CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
APC Symmetra LX
GUIDE SPECIFICATIONS FOR
4kVA-16kVA
Uninterruptible Power System
PART 1 - GENERAL
1.1 SUMMARY A. This specification describes the operation and functionality of a continuous duty, single-
phase, solid-state, static Uninterruptible Power System (UPS) hereafter referred to as the UPS.
B. The UPS shall utilize modular power protection technology designed to allow internal
redundancy, scalability of power and runtime, and fast mean time to repair (MTTR). The UPS should be configured from five basic components- UPS frames, extended run battery frames (XR frames), power modules, battery modules, and intelligence modules. UPS and XR frames should be capable of shipping with modules installed. XR frames should be capable of communicating battery and runtime status to intelligence modules. Power, battery, and intelligence modules should be hot-swappable and user-replaceable for fast MTTR.
C. Configuration Specifics:
1. The UPS frame(s) should be capable of the following configurations:
____4-8kVA N+1 Redundant Tower ____4-16kVA N+1 Redundant Tower ____4-16kVA N+1 Redundant Tower with nine (9) extra Battery Module slots ____4-8kVA N+1 Redundant 13U Rack-mount ____4-16kVA N+1 Redundant 19U Rack-mount
2. The system power train shall be comprised of hot-swappable, user-replaceable
3.2kW/4kVA and 10% Battery charger circuit power modules, which shall operate in parallel, and be configurable for N+1 redundant operation at rated load.
3. The system shall also include a field-replaceable internal automatic and manual
bypass system module, field-replaceable output power distribution panels, removable input/output wiring tray, standard redundant intelligent modules, battery disconnects, an LCD interface display, EPO, and an integrated UPS network management card with temperature monitoring.
D. In addition, this specification describes the performance, functionality, and design of
the UPS Service Bypass Panel, hereafter referred to as the SBP, the external Battery Systems, and connectivity solutions.
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
E. The UPS and associated equipment shall operate in conjunction with a primary power
supply and an output distribution system to provide quality uninterrupted power for mission critical, electronic equipment load.
F. All programming and miscellaneous components for a fully operational system as
described in this specification shall be available as part of the UPS.
1.2 STANDARDS A. UL 1778 Uninterruptible Power Supply Equipment B. CSA C. FCC Class A D. ISO 9001 E. ISO 14001
1.3 MODES OF OPERATION A. Normal: The input converter and output inverter shall operate in an on-line manner to
continuously regulate power to the critical load. The input and output converters shall be capable of full battery recharge while simultaneously providing regulated power to the load for all line and load conditions within the range of the UPS specifications.
B. Battery : Upon failure of the AC input source, the critical load shall continue being
supplied by the output inverter, which shall derive its power from the battery system. There shall be no interruption in power to the critical load during both transfers to battery operation and retransfers from battery to normal operation.
C. Recharge: Up on restoration of the AC input source, the input converter and output
inverter shall simultaneously recharge the battery and provide regulated power to the critical load.
D. Automatic Bypass: The automatic bypass shall be used to provide transfer of critical
load from the Inverter output to the bypass source. This transfer, along with its retransfer, shall take place with no power interruption to the critical load. In the event of an emergency, this transfer shall be an automatic function.
E. Manuel Bypass: The system shall be equipped with an internal make-before-break two
pole switch to electrically isolate the UPS from the input and output during preventative maintenance, module upgrades, or limited frame service. The manual bypass shall also be considered a partial ‘wrap-around’ bypass, and shall be configured to wrap around the power modules (recitifier, battery charger, inverter) , and battery modules in the same manner as the automatic bypass will still supplying surge and EMI filtering, and overcurrent protection. There will be a positional sense supplied to alert users that the UPS is in manual bypass.
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
F. External Service Bypass Panel (SBP): The maintenance service bypass cabinet shall
provide power to the critical load bus from the bypass source, during times where maintenance or service of the UPS frame is required or when removal of the frame is desired. The SBP shall provide a mechanical means of complete isolation of the UPS from the electrical wiring of the installation. The SBP shall be constructed in a free­standing, rack mounted or wall-mounted NEMA 1 enclosure unless otherwise stated in this specification. It shall be designed for either three phase input or single phase input with a “ no break” transfer between bypass and UPS power.
