American Power Conversion Smart UPS SUA3000XL, Smart UPS 230 Vac, Smart UPS 120 Vac, Smart UPS 3000 VA XL, Smart UPS 208 VAC User Manual

...
User Manual English
APC Smart-UPS® XL
2200/3000 VA XL
120/208/230 VAC
Tower/Rack-Mount 5U
990-2975 09/2006
Introduction
About this UPS
The American Power Conversion (APC®) Uninterruptible Power Supply (UPS) provides protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power. The UPS provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully discharged.
Unpack
Read the Safety Guide before installing the UPS.
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage.
The packaging is recyclable; save it for reuse or dispose of it properly.
Check the package contents:
•UPS
•Front bezel
•Literature kit containing: – EPO connector – Serial cable – USB cable – Eight ornamental screws for
securing the unit in the rack
– Eight 5/16 in (.8 cm) pan-head
screws for attaching cleats to the chassis rails (required for four post rack only)
– Eight 5/8 in (1.6 cm) pan-head
screws for attaching rack-mount brackets to the unit
– Eight snap-on speed nuts – Two rail cleats (required for four post
rack only) – Two rack-mount brackets – Product documentation – Smart-UPS® User Manuals CD – PowerChute® Business Edition CD – Safety information – Warranty information
Additional contents for 230 V models:
– APC power cable – Alternate input power cord
(UK customers) –IEC Power cord – IEC jumper cables
Specifications
Temperature
Operating Storage
32° to 104° F (0° to 40° C) 5
° to 86° F (-15° to 30° C) charge the UPS battery every six months
86
° to 113° F (30° to 45° C) charge the UPS battery every three months
Maximum Elevation
Operating Storage
Humidity
Wei ght
Maximum Number of External Battery Packs Supported by the Smart-UPS XL
10,000 ft (3,000 m) 50,000 ft (15,240 m)
0 to 95% relative humidity, non-condensing
142 lbs (64 kg) with battery module 89 lbs (40 kg) without battery module 27 lbs (12 kg) each battery module
NOTE: The model and serial numbers are located on a small, rear panel label. For some models, an additional label is located on the chassis under the front bezel.
Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual 3
This unit is intended for indoor use only. Select a location sturdy enough to handle the weight.
Do not operate the UPS where there is excessive dust or the temperature or humidity are outside the specified limits.
Environmental factors impact battery life. High temperatures, poor utility power, and frequent, short duration discharges will shorten battery life.
142 lbs (64 kg)
10
Installation
The UPS is shipped in tower configuration.
Tower Configuration
Connect the battery.
After the battery has been connected, tuck the battery cables in between the battery and the battery door. This will ensure a secure fit of the bezel to the unit.
4 Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual
Rack-Mount Configuration
This unit is intended for mounting in a two post rack. To order a four post rack-mount kit contact your dealer or refer to the APC Web site, www.apc.com.
Tower to rack-mount conversion procedure
The UPS and the battery modules are heavy. Remove the battery modules to lighten the UPS during installation.
Pull the battery disconnect strap attached to the battery connector. DO NOT pull the battery cables to disconnect the battery.
Battery Disconnect Strap
Remove the top cover and . Remove and rotate the display
panel .
Foam Spacer
Disconnect Battery
Four post rack-mount bracket position
Two post rack-mount bracket position
x4
5/8 in
1.6 cm
A four post rack configuration requires installation of two brackets in the forward position (see diagram above), two cleats (supplied with this unit), and the four post rails. The rails can be ordered through the APC Web site www.apc.com.
Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual 5
Install unit in rack
Ensure rack stability prior to installing devices in the rack.
The UPS should be installed at or near the bottom of the rack. If external battery packs are to be installed in the rack, the UPS must be the top unit in the configuration.
Connect Battery
x4 Ornamental
Foam Spacer
After all of the batteries have been connected, tuck the battery cables in between the batteries and the battery doors. This will ensure a secure fit of the bezel to the unit.
Accessories
This UPS is equipped with an accessory SmartSlot. Refer to the APC Web site, www.apc.com for available accessories.
If a standard accessory, such as a Network Management card is to be installed on this UPS, refer to the Utility CD for user documentation.
Install accessories prior to connecting power to the UPS.
6 Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual
Start-Up
Connect Equipment and Power to the UPS
1. The UPS features a transient voltage surge-suppression (TVSS) screw located on the rear panel, for connecting the ground lead on surge suppression devices such as telephone and network line protectors.
Prior to connecting the grounding cable, ensure that the UPS is NOT connected to utility or battery power.
