APC GALAXY 990-2258B-001 User Manual

Installation
UPS
UPS
XR battery enclosure
Note: Ensure that the unit is in its final location prior to installation.
Note: Battery and utility/mains power must not be connected until all other wiring has been completed.
Prepare for Cables
Bottom cable entry
From the rear of the UPS, loosen the six
M4 screws from the upper cover (the cable
landing area) on the back and remove.
MGE™ Galaxy™ 3500
10-40 kVA 380/400/415 V with batteries
See Also: For parallel configurations see manual 990-
3568.
Level the Enclosure
Warning: The system must be installed on a level floor.
The leveling feet will stabilize the enclosure, but will not account for a badly sloped floor.
Use a 13/14 mm wrench to adjust the four leveling feet.
Ensure that the system is level.
Caution: Do not move the enclosure after the leveling feet have been lowered.
Route the cables from the
slanted back plate, up
through the punched
bracket, and into the cable
landing area.
Fasten the cables with
cable ties
IMPORTANT SAFETY INSTRUCTIONS
990-2258B-001
SAVE THESE INSTRUCTIONS
(990-2940) must be read, understood, and followed when installing the UPS system. Failure to do so could result in equipment damage, serious injury, or death.
Warning: After the UPS has been electrically wired, do not start it up. Start-up is commissioned to authorized personnel from Schneider Electric.
Caution: All electrical power and power control wiring must be installed by a qualified electrician, and must comply with local and national regulations for maximum power rating.
*990-2258B-
9/2009
Floor Anchoring (if applicable)
Anchor the UPS enclosure to the floor
Note: Floor-anchoring bolts are not provided with the UPS.
Purchase the bolts locally (minimum size: M8). Follow the specifications given by the manufacturer of the floor anchoring system when bolting the UPS system to the floor.
Reuse the two transport brackets (one
on each side) that were used to secure the
UPS to the pallet during transport.
Drill two to six holes in the floor for
each bracket. Attach with bolts.
Note: A conduit box (part no. SUVTOPT001 or SUVTOPT002) is available as an option.
Connect the AC Input and AC
J108 pin connections:
1 Normally open EPO 2 Normally open EPO return 3 Normally closed EPO 4 Normally closed EPO return 5 +24 V SELV supply 6 SELV ground
J106 pin connections:
8 Ext. charging control return 7 External control of charging 6 Q3 active return 5 Q3 active 4 Battery measurement supply* 3 Battery unit quantity* 2 Max. battery temperature* 1 Battery measurement return*
* Should be used with MGE Galaxy 3500 XR Enclosures
Dual mains
Connect the Communication
Output Cables
Warning: Use compression type lugs ONLY.
Do not loosen or add cables to any factory preinstalled cables on busbars. Use the front part of busbar for connection only.
See Also: For different grounding configurations please see manual 990-3606.
Single mains
Connect the AC input cables
and the neutral to the input
cable landings.
Connect the AC output
cables and the neutral to the
output cable landings.
Connect the ground cables to
the studs (earth symbol
beneath) using a screw.
Remove the
three busbars A,
B, and C by
removing two M6
screws from each
busbar.
Connect the AC
input cables and
the neutral to the
input cable
landings.
Connect the
bypass cables and
the neutral to the
bypass cable
landings.
Connect the
output cables and
the neutral to the
output cable
landings.
Cables
Warning: Make sure that the UPS is completely OFF as
the connectors are very close to the power busbars.
J106 (XR Battery Enclosure) and J108 (EPO)
Note: Use only 1-1½ mm² copper wire for the connection of
the Emergency Power Off (EPO) and other optional equipment.
Note: The UPS must be connected to either a dry contact or a 24 VDC EPO (Emergency Power Off) switch.
Note: The external EPO +24 VDC, 1500 mA circuit can be supplied through other vendors.
Note: Always follow the pin connection procedures from the top and work down: J106 (8-1), J108 (1-6).
Connect the
ground cables to
the studs (earth
symbol beneath)
using a screw.
Connect the DC Battery Cables (if applicable)
Connect battery cables BAT+,
BAT–, and N to the battery cable
landings.
2
EPO wiring – pin connections J108. Connect the EPO cable using
J108
1: Dry Contacts Normally Open
J108
EPO circuit
J108
EPO circuit
J108
EPO circuit
2: +24 V Normally Open
EPO is activated when an isolated SELV 24 VDC voltage is supplied on pin 1 with reference to pin 2. Connections: 3-5 and 4-6.
