Main Menu
Time.
Logging
Display
Diags
Help
The clock function is used to time-stamp events in the event log. To avoid inaccuracies, change the
clock-setting at e.g. daylight-saving time.
Date
• To change the date, press ENTER (the day field will become active). Press the UP/DOWN
arrow to select the desired date.
• To change the month and the year , follow the same procedures.
• Press ENTER to confirm the new settings, or ESC to cancel.
Time
• To change the time, press ENTER (the hour field will become active). Press the UP/DOWN
arrow to select the desired time.
• Follow the same procedure to change the minute and the second fields.
• Press ENTER to save, or ESC to cancel.
Press ESC to return to the Main Menu.
12 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Operation – Navigation
Logging
From the logging screen on the Main Menu, you can view the 100 most recent UPS log events, and
view the logged details of the events, such as date and time of occurrence, and event number.
Control
Status
Setup
Main Menu
Logging
Display
Diags
Help
• From the Main Menu, select Logging
• Select Vie w L o g
• Press ESC to return to Main Menu
Example:
24-Sep 15:06:48 #15
Mains out of
On Line
===================
Logging Screen (example)
Range
The top line indicates date, time and event number.
Lines 2, 3 and 4 are part of the event list. To view the entire list, use UP/DOWN arrows to navigate.
For a detailed description of a particular event, position the arrow, and press ENTER.
View Statistics (submenu under Logging).
From the Logging screen on the Main Menu, you can view the statistics on operation mode changes,
inverter time, duration of battery operation.
Control
Status
Setup
Main Menu
Logging
Display
Diags
Help
• From the Main Menu, select Logging
• Select View Statistics
• Press ESC to return to Main Menu
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 13
Operation – Navigation
Alarm threshold
If the load level exceeds the preprogrammed threshold, the UPS will display a warning.
Example:
Alarm Thresholds
Load: 20.0 kVA
Runtime: 0 hr 0 min
Alarm Threshold Screen
To change the Alarm Thresholds,
• Select Setup from the Main Menu
• Select Alarms from the Setup Menu
• Press ESC to return to the Main Menu
Display setup
From the Display setup screen, you can select your display Language, Contrast and Beeper
functions.
Display setup
Language: English
Contrast: 0
Beeper Setup
Display Setup Menu
Language selection.
From the Main Menu, select Display Setup .
To change the language, select Language , and press ENTER. The Language line is now active. Use
the UP/DOWN arrows to select the desired language. Press ENTER to confirm your selection.
Contrast setting.
From the Display Setup Menu, select Contrast.
To change the contrast, select Contrast , and press ENTER. Use the UP/DOWN arrows to select the
contrast level - the lower the number, the darker the contrast. Select ENTER to confirm the setting.
Beeper setup.
Beeper setup
Beep at: PwrFail+30
Vol: Low
Key Click: Off
Beeper Setup Menu
14 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Operation – Navigation
From the Beeper Setup Menu, select Beeper Setup .
To change the beeper setup, select Beep at and press ENTER. You now have the following options:
• Never : If you select this setting, the Beeper will be active at internal UPS errors only.
• PwrFail+30 : If you select this setting, the Beeper will be active at Internal UPS errors and at
main or bypass errors. The Beeper will only sound if the fault has been present for more than 30
seconds.
• PwrFail : If you select this setting, the Beeper will be active at Internal UPS errors and at main
or bypass errors. The Beeper will sound immediately the error is occurring.
• Low Batt: If you select this setting, the Beeper will be active at internal UPS errors and at main
or bypass errors and at power failures and at low battery level (if the UPS runs in battery
operation).
Press ENTER to confirm your setting, or ESC to cancel.
Vo l:
The default setting is low. This setting can be changed to medium, high, or Off. Press ENTER to
confirm your setting, or ESC to cancel.
Key Click:
The default Key Click function is set to Off. Select On if you want to change this setting to On . Press
ENTER to confirm your setting, or ESC to cancel.
Press ESC to return to previous screen.
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 15
Operation – Navigation
Diagnostics screen
From the Diags screen on the Main Menu, you can view the information given on failures for use in
troubleshooting.
Control
Status
Setup
Logging
Display
Diags
Help
Main Menu
• From the Main Menu, select Diags , and press ENTER
• Use UP/DOWN arrow to select Fault and Diagnostics and press ENTER
For more details on Fault and Diagnostics screens, see the Troubleshooting section.
Note
16 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Display Messages/Troubleshooting
This section lists the status and alarm messages that the UPS might display. The messages are listed
in alphabetical order, and a suggested corrective action is listed with each alarm message to help you
troubleshoot problems.
Display messages
Display message Meaning Corrective action
Automatic Self Test
Started.
Batt Temperature
Exceeded Upper Limit.
Battery over-voltage
warning.
Bypass Not Available
Input Freq/Volt Out Of
Range.
Discharged Battery. The UPS is in battery operation and
Emergency PSU Fault. Redundant Emergency Power Supply
The UPS has started pre-programmed
battery test.
The temperature of one or more battery un its has exceeded system
specifications.
The battery voltage is too high and
the charger has been deactivated.
The frequency or voltage is out of
acceptable range for bypass. This
message occurs when the UPS is
online, and indicates that the bypass
mode may not be available if
required.
the battery charge is low.
Note: Runtime is limited in duration.
Unit (PSU) is not working. The UPS
will continue to work normally, but
the PSU should be replaced.
No corrective action necessary.
Contact APC Customer Support.
See rear cover.
Contact APC Customer Support.
See rear cover.
Correct the input voltage to provide
acceptable voltage or frequency.
No corrective action necessary. Shut
down the system and the load
equipment or restore incoming
voltage.
Contact APC Customer Support. See
rear cover.
EPO Activated. Emergency Power Off Switch has
been ac tivat ed.
Fan fault. A fan has failed. Contact APC Customer Support. See
Int. Mech. Bypass
Switch Closed.
Int. Mech. Bypass
Switch Open.
Low-Battery. The UPS is in battery operation and
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 17
The intern al m echani cal s witchg ear is
closed.
The intern al m echani cal s witchg ear is
open.
the battery charge is low.
Note: Ru ntime is limited in duration.
Deactivate Emergency Power Off
Switch.
rear cover.
No corrective action necessary. The
UPS is in interna l mechanical bypass
operation.
No corrective action necessary.
Shut down the system and the load
equipment or restore incoming voltage.
Operation – Display Messages/Troubleshooting
Display message Meaning Corrective action
Load Is No Longer
Above Alarm Threshold.
The load previously exceeded the
alarm threshold and the situation has
been corrected either because the load
decreased or the threshold was
increased.
Load Power Is Above
Alarm Limit.
Mains Not Available.
Input Freq/Volt Out of
Range.
The load has exceeded the userspecified load alarm threshold.
The frequency or voltage is out of
acceptable range for normal
operation.
Min Runtime Restored. The system runtime dropped below
the configured minimum and has
been restored. Additional Battery
Modules were installed, the existing
Battery Modules were recharged, the
load was reduced, or the threshold
was decreased.
No Batteries Are
No battery power is available. Check that batt eries ar e insert ed
Connected.
Number of Battery
Modules Decreased.
One or more battery modules were
removed.
No corrective action necessary.
Option 1 : Use the display interface to
raise the alarm threshold.
Option 2 : Reduce the load.
Correct the input voltage to provide
acceptable voltage or frequency.
No corrective action necessary.
properly.
No corrective action necessary.
Number of Battery
Modules Increased.
One or more battery modules were
added.
Replace Batt(s). One or more Battery Modules need
replacement (only applicable with
internal batteries).
Runtime Is Below Alarm
Threshold.
The predicted runtime is lower than
the user-specified minimum runtime
alarm threshold. Either the battery
capacity has decreased, or the load
has increased.
Site Wiring Fault. Wrong phase rotation on the input
side. The UPS will contin ue to su pply
conditioned power, but bypass is
unavailable.
Shutdown Due To Low
Battery.
The UPS was in Battery Operation
and shut down the load whe n no more
battery power was available.
Static Bypass Switch
The Static Bypass Switch has failed. Contact APC Customer Support. See
Fault.
No corrective action necessary.
Refer to Module Re placem ent secti on
for proc edures.
Option 1: Allow the battery modules
to recharge.
Option 2: If possible, increase the
number of battery modules.
Option 3: Reduce load.
Option 4: Decrease alarm threshold.
Contact APC Customer Support.
See rear cover.
An electrician should check that the
UPS has been wired properly.
No corrective action necessary.
Note: If the problem reoccurs, consider increasing the battery capacit y.
rear cover.