2. Connect equipment to the UPS. NOTE: This UPS is equipped with an external battery connector on the rear panel of the unit.
Where appropriate use an APC extension battery cable. For ordering details contact your dealer or APC through the Web site www.apc.com.
3. Add optional accessories to the SmartSlot located on the rear panel.
4. Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.
230 V models: The utility power cord is supplied in the UPS literature kit. Prior to connecting the
utility power, connect the ground lead (optional) to the TVSS screw.
5. 120 V models: Check the SITE WIRING FAULT LED located on the rear panel. The LED will be illuminated if the UPS is plugged into an improperly wired utility power outlet, (see Troubleshooting).
6. To use the UPS as a master on/off switch be sure all connected equipment is switched on.
Rear Panels
3000 VA
120 VAC
2200 VA
120 VAC
3000 VA
208 VAC
2200 VA 3000 VA
230 VAC
Start the UPS
1. Press the button on the front panel to start the UPS.
The battery charges to 90% capacity during the first four hours of normal operation. Do not
expect full battery run capability during this initial charge period.
Refer to the APC Web site, www.apc.com for battery runtimes.
2. For optimal computer system security, install PowerChute Smart-UPS monitoring software.
Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual 7
Communication Ports
SERIAL PORT
USB PORT
Use only the supplied cable to connect to the serial port. A standard serial interface cable is incompatible with the UPS.
Serial and USB ports cannot be used simultaneously.
Emergency Power Off
The emergency power off (EPO) feature is user configurable. EPO provides immediate de-energizing of connected equipment from a remote location, without switching to battery operation.
1. Use the EPO connector supplied with the UPS.
2. Use a normally-open contact to connect the +24 terminal to the IN terminal. External voltage is not required.
3. Wire the four-pin connector to the EPO system.
EPO PORT
(located on rear panel)
The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect it only to other SELV circuits. The EPO interface monitors circuits that have no determined voltage potential. Such closure circuits may be provided by a switch or relay properly isolated from the utility. To avoid damage to the UPS, do not connect the EPO interface to any circuit other than a closure type circuit.
Use one of the following cable types to connect the UPS to the EPO switch.
CL2: Class 2 cable for general use.
CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.
CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.
CLEX: Limited use cable for use in dwellings and for use in raceways.
For installation in Canada: Use only CSA certified, type ELC, (extra-low voltage control cable).
For installation in other countries: Use standard low-voltage cable in accordance with national and local regulations.
EPO
Connector
8 Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual
Operation
Display Panels
120/208 V models
120/208 V
Battery Charge
230 V models
Display Panel Indicators and Function Buttons
Indicator
LED
Indicator Title Description
230 V
On Line The UPS is supplying utility power to the connected equipment,
(see Troubleshooting).
AVR Trim The UPS is compensating for a high utility voltage. Refer to the APC Web site,
AVR Boost The UPS is compensating for a low utility voltage. Refer to the APC Web site,
On Battery The UPS is supplying battery power to the connected equipment.
Overload The connected equipment is drawing more than the UPS power rating allows,
Replace Battery/Battery Disconnected
Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual 9
www.apc.com for AVR settings.
www.apc.com for AVR settings.
(see Troubleshooting).
The battery is disconnected or must be replaced, (see Troubleshooting).
Indicator
LED
Indicator Title Description
120 V
Battery Charge
Feature
Button
230 V
208 V
Diagnostic Utility Voltage
The UPS has a diagnostic feature that indicates the utility voltage.
The UPS starts a self-test as part of this procedure. The self-test does not affect the voltage display.
Press and hold the button to view the utility voltage bar graph indicator.
Battery Charge
After a few seconds, this five-LED Battery Charge indicator on the right of the display panel will show the utility input voltage.
Refer to the figure on the left for the voltage reading. Values are not listed on the UPS.
The indicator on the UPS shows the voltage is between the displayed value on the list and the next higher value, (see Troubleshooting).
Feature Title Function
Power On Press this button to turn on the UPS. Continue reading for additional
capabilities.
Self-Test Automatic: The UPS performs a self-test automatically when tuned on, and
every two weeks thereafter (by default). During the self-test, the UPS briefly operates the connected equipment on battery.
Manual: Press and hold the
button for a few seconds to initiate the
self-test.
Cold Start When there is no utility power and the UPS is off, the cold start feature will
switch the UPS and connected equipment onto battery power, (see Troubleshooting).
Power Off Press this button to turn off the UPS.
10 Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual
Configuration
UPS settings
Settings are adjusted through PowerChute software or optional SmartSlot accessory cards.
