APC SURT6KRMXL3U-TF5 Datasheet

Product data sheet
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Characteristics
i This Product is Obsolete
SURT6KRMXL3U-TF5
APC Smart-UPS RT 6KVA RM 208V w/ 208V to 120V 2U Step-Down Transformer
Commercial status
This Product is Obsolete :
Lead time Usually in Stock
General
Provided equipment CD with software
Performance multiplier 1
Number of tare power 88W
Number of power module free slots 0
Number of power module filled slots 0
Redundant No
Size UPS version Internetworking
UPS size S
Value multiplier 1
Rack mounting support rails Smart UPS signalling RS-232 cable User manual Web/SNMP management card
Server Telecom
Physical
Cable length 10Ft (3.05m)
Number of rack unit 5U
Color Black
Depth 25.98In (66cm)
Height 8.58In (21.8cm)
Mounting location Front
Mounting preference Lower
Net weight 221.45Lb(US) (100.45kg)
Mounting mode Rack-mounted
Two post mountable 0
Apr 13, 2021
1
USB compatible No
Width 17.01In (43.2cm)
Input
Input Frequency 50/60 Hz +/- 5 Hz auto-sensing
Plug standard NEMA L6-30P
Efficiency at full load 100...280 V adjustable
Number of cables 1
Nominal Input Voltage 208 V
160...280 V
Output
Rated power in W 4200W
Max Configurable Power (Watts) 4200W
Harmonic distortion Less than 3%
Output Frequency (sync to mains) 50/60 Hz +/- 3 Hz user adjustable +/- 0.1 Hz sync to mains
Crest factor 3 : 1
Topology Double Conversion Online
Waveform Type Sine wave
Nb of power socket outlets 12 NEMA 5-20R
Bypass type Internal Bypass (Automatic and Manual)
Curve equation Efficiency
Curve load maximum 100%
Curve X-axis maximum 100%
Curve X-axis minimum 0%
Curve X-axis title Load
Curve X-axis units Percentage
Curve Y-axis maximum 100%
Curve Y-axis minimum 50%
Curve Y-axis title Efficiency
Curve Y-axis units Percentage
Efficiency at full load 92% full load)
Graph display 1
Output voltage 120 V
Maximum configurable power in VA 6000VA
Rated power in VA 6000VA
2 NEMA L6-20R 1 NEMA L6-30R
208 V
Conformance
Product certifications CSA
Standards FCC Part 15 class A
UL 1778
Environmental
Ambient air temperature for operation 32…104°F (0…40°C)
Relative humidity 0…95% non-condensing
Operating altitude 0...10000 ft
Ambient air temperature for storage 5…113°F (-15…45°C)
Storage altitude 0…50000Ft (0.00…15240.00m)
Acoustic level 55 dBA
Online Thermal Dissipation 1324Btu/H