Thank you for chosing the APC Silcon Series UPS. Please read this Installation Guide
thoroughly prior to installing the system. It provides important information on safe and
efficient installation.
The installation and use of this product must comply with national, federal, state, municipal
and local codes.
Safety Symbols used in this manual
WARNING! Indicates a hazard which, if not avoided, could result in injury or death.
CAUTION!
NOTICE!
WARNING!
This UPS unit contains hazardous AC and DC voltages. Only qualified electricians should install
the UPS, AC line and external batteries, and must be familiar with batteries and battery
installation.
Before installing, maintaining or servicing the UPS, shut off the UPS and disconnect all sources
of AC and DC power.
As the UPS has no built-in disconnection devices to switch off external AC and DC input power,
ensure that disconnection devices are provided as separate parts in connection with the
installation!
The installer must provide each external disconnecting device for this UPS system with labels
with the following text:
“Isolate the Uninterruptible Power Supply (UPS) as instructed in this guide before working on
circuit”
AC and/or DC voltage will always involve a potential risk of AC voltage at UPS output generated
from either batteries or mains. To avoid equipment damage or personal injury, always assume
that there may be voltage at UPS output.
This system is equipped with an auto-start function. If activated, the system may start without
warning. Refer to the “Programming” section of this guide for information on de-activation.
Indicates a hazard which, if not avoided, could result in damage to the
product or other property.
Read and pay attention to this important information.
TEST BEFORE YOU TOUCH!
To reduce the risk of fire or electric shocks, install the UPS and external batteries in a
temperature and humidity controlled indoor area, free of conductive contaminants.
UPS batteries are high-current sources. Shorting battery terminals or DC terminals, DC busbars
can cause severe arcing, equipment damage and injury. A short circuit can cause a battery to
explode. Always wear protective clothing and eye protection and use insulated tools when
working on batteries.
CAUTION!
This unit contains components sensitive to electrostatic discharge (ESD). If you do not follow the
ESD procedures, you may cause severe damage to electronic components.
990-4050
2Installation Guide APC Silcon 10-40kW 400V UPS
Contents
1.0Introduction 5
1.1Tools and Equipment 5
2.0Unpacking 6
3.0Installation 8
3.1Requirements on Site 8
3.1.1Cabinet Dimensions H*xWxD - 1400xWx800 [mm]. Width as in below table: 8
3.2Footprint 10
3.2.1600mm UPS Cabinet with 1xBP I or Isolation Transformer 10
3.2.2800mm UPS Cabinet with 1xBP I or Built-in Isolation Transformer, or 2xBP I 10
3.2.31000mm Cabinet for 10-20kW UPS with 3xBP I 11
3.2.4600mm Cabinet for 40kW UPS without Batteries 11
3.2.51000mm Cabinet for 40kW UPS with 2xBP I 12
4.0External Connection 13
4.1Connecting the UPS 13
4.1.1Connecting the 10-20kW UPS 13
4.1.2Connecting the 40kW UPS 15
4.2System Integration Interface 17
4.2.1Connections 18
4.3Parallel Board 19
4.4Communication Interface Board 22
4.4.1Connections 22
4.5Connecting of APC Silcon Tripel Chassis 23
4.6APC Silcon Triple Chassis 24
4.6.1Safety Warnings 24
4.6.2Product Description 24
4.6.3Installing Management Peripherals 25
4.6.4Powering the APC Silcon Triple Chassis 27
4.6.5Troubleshooting 28
4.6.6Product Specifications 29
4.7APC Silcon Battery Cabinets 32
4.7.1Cabinets 33
4.7.2Preparing Batteries 33
4.7.3Mounting Batteries 35
4.7.4Final Checks 37
4.7.5APC Silcon Battery Cabinets 38
4.8Battery Breaker Box/Fuse-box 40
4.8.1Battery Breaker Box 41
4.8.2Battery Breaker Box Connection Diagram 42
4.8.3Fuse-box 43
4.8.4Fuse-box Connection Diagram 44