18 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Operation – Display Messages/Troubleshooting
Display message Meaning Corrective action
System Failure Detect ed
by Survei llance.
System Start Up Configuration Failed.
System Not Synchronized to Bypass.
UPS In Bypass Due To
Fault.
UPS In Bypass Due To
Overload.
UPS Is Overloaded. The load exceeded the system power
The system has detected an internal
error.
System configuration err or. Unable t o
determine system voltage and/or
Enclosure size.
System cannot syn chronize to bypass.
Mode may not be available.
The UPS has transferred to Bypass
Mode because a fault has occurred.
The load exceeded the power
capacity. The UPS has switched to
Bypass Mode.
capacity.
Check for other alarms and contact
APC customer support if problem
persists.
Check for other alarms and contact
APC customer support if problem
persists.
Option 1 : Decrease the input frequency sensitivity .
Contact APC Customer Support
(see rear cover).
Option 2 : Correct the bypass input
voltage to provide acce ptable voltage
on frequency.
Contact APC Customer Support
(see rear cover).
Decrease the load.
Option 1: Decrease the load.
Option 2: Check the load distribution
on the 3 phases via the display. If the
load is unevenly distributed, adjust
the load distribution.
Weak Batt(s) Detected.
Reduced Runtime.
XR Battery Breaker
Open, or Fuse Blown.
One or more weak batteries det ected. Replace the weak batteri es.
The external DC disconnect switch
tripped. Batte ry power is not a v ailable
or the runtime is lower than expected.
Activate the external DC Disconnect
Switch or replace blown fuse in XR
Enclosure (only applicable if your
installation includes an XR
Enclosure).
If a problem persists, note UPS model #, serial #, and date purchased before calling APC Customer
Support (Type label located on rear cover, bottom section).
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 19
Front Panel Removal/Installation
Front Panel removal
O
u
tp
u
t
P
w
r
!
Z
o
n
e
P
r
o
b
e
1
0
/
1
0
0
B
a
s
e
-
T
R
e
s
e
t
1
0
/1
0
0
A
P
9
6
1
9
N
e
t
w
o
r
k
M
a
n
a
g
e
m
e
n
t
C
a
r
d
E
M
Se
ri
al
:
M
o
d
e
l
:
S
eri
al
:
M
o
d
e
l
:
B
A
TT
ER
Y
U
N
IT
S
e
r
ia
l:
M
o
d
e
l:
B
A
TT
E
R
Y
U
N
IT
S
e
ria
l:
M
o
d
e
l:
B
A
T
TE
R
Y
U
N
IT
S
e
r
ia
l:
M
o
d
e
l:
B
A
TT
E
R
Y
U
N
IT
S
M
B
A
T
TE
RY
U
N
IT
S
e
ria
l
:
M
o
d
e
l:
S
M
B
A
TT
E
R
Y
U
N
IT
S
eri
a
l:
M
o
d
e
l
:
S
M
B
A
T
T
ER
Y
U
N
IT
S
e
r
ia
l:
M
o
d
e
l
:
S
M
B
A
T
T
E
R
Y
U
N
IT
To remove a Front Panel, turn screw clockwise to unlocked position.
eri
a
l:
o
d
e
l
:
S
eri
al
:
M
o
d
e
l:
B
A
TT
ER
Y U
N
IT
B
A
T
TE
RY
U
N
IT
e
ria
l:
o
d
e
l
:
S
e
ri
a
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
B
A
T
T
E
R
Y
U
N
IT
er
ia
l:
o
d
e
l
:
S
e
r
ia
l:
M
o
d
e
l
:
B
A
TT
E
R
Y
U
N
IT
B
A
TT
E R
Y
U
N
IT
e
r
ia
l:
o
d
e
l:
S
e
r
ia
l:
M
o
d
e
l:
B
A
TT
E
R
Y
U
N
IT
B
A
T
TE
R
Y
U
N
IT
Pull top of Front Panel free of UPS.
Lift the Front Panel free of the two slots at the bottom of the Enclosure.
20 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Installation
Operation – Front Panel Removal/Installation
Ou
tput
Pw
r
!
Z
o
ne
Pro
be
10/1
0
0B
ase
-T
R
e
s
e
t
10
/1
00
A
P
9
6
1
9
N
e
t
w
o
r
k
M
a
n
a
g
e
m
e
n
t
C
a
r
d
E
M
S
e
r
ia
l:
M
o
d
e
l
:
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l:
M
o
d
e
l
:
S
e
r
ia
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
S
e
r
ia
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l:
M
o
d
e
l
:
S
e
r
i
a
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
S
e
r
ia
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
B
A
T
T
E
R
Y
U
N
I
T
Insert the two protrusions at the bottom of the Front Panel into the two slots at the bottom of the
Enclosure.
Push the Front Panel into place.
To secure the Front Panel, turn the screw counterclockwise to locked position.
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 21
Total-Power-Off Procedure
WARNING!
Risk of electric shock – parts inside the UPS and XR Batterty Enclosure are energized
from the battery supply even when the AC power is disconnected. Before electrical
installation begins, follow the Total-Power-Off procedure to completely de-energize the
system.
O
u
t
p
u
t
P
w
r
!
Z
o
n
e
P
r
o
b
e
1
0
/
1
0
0
B
a
s
e
-T
R
e
s
e
t
1
0
/
1
0
0
A
P
9
6
1
9
N
e
t
w
o
r
k
M
a
n
a
g
e
m
e
n
t
C
a
r
d
E
M
ON
OFF
Utility/
Mains
breaker
Se
ria
l:
M
o
d
e
l
:
S
eri
al
:
M
o
d
e
l
:
B
A
T
T
E
S
er
R
ia
l:
Y
U
N
I
T
M
o
d
e
l
:
B
A
T
T
E
R
Y
Se
U
ria
N
l:
I
T
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
B
A
T
T
E
R
Y
U
N
I
T
Se
ria
l:
M
o
d
e
l
:
S
er
ial
:
M
o
d
e
l
:
B
A
T
T
E
Se
R
ri
al
Y
:
U
N
I
T
M
o
d
e
l
:
B
A
T
T
E
R
Y
S
U
eri
N
al:
I
T
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
B
A
T
T
E
R
Y
U
N
I
T
Serial:
M
o
d
e
l
:
Serial:
M
o
d
e
l
:
B
Serial:
A
T
T
E
R
Y
U
N
I
T
M
o
d
e
l
:
B
A
T
T
E
R
Serial:
Y
U
N
I
T
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
erial:
M
o
d
e
l
:
Serial:
M
o
d
e
l
:
B
S
eria
A
l:
T
T
E
R
Y
U
N
I
T
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
B
A
T
T
E
R
Y
U
N
I
T
S
er
ial:
M
o
d
e
l
:
Se
ria
l:
M
o
d
e
l
:
B
S
erial:
A
T
T
E
R
Y
U
N
I
T
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
B
A
T
T
E
R
Y
U
N
I
T
S
erial:
M
o
d
e
l
:
Serial
:
M
o
d
e
l
:
B
Ser
A
ial:
T
T
E
R
Y
U
N
I
T
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
B
A
T
T
E
R
Y
U
N
I
T
Serial:
B
A
M
T
o
d
T
e
l
E
:
R
Y
U
N
I
T
Serial:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
Se
rial:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
Serial:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
Serial:
M
o
d
e
l
:
B
A
T
T
E
Se
R
rial:
Y
U
N
I
T
M
o
d
e
l
:
B
A
T
T
E
R
Y
Se
U
ria
N
l:
I
T
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
B
A
T
T
E
R
Y
U
N
I
T
Serial:
M
o
d
e
l
:
Seria
l:
M
o
d
e
l
:
B
A
T
T
E
Se
R
ria
l:
Y
U
N
I
T
M
o
d
e
l
:
B
A
T
T
E
R
Y
Serial:
U
N
I
T
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
B
A
T
T
E
R
Y
U
N
I
T
Seria
l:
M
o
d
e
l
:
S
erial:
M
o
d
e
l
:
B
A
T
T
E
Seria
R
l:
Y
U
N
I
T
M
o
d
e
l
:
B
A
T
T
E
R
Y
S
U
eri
N
al:
I
T
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
B
A
T
T
E
R
Y
U
N
I
T
Serial
:
M
o
d
e
l
:
Ser
ial:
M
o
d
e
l
:
B
A
T
T
E
S
erial:
R
Y
U
N
I
T
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
Serial:
N
I
T
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
B
A
T
T
E
R
Y
U
N
I
T
Serial:
M
o
d
e
l:
B
A
TTE
R
Y
U
N
IT
UPS
XR Battery Enclosure
Set the DC disconnect switch on the XR Enclosure (if available) to the OFF position.