3: Dry Contacts Normally Closed
EPO is activated when a connection from pin 3 to pin 5 is opened. Connections: 4-6.
4: +24 V Normally Closed
EPO is activated when a SELV 24 VDC voltage is removed from pin 3 with reference to pin 4.
EPO circuit
+24 V
0 V
+24 V
0 V
EPO is activated when pin 1 is connected to pins 3 and 5. Connections: 2-4-6, 3-5 and 1 ( )
J106
Q3 switch
Charging control switch
J200 (XR
Batteries)
Pins 1 to 4 are for battery measurement (only applicable to MGE Galaxy 3500 XR Battery Enclosures (see J200 drawing).
Pins 5 and 6 are for external maintenance bypass Q3 (auxiliary switch N/C type). When Q3 is closed, signals are fed back to the UPS controller (see Q3 drawing).
Pins 7 and 8 are for external charge control. When 7 and 8 are closed, the UPS charges batteries with a pre-defined percentage (0-25-50-75-100%) of the maximum charging power. To be used in generator applications, or if special codes require control of charging. When Q3 is closed, signals are fed back to the UPS controller.
BATBA
T
XR battery enclosure
J200
Model:
Serial:
BATTER
Y U
NIT
Model:
Serial:
BATTER
Y U
NIT
Model:
Serial:
BATTER
Y U
NIT
Model:
Serial:
BATTER
Y U
NIT
Model:
Serial:
BATTER
Y U
NIT
Model:
Serial:
BATTERY U
NIT
Model
:
Serial:
BATTER
Y U
NIT
Model:
Serial:
BATTERY U
NIT
one of the following four wiring configurations.
Note: When connecting the Q3 auxiliary signal, use gold­plated N/C auxiliary switch.
Front panel removal.
Use a coin or similar to
turn the two black lock
devices on either side of the
display in the direction of
each other to a vertical
positon.
Push the front panel
upwards and pull it outwards
to disengage the locking
device at the top of the
enclosure.
Lift the front panel free of
the two slots at the bottom of
the enclosure.
Pin connections J106 (UPS).
Note: Reinstall the cable landing cover.
Connect APC communication options
Note: The cable routing of the power chute software and the temperature sensor is identical.
Note: The temperature sensor is provided in a plastic bag attached to the front of the UPS behind the front panel.
3
Remove the two screws
Network Management card
from the cable-inlet at the
front and remove the cable-
inlet plate.
Guide the cable through
the hole in the bottom plate
and up through the cable-
inlet.
Guide the cable through
the side panel hole and run
the cable upwards inside the
panel.
Specifications
Warning: The UPS must be supplied from a 380/220 V,
400/230 V or 415/240 V L1, L2, L3, N, PE, 50 Hz.
AC input
10 kVA
UPS ratings 380 V 400 V 415 V
Input frequency (Hz) 40-70 40-70 40-70
Nominal input current (A)
1
13.0 12.3 11.9
AC output
10 kVA
UPS ratings 380 V 400 V 415 V
Nominal output current (A) 15.2 14.4 13.9
15 kVA 20 kVA
UPS ratings 380 V 400 V 415 V 380 V 400 V 415 V
Nominal output current (A) 22.8 21.7 20.9 30.4 28.9 27.8
Pull the cable out of the
side panel through the hole
closest to the Network
Management Card area.
Plug the cable into the
probe socket / PowerChute
inlet.
Reattach the cable-inlet
plate (
).