4.8.5UPS with External Battery in Battery Breaker Box/Fuse-box Configuration 45
5.0Programming Parameters 46
5.1Parameters 46
5.1.1Programming Keys 47
5.1.2Programming Example - Switch to Bypass Operation 48
5.2System Configuration 48
5.2.1Programming Example - Change Charge Voltage to 446 50
5.2.2Programming Example - Change to Output Isolation Transformer available 51
5.3Programming Parameters for Advanced Parallel Operation 52
5.3.1Description of Settings 52
5.3.2Programming example 53
5.4Battery Monitor 53
5.4.1Installation of new batteries 53
6.0Options/Accessories 54
6.1Service Bypass Panel for Single Operation 54
6.1.1Wiring up UPS with SBP in TN-C-S Network 56
6.1.2Wiring up UPS with SBP in TN-S Network 56
990-4050
Installation Guide APC Silcon 10-40kW 400V UPS 3
6.1.3Operating The External Service Bypass Switch 57
6.2Service Bypass Panel for Parallel Redundant Operation 59
6.2.1Two Parallel Systems with Service Bypass Panel 60
6.2.2Parallel/Redundant Operation with Service Bypass Panel and External Battery
via MCCB 61
6.2.3Operating External Service Bypass Switch for Parallel Systems 62
6.2.4Isolating One UPS for Service/Maintenance 66
6.2.5Switching Back to Normal Parallel/Redundant Operation 67
6.3Intersystem Synchronization Unit 68
6.4Relay Board 69
6.4.1Relay Board/Relay Functions 70
6.5Weight Equalizer 72
6.6Remote Display 74
6.6.1Extension of Remote Display Communication Distance 74
6.6.2Remote Display Installation 76
6.6.3 Remote Display Use 77
6.7Isolation Transformer 78
6.7.1Connecting Isolation Transformer 79
6.7.2Wiring up UPS with External Yyn0 Isolation Transformer at Output 81
6.7.3Wiring up UPS with External Yyn0 Isolation Transformer at Input 82
6.7.4Wiring up UPS with External Optional Dzn0 Isolation Transformer at Input 83
6.7.5Wiring up UPS with External Optional Dzn0 Isolation Transformer at Output 84
6.7.6Wiring up UPS with External Optional Dyn11 Isolation Transformer at Input 85
7.0System Specifications 86
7.1Technical Data 86
7.2Back-up Time / Dimensions / Weigh 86
8.0Warranty 87
8.1APC Silcon Series Limited Factory Warranty 87
9.0Appendix 88
9.1Table 1. Installation Planning Data 88
10.0How to Contact APC 90
990-4050
4Installation Guide APC Silcon 10-40kW 400V UPS
Introduction
1.0Introduction
Power regulation varies from country to country, and information given in this installation
guide can therefore only be of a general nature. Electricians should therefore always refer to
national and local electrical codes prior to installing the UPS system.
1.1Tools and Equipment
CAUTION!
Heavy equipment. To prevent personal injury or equipment damage, take extreme care when
handling and transporting UPS cabinet and equipment.
CAUTION!
Ensure that front doors are in place and that internal front cover is fastened by screws before
attempting to lift or transport the system.
This section lists all tools and equipment required to install all UPS configurations. See also
section 4.0 of this guide for further details on connection.
Tools:
• 10mm socket
• 13mm socket-deep
• 17mm socket
• 19mm socket-deep
• 19mm combo wrench
• Small flat head/regular screwdriver
• #3 philips screwdriver
• Compression lug crimping tool
• Knock-out set (for glands)
Equipment:
• Compression lugs for cable terminations
• Cable to Service Bypass Panel from system feeder
• Cable to UPS input from Service Bypass Panel
• Cable to Service Bypass Panel from UPS output
• Cable from Service Bypass Panel to customer distribution
• Cable to UPS input from external batteries/external Battery Breaker Box
(systems with external battery)
• Solid core, control cable to UPS from Service Bypass Panel
• Solid core, control cable to UPS from external batteries/external Battery
Breaker Box
990-4050
Installation Guide APC Silcon 10-40kW 400V UPS 5
Unpacking
2.0Unpacking
NOTICE!
