Back-UPS ES 525
w w w
Inspection/Placement Connect Equipment
1
1
11
Ensure the following items are inside the box:
Notify the reseller if damage is found. Please fill out the
Warranty Registration Card, or fill out an on-line form at
www.apc.com/ru, to obtain warranty coverage.
Place the UPS as follows:
.apc.com
• User’s Manual
• USB Cable
• Safety Manual
• Warranty Registration Card
• PowerChute
• Provide 5 cm clearance at the top and sides for
adequate airflow around the UPS.
• Avoid direct sunlight.
• Avoid excessive heat.
• Avoid excessive humidity or liquids.
• Avoid excessive dust.
0 - 40oC
®
Personal Edition Software CD-ROM
Operation and
User’s Manual
2
2
22
Connect Universal Serial Bus (USB) Cable
The supplied USB cable and software provide automatic file saving and shutdown of the
operating system in the case of a sustained power cut.
Connect the USB cable to the Back-UPS ES Data Port. Connect the other end of the cable to
computer’s USB port. When installed the software will automatically find the USB Port of your
computer.
If your computer has a serial port, instead of a USB port, you can request a serial cable from
APC for use in connecting to the Back-UPS ES 525. Contact the office closest to you (see
APC Contact Information below). A serial cable will be sent to you at no charge.
These outlets are powered whenever the Back-UPS ES is switched ON. During a power
outage or other utility problems (low and high voltages), these outlets will be powered for a
limited time by the Back-UPS ES. Plug your computer, monitor, and one other device into
these outlets.
Caution: The plug on
the supply cord is the
disconnect device for
this product. The socketoutlet that you plug into
shall be located near the
equipment and shall be
easily accessible. The
socket-outlet must be a
grounding type.
Plug the Back-UPS ES power cord directly into a wall outlet; not a surge
protector or power strip.
Battery Back-up plus Surge Protection
Battery Backup plus Surge Pr otection
Surge Protec tion
Status
see back
panel
Back-UPS ES
3
3
33
Battery Replacement
The Back-UPS ES is shipped with battery connected.
Typical battery life is 3 to 6 years. Battery replacement
is a safe procedure isolated from electrical hazards.
Do not replace the battery when the UPS is On
Battery (amber indicator is lit).
NOTE: Small sparks may occur during battery
connection. This is normal.
1
2
Software Installation
Press the ON/OFF switch to power the unit ON.
A single short beep and the green “Power On”
indicator confirms that Back-UPS ES is on and ready
to provide protection.
The Back-UPS ES should initially charge for at least
16 hours to ensure sufficient runtime. The unit is
being charged whenever it is connected to utility
power, whether the unit is turned ON or OFF.
Install PowerChute
Place the PowerChute Personal Edition Software CDROM into your computer and follow the installation
instructions on the screen.
Turn the Back-UPS over. Press down on the two
release tabs. Slide the battery cover completely
off of the unit.
Battery
Cover
Lift the battery out of the UPS. Note the wire
color at each terminal. Disconnect the two wires
from the battery terminals.
®
Personal Edition Software
Release Tabs
Surge Protection
This outlet provides full-time protection from surges even if the Back-UPS ES is switched
OFF. Plug your printer, fax machine, scanner, or other peripheral that does not need battery
power into this outlet.
Connect FAX/Modem/Phone
Back-UPS ES protects a single line (2-wire) fax, modem or phone from surges when it is
connected through the Back-UPS ES as shown.
Wall Outlet
Modem/Phone/Fax
Computer
USB Port
Breaker
AC Line
Cord
Circuit
Power
Switch
Status
see back
panel
UPS Status
Indicator
Status Indications
The Back-UPS ES indicates operating status using a combination of visual and audible indicators.
Status LED Audible Indication Status Alarm Terminates When
Green None On Line - UPS is supplying conditioned AC
Amber 4 beeps every 30
Amber Rapid beeping Low Battery Warning - UPS is supplying
Amber, flashing None Start-up Self-Test -UPS software is
Red Beeps for 1 minute
Red Constant tone Overloaded - Occurs when one or more of
Alternating Ambe r
and Green
Green and
Amber, flashing
seconds
every 5 hours.