Factory
Function
Automatic Self-Test
UPS ID UPS_IDEN Up to eight characters
Date of Last Battery Replacement
Minimum Capacity Before Return from Shutdown
Voltage Sensitivity
The UPS detects and reacts to line voltage distortions by transferring to battery operation to protect the connected equipment.
Default
On startup and every 14 days (336 hours) there after
Manufacture Date
0 percent • 0%
High sensitivity Brightly
User Selectable
Choices Description
• On startup and every 7 days (168 hours) there after
• On startup and every 14 days (336 hours) there after
• On startup only
• No self-test
(alphanumeric)
mm/dd/yy Reset this date when you replace the battery
• 60%
• 15%
• 30%
• 45%
illuminated: high sensitivity
Dimly illuminated: medium sensitivity
No illumination: low sensitivity
• 75%
• 90%
Set the interval at which the UPS will execute a self-test.
Uniquely identify the UPS, (i.e. server name or location) for network management purposes.
module.
Specify the percentage to which batteries will be charged following a low battery shutdown before powering connected equipment.
Adjust by pressing the VOLTAGE SENSITIVIY switch (rear panel). Use a pointed object, (such as a pen) to do so.
Note: In situations of poor power quality, the UPS may frequently transfer to battery operation. If the connected equipment can operate normally under such conditions, reduce the sensitivity setting to conserve battery capacity and service life.
Alarm Delay Control
Shutdown Delay 90 seconds • 0 s
Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual 11
Enable • Enable
• Mute
• Disable
• 90 s
• 180 s
• 270 s
• 360 s
• 450 s
• 540 s
• 630 s
Mute ongoing alarms or disable all alarms.
Set the interval between the time when the UPS receives a shutdown command and actual shutdown.
Function
Factory
Default
User Selectable
Choices Description
Low Battery Warning
PowerChute software interface provides automatic, unattended shutdown when approximately two minutes of battery operated run time remains.
Synchronized Turn-on Delay
High Transfer Point 208 V models:
2 minutes
LED is located on rear panel
0 seconds • 0 s
225 VAC
120 V models: 127 VAC
230 V models:
253 VAC
Brightly illuminated:
low battery warning level of about 2 minutes
Dimly illuminated:
low battery warning level of about 5 minutes
No illumination:
low battery warning level is about 8 minutes
• 240 s
• 60 s
• 120 s
• 180 s
• 225 VAC
• 229 VAC
• 127 VAC
• 130 VAC
• 253 VAC
• 257 VAC
• 300 s
• 360 s
• 420 s
• 233 VAC
• 237 VAC
• 133 VAC
• 136 VAC
• 261 VAC
• 265 VAC
The low-battery warning beeps are continuous when two minutes of run time remain.
To change the default interval setting, use a pointed object such as a pen to press the VOLTAGE SENSITIVIY switch (rear panel), while
pressing the button, (front display).
Change the low battery warning interval setting to the time that the operating system or system software requires to safely shut down.
Specify the time the UPS will wait after the return of utility power before start up, (to avoid branch circuit overload).
To avoid unnecessary use of the battery where utility voltage is chronically high, set the high transfer point higher if the connected equipment can tolerate this condition.
Low Transfer Point 120 V models:
106 VAC
208 V models:
182 VAC
230 V models:
208 VAC
Output Voltage
230 V models 230 VAC
12 Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual
• 97 VAC
• 100 VAC
• 182 VAC
• 178 VAC
• 196 VAC
• 200 VAC
• 220 VAC
• 230 VAC
• 103 VAC
• 106 VAC
• 174 VAC
• 170 VAC
• 204 VAC
• 208 VAC
• 240 VAC
To avoid unnecessary use of the battery where utility voltage is chronically low, set the low transfer point lower if the connected equipment can tolerate this condition.
Set the output voltage of the UPS.
Troubleshooting
Use this chart to solve minor UPS installation and operation problems. Refer to www.apc.com for assistance with complex UPS problems.
Problem and/or Possible Cause Solution
UPS will not turn on
The battery is not connected properly. Check that the battery connector is fully engaged.
button not pushed.
The UPS is not connected to utility power supply.
Very low or no utility voltage Check the utility power supply to the UPS by plugging in a table lamp. If the
UPS will not turn off
The UPS is experiencing an internal fault
UPS beeps occasionally
Normal UPS operation when running on battery.
UPS is not providing expected backup time
The UPS battery(s) are weak due to a recent power outage or battery(s) are near the end of their service life.
All LEDs are illuminated and the UPS emits a constant beeping
The UPS is experiencing an internal fault.
Press the
Check that the power cable from the UPS to the utility power supply is securely connected at both ends.
light is very dim, have the utility voltage checked.
Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately.
None: The UPS is protecting the connected equipment. Press the button to silence this alarm.
Charge the battery(s). Batteries require recharging after extended outages. Batteries can wear faster when put into service often or when operated at elevated temperatures. If the battery(s) are near the end of their service life, consider replacing the battery(s) even if the replace battery LED is not yet illuminated.
Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately.
button once to power-up the UPS and connected equipment.
Front panel LEDs flash sequentially
The UPS has been shut down remotely through software or an optional accessory card.
All LEDs are off and the UPS is plugged into a wall outlet
The UPS is shut down or the battery is discharged from an extended outage.
Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual 13
None: The UPS will restart automatically when utility power returns.
None: The UPS will restart automatically when utility power is restored and the battery has a sufficient charge.
Problem and/or Possible Cause Solution
The Overload LED is illuminated and the UPS emits a sustained alarm tone
The UPS is overloaded. The connected equipment exceeds the specified “maximum load” as defined
in Specifications on the APC Web site, www.apc.com.
The alarm remains on until the overload is removed. Disconnect nonessential equipment from the UPS to eliminate the overload condition.
The UPS continues to supply power as long as it is online and the circuit breaker does not trip; the UPS will not provide power from batteries in the event of a utility voltage interruption.
The Replace Battery/Battery Disconnected LED is illuminated
The Replace Battery/Battery
Check that the battery connectors are fully engaged. Disconnected LED flashes and a short beep is emitted every two seconds to indicate the battery is disconnected.
Weak battery Allow the battery to recharge for 24 hours and perform a self-test. If the
problem persists after recharging, replace the battery.
Failure of a battery self-test: Replace Battery/Battery Disconnected LED illuminates and the UPS emits short beeps for one minute. The UPS repeats the alarm every five hours.
Allow the battery to recharge for 24 hours. Perform the self-test procedure to
confirm the replace battery condition. The alarm stops and the LED clears if
the battery passes the self-test.
If the battery fails again, it must be replaced. The connected equipment is
unaffected.
The Site Wiring Fault LED on the rear panel is illuminated (120 V model only)
The UPS is plugged into an improperly wired utility power outlet.
Wiring faults detected include missing ground, hot-neutral polarity reversal,
and overloaded neutral circuit.
Contact a qualified electrician to correct the building wiring.
The input circuit breaker trips
The connected equipment exceeds the specified “maximum load” as defined in Specifications on the APC Web site,
Unplug all nonessential equipment from the UPS.
Reset the circuit breaker.
www.apc.com.
The AVR Boost or AVR Trim LEDs are illuminated
The system is experiencing very high or low utility voltage.
Have a qualified service personnel check your facility for electrical
problems. If the problem persists, contact the utility company for further
assistance.
14 Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual
Problem and/or Possible Cause Solution
There is no utility power
There is no utility power and the UPS is off.
UPS operates on battery although line voltage exists
The UPS input circuit breaker trips. Unplug all nonessential equipment from the UPS.
Your system is experiencing very high, low or distorted line voltage.
Battery Charge and Load LEDs flash simultaneously
The UPS has shut down.
The internal temperature of the UPS has exceeded the allowable threshold for safe operation.
Diagnostic utility voltage
All five LEDs are illuminated. The line voltage is extremely high and should be checked by an electrician.
There is no LED illumination. The line voltage is extremely low and should be checked by an electrician.
Use the cold start feature to supply power to the connected equipment front
the UPS battery(s).
Press and hold the
longer beep. Release the button during the second beep.
Reset the circuit breaker.
Move the UPS to a different outlet on a different circuit: Inexpensive fuel
powered generators may distort the voltage. Test the input voltage with the
utility voltage display, (see Operation). If acceptable to the connected
equipment, reduce the UPS sensitivity.
Check that the room temperature is within the specified limits for operation.
Check that the UPS is properly installed, allowing for adequate ventilation.
Allow the UPS to cool down. Restart the UPS. If the problem persists,
contact APC at www.apc.com.
button. There will be a short beep followed by a
On Line LED
There is no LED illumination. The UPS is running on battery, or it must be turned on.
The LED is blinking. The UPS is running an internal self-test.
Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual 15
Maintenance, Transport, and Service
Replacing the Battery Module
This UPS has easy-to-replace, hot-swappable battery modules. Replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and connected equipment on during the replacement procedure.
Once the batteries are disconnected the connected equipment is not protected from power outages.