Unless otherwise specified by the shipping company use a fork lift to unload equipment from
pallet
1. To unpack UPS unit, remove top and bottom screws from side plates of packaging and lift up side plates
2. Verify compliance between type label on reverse side of front door and system ordered. Check input and
output voltage
3. Copy type label data to label copy below for easy identification of system
4. Use fork lift to transport system to installation site
5. Open UPS doors and unscrew metal straps mounted on front cover of UPS
990-4050
6Installation Guide APC Silcon 10-40kW 400V UPS
Copy of type label
Unpacking
PLEASE RECYCLE
The shipping materials for the APC Silcon UPS are recyclable. Please save them for later use or
dispose of them appropriately.
990-4050
Installation Guide APC Silcon 10-40kW 400V UPS 7
Installation
3.0Installation
3.1Requirements on Site
All system parts are accessible from front or top of UPS. Cable entries are accessible from
bottom. A 1m free space on all sides should be allowed during installation. Once the system is
installed it may be placed close to walls as long as free space is allowed for system doors to open.
(Per applicable national and/or local codes.)
For ventilation and service purposes allow for free space of minimum 1m above the unit or per
national and/or local codes and in front of UPS. Never install systems in direct sunlight.
NOTICE!
For reliability reasons do not stand on the UPS. keep the UPS cabinet surface free of any objects.
3.1.1 Cabinet Dimensions H*xWxD - 1400xWx800 [mm]. Width as in below table:
* H is 1500 mm for optional IP31 cabinets
Width
Without
Batteries
[mm]
UPS1xBP I*2xBP I*3xBP I*1xBP II**1xBP III***
10kW60060080010001x8001x1000
20kW60060080010001x8001x1000
40kW60010001x8001x1000
* BP I = Battery Pack I = 1 x 64 x 7 Ah batteries
** BP II = Battery Pack II = 1 x 64 x 24Ah batteries
*** BP III = Battery Pack III = 1 x 64 x 38 Ah batteries
Width With Built-in Batteries
[mm]
Width for Separate
Battery Cabinets
[mm]
990-4050
8Installation Guide APC Silcon 10-40kW 400V UPS
Cabinets
Installation
600 mm wide
1400 mm
10-20kW
with 1xBP l
600 mm wide
1400 mm
40kW
without batteries
800 mm wide
1400 mm
10-20kW
with 2xBP l
1000 mm wide
1400 mm
40kW with 2xBP l
1000 mm wide
1400 mm
10-20kW
with 3xBP l
600 mm wide
1400 mm
APC Isolation
Transformer module
10-80kW
800 mm wide
1400 mm
Battery cabinet
for 1xBP ll
1000 mm wide
1400 mm
Battery cabinet
for 1xBP lll
990-4050
Installation Guide APC Silcon 10-40kW 400V UPS 9
Installation
3.2Footprint
3.2.1 600mm UPS Cabinet with 1xBP I or Isolation Transformer
Rear
Power cable entry
Com. cable
entry
Front
3.2.2 800mm UPS Cabinet with 1xBP I or Built-in Isolation Transformer, or 2xBP I
Rear
Power cable entry
Front
990-4050
Com. cable
entry
10Installation Guide APC Silcon 10-40kW 400V UPS
3.2.3 1000mm Cabinet for 10-20kW UPS with 3xBP I
Rear
Installation
Power cable entry
3.2.4 600mm Cabinet for 40kW UPS without Batteries
Com. cable
entry
Front
Rear
Power cable entry
Com. cable
entry
Front
990-4050
Installation Guide APC Silcon 10-40kW 400V UPS 11
Installation
3.2.5 1000mm Cabinet for 40kW UPS with 2xBP I
Rear
Power cable entry
Front
Com. cable entry
0
195
990-4050
12Installation Guide APC Silcon 10-40kW 400V UPS
External Connection
4.0External Connection
4.1Connecting the UPS
4.1.1 Connecting the 10-20kW UPS
CAUTION!