None Shutdown - Occurs when the UPS is
Beeps every 2
seconds.
power to the connected equipment.
On Battery - UPS is supplying battery
power to the equipment connected to the
Battery outlets.
battery power to the equipment connected
to the Battery outlets and the battery is near
exhaustion.
running a diagnostic test.
Replace Battery - occurs when the battery
fails self-test.
the battery powered outlets is overloaded.
operating On Battery and has shutdown the
applications running on the connected
computer and has shutdown the computer.
Unit is online and battery is disconnected. UPS power switch is turned
See the Troubleshooting section for additional assistance.
n/a
The UPS transfers back to On
Line operation, or when the
UPS is turned off.
The UPS transfers back to On
Line operation, or when the
UPS is turned off.
The UPS is turned off with the
power switch or when the test is
completed.
The UPS is turned off with the
power switch or the battery is
replaced.
The UPS is turned off with the
power switch, or the equipment
connected to the overloaded
outlet(s) is disconnected.
n/a
OFF or when the battery is
connected.
Battery WireBattery Terminal
990-1466 Copyright © 2003 American Power Conversion Corp. All rights reserved.
Connect the two wires to the replacement
3
battery and install the battery into the unit.
APC, Back-UPS and PowerChute are registered trademarks of American Power Conversion Corp.
Slide the battery cover on the unit until it
4
locks in place.
All other trademarks are property of their respective owners.
Use the table below to solve minor Back-UPS ES installation or operation problems. Consult APC Online Technical Support or call APC
Troubleshooting
Technical Support for assistance with problems that cannot be resolved using the table below:
Problem Probable Cause Solution
Back-UPS ES will not turn on.
No power available at the Surge Protection
outlet.
Connected equipment loses power.
The Status indicator is lit (amber) and the
Back-UPS ES is beeping four times every 30
seconds.
The Status indicator flashes (amber) once
per second and the Back-UPS ES beeps
once per second at the same time.
Inadequate runtime.
Battery is disconnected and utility power is not available at
the wall outlet.
Surge Protection outlet has been overloaded.
Utility power not available at the wall outlet.
Equipment is connected to the “Surge Protection” outlet.
The Back-UPS ES is overloaded.
The PowerChute Personal Edition software has performed
a shutdown due to a power failure.
The Back-UPS ES has exhausted its available battery
power.
Connected equipment does not accept the stepapproximated sine waveform the Back-UPS ES.
The Back-UPS ES may require service.
The Back-UPS ES is operating on battery.
Battery capacity is low (about 2 minutes of use remaining).
The battery is not fully charged.
Battery is near the end of useful life.
Connect the battery (see Battery Replacement) and ensure power is available at the
wall outlet.
Move equipment plugged into Surge Protection outlet to Battery Backup plus Surge
Protection outet.
Ensure that the fuse or circuit breaker for the outlet is not tripped, and that the wall
switch controlling the outlet (if any) is in the ON position.
Ensure that the equipment you want to stay powered during a power failure is
plugged into the “Battery Backup plus Surge Protection” outlets and NOT the “Surge
Protection” outlet.
Make sure the equipment plugged into the outlets of the unit are not overloading the
capacity of the unit. Try disconnecting some of the equipment and see if the problem
continues.
The Back-UPS ES is operating normally.
The Back-UPS ES can only operate on battery power for a limited amount of time.
The unit will eventually turn off when the available battery power has been used.
Allow the unit to recharge for 5 hours before continuing use of the unit.
The output waveform is designed for computers and computer-related equipment. It
is not designed for use with motor-type equipment.
Contact APC Technical Support for further troubleshooting.
The Back-UPS ES is operating normally and using battery power. Once On Battery,
you should save your current work, power down your equipment, and turn the unit
OFF. Once normal power is restored, you may turn the unit back ON and power your
equipment.
The Back-UPS ES is about to shut off due to a low battery charge condition! When
the unit beeps once every second, the battery has about 2 minutes of power
remaining. Immediately power down your computer and turn the unit OFF. When
normal power returns, the unit will recharge the battery.
Allow the unit to charge by leaving it plugged into the wall at least 16 hours.
As a battery ages, the amount of runtime available will decrease. You can replace
the battery by ordering one at www.apc.com/ru. Batteries also age prematurely if the
Back-UPS ES is placed near excessive heat.
Specifications
Model BE525-RS
Input Voltage 230 V AC Nominal
Frequency 47 - 53 Hz
Brownout Transfer 160 V AC, typical
Over-voltage Transfer 280 V AC, typical
Output Battery Backup with Surge
Capacity (3 outlets)
Surge Only Capacity (1 outlet) 6 Amps (including UPS output)
Voltage - On Battery 230 V AC +
Transfer Time 5 ms typical, 10 ms maximum
Protection and Filter AC Surge Protection Full time, 150 joules
Telephone Surge Protection Single line (2-wire)
EMI/RFI Filter Full time
AC Input Resettable circuit breaker
Battery Type Sealed, maintenance-free lead acid
Typical Life 3 - 6 years depending on the number of
discharge cycles and environmental temperature
Physical Net Weight 7.3 kg (16 lb)
Size (UPS only) 12 x 28.5 x 19.7 cm
Operating Temperature
Storage Temperature
Operating Relative Humidity 0 to 95% non-condensing
Operating Elevation 0 to 10,000 ft (0 to 3,000m)
525 VA / 300 W
(step-approximated sine wave)
(4.72” (H) x 11.2” (W) x 7.8” (D))
o
0
C to 40oC (+32oF to 104oF)
o
-15
C to 45oC (+5oF to 113oF)
8%
APC Contact Information
Online Technical Support . . . . . . . . . . http://support.apc.com
Web Site . . . . . . . . . . . . . . . . . . . . . . . www.apc.com/ru
Worldwide . . . . . . . . . . . . . . . . . . . . . . +1.800.800.4272
APC Russia: . . . . . . . . . . . . . . . . . . . 7 (095) 916 71 66 Technical Support
7 (095) 929 90 95 Sales Support
Order Replacement Battery
Replace with an APC qualified battery. Replacement batteries can be ordered from
APC Global Services. Have your Back-UPS ES model number available when
ordering. Your model number can be found on the bottom of the unit.
Warranty
The standard warranty is 2 years from the date of purchase. APC’s standard
procedure is to replace the original unit with a factory-reconditioned unit. Customers
who must have the original unit back due to assigned asset tags and set depreciation
schedules must declare such a need at first contact with APC Technical Support. APC
will ship the replacement unit once the defective unit is received by the repair
department, or cross-ship upon the provision of a valid credit card number. The
customer pays for shipping to APC. APC pays ground freight transportations costs
back to the customer.
Service
1. Consult the Troubleshooting section to eliminate common problems.
2. Verify the battery is connected (see Battery Replacement) and the Circuit Breaker is
not tripped (see Troubleshooting section).
If you still have problems or questions, please contact APC via the internet or at one of
the phone numbers listed below.
3. Before contacting APC, please be sure to record the date purchased, UPS model,
and serial number (on bottom of unit).
4. Be prepared to troubleshoot the problem over the telephone with a Technical
Support Representative. If this is not successful, the representative will issue a Return
Material Authorization Number (RMA#) and a shipping address.
Pack the unit in its original packaging. If the original packaging is not available, ask
APC Technical Support about obtaining a new set. Pack the unit properly to avoid
damage in transit. Never use foam beads for packaging. Damage sustained in transit is
not covered under the warranty (insuring the package for full value is recommended).
5. Write the RMA# on the outside of the package.
6. Return the unit by insured carrier to the address given to you by the APC Technical
Support representative.