Remove all batteries from the system, or, alternatively, pull out all batteries to the red
disconnect line shown on the battery. To ensure sufficient stability, do not pull batteries out
beyond the red disconnect line unless completely removing them from the Enclosure.
Set the utility breaker to the OFF or LOCKED-OUT position. If the UPS has dual mains supply,
set both supplies to the OFF or LOCKED-OUT position.
WARNING!
Correct lock-out procedures at utility breaker must be followed. If necessary, install a
padlock.
22 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Restart Procedure
Start-up is included with the UPS, and the start-up procedure described here is only
applicable if the UPS requires a subsequent start-up.
Note
Power application
WARNING!
Only trained personnel familiar with the construction and the equipment may carry out
the Start-Up procedure.
O
u
t
p
u
t
P
w
r
!
Z
o
n
e
P
r
o
b
e
1
0
/
1
0
0
B
a
s
e
T
R
e
s
e
t
1
0
/
1
0
0
A
P
9
6
1
9
N
e
tw
o
r
k
M
a
n
a
g
e
m
e
n
t
C
a
r
d
E
M
S
e
r
i
a
l
:
M
o
d
e
l
:
S
e
r
i
a
M
o
d
e
B
AT
TE
R
Y
U
N
IT
B
S
e
r
i
a
l
:
M
o
d
e
l
:
S
e
r
i
a
M
o
d
e
B
AT
TE
R
Y
U
N
IT
B
S
e
r
i
a
l
:
M
o
d
e
l
:
S
e
r
i
a
l
:
M
o
d
e
l
:
BATTE
S
e
r
i
a
l
:
RY
U
N
IT
M
o
d
e
l
:
S
e
r
i
a
l
:
B
AT
TER
Y
U
NIT
M
o
d
e
l
:
BATTE
RY UN
IT
BATT
S
e
r
i
a
l
:
ER
Y UN
IT
M
o
d
e
l
:
S
e
r
i
M
o
d
B
A
TTER
Y
UNIT
B
S
e
r
i
a
l
:
M
o
d
e
l
:
S
e
r
i
a
l
:
M
o
d
e
l
:
B
S
e
r
A
i
a
l
:
TTE
R
Y U
NIT
M
o
d
e
l
:
S
e
r
i
a
l
:
B
ATTER
Y UN
IT
M
o
d
e
l
:
BA
TTER
Y
U
NIT
S
e
r
i
a
l
:
M
o
d
e
l
:
S
e
r
i
a
l
:
M
o
d
e
l
:
B
S
e
r
A
i
a
l
:
TTER
Y U
NIT
M
o
d
e
l
:
BA
TTER
Y
U
NIT
BA
TTER
Y
U
NIT
S
e
r
i
a
l
:
M
o
d
e
l
:
S
e
r
i
a
l
:
M
o
d
e
l
:
BA
S
e
r
i
a
l
:
TTER
Y U
NIT
M
o
d
e
l
:
BA
T
TE
RY UN
IT
BA
TTER
Y UN
IT
S
e
r
i
a
l
:
BA
T
TER
Y
U
NIT
M
o
d
e
l
:
S
e
r
i
a
M
o
d
e
BA
TTER
Y U
NIT
BA
S
e
r
i
a
l
:
M
o
d
e
l
:
BA
TTER
Y
U
NIT
S
e
r
i
a
l
:
M
o
d
e
l
:
S
e
r
i
a
M
o
d
e
BA
TTER
Y
U
NIT
BA
S
e
r
i
a
l
:
M
o
d
e
l
:
BA
S
e
r
i
TTER
a
l
:
Y U
N
IT
M
o
d
e
l
:
S
e
r
i
a
M
o
d
e
BA
TTER
Y UN
IT
BA
UPS
XR Battery Enclosure
Set the utility breaker to the ON position.
ON
OFF
Utility
breaker
l
:
l
:
S
e
r
i
a
l
:
M
o
d
e
l
:
S
e
r
i
a
l
:
A
T
TE
R
Y U
N
IT
M
o
d
e
l
:
BA T
TE
RY
U
N
IT
BA
TT
ER
Y
UN
IT
l
:
l
:
S
e
r
i
a
l
:
M
o
d
e
l
:
S
e
r
i
a
l
:
A
TT
ER
Y
U
NIT
M
o
d
e
l
:
BA
T
TE
R
Y U
N
IT
B
AT
TER
Y
U
NIT
a
l
:
e
l
:
S
e
r
i
a
l
:
M
o
d
e
l
:
S
e
r
i
a
l
:
ATTER
Y UN
IT
M
o
d
e
l
:
B
A
TTE
R
Y U
NIT
B
A TTER
Y U
N
IT
l
:
l
:
S
e
r
i
a
l
:
M
o
d
e
l
:
S
e
r
i
a
l
:
T
TE
RY
U
NIT
M
o
d
e
l
:
B
ATTE
RY
UN
IT
B
A
TTER
Y UNIT
l
:
l
:
S
e
r
i
a
l
:
M
o
d
e
l
:
S
e
r
i
a
l
:
TTE
RY
U
NIT
M
o
d
e
l
:
B
ATTE
RY
UN
IT
BA
TTER
Y UN
IT
l
:
l
:
S
e
r
i
a
l
:
M
o
d
e
l
:
S
e
r
i
a
l
:
T
TER
Y U
NIT
M
o
d
e
l
:
BA
TTER
Y UN
IT
BA
TTERY
U
NIT
If your installation includes an XR Battery Enclosure with a DC disconnect switch, set the DC
disconnect switch to the ON position.
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 23
Operation – Restart Procedure
Wait approximately 30 seconds for the system to boot up and carry out self test.
Note
After system boot-up, the display will automatically prompt you on how to confirm/select voltage
and frequency as shown in the following.
Voltage confirmation
See display introduction under The Display.
At the restart, the display will prompt you through the following screens:
Confirm Voltage
Use 208V
Yes, use 208V
No, select another
• When the Confirm Voltage prompt appears on the screen, select desired voltage and press
ENTER.
Apply load?
Yes
No
• When the prompt Apply load appears, select Yes if you want the UPS to provide a load output
now. (If you do not want a UPS load output at this point, select No).
Chrg xxx% ||||||||||
Load xxx% ||||||||||
xxx Vin xxxVout xxHz
Runtime: xxhr xxmin
Status screen
LOAD ON LED is now lit, and the display will show the Confirm Menu Screen.
The UPS is now ready to support the load.
Note
Auto-detection on frequency – if problem occurs call APC Customer Support.
Note
24 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Mechanical Bypass
Mechanical Bypass Lever
For increased availability, the UPS is equipped with an internal mechanical bypass system providing
mains power directly to the output, bypassing all UPS electronics.
CAUTION!
The load is not protected by the UPS when the internal mechanical bypass system is
active, and, the power is not conditioned.
Turn into mechanical bypass
If the UPS is running and controllable through the display, carry out steps 1 through 6.
If not, go directly to step 4.
Note
Control
Status
Setup
Logging
Main Menu
From the Main Menu, select Control and press ENTER
Use UP/DOWN key to navigate to UPS into Bypass and press ENTER
Use UP/DOWN key to navigate to YES, confirm UPS into bypass , and press ENTER
Remove UPS Front Panel
Display
Diags
Help
See “Front Panel removal” on page 20.
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 25
Operation – Mechanical Bypass
Turn the Mechanical Bypass Lever upwards to activate the internal mechanical bypass switch.
Reinstall the Front Panel.
O
ut
p
u
t
P
w
r
!
Z
o
n
e
P
ro
b
e
10
/
10
0
B
a
se
-T
R
eset
1
0
/
10
0
A
P
9
6
1
9
N
e
tw
o
r
k
M
a
n
a
g
e
m
e
n
t
C
a
rd
E
M
See Front Panel “Installation” on page 21.
The load will now be supported directly by utility power.
Switch into normal operation (from mechanical bypass operation)
CAUTION!
Never attempt to switch back the UPS into normal operation till you have verified that
there are no internal UPS faults. Call APC Customer Support (see rear cover of this
manual) before switching back to normal operation.
Verify the presence of utility supply.
UPS will start up and perform self test (see Restart Procedure).
Ensure no error messages appear in the display and select “YES” when “Apply load” appears in
the display. The UPS will automatically turn into static bypass.
Verify UPS is in static bypass. Green and yellow LED are ON.
Turn the Mechanical Bypass Lever downwards into horizontal position.
Verify UPS is in normal operation. Yellow LED turns OFF and green LED remains ON.
26 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Network Management Card with
Environmental Monitor
The APC Network Management Card with Environmental Monitor (AP9619) is installed in the UPS
as default. It is used for remote system control and monitoring, e-mail notifications etc.