At a switch mode load of 100% the neutral must be rated for 200% output phase current
CAUTION!
This UPS unit is an EN 50091-2 product and may cause radio interference in a domestic
environment. Take preventive measures if necessary.
Optional
Ext. batteries
optional
Output
System Integration Interface
Relay Board (Optional)
Communication Interface
Parallel Controller Board
Input
990-4050
Installation Guide APC Silcon 10-40kW 400V UPS 13
External Connection
NOTICE!
Check correct phase rotation of mains input voltage!!
Max. input/output cables: 35mm
If there is no neutral input Dzn0 or Dyn11 input isolation transformer is required.
2
.
UPSExternal
Input Fuses*
FM [A]
380-415V
10kW2044162.5
20kW401010326
* DIN gL types
NOTICE!
All cable dimensions are recommended sizes only.
Refer to local legal regulations.
UPSExternal Alarm
Cable max.
[mm2]
External
Input Cable
[mm2]
380-415V
External System
Earth Cable
External PE
Cable [mm2]
[mm2]**
Maximum
External
Output
Fuses*
[A]
External Battery
Breaker
[A]
External
Output Cable
[mm2]
External
Battery Cable
[mm2]
10kW24254
20kW245010
PVC cables isolated to withstand ambient temperature of max. 30oC
** Must be rated as external PE cable if mains system is not supplying PE
NOTICE!
If an MCCB is used instead of external input fuses, the MCCB load capacity must be 8xIn
(nominal current) for min. 10ms.
990-4050
14Installation Guide APC Silcon 10-40kW 400V UPS
External Connection
NOTICE!
Install gland plate in bottom of unit
4.1.2 Connecting the 40kW UPS
CAUTION!
At a switch mode load of 100% the neutral must be rated for 200% output phase current.
CAUTION!
This UPS unit is an EN 50091-2 product and may cause radio interference in a domestic
environment. Take preventive measures if necessary.
Optional
Input
Output
Parallel Controller
Please refer to 8.5
System Integration interface
Communication Interface
Relay Board (Optional)
990-4050
Installation Guide APC Silcon 10-40kW 400V UPS 15
External Connection
NOTICE!
Check correct phase rotation of mains input voltage!!
Max. input/output cables: 120mm
If there is no neutral input Dzn0 or Dyn11 input isolation transformer is required.
2
. Battery: 70 mm
2
.
UPSExternal
Input
Fuses* FM
[A]
380-415V
40kW8025166316
* DIN gL types
NOTICE!
All cable dimensions are recommended sizes only.
Refer to local legal regulations.
UPSExternal Alarm
Cable max.
[mm2]
40KW2106316
External
Input Cable
[mm2]
380-415V
External System
Earth Cable
External PE
Cable
[mm2]
External Battery
[mm2]**
Maximum
External
Output
Fuses*
[A]
Breaker
[A]
External
Output
Cable
[mm2]
External
Battery Cable
[mm2]
PVC cables isolated to withstand ambient temperature of max. 30oC.
** Must be rated as external PE cable if mains system is not supplying PE.
NOTICE!
Install gland plate in bottom of unit.
990-4050
16Installation Guide APC Silcon 10-40kW 400V UPS
4.2System Integration Interface
External Connection
NOTICE!
Consistent use of designations (Q001, Q002, Q003, H002, H003) in diagrams simplifies
information exchange.
System Integration Interface (SII) is the control link between UPS and system main switches
as shown in above diagram. The purpose of the SII is to ensure correct operation of switches
without losing system output power.
Auxiliary contacts on the main switches transmit the SII board inputs. Lamps on Service
Bypass Panel and Battery Breaker Box/Battery Cabinet indicate “green light” for operation of
output switches.
SII board also integrates input facilities for emergency shut-down and temperature
compensation of charge voltage for external battery (use with battery monitor). “Battery
operation” and “Common fault” are two main SII board status relay signals.