Max. input current (A)
Input current limit (A)
UPS ratings 380 V 400 V 415 V 380 V 400 V 415 V
Input frequency (Hz) 40-70 40-70 40-70 40-70 40-70 40-70
Nominal input current (A)
Max. input current (A)
Input current limit (A)
UPS ratings 380 V 400 V 415 V 380 V 400 V 415 V
Input frequency (Hz) 40-70 40-70 40-70 40-70 40-70 40-70
2
3
15 kVA 20 kVA
1
19.4 18.5 17.8 26.0 24.7 23.8
2
21.4 20.3 19.6 28.6 27.2 26.2
3
25.2 25.2 25.2 33.8 33.8 33.8
30 kVA 40 kVA
14.3 13.5 13.1
16.8 16.8 16.8
30 kVA 40 kVA
UPS ratings 380 V 400 V 415 V 380 V 400 V 415 V
Nominal output current (A) 45.6 43.3 41.7 60.8 57.7 55.6
Battery input
UPS ratings
Nominal voltage (V) ± 192 ± 192 ± 192 ± 192 ± 192
External battery fuse (A) 125 125 125 125 125
10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
1.6-1.75 V/cell (automatic, depending on load)
Nominal input current (A)
Max. input current (A)
Input current limit (A)
2
3
1
38.6 36.7 35.3 51.7 49.1 47.3
42.5 40.3 38.9 56.8 54.0 52.1
50.1 50.1 50.1 66.9 66.9 66.9
4
Bypass input
∞∞∞∞∞
Recommended current protection
Minimum breaker settings
10 kVA
UPS ratings 380 V 400 V 415 V
Input frequency (Hz)
Nominal input current (A)
4
1
50±10 or 60±10
50±10 or 60±10
50±10 or 60±10
15.2 14.4 13.9
15 kVA 20 kVA
UPS ratings
Input frequency (Hz)
Nominal
380 V 400 V 415 V 380 V 400 V 415 V
50±10 or 60±10
4
50±10 or 60±10
50±10 or 60±10
50±10 or 60±10
50±10 or 60±10
22.8 21.7 20.9 30.4 28.9 27.8 input current
1
(A)
30 kVA 40 kVA
UPS ratings
Input frequency (Hz)
Nominal
380 V 400 V 415 V 380 V 400 V 415 V
50±10 or 60±10
4
50±10 or 60±10
50±10 or 60±10
50±10 or 60±10
50±10 or 60±10
45.6 43.3 41.7 60.8 57.7 55.6 input current
1
(A)
Notes
1
Input current based on rated load and batteries fully charged.
2
Input current based on full battery recharge, nominal voltage and rated load.
3
Current limitation through electronic current limiting is based on full battery
recharge and low input voltage.
4
Synchronization adjustable: ± 10Hz, ± 3Hz or ± 0.1Hz.
50±10 or 60±10
50±10 or 60±10
Note: AC input/output over-current protection and AC input/output disconnect must be provided by the customer
1
Q1
Q3 Q2
Utility input Bypass input Output
10 kVA
15 kVA
20 kVA
30 kVA
40 kVA
1
Required upstream current protection, mains input: gL type fuse.
16 16 16
25 25 25
35 35 35
50 50 50
63 63 63
.
Recommended cable sizes
Note: The recommended cable sizes are based on an
environment with an ambient temperature of 30°C.
Battery input
2
[mm
] 75ºC
Wire
10 kVA
15 kVA
20 kVA
30 kVA
40 kVA
Mains input
2
[mm
]
AC output [mm2]
2.5 2.5 50 2.5
66506
10 10 50 10
16 16 50 16
25 25 50 25
Note: Use Molex lug type or equivalent, and crimp to manufacturer’s specifications.
Warning: At 100% switch mode load, the neutral must be rated for 200% phase current.
Bypass input
2
[mm
]
125% overload normal/ battery operation Continuously
800% overload bypass operation
150% overload normal/ battery operation
10 kVA
Mains input
1
–– 16.4 A
Bypass input 121.5 A 16.7 A
Output 121.5 A 22.8 A 19 A 16.7 A
Duration 500 ms 60 s 10 min.
15 kVA
Mains input
1
–– 24.6 A
Bypass input 182 A 25.1 A
Output 182 A 34.2 A 25.4 A 25.1 A
Duration 500 ms 60 s 10 min.
20 kVA
Mains input
1
–– 32.5 A
Bypass input 244 A 33.4 A
Output 244 A 45.6 A 38 A 33.4 A
Duration 500 ms 60 s 10 min.
30 kVA
Mains input
1
–– 49.1 A
Bypass input 364 A 50.1 A
Output 364 A 68.4 A 57 A 50.1 A
Duration 500 ms 60 s 10 min.
40 kVA
Mains input
1
–– 65.6 A
Bypass input 487 A 66.9 A
Output 487 A 91.2 A 76 A 66.9 A
Duration 500 ms 60 s 10 min.
1
At single feed use the higher value of mains and bypass.
Recommended lug size and torque value
Note: Power terminal lug diameter: 6 mm. Torque value: 7
Nm.
5
Contact Information
Diagram with Maintenance
Bypass Panel
Diagram without
Maintenance Bypass Panel
For local, country-specific centers: go to www.apc.com/support/ contact.
Appendix
Wiring diagrams
6
Loading...