Characteristics
SUVTP30KH
APC Smart-UPS VT 30kVA 400V, w/Internal
Maintenance Bypass & Parallel Capability
Overview
Lead time Special Order - Call for Quoted Lead Times
General
Provided equipment CD with software
Performance multiplier 1
Number of tare power 360W
Number of power module free slots 0
Number of power module filled slots 0
Redundant No
UPS size L
Value multiplier 1
Network management card
Power modules ship installed
User manual
Bolt down brackets
Installation guide
Physical
Colour Black
Depth 83.8Cm
Height 82.3Cm
Mounting location Front
Mounting preference No preference
Net weight 182.5Kg
Mounting mode Not rack-mountable
USB compatible No
Width 52.3Cm
Input
Network frequency 47...70 Hz auto-sensing
Number of input connectors 1 hard wire 5-wire (3P + N + E)
Input voltage limits 304...477 V
Inputvolt_other 380 V
Maximum input current 41A
13-Apr-2021
415 V
1
Switching current capacity 63A
Input voltage 400 V 3 phases
Cos phi 0.98
Output
Rated power in W 24000W
Maximum configurable power in W 24000W
Harmonic distortion Less than 5 % at full load
Output frequency 47...53 Hz for 50 Hz nominal sync to mains
Outputvolt_other 380 V
Crest factor Unlimited
UPS type Double conversion online
Wave type Sine wave
Connections - terminals 1 screw terminals
Output connector type Hard wire 4-wire (3P + E) 1
Output overload operation 10 minutes at 125% and 60 seconds at 150%
Bypass type Built-in maintenance bypass
Curve equation Efficiency
Curve fixed loss 0.01
Curve load maximum 100%
Curve load minimum 2%
Curve proportional loss 0.0176
Curve square loss 0.0134
Curve X-axis maximum 100%
Curve test cond ID Curve fit to measured efficiency data. All measurements taken in normal operat-
Curve X-axis minimum 0%
Curve X-axis title Load
Curve X-axis units Percentage
Curve Y-axis maximum 100%
Curve Y-axis minimum 50%
Curve Y-axis title Efficiency
Curve Y-axis units Percentage
Graph display 1
Maximum output current 48A
Output voltage 230 V
Maximum configurable power in VA 30000VA
Rated power in VA 30000VA
50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
415 V
Hard wire 5-wire (3P + N + E) 1
Built-in static bypass
ing mode, at typical environmental conditions, with nominal electrical input and balanced PF = 0.8 output.
400 V 3 phases
Conformance
Product certifications C-Tick
Standards EN 50091-2
2
EN/IEC 62040-3
IEC 61000-3-2
ISO 14001
ISO 9001
VFI-SS-112