1.4 SUBMITTALS A. Proposal Submittals:
1. As bid system bill of materials.
2. Product catalog sheets or equipment brochures.
3. Product guide specifications.
4. System single-line operation diagram.
5. Installation information, including weights and dimensions.
6. Information about terminal locations for power and control connections.
B. Delivery Submittals:
1. Installation manual, which includes instructions for storage, handling,
examination, preparation, installation, and start-up of UPS.
2. User manual, which includes operating instructions.
PART 2 – PRODUCT
2.1 DESIGN REQUIREMENTS
A. The UPS shall be sized for initial capacity of _____ kVA and _____ kW load. B. The UPS shall be scalable to final capacity of _____ kVA and _____ kW load. C. The UPS battery shall be sized for _____ kVA at a Power Factor of_____ for _____
minutes.
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
2.2 SYSTEM CHARACTERISTICS
A. System Capacity: The system shall be rated for .8 Pf output in the following frame sizes:
1. 8 kVA/ 6.4kW - Can be configured with up to (3), 3.2kW power modules for
N+1
2. 16 kVA/ 12.8kW - Can be configured with up to (5), 3.2kW power modules for
N+1
B. Input:
1. AC Input Nominal Voltage: 208 V or 240V, Single Phase, 4 wire (2 Phase+ N + G), 60 Hz.
2. AC Input Voltage Window: 155 -276 for 240V or 166-240V for 208V (while providing nominal charging to the battery system).
3. Maximum Frequency Range: 45-65Hz
4. Input Power Factor:
a. Minimum .90 lagging at 100% load at 208 V b. Minimum .98 lagging at 100% at 240 V
6. Input Current Distortion with no additional filters:
a. < 5% at 100% load at 240V
D. UPS Output:
1. AC Output Nominal Output: 120/208V or 120/240V , Single Phase, 4 wire
2. AC Output Voltage Distortion: Max. 5% @ 100% Linear Load, phase to neutral
3. AC Output Voltage Regulation:
4. Voltage Transient Response:
5. Voltage Transient Recovery within <60 milliseconds
6. Output Voltage Harmonic Distortion:
7. Overload Rating:
(2Phase + N + G), 50 or 60 Hz.
loads.
+
/- 3% For 100 % Linear or Nonlinear Load,
phase to neutral loads.
+
/- 5% maximum for 100% load step
a. <2% THD maximum and 1% single harmonic for a 100% linear load b. <5% THD maximum for a 100% non-linear load
a. Normal Operation:
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
1) >130% for 4 seconds
2) 105% continuous
3) <130% Continuous at N+1
b. Bypass Operation:
1) 100A continuous
8. System AC-AC Efficiency: >90% at 100% load
10. Output Power Factor Rating: The UPS output shall be .8 lagging
2.3 ENVIRONMENTAL
A. Storage Ambient Temperature: 5°F to 113°F (-15°C to 45°C).
B. Operating Ambient Temperature: +32°F to 104°F (0°C to 40°C). (77°F is ideal for
most battery types).
C. Relative Humidity: 0 to 95% Non-condensing E. Altitude: Maximum installation with no derating of the UPS output shall be 10,000 feet
(3000m) above sea level.
2.4 INPUT POWER CONVERTER
A. The input power converters of the system are housed within the parallel connected,
removable power modules, and shall constantly control the power imported from the mains input of the system, to provide the necessary UPS power for precise regulation of the DC bus voltage, battery charging, and Main Inverter regulated output power.
B. Input Current Total Harmonic Distortion: The input current THD
shall be held to 6%
I
or less at full system, while providing conditioned power to the critical load bus, and charging the batteries under steady-state operating conditions. This shall be true while supporting loads of both a linear or non-linear type. This shall be accomplished with no additional filters, magnetic devices, or other components.
E. Input Current Limit:
1. The input converter shall control and limit the input current draw from utility to 150% of the UPS output. During conditions where input current limit is active, the UPS shall be able to support 100% load, charge batteries at 10% of the UPS output rating, and provide voltage regulation with mains deviation of up to +/­20% of the nominal input voltage.
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM