American Power Conversion Smart UPS SUA3000XL, Smart UPS 230 Vac, Smart UPS 120 Vac, Smart UPS 3000 VA XL, Smart UPS 208 VAC User Manual

...
User Manual English
APC Smart-UPS® XL
2200/3000 VA XL
120/208/230 VAC
Tower/Rack-Mount 5U
990-2975 09/2006
Introduction
About this UPS
The American Power Conversion (APC®) Uninterruptible Power Supply (UPS) provides protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power. The UPS provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully discharged.
Unpack
Read the Safety Guide before installing the UPS.
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage.
The packaging is recyclable; save it for reuse or dispose of it properly.
Check the package contents:
•UPS
•Front bezel
•Literature kit containing: – EPO connector – Serial cable – USB cable – Eight ornamental screws for
securing the unit in the rack
– Eight 5/16 in (.8 cm) pan-head
screws for attaching cleats to the chassis rails (required for four post rack only)
– Eight 5/8 in (1.6 cm) pan-head
screws for attaching rack-mount brackets to the unit
– Eight snap-on speed nuts – Two rail cleats (required for four post
rack only) – Two rack-mount brackets – Product documentation – Smart-UPS® User Manuals CD – PowerChute® Business Edition CD – Safety information – Warranty information
Additional contents for 230 V models:
– APC power cable – Alternate input power cord
(UK customers) –IEC Power cord – IEC jumper cables
Specifications
Temperature
Operating Storage
32° to 104° F (0° to 40° C) 5
° to 86° F (-15° to 30° C) charge the UPS battery every six months
86
° to 113° F (30° to 45° C) charge the UPS battery every three months
Maximum Elevation
Operating Storage
Humidity
Wei ght
Maximum Number of External Battery Packs Supported by the Smart-UPS XL
10,000 ft (3,000 m) 50,000 ft (15,240 m)
0 to 95% relative humidity, non-condensing
142 lbs (64 kg) with battery module 89 lbs (40 kg) without battery module 27 lbs (12 kg) each battery module
NOTE: The model and serial numbers are located on a small, rear panel label. For some models, an additional label is located on the chassis under the front bezel.
Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual 3
This unit is intended for indoor use only. Select a location sturdy enough to handle the weight.
Do not operate the UPS where there is excessive dust or the temperature or humidity are outside the specified limits.
Environmental factors impact battery life. High temperatures, poor utility power, and frequent, short duration discharges will shorten battery life.
142 lbs (64 kg)
10
Installation
The UPS is shipped in tower configuration.
Tower Configuration
Connect the battery.
After the battery has been connected, tuck the battery cables in between the battery and the battery door. This will ensure a secure fit of the bezel to the unit.
4 Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual
Rack-Mount Configuration
This unit is intended for mounting in a two post rack. To order a four post rack-mount kit contact your dealer or refer to the APC Web site, www.apc.com.
Tower to rack-mount conversion procedure
The UPS and the battery modules are heavy. Remove the battery modules to lighten the UPS during installation.
Pull the battery disconnect strap attached to the battery connector. DO NOT pull the battery cables to disconnect the battery.
Battery Disconnect Strap
Remove the top cover and . Remove and rotate the display
panel .
Foam Spacer
Disconnect Battery
Four post rack-mount bracket position
Two post rack-mount bracket position
x4
5/8 in
1.6 cm
A four post rack configuration requires installation of two brackets in the forward position (see diagram above), two cleats (supplied with this unit), and the four post rails. The rails can be ordered through the APC Web site www.apc.com.
Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual 5
Install unit in rack
Ensure rack stability prior to installing devices in the rack.
The UPS should be installed at or near the bottom of the rack. If external battery packs are to be installed in the rack, the UPS must be the top unit in the configuration.
Connect Battery
x4 Ornamental
Foam Spacer
After all of the batteries have been connected, tuck the battery cables in between the batteries and the battery doors. This will ensure a secure fit of the bezel to the unit.
Accessories
This UPS is equipped with an accessory SmartSlot. Refer to the APC Web site, www.apc.com for available accessories.
If a standard accessory, such as a Network Management card is to be installed on this UPS, refer to the Utility CD for user documentation.
Install accessories prior to connecting power to the UPS.
6 Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual
Loading...
+ 13 hidden pages