For configuration and use, refer to the separate user manual - Network Management
Card with Environmental Monitor - shipped with the UPS.
Network Management Card replacement
O
u
t
p
u
t
P
w
r
!
Z
o
n
e
P
r
o
b
e
1
0
/
1
0
0
B
a
s
e
T
R
e
s
e
t
1
0
/1
0
0
A
P
9
6
1
9
N
e
t
w
o
r
k
M
a
n
a
g
e
m
e
n
t
C
a
r
d
E
M
O
utp
u
t
P
w
r
!
Z
o
n
e
P
ro
b
e
10
/1
00
B
a
s
R
e
s
e
t
e-T
10
/1
0
0
AP9619 Netwo rk Management Card EM
Loosen the 2 torx screws (one each side of the card).
Carefully pull out the card.
Reversed procedures for installation.
S
e
ria
l
:
Model:
S
e
ria
l:
Model:
BATTERY UNIT
S
e
r
ia
l:
Model:
BATTERY UNIT
S
eria
l:
Model:
S
e
ri
a
BATTERY UNIT
S
e
r
ia
l:
Model:
BATTERY UNIT
l:
Model:
BATTERY UNIT
BATTERY UNIT
S
e
ria
l
:
Model:
S
e
ria
l:
Model:
BATTERY UNIT
BATTERY UNIT
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 27
Battery Replacement
General safety prior to module replacement
WARNING!
• Only trained personnel familiar with the operation of the equipment, and the
electrical and mechanical hazards involved, may install and remove system
components.
• The UPS and Battery Enclosure contain an internal energy source. Hazardous
voltage may be present even when disconnected from the power source. Follow
Total Power Off Procedure to completely de-energize the system.
• Never replace batteries when the UPS is running in battery mode!
• Risk of Energy Hazard, 96 V, 7.2 Ampere-hour battery. Before replacing
batteries, remove all conductive jewelry such as chains, watches, and rings.
High energy through conductive materials could cause severe burns.
• Batteries do not contain serviceable parts. Do not open.
• Do not open or mutilate batteries. Released material is harmful to the skin and
eyes. It may be toxic. Do not dispose of batteries in a fire, as they may explode.
• To ensure continuous battery back-up, only replace one Battery Module at a
time.
• For configurations that include customer-supplied external batteries, refer to
manufacturer’s battery installation and maintenance instructions.
Two people to lift components weighing between 40 - 70 lbs / 18 - 32 kg.
Battery Module
One Battery Module consists of 4 Battery Units (max. 2 Battery Modules shipped in the Enclosures).
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
4 x 50lb / 4 x 24kg
28 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Operation – Battery Replacement
Removal and installation of Battery Locks (if applicable)
If your system is equipped with Battery Locks, follow the below procedure to remove the Battery
Locks.
Remove the M3 screw attaching the Battery Lock to the shelf.
Push the Battery Lock to the left, push it upwards and remove.
Use reversed procedures for installation of Battery Locks.
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 29
Operation – Battery Replacement
Battery Module removal
Two people to lift components weighing between 40 - 70 lbs / 18 - 32 kg.
Follow the below procedures if you need to change or add a Battery Module, e.g. if you receive a
display message reporting a bad battery, or if you need to add batteries for increased runtime:
UPS XR
O
u
t
p
u
t
P
w
r
!
Z
o
n
e
P
r
o
b
e
1
0
/
1
0
0
B
a
s
e
T
R
e
s
et
1
0
/
1
0
0
A
P
9
6
1
9
N
e
t
w
o
r
k
M
a
n
a
g
e
m
e
n
t
C
a
r
d
E
M
S
e
r
i
a
l
:
M
od
el
:
S
e
r
ia
l
:
M
o
d
el:
B
S
e
r
A
ia
l:
TT
E
R
Y
U
N
IT
M
o
del
:
B
A
T
TE
R
Y
U
N
IT
B
A
TT
E
R
Y
U
N
IT
S
e
r
i
a
l
:
M
o
de
l:
BATTE
RY UNIT
S
e
r
i
a
l
:
M
o
d
e
l:
S
e
r
i
a
l
:
Mo
del
:
B
S
e
r
A
i
a
l
:
T
TE
R
Y U
N
IT
M
o
d
e
l
:
S
e
r
i
a
l
:
B
A
T
TE
R
Y U
N
IT
M
o
d
el:
B
A
T
T
E
R
Y U
N
IT
B
A
TT
E
R
Y
U
N
IT
S
e
ri
al
:
M
ode
l:
S
e
ri
a
l:
M
o
d
el
:
B
S
e
r
A
i
al
:
T
T
E
R
Y U
N
IT
M
ode
l:
S
e
r
ia
l:
B
A
T
TE
R
Y
U
N
IT
M
o
de
l:
B
A
T
T
E
R
Y
U
N
IT
B
A
TT
E
R
Y
U
N
IT
S
e
ri
a
l
:
M
o
de
l:
S
e
r
ia
l
:
M
o
de
l:
B
S
e
r
A
ia
l:
T
T
E
R
Y
U
N
IT
M
od
el:
S
e
ri
a
l:
B
A
T
T
E
R
Y
U
N
I
T
M
od
el
:
B
A
T
T
E
R
Y
U
N
IT
B
A
T
T
E
R
Y
U
N
I
T
S
e
ri
a
l:
M
o
de
l:
S
e
ri
a
l:
Mo
d
el
:
B
S
e
r
A
i
a
l:
T
T
E
R
Y
U
N
IT
Mo
de
l:
S
e
r
i
a
l:
B
A
T
T
E
R
Y
U
N
IT
Mo
de
l
:
B
A
T
T
E
R
Y
U
N
IT
B
A
T
T
E
R
Y
U
N
IT
S
er
i
a
l
:
M
odel
:
S
e
r
ia
l:
Mode
l:
B
S
e
ri
A
a
l:
T
T
E
R
Y
U
N
IT
Mode
l:
S
er
i
a
l:
B
A
T
T
E
R
Y
U
N
IT
Mo
del:
B
A
T
T
E
R
Y
U
N
IT
B
A
T
T
E
R
Y
U
N
IT
S
e
r
i
a
l
:
M
o
d
e
l
:
S
e
r
i
a
l
:
M
o
d
e
l:
S
e
r
i
a
l
:
BATTERY UNIT
M
o
d
e
l
:
BATT
ERY UNIT
BAT
TERY UNIT
S
e
r
i
a
l
:
M
o
d
e
l
:
BATTERY UNIT
S
e
r
i
a
l
:
M
o
d
e
l:
S
e
r
i
a
l
:
M
o
d
e
l:
BATTERY UNIT
M
BATTERY UNIT
S
e
r
i
a
l
:
M
o
d
e
l:
S
e
r
i
a
l
:
M
o
d
e
l
:
BATTERY UNIT
M
BATTERY UNIT
S
e
r
ia
l
:
M
o
d
e
l:
S
e
r
i
a
l
:
M
o
d
e
l
:
BATTERY UNIT
M
BATTERY UNIT
S
e
r
i
a
l
:
o
d
e
l:
S
e
r
i
a
l
:
M
o
d
e
l
:
BATTERY UNIT
BATTERY UNIT
S
e
r
ia
l
:
o
d
e
l
:
S
e
r
i
a
l
:
M
o
d
e
l:
BATTER
Y UNIT
BATTERY UNIT
S
e
r
i
a
l
:
o
d
el
:
S
e
r
i
a
l
:
M
o
d
e
l:
BATTERY UNIT
BATTERY UNIT
When removing Battery Modules, start from the highest level and work down.
Holding the battery handle, gently push the battery unit upwards and pull it halfway out of the
Enclosure. A lock mechanism prevents it from being pulled all the way out.
To release the battery from the lock mechanism, one person gently pushes the battery upwards
again and pulls it out, while the other person supports the battery.
How to install a Battery Module
If additional batteries are needed for extra run-time, or if you install battery replacement modules
etc., follow the below procedure:
CAUTION!
Wait until you are ready to power up the system before installing Battery Modules in the
UPS. Failure to do so can result in a deep discharge of the batteries and cause permanent
damage (the time from the battery installation time till the UPS is powered up should
not exceed 72 hours or 3 days).
30 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Operation – Battery Replacement
UPS / XR
S
e
r
i
a
l
:
M
o
d
e
l
:
BATTERY UNIT
S
e
ri
a
l:
Mo
d
el:
B
A
T
T
E
R
Y
U
N
I
T
Install the Battery Modules in the lowest available bay (4 across in 20.59inch/523mm UPS
versions, 2 across in 13.85inch/352mm UPS versions).