990-4050
Installation Guide APC Silcon 10-40kW 400V UPS 17
External Connection
4.2.1 Connections
Blue
Brown
990-4050
18Installation Guide APC Silcon 10-40kW 400V UPS
External Connection
Terminal Blocks: X003/X004 (Anxiliary Contacts)
When switching Q001, Q002, Q010, Battery Breaker 1 or Battery Breaker 2 from “ON or 1” to
“OFF or 0”, the anxiliary contact has to be open BEFORE the corresponding main contacts are
opened. When switching Q001, Q002, Q010, Battery Breaker 1 or Battery Breaker 2 the
opposite way from “OFF or 0” to “ON or 1”, the anxiliary contact has to close with a maximum
delay of 0.5 seconds from the time the corresponding main contacts are closed.
• This type of auxillary contact is called a “late make” contact. (This also means that it will
“break early” when activated in opposite direction.)
• This auxillary contact is also called “NORMALLY OPEN” (NO), because the auxillary
contact will be open when the main contacts are open.
• Please note that the above term “NORMALLY” has nothing to do with NORMAL UPS
OPERATION MODE.
When switching Q003 from “OFF or 0” to “ON or 1”, the anxiliary contact has to open BEFORE
the corresponding main contacts are closed. When switching Q003 the opposite way from “ON
or 1” to “OFF or 0”, the auxillary contact has to close with a maximum delay of 0.5 seconds from
the time when the corresponding main contacts are opened.
• This type of anxiliary contact is called an “early break” contact. (This also means that it will
“make late” when activated in the opposite direction.)
• The auxiliary contact is also called “NORMALLY CLOSED” (NC), because the auxiliary
contact will be closed when the main contacts are open.
• Please note that the above term “NORMALLY” has nothing to do with NORMAL UPS
OPERATION.
X005 (Output Relays)
Battery operation signals are received with a 30-second delay. This function is inactive during
battery test. Common fault relay facility is programmable (standard factory setting: 10 sec.)
See APC Silcon User Guide for details.
Maximum nominal voltage on contact circuits is 277VAC. If two different phases are involved,
maximum phase to neutral voltage should be below 160VAC. Please note that phase L1 is
already present on the System Integration Interface board, supplied from the Service Bypass
Panel. Therefore, if a phase is needed for alarm or signal purposes, Phase L1 should be used.
4.3Parallel Board
CAUTION!
Control cables must be separated from AC and DC power cables.
Parallel Board
990-4050
Installation Guide APC Silcon 10-40kW 400V UPS 19
External Connection
The built-in parallel board connects two or more UPS systems in parallel, either to obtain
increased system reliability or to obtain higher output power. The parallel board also ensures
correct load-sharing between paralled systems.
NOTICE!
For reliability reasons, APC recommends separate battery packs in redundant/parallel
conigurations.
To prepare the UPS for parallel/redundant mode, disconnect all sources of AC and DC power
supply to the UPS and connect the ribbon cable from the parallel board to the main controller
board (the ribbon cable is delivered with the UPS).
CAUTION!
DO NOT connect ribbon cable between controller and parallel card in single configurations.
Ribbon cable is for parallel operation only.
Complete the parallel system set-up by connecting the external control cables (see below).
Follow the instructions in the “Programming Parameters for Advanced Parallel” section of this
guide to execute necessary re-programming.
990-4050
20Installation Guide APC Silcon 10-40kW 400V UPS
External Connection
Parallel Board
X021:15-pin SUB-D female
X020:15-pin SUB-D female
External multicore cable with 14 wires + shield
to other parallel units
UPS 1
External Control Cables
External multicore cable is equipped with 15-pin SUB-D plug at either end. Connect pin 1 to
pin 1, and pin 2 to pin 2 etc. up to pin 15 - with the exception of pin 8, which is not to be
connected.
Shield is connected to plug cover at both ends.
Terminals X020 and X021 for control cables located on parallel board. Connect X020 in UPS1
to X021 in UPS2, and connect X020 in UPS2 to X021 in UPS3 etc. Connect X020 in last UPS
to X021 in UPS1.
Cable is delivered with the UPS.
Power Cables
To optimize load-sharing in parallel operation, external power circuits must be “symmetrical”:
Power input and output cables to have same length and identical cross-sections.