Refer to the appropriate replacement battery user manual for battery module installation instructions. See your dealer or contact APC at www.apc.com for information on replacement battery modules.
Be sure to deliver the spent battery(s) to a recycling facility or ship it to APC in the replacement battery packing material.
Service
If the UPS requires service do not return it to the dealer. Follow these steps:
1. Review the problems discussed in Troubleshooting to eliminate common problems.
2. If the problem persists, contact APC Customer Support through the APC Web site, www.apc.com.
Note the model number of the UPS, the serial number located on the back of the unit, and the date
purchased. If you call APC Customer Support, a technician will ask you to describe the problem and attempt to solve it over the phone. If this is not possible, the technician will issue a Returned
Material Authorization Number (RMA#). – If the UPS is under warranty, repairs are free. – Procedures for servicing or returning products may vary internationally. Refer to the APC Web
site for country specific instructions.
3. Pack the UPS in its original packaging. If this is not available, refer to www.apc.com for information about obtaining a new set.
Pack the UPS properly to avoid damage in transit. Never use Styrofoam beads for packaging.
Damage sustained in transit is not covered under warranty.
Always DISCONNECT THE UPS BATTERY before shipping in compliance with U.S.
Department of Transportation (DOT) and IATA regulations. The battery may remain in the UPS.
4. Mark the RMA# on the outside of the package.
5. Return the UPS by insured, prepaid carrier to the address given to you by Customer Support.
16 Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual
Two-Year Warranty
The limited warranty provided by American Power Conversion (APC®) in this statement of Limited Factory Warranty applies only to products you purchase for your commercial or industrial use in the ordinary course of your business.
Terms of warranty
APC warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase. The obligation of APC under this warranty is limited to repairing or replacing, at its sole discretion, any such defective products. This warranty does not apply to equipment that has been damaged by accident, negligence or misapplication or has been altered or modified in any way. Repair or replacement of a defective product or part thereof does not extend the original warranty period. Any parts furnished under this warranty may be new or factory-remanufactured.
Non-transferable warranty
This warranty extends only to the original purchaser who must have properly registered the product. The product may be registered at the APC Web site, www.apc.com.
Exclusions
APC shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user or any third person misuse, negligence, improper installation or testing. Further, APC shall not be liable under the warranty for unauthorized attempts to repair or modify wrong or inadequate electrical voltage or connection, inappropriate on-site operation conditions, corrosive atmosphere, repair, installation, start-up by non-APC designated personnel, a change in location or operating use, exposure to the elements, Acts of God, fire, theft, or installation contrary to APC recommendations or specifications or in any event if the APC serial number has been altered, defaced, or removed, or any other cause beyond the range of the intended use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. APC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. APC EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, APC RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE APC SOLE LIABILITY AND PURCHASER EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. APC WARRANTIES EXTEND ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL APC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, APC IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUENTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NO SALESMAN, EMPLOYEE OR AGENT OF APC IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY. WARRANTY TERMS MAY BE MODIFIED, IF AT ALL, ONLY IN WRITING SIGNED BY AN APC OFFICER AND LEGAL DEPARTMENT.
Warranty claims
Customers with warranty claims issues may access the APC customer support network through the Support page of the APC Web site, www.apc.com/support. Select your country from the country selection pull-down menu. Open the Support tab at the top of the Web page to obtain contact information for customer support in your region.
Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual 17
Regulatory Information
Regulatory Agency Approvals and Radio Frequency Warnings
FCC Compliance Notice
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy. If it is not installed and used in accordance with the instruction manual, it may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case users will be required to take whatever measures may be necessary to correct the interference at their own expense.
120/208 V models
LISTED 42C2
E95463
230 V models
geprüfte
N 394
Sicherheit
APC Worldwide Customer Support
Customer support for this or any other APC product is available at no charge in any of the following ways:
Refer to the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests.
www.apc.com (Corporate Headquarters)
Connect to localized APC Web sites for specific countries, each of which provides customer support information.
www.apc.com/support/
Global support searching APC Knowledge Base and using e-support.
Contact an APC Customer Support center by telephone or e-mail. Local, country-specific centers: go to www.apc.com/support/contact for information.
Contact the APC representative or other distributor from whom you purchased your APC product for information on how to obtain local customer support.
Entire contents copyright 2006 American Power Conversion Corporation. All rights reserved. Reproduction in whole or in part without permission is prohibited.
APC, the APC logo, Smart-UPS and PowerChute are trademarks of American Power Conversion Corporation. All other trademarks, product names, and corporate names are the property of their respective owners and are used for informational purposes only.
18 Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual
Date of product declaration
Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual 19
Loading...