Position the Battery Unit to slide in between the grooves and push completely into the UPS to
ensure connection.
Note
Note
If a problem is reported, ensure that the modules in question are correctly installed. If the
problem persists, refer to the Troubleshooting section of this guide.
Allow for a 24-hour recharging period of the batteries after system start-up / battery
replacement for battery monitoring data to become fully reliable.
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 31
How to Obtain Replacement Parts
To obtain a replacement part, contact APC Customer Support (see rear cover).
1. In the event of a Battery Module failure, the display may show additional “fault list” screens.
Press any key to scroll through these fault lists, record the information, and relay it to the APC
representative.
2. If possible, call APC Customer Support from a telephone that is within reach of the UPS display
interface so that you can gather and report additional information to the APC representative.
3. Be ready to provide a detailed description of the problem. Our representative will help you
solve the problem over the telephone, if possible, or will give you a return material
authorization (RMA) number. If a module is returned to APC, this RMA number must be
clearly printed on the outside of the package.
4. If the UPS is within the warranty period, or covered by an APC On-Site Service contract, there
will be no charge for repair labor, parts and travel expenses. Please refer to the Limited Factory
Warranty section. If it is not within the warranty period, there will be a charge for repair.
See Limited Factory War ra nt y section for more information.
5. If the UPS is covered by an APC service contract, have that information available and give it to
the representative.
Orderable parts
Description APC SKU No.
Smart-UPS® VT XR Battery Enclosure with DC breaker, DC fuses and 2 Battery
Modules (expandable to 6).
Smart-UPS
Modules.
Smart-UPS
(expandable to 6).
Smart-UPS
Battery Module. SYBT4
Network Management Card with Environmental Monitor. AP9619
®
®
®
SUVTBXR2B6S
VT XR Battery Enclosure with DC breaker, DC fuses and 6 Battery
VT XR Battery Enclosure with DC fuses and 2 Battery Modules
VT XR Battery Enclosure with DC fuses and 6 Battery Modules. SUVTXR6B6S
SUVTBXR6B6S
SUVTXR2B6S
32 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Maintenance Bypass Panel
Operation procedure
The Maintenance Bypass Panel (MBP) can be used to completely isolate the UPS in the event of an
internal UPS fault.
MBP (line-up-and-match) with and
MBP (wall mounted)
without PDU capabilities
To carry out this procedure, refer to the product-specific manual supplied with the
Maintenance Bypass Panel.
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 33
Warranty
LIMITED FACTORY WARRANTY
The limited warranty provided by American Power Conversion Corporation (“APC”) in this
Statement of Limited Factory Warranty applies only to Products you purchase for your commercial or
industrial use in the ordinary course of your business.
APC product covered
Smart-UPS® VT and Smart-UPS® VT Extended Run Battery Enclosure
Terms of warranty
APC warrants that the Product shall be free from defects in materials and workmanship for a period
of one (1) year from the date of start-up when APC authorized service personnel performed the start-
up of the Product, or a maximum of 18 months from the date of Product shipment from APC, when
APC authorized service personnel have not performed the start-up of the Product (“Warranty
Period”). In the event that the Product fails to meet the foregoing warranty, APC shall repair or
replace any defective parts, such repair or replacement to be without charge for on-site labor and
travel if APC authorized personnel have conducted start-up of the Product. An APC Start-Up Service
must be performed/completed by APC authorized service personnel or replacement of defective parts
only will be covered. APC shall have no liability and no obligation to repair the installed Product if
non-authorized personnel performed the start-up and such start-up caused the Product to be defective.
Any parts furnished under this warranty may be new or factory-remanufactured. Repair or
replacement of a defective product or part thereof does not extend the original warranty
period.
Non-transferable warranty extends to first purchaser for use
This Warranty is extended to the first person, firm, association or corporation (herein referred to by
“You” or “Your”) for whom the APC Product specified herein has been purchased. This Warranty is
not transferable or assignable without the prior written permission of APC.
34 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Warranty – LIMITED FACTORY WARRANTY
Assignment of warranties
APC will assign to you any warranties which are made by manufacturers and suppliers of
components of the APC Product and which are assignable. Any such warranties are assigned “AS IS”
and APC makes no representations as to the effectiveness or extent of such warranties, assumes NO
RESPONSIBILITY for any matters which may be warranted by such manufacturers or suppliers and
extends no coverage under this Warranty to such components.
Drawings, descriptions
APC warrants for the Warranty Period and on the terms of the Warranty set forth herein that the APC
Product will substantially conform to the descriptions contained in the APC Official Published
Specifications or any of the drawings certified and agreed to by an authorized APC representative, if
applicable thereto (“Specifications”). It is understood that the Specifications are not warranties of
performance and not warranties of fitness for a particular purpose .
Warranty claims procedure
To obtain service under Warranty, contact APC Customer Support (see rear cover).You will need the
model number of the Product, the serial number, and the date purchased. A technician will ask you to
describe the problem. If it is determined that the Product will need to be returned to APC you must
obtain a returned material authorization (RMA) number from APC Customer Support. Products that
must be returned must have the RMA number marked on the outside of the package, and be returned
with transportation charges prepaid. If it is determined by APC Customer Support that on-site repair
of the Product is allowed, APC will arrange to have APC authorized service personnel dispatched to
the Product location to repair or replace the Product at the discretion of APC.
Exclusions
APC shall not be liable under the Warranty if its testing and examination discloses that the alleged
defect in the product does not exist or was caused by your or any third person’s misuse, negligence,
improper installation or testing, unauthorized attempts to repair or modify, or any other cause beyond
the range of the intended use, or by accident, fire, lightning or other hazard.
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 35
Warranty – LIMITED FACTORY WARRANTY
There are no warranties, expressed or implied, by operation of law or otherwise, of products
sold, serviced or furnished under this agreement or in connection herewith. APC disclaims all
implied warranties of merchantability, satisfaction and fitness for a particular purpose. The
APC express warranties will not be enlarged, diminished, or affected by and no obligation or
liability will arise out of APC rendering technical or other advice or service in connection with
the products. The foregoing warranties and remedies are exclusive and in lieu of all other
warranties and remedies. The warranties set forth above, constitute sole liability of APC and
your exclusive remedy for any breach of such warranties. THE warranties EXTEND only to
you and are not extended to any third parties.
In no event shall APC, its officers, directors, affiliates or employees be liable for any form oF
indirect, special, consequential or punitive damages arising out of the use, service or
installation of the products, whether such damages arise in contract or tort, irrespective of
fault, negligence or strict liability or whether APC has been advised in advance of the
possibility of such damage.
36 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Appendix
UPS Components and Options
13.85 in/352 mm Enclosures
H
o
t
l
i
n
e
i
n
U
S
H
/
C
o
a
t
l
n
i
n
a
e
d
a
i
n
/
L
E
A
W
M
M
o
E
:
U
r
A
l
+
n
d
:
1
i
w
t
S
8
+
i
d
e
0
3
e
r
0
5
i
a
3
S
8
l
u
0
9
N
0
1
p
o
p
4
7
o
A
0
r
P
2
t
C
0
n
0
u
0
m
b
A
e
P
r
C
s
:
S
K
w
U
w
w
.
a
p
c
c
.
c
o
m
/
s
u
p
M
p
o
o
d
r
e
t
l
/
s
e
r
v
S
i
c
U
e
V
/
T
g
F
e
1
o
0
m
K
S
B
a
U
2
p
V
F
B
_
T
a
w
1
t
0
t
o
e
K
r
r
F
l
y
d
1
C
.
B
A
d
a
2
P
f
p
S
m
C
a
c
S
i
m
t
y
a
r
t
U
P
@
S
S
–
U
w
V
V
1
/
1
T
A
T
9
2
B
1
1
p
V
0
0
a
p
K
k
t
a
D
t
V
.
F
r
C
A
e
M
2
n
B
2
o
t
2
0
d
/
S
8
u
A
V
l
e
P
E
C
x
R
S
p
a
.
m
A
t
t
e
o
a
c
d
r
t
2
t
i
S
-
I
v
n
U
e
U
p
P
V
P
u
S
T
o
t
1
V
w
C
0
T
u
e
K
r
r
w
1
7
F
r
0
e
/
.
1
2
2
k
n
B
A
V
B
t
4
h
A
a
S
t
R
2
t
S
.
A
0
a
U
M
8
P
t
e
V
V
C
o
d
T
d
S
u
F
O
m
l
1
e
u
0
s
a
t
K
p
r
S
t
u
B
-
U
U
t
4
V
P
C
F
T
S
u
1
w
r
0
V
r
/
e
K
1
T
n
F
B
1
t
2
0
a
B
k
t
1
B
t
4
V
.