UPS 2
UPS 3
990-4050
Installation Guide APC Silcon 10-40kW 400V UPS 21
External Connection
4.4Communication Interface Board
The 3-port ComInterface is used to establish an interaction between UPS and e.g. a computer
system. Main purpose: To ensure a controlled computer shut-down in case of a mains supply
failure.
4.4.1 Connections
.
990-4050
.
22Installation Guide APC Silcon 10-40kW 400V UPS
External Connection
4.5Connecting of APC Silcon Tripel Chassis
The enclosed Triple Chassis must be connected to the serial port on the Communication
Interface Board, and to the 24V supply (cables included). Terminal locations shown below.
23.62 inch/600mm Cabinet
Serial ports
Front view of UPS Cabinet (doors open)
APC Silcon Triple Chassis
For more information please refer to the following section.
X50 is a 24V supply for Triple Chassis.
Only to be used for this purpose.
Not suitable for telephone equipment.
Triple Chassis must be connected to both
X50 and a serial port.
990-4050
Installation Guide APC Silcon 10-40kW 400V UPS 23
External Connection
4.6APC Silcon Triple Chassis
The APC Silcon Triple Chassis (AP9604S) is an American Power Conversion (APC) external
management peripheral that allows you to use monitoring and control management
peripherals with your APC Silcon series UPS. The retrofit model (AP9604SR) is for use with
Silcon series UPSs that are not equipped with a 24 VDC power port.
4.6.1 Safety Warnings
Use the APC Silcon Triple Chassis only in conjunction with an APC Silcon UPS.
Do not connect a computer to any APC Silcon Triple Chassis port using a straight-through
extension cable. Use the communications cable provided with the APC Silcon Triple Chassis.
Connections using a cable made by any other manufacturer may cause damage or improper
operation of the APC Silcon Triple Chassis, the UPS, or the computer.
4.6.2 Product Description
➊
➍
➋
➌
Monitoring port
1
To UPS port
2
4.6.2.1Monitoring Port
The Monitoring port has two functions:
• Connecting to a terminal for configuration of the chassis. For direct connection to the
Monitoring port, you must use the Monitoring cable supplied with the chassis (APC
P/N 940-0024C).
• Connecting to other APC external management peripherals in a daisy chain.
4.6.2.2To UPS Port
The “To UPS” port connects the chassis to the UPS, using the Silcon UPS cable (APC P/N 940-
0071). The cable connector plugs into a communications port on an APC Silcon UPS.
Status LED
3
Optional Power port
4
990-4050
24Installation Guide APC Silcon 10-40kW 400V UPS
External Connection
4.6.2.3LEDs
The APC Silcon Triple Chassis status LED provides important information concerning
operation of the chassis. Refer to the table below for a description of the conditions indicated
by the LED.
IF the LED is…THEN the Silcon Triple Chassis…
offis not receiving power.
has not been configured. See the APC Silcon Management Quick
flashing quickly
(5 times per second)
Start Guide provided with your chassis or the Web/SNMP
Management Card Installation Guide on the CD for more
information.
flashing slowly
(1 time per second)
onis operating normally.
4.6.2.4Optional Power Input
With the Optional Power input, you can power the APC Silcon Triple Chassis from an external
source, using a 24 VDC power adapter. A universal adapter (AP9505i) or a standard adapter
(AP9505) can be purchased separately from APC.
4.6.3 Installing Management Peripherals
There are two basic types of APC management peripherals that work with the APC Silcon
Triple Chassis:
• Management peripheral cards, which fit into external management peripherals that
are equipped with a card slot.
• External management peripherals, which connect to the Monitoring (or Advanced)
port of other external management peripherals.
NOTICE!
The name “Monitoring” port varies from product to product, but its purpose is the same – to
replicate the UPS communications port.
is powered on but is not communicating with the UPS.