4
S
a
A
M
.
t
4
t
2
o
A
e
A
0
d
r
h
8
u
y
P
V
l
C
e
C
u
E
S
r
x
m
r
p
e
a
S
.
n
r
t
U
t
t
o
-
V
U
4
T
P
1
S
w
0
K
V
/
2
F
T
B
3
1
B
a
0
t
4
7
k
t
.
S
.
V
2
M
A
A
o
h
2
d
A
0
u
8
P
l
e
V
C
s
S
E
m
x
S
p
a
U
.
r
V
t
t
-
o
U
T
4
1
P
0
S
w
K
V
F
/
3
1
T
4
0
B
B
1
k
1
a
4
0
V
4
t
S
k
A
t
.
.
4
V
S
/
M
8
A
A
U
A
k
h
o
2
W
V
P
d
0
T
C
u
8
F
l
e
V
S
1
s
m
5
E
K
a
x
B
r
p
t
2
-
.
U
F
t
o
P
S
4
2
V
7
T
.
1
w
1
A
0
2
S
/
4
k
1
U
V
.
B
6
V
A
a
A
T
t
2
h
t
1
.
0
5
M
8
2
K
V
0
o
F
8
d
2
V
u
B
l
e
2
s
S
A
2
P
7
C
.
8
S
A
m
a
r
2
t
8
U
.
8
P
A
2
S
h
0
V
8
T
V
w
1
5
/
2
k
S
V
B
U
A
a
V
S
t
2
t
T
.
U
0
2
1
M
8
8
V
5
V
.
o
T
9
K
d
F
A
F
u
1
2
l
5
e
B
K
s
4
B
S
A
4
P
F
C
S
m
a
r
t
-
1
U
S
4
U
P
.
4
S
V
w
A
T
V
/
h
1
2
T
5
B
K
1
a
5
F
t
k
t
3
.
V
B
M
A
4
A
o
S
2
P
d
0
C
u
8
l
e
V
S
s
m
E
a
x
r
p
t
.
U
t
S
o
P
U
S
4
w
V
V
/
T
3
T
1
B
5
1
a
K
5
t
F
k
t
.
V
4
M
B
A
1
o
4
2
4
d
S
A
0
.
u
4
8
P
l
A
e
V
C
h
s
S
E
m
x
p
a
.
r
t
t
-
o
U
4
P
S
V
S
T
U
w
1
V
5
S
/
4
k
T
U
V
2
B
V
2
A
0
a
1
T
K
t
2
.
t
F
6
F
.
0
1
2
A
M
2
8
5
0
A
B
h
V
k
o
K
P
V
4
d
B
A
C
S
u
4
/
l
1
e
S
F
2
s
m
k
a
W
r
t
U
P
S
S
w
4
U
V
/
0
2
V
T
.
6
T
B
A
2
2
a
0
2
0
t
k
8
t
K
.
V
.
8
F
M
A
A
A
3
o
2
B
h
P
d
0
4
C
u
8
2
S
l
e
V
0
S
s
8
m
V
E
a
x
r
p
t
-
.
U
t
o
P
4
S
1
4
w
S
.
6
V
/
U
3
A
T
V
B
2
T
a
0
2
t
1
k
t
0
.
4
V
K
M
.
A
4
F
o
A
4
2
2
d
A
B
h
0
0
u
8
P
4
8
l
e
V
S
V
C
s
S
S
E
U
m
x
V
p
a
T
.
r
t
F
t
-
o
U
3
4
0
4
P
K
3
S
S
.
B
U
3
V
4
A
V
T
F
T
w
2
3
2
0
0
/
4
1
k
K
.
V
B
6
F
A
A
a
3
t
B
h
2
t
.
0
4
M
8
S
V
o
A
d
u
P
l
C
e
s
S
m
a
S
r
t
U
U
V
2
P
T
0
S
k
3
w
2
V
0
V
8
/
A
K
3
.
T
/
8
F
1
B
A
3
4
6
a
0
B
h
k
t
k
t
4
W
.
V
S
M
A
o
2
d
A
0
u
8
P
l
5
e
V
C
4
s
.
S
2
E
A
m
x
p
a
.
r
V
t
t
-
o
o
U
l
4
t
P
a
S
g
2
e
V
0
&
T
8
5
V
w
3
C
5
2
0
.
/
o
5
4
1
k
n
A
.
V
A
B
6
n
A
C
A
a
e
t
h
2
c
t
I
.
0
n
t
i
M
8
p
o
V
u
n
o
d
t
2
T
u
0
y
l
e
8
p
s
V
e
s
2
0
8
Y
/
1
2
2
8
0
.
8
V
3
A
0
5
4
h
k
7
W
V
A
.
A
7
+
C
A
/
G
2
O
4
N
k
u
D
W
t
p
6
u
0
t
H
z
8
1
.
3
A
2
0
8
D
Y
C
/
1
B
2
I
n
a
0
2
p
t
V
0
t
u
D
e
8
4
t
r
a
V
W
i
t
e
e
s
+
G
N
8
D
3
.
6
3
i
0
A
n
H
s
D
t
z
a
a
l
t
l
e
e
d
f
+
o
/
2
r
0
1
1
8
.
9
V
2
R
V
e
p
l
D
a
c
a
e
t
e
m
8
f
6
S
e
o
.
n
r
6
E
t
A
2
E
.
R
I
N
e
p
S
l
a
T
c
A
e
m
L
L
e
n
A
B
t
T
E
I
O
F
O
N
R
I
N
E
S
C
T
O
R
N
U
N
S
C
U
E
T
C
P
I
O
P
T
N
I
L
N
Y
S
G
T
O
T
H
T
E
H
I
S
R
E
A
R
C
O
P
V
L
E
A
R
C
E
M
D
U
O
S
T
N
B
U
E
P
S
8
8
5
-
2
3
2
1
C
_
r
e
v
0
4
!
Outpu
t
Pwr
Z
one
Pr
obe
10/
10
0Base-T
R
e
s
e
t
A
10/100
P
9
6
1
9
N
e
t
w
o
r
k
M
a
n
a
g
e
m
e
n
t
C
a
r
d
E
M
S
er
ia
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
S
er
ial
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
ia
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
Se
r
i
a
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
S
e
ri
a
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
ria
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
S
e
r
ia
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
ia
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
Front Rear Front without front panel
20.59 in/523 mm Enclosures
H
o
t
l
i
n
e
i
n
U
H
S
o
/
C
t
l
a
i
n
n
e
a
d
i
n
a
/
W
E
L
U
M
A
o
n
E
r
M
it
l
A
d
S
:
w
:
e
+
r
i
ia
1
d
+
e
l
3
8
N
5
0
S
o
3
0
u
p
9
8
1
0
p
0
o
7
r
0
4
t
A
2
n
P
0
u
0
C
m
A
0
P
b
C
e
S
r
s
K
:
U
w
w
w
.
a
p
c
c
.
c
o
m
/
s
M
u
o
p
d
p
S
e
o
U
l
r
V
t
T
/
s
F
e
1
r
0K
v
i
c
B
S
e
2
U
/
F
g
V
T
1
0
K
F
B
1
a
B
tt
A
2
e
P
S
ry
C
C
S
a
m
p
ar
a
c
t-U
S
ity
U
P
V
w
S
T
/
V
1
@
1
0
B
T
K
– 1
1
a
F
tt.
0
2
9
k
B
2
M
V
2
V
A
S
o
D
2
A
d
C
P
u
0
le
8
C
V
E
S
xp
m
S
ar
. to
U
t-
V
U
2
T
P
1
S
0
K
V
F
T
w
1
1
B
S
/2
0
4
U
B
k
S
V
7
V
a
T
.2
A
A
tt.
F
P
2
A
M
10
C
h
0
S
8
o
K
V
d
B
m
S
u
4
U
a
le
F
r
V
s
t-U
T
1
P
0
w
S
K
/1
V
F
2
B
T
B
1
a
4S
tt. M
0
kV
A
A
1
o
P
2
4
du
C
.4
0
le
S
8
A
V
S
E
h
m
U
xp
a
V
r
t-
T
. to
U
1
0
P
4
w
K
S
/
F
V
2
3
B
B
T
a
4S
10
tt.
M
k
V
A
A
o
7
P
du
.2
20
C
A
les
8
h
S
S
V
U
m
E
V
a
xp
T
r
t-
1
.
U
0
to
P
K
w
4
F
S
/3
4
V
B
S
B
T
4S
U
a
1
V
tt.
0
T
M
kV
F
14
1
A
A
o
5
.
P
d
2
4A
K
u
C
0
B
le
h
8V
2
S
s E
F
m
a
xp
r
t-U
. to
P
4
S
S
VT
U
w
V
1
/4
T
0
1
B
k
2
5
V
1
a
K
A
.
tt.
F2
6A
2
M
0
B
h
8
o
2
V
d
S
u
le
A
s
P
C
S
m
a
r
t-U
2
P
8
.8
S
V
A
S
S
h
T
w
U
U
15
/2
V
V
T
B
T
k
1
F
V
at
5
1
A
K
t.
5
20
F2
M
K
B
8
od
B
4
V
4
F
u
S
le
s
S
A
U
P
V
C
T
S
1
1
5
m
4
K
a
.4
F
rt
A
3
-U
B
h
4
PS
w
S
/2
VT
B
a
1
tt
5
. M
kV
A
S
P
UV
A
od
C
2
ule
T
Sm
0
15
8
s
V
a
E
K
rt-U
F4
x
p.
B
P
to
w
4
S
S
/3
V
4
B
T
14
a
1
tt. M
5
.4
k
A
V
h
A
A
o
P
d
2
u
C
08
le
S
S
s
S
V
m
E
U
U
a
V
xp
V
r
T
TF
t-U
.
2
to
0
2
P
K
0
S
4
F
KB
V
2
B
2
T
4F
w
4
1
1
/4
S
.6A
5
k
Ba
V
h
A
tt.
2
A
M
PC
08
S
o
V
U
d
S
u
V
m
l
T
es
a
2
rt
0
-U
K
F
P
3
w
S
B
2
/2
VT
4
8
B
S
.8A
a
20
tt.
h
M
k
A
V
P
A
o
C
du
2
S
S
U
0
les
8
m
V
V
T2
a
E
rt-
x
0
p.
U
K
P
F
to 4
w
4
S
/3
B
S
V
1
4
U
4
B
T
S
.4
V
a
2
T
A
tt. M
0
F
h
k
3
V
0
A
A
od
K
P
2
B
S
u
C
08
4
le
U
S
F
s
V
V
m
E
T3
a
x
r
0K
p.
t-U
to
F
P
3B
4
S
2
VT
4
1
S
.6
w
2
A
/4
h
0
Ba
k
V
A
tt. M
2
S
U
0
A
8V
V
o
P
d
T3
C
u
S
l
0K
es
m
F
a
4
rt-U
B
2
4
8
S
.8A
P
w
S
/3
V
h
B
T
V
a
3
tt.
0k
M
V
o
A
A
o
lt
P
du
2
a
C
0
ge
les
S
8
V
m
&
E
C
a
x
A
r
p
t-U
o
C
.
n
to
I
n
P
n
e
S
4
p
2
c
V
u
1.
tio
t
T
6
w
n
3
A
/4
Ty
h
0k
B
V
pe
a
2
A
tt. M
0
2
s
8Y
0
8
/1
o
V
d
2
u
0
le
V
s
4
W
+G
2
8
A
.8
N
C
A
D
O
h
6
u
0
tp
H
u
z
t
20
8
Y
/12
D
C
0
V
In
4
p
B
W
u
at
D
+G
t
te
a
te
N
r
D
60
H
in
z
st
a
D
lle
a
+
te
/-
d
f
19
o
2V
R
e
pl
a
ce
m
Front
10-15 kVA
!
O
u
t
p
u
t
P
w
r
Z
o
n
e
P
r
o
b
e
1
Res
0
/
1
0
e
0
t
B
a
s
e
T
AP
96
1
0
1
/
1
9 N
0
0
et
wo
rk
M
an
ag
em
e
nt
C
ar
d E
M
!
O
u
t
p
u
t
P
w
r
Z
o
n
e
P
r
o
b
e
1
R
0
/
e
1
s
0
e
0
t
B
a
s
e
T
A
P96
1
0
1
/
1
9 N
0
0
e
tw
or
k
Ma
n
a
ge
m
ent
C
ar
d
EM
Blind
plates
cover
empty
battery
bays
e
o
m
a
p
_
w
o
r
l
d
.
d
f
m
A
p
p
a
re
n
t
/
R
A
a
c
te
ti
v
d
e
I
P
n
pu
o
w
t C
e
r
u
rre
n
t
R
a
te
d
O
ut
p
u
t
C
u
rre
n
t
B
a
tte
r
y
C
u
r
re
n
t
1
0
kV
A
/8
k
W
2
7
.1
A
2
0
8
V
2
7
.8
A
2
0
8
V
28
.9
A
15
k
V
A
/1
2
k
W
4
0.6
A
20
8V
4
1
.6
A
2
08
V
4
3
.
3A
2
0
k
V
A
/1
6
k
W
5
4
.
2A
2
08
V
5
5
.5
A
20
8
V
30
k
V
A
/2
4k
5
W
7
.7
A
8
1
.3
A
2
i
e
0
s
8V
8
3.
3A
r 1.
2
0
8
D
V
a
te
e
n
fo
t
r 2
S
E
.
R
8
E
ep
6
.6A
I
la
N
c
S
e
m
T
A
e
nt
L
L
B
A
E
T
F
I
O
O
R
N
E
I
N
C
S
O
T
S
N
R
U
N
U
P
E
C
P
C
T
L
T
I
Y
O
I
N
N
G
S
T
O
T
T
H
H
I
S
E
R
E
A
R
C
P
O
L
A
V
E
C
R
E
D
M
O
U
N
S
T
U
B
P
E
S
88
5
-2
3
2
1C
_
re
v
04
Rear
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
ia
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
Se
r
ia
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
Front without
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
TT
ER
Y
U
N
IT
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
TTE
R
Y UN
IT
S
e
r
i
a
l
:
M
o
d
e
l
:
BA
TT
E
RY UNIT
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
ER
Y
U
N
IT
S
e
r
i
a
l
:
M
o
d
e
l
:
BA
T
T
ER
Y
UN
IT
S
e
r
ia
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
TT
ER
Y
UN
IT
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
TT
ER
Y UNIT
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
TT
ER
Y UN
IT
S
e
r
i
a
l
:
M
o
d
e
l
:
BA
TT
ER
Y UNIT
S
e
r
ia
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
front panel 10-15 kVA
Front without
front panel 20-30 kVA
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 37
Appendix – UPS Components and Options
System sizes, part nos., number of Battery Modules and weights
Height (identical for all Enclosure sizes) 58.66 in/1490 mm
Depth (identical for all Enclosure sizes) 33 in/838 mm
System Size/ Enclosure
width
10 kVA 13.85 in/352 mm SUVT10KF1B2S 671.1 305.2 SUVT10KF2B2S 882.2 401.2
10 kVA 20.59 in/523 mm SUVT10KF1B4S 743.4 338.1 SUVT10KF2B4S 954.5 434.1
10 kVA 20.59 in/523 mm SUVT10KF3B4S 1165.6 530.1 SUVT10KF4B4S 1376.7 626.1
15 kVA 13.85 in/352 mm SUVT15KF2B2S 882.2 401.2
15 kVA 20.59 in/523 mm SUVT15KF2B4S 954.5 434.1 SUVT15KF3B4 1165.6 530.1
15 kVA 20.59 in/523 mm SUVT15KF4B4S 1376.7 626.1
20 kVA 20.59 in/523 mm SUVT20KF2B4S 1021.9 464.7 SUVT20KF3B4S 1233.0 560.7
20 kVA 20.59 in/523 mm SUVT20KF4B4S 1441.1 656.7
30 kVA 20.59 in/523 mm SUVT30KF3B4S 1235.2 561.7 SUVT30KF4B4S 1446.3 657.7
Part number coding:
Installed
weight
APC Part No. lbs kg APC Part No. lbs kg
Installed
weight
SUVT10KF 1B2S
SUVT 10K F 1B 2* S
Product
kVA
Voltage
1 Batt.
Module
*) 4 = max. 4 Battery Modules
With
start-up
service
Max.
2 Batt.
Modules
38 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Appendix – UPS Components and Options
Battery Module
One Battery Module consists of 4 Battery Units (shipping in the UPS Enclosure).
S
eri
a
l
:
M
o
d
e
l
:
B
ATT
ER
Y U
N
IT
S
eri
a
l
:
M
o
d
e
l
:
B
ATTE
R
Y U
N
IT
S
e
r
ial:
M
o
d
e
l
:
B
A
T
TER
Y
UN
IT
Se
ria
l:
M
o
d
e
l
:
B
A
TT
ER
Y
UN
IT
4 x 52.8 lb / 4 x 24
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 39
Appendix – UPS Components and Options
User interface
O
u
tp
ut
Pw
r
!
Z
o
ne
P
ro
b
e
10
/10
0
B
as
e
-T
R
e
se
t
1
0
/1
00
A
P
9
6
1
9
N
e
tw
o
r
k
M
a
n
a
g
e
m
e
n
t
C
a
r
d
E
M
Serial:
M
o
d
e
l
:
Serial:
M
o
d
e
BATTERY UNIT
Serial:
M
o
d
BATTERY UNIT
Serial:
M
o
d
BATTERY UNIT
Serial:
M
o
d
BATTERY UNIT
e
l:
e
l:
e
l:
BATTERY UNIT
Serial:
M
o
d
BATTERY UNIT
Serial:
M
o
d
BATTERY UNIT
Serial:
M
o
d
BATTERY UNIT
l:
Serial:
M
o
d
e
l:
Serial:
M
o
d
e
BATTERY UNIT
e
l:
Serial:
M
o
d
e
l:
BATTERY UNIT
e
l:
Serial:
M
o
d
e
l:
BATTERY UNIT
e
l:
Serial:
M
o
d
e
l:
BATTERY UNIT
l:
BATTERY UNIT
Serial:
M
o
d
e
l:
BATTERY UNIT
Serial:
M
o
d
e
l:
BATTERY UNIT
Serial:
M
o
d
e
l:
BATTERY UNIT
Display: user-control interface used to configure the functionality, monitor the system, set alarm
thresholds, and to provide audible and visual alarms.
Network Management Card with Environmental Monitor (AP9619): used for remote system
control and monitoring, e-mail notifications etc.
Computer-interface port for the connection of computers with APC Powerchute® software.
Mechanical Bypass Lever: used to bypass the upstream mains power around the UPS to support
the load directly = internal mechanical bypass operation.
Service port (for APC maintenance personnel only).
40 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Display port for the connection of display communication cable.
Documentation storage.
Inlet for communication cables.
Appendix – UPS Components and Options
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 41
Appendix – UPS Components and Options
Foot print
Rear Rear
926mm
Conduit Box.
Levelling feet.
523mm
352mm
Castors.
Communication cable inlets.
42 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Appendix – UPS Components and Options
APC Network Management Card AP9619 (installed in UPS) and APC Humidity Sensor
(Optional)
Humidity Sensor
Output
Pwr
!
APC Network Management Card with Environmental Monitor AP9619
Reset
Zone
Probe
10/100
AP9619 Network Management Card EM
10/100Base-T
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 43
Options
Battery Securing Bracket and Floor Anchoring
S
e
ri
a
l:
M
o
d
e
l
:
S
e
r
i
a
l
:
M
o
d
e
l
:
S
e
r
i
a
l
BATTERY UNIT
S
e
ri
M
o
d
BATTERY UNIT
:
M
o
d
e
l
:
S
e
r
ia
l
:
M
o
d
e
l:
BATTERY UNIT
BATTERY UNIT
a
l:
e
l:
S
e
r
i
a
l
:
M
o
d
e
l
:
S
e
r
i
a
l:
M
o
d
e
l
:
BATTERY UNIT
BATTERY UNIT
BATTERY UNIT
Battery Lock
for 2 Battery
Units
S
e
r
i
M
o
d
BATTERY UNIT
a
l
:
e
l
:
APC Smart-UPS VT Battery Lock Kit for 1 Battery Module SUVTOPT003
Reuse transport
brackets
as Floor Anchoring
Brackets
Note
Note
Battery Locks are also applicable to XR Battery Enclosure.
Floor-anchoring bolts are not provided with the UPS. Purchase the floor anchors locally.
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 44
Extended Run Battery Enclosure (XR Battery Enclosure)
XR Battery Enclosure with Front Panel
58.66 in/
1490 mm
36.45 in/
926 mm with Conduit Box.
20.59 in / 523 mm
Battery Module
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
Appendix – Options
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
XR with DC Breaker, DC
Fuses and 2 Batt. Modules
S
er
ial:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
S
T
eri
al:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
er
ial
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
S
e
ri
al:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
Se
ria
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
IT
S
er
ial:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
Se
ria
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
S
T
e
r
ial:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
Version with DC fuses
and 2 Battery Modules
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
S
I
T
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
S
T
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
IT
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
S
T
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
XR with DC Breaker, DC
Fuses and 6 Batt. Modules
S
e
ria
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
S
T
er
ia
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
S
e
ri
a
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
Se
T
r
ia
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
S
e
ria
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
er
ia
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
S
er
i
al
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
S
er
i
al:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
Se
ria
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
T
S
e
ri
a
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
Se
r
ial
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
S
er
ia
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
ial
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
Se
r
ia
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
S
eri
a
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
ria
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
ri
al
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
S
T
e
r
ial
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
er
ia
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
ial
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
S
T
e
ri
al:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
er
ia
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
Se
ria
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
S
T
e
r
ial
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
Version with DC fuses
and 6 Battery Modules
S
e
r
ia
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
S
T
e
r
ial
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
S
e
ri
al
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
S
T
e
r
i
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
S
e
r
ia
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
r
ial
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
S
e
r
ial
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
S
er
ial
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
S
e
ria
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
T
S
er
ia
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
er
ia
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
S
T
e
ri
al:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
S
er
ia
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
S
e
ri
al:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
S
e
ri
al:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
eri
a
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
ria
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
S
T
e
ri
a
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
e
ri
al:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
er
ia
l
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
IT
S
eri
al
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
S
er
ial
:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
Se
r
i
a
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
S
T
er
ia
l:
M
o
d
e
l
:
B
A
T
T
E
R
Y
U
N
I
T
XR Battery Enclosure weights
2 Battery Modules 887.3 lbs/403.5 kg
6 Battery Modules 1731.7 lbs/787.5 kg
Battery Module weight
4 units = 1 Battery Module 4x50 lbs/4x24 kg
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 45
Appendix – Options
Part numbers for XR Battery Enclosures
XR Battery Enclosure
Enclosure with DC breaker, DC fuses and 2 Battery Modules (expandable to 6) SUVTBXR2B6S
Enclosure with DC breaker, DC fuses and 6 Battery Modules SUVTBXR6B6S
Enclosure with DC fuses and 2 Battery Modules (expandable to 6) SUVTXR2B6S
Enclosure without DC fuses and 6 Battery Modules SUVTXR6B6S
Part number for Battery Module
One Battery Module consists of 4 Battery Units.
Battery Module
Battery Module (4 battery units) SYBT4
46 Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B
Maintenance Bypass Panels with Power Distribution Capability
Further details on APC Maintenance Bypass Panel (MBP) with Power Distribution
Capability are available on www.apc.com.
Note
Appendix – Options
MBP
(line-up-and-match)
(wall-mount)
29.53 in/
750 mm
MBP
37.36 in/
949 mm
7.48 in/
190 mm
MBP (line-up-and-match) with
Power Distribution Capability
33 in/
13.85 in/352 mm
838 mm
58.66 in/
1490 mm
The Maintenance Bypass Panel provides overcurrent protection to the entire UPS system. It is also
used to bypass the utility power around the UPS instead of through the system, e.g. when UPS
maintenance is carried out.
For more details on optional APC equipment for the APC Smart-UPS® VT, contact APC
Technical Support in the U.S. at 800-555-2725. For other countries, see technical
Note
990-1599B Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 47
support numbers on rear cover.
APC Worldwide Customer Support
Customer support for this or any other APC product is available at no charge in any of the following ways:
• Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer
support requests.
– www.apc.com (Corporate Headquarters)
Connect to localized APC Web sites for specific countries, each of which provides customer
support information.
– www.apc.com/support/
Global support searching APC Knowledge Base and using e-support.
• Contact an APC Customer Support center by telephone or e-mail.
– Regional centers:
Direct InfraStruXure Customer Support Line (1)(877)537-0607 (toll free)
APC headquarters U.S., Canada (1)(800)800-4272 (toll free)
Latin America (1)(401)789-5735 (USA)
Europe, Middle East, Africa (353)(91)702000 (Ireland)
Japan (0) 35434-2021
Australia, New Zealand, South Pacific area (61) (2) 9955 9366 (Australia)
– Local, country-specific centers: go to www.apc.com/support/contact for contact information.
Contact the
information on how to obtain local customer support.
APC representative or other distributor from whom you purchased your APC product for
Entire contents © 2005 American Power Conversion. All rights reserved. Reproduction in
whole or in part without permission is prohibited. APC, the APC logo, the APC Powerchute
and Smart-UPS VT are trademarks of American Power Conversion Corporation and may be
registered in some jurisdictions. All other trademarks, product names, and corporate names
are the property of their respective owners and are used for informational purposes only.