990-4050
Installation Guide APC Silcon 10-40kW 400V UPS 25
External Connection
4.6.3.1Order of Management Peripheral Cards
Because UPS signals are passed between management peripherals, you must install
management peripheral cards in the correct order for them to work together properly. The card
slots are numbered 1 to 3, from left to right, as viewed from the rear of the chassis. The
following table lists the management peripheral cards, their priority, and proper position.
Management
Peripheral Card
Web/
SNMP Management
Card
Out-of-Band
Management Card
(Call-
UPS®II)
Interface ExpanderAP9607Second lowest
Environmental
Monitoring Card
(Measure-
4.6.3.2Installing Management Peripheral Cards
To install management peripherals, perform the following steps.
1) Make sure that the chassis is powered off.
2) Install management peripheral cards into the housings on the rear of the chassis. See the
instructions supplied with the cards and the table above.
3) If you are daisy-chaining other APC external management peripherals to the APC Silcon
Triple Chassis: Connect the UPS cable (supplied with the management peripheral) to the
Monitoring port of the chassis and to the “To UPS” port of the other management peripheral
(Share-UPS, MasterSwitch, etc.). See “Daisy-chaining the APC Silcon Triple Chassis”.
4) Power the APC Silcon Triple Chassis and all external management peripherals.
UPS
®
II)
P/NPriorityPosition
AP9606Highest
AP9608Second-highest
AP9612T
AP9612TH
Lowest
High-numbered slot
Low-numbered slot
NOTICE!
If your configuration requires additional power, connect a 24V AC/DC power adapter available
from APC (part number AP9505 or AP9505i) for all models of Triple Chassis.
4.6.3.3Daisy-chaining the APC Silcon Triple Chassis
If you need more than the three card slots available with the APC Silcon Triple Chassis, or if
you want to use other external management peripherals, you can daisy-chain external
management peripherals together, provided that the total amperage of all installed
management peripherals — cards and external — does not exceed the supplied amperage. (See
“Determining Power Requirements:”).
NOTICE!
When daisy-chaining Triple Chassis units, you may need to use a power adapter.
990-4050
26Installation Guide APC Silcon 10-40kW 400V UPS
External Connection
To add card slots, you can daisy-chain the APC Silcon Triple Chassis with the standard Triple
Chassis (AP9604) management peripheral, installing the APC Silcon Triple Chassis closer to
the UPS.
4.6.4 Powering the APC Silcon Triple Chassis
The APC Silcon Triple Chassis supplies power to the installed management peripheral cards
and to the Monitoring port, allowing you to power multiple management peripherals.
4.6.4.1AP9604S Power Considerations
The AP9604S model of the APC Silcon Triple Chassis receives its power from the UPS through
the power connector of the Silcon UPS cable. If the total current required by all the installed
management peripherals exceeds 500 mA, you must use a 24 VDC power adapter. To find out
whether you need additional power, see “Determining power requirements”.
4.6.4.2Power Adapters
APC offers two models of 24 VDC power adapter.
• The standard adapter (AP9505) can provide an additional 400 mA.
• The universal adapter (AP9505i) can provide 850 mA.
4.6.4.3Using a Power Adapter
To use the adapter, plug it into a protected power outlet and into the Optional Power port of
the APC Silcon Triple Chassis.
NOTICE!
If the power adapter loses power because of a UPS shutdown, its attached management
peripherals may not operate properly, thus adversely affecting the UPS and its protected
equipment.
4.6.4.4AP9604SR Power Considerations
The AP9604SR model receives its power from the UPS through the supplied 24 VDC universal
adapter. The total current required by your management peripherals must not exceed the 850
mA limit of the power adapter. See ““Determining power requirements”.
4.6.4.5Determining Power Requirements:
To determine the total amount of current required by your management peripherals, add the
individual current requirements for each management peripheral to be installed with the APC
Silcon Triple Chassis to the current requirements of the chassis itself. Refer to this table
Part #Management PeripheralDraw (mA)
AP9207Share-UPS 8-port Interface Expander65
AP9600Expansion Chassis30
AP9604Triple Chassis20
990-4050
Installation Guide APC Silcon 10-40kW 400V UPS 27
Loading...
+ 63 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.