Note: Ensure that the unit is in its final location prior to
installation.
Note: Battery and utility/mains power must not be
connected until all other wiring has been completed.
Prepare for Cables
Bottom cable entry
From the rear of the UPS, loosen the six
M4 screws from the upper cover (the cable
landing area) on the back and remove.
MGE™ Galaxy™ 3500
10-40 kVA 380/400/415 V with batteries
See Also: For parallel configurations see manual 990-
3568.
Level the Enclosure
Warning: The system must be installed on a level floor.
The leveling feet will stabilize the enclosure, but will not
account for a badly sloped floor.
Use a 13/14 mm wrench to adjust the four leveling feet.
Ensure that the system is level.
Caution: Do not move the enclosure after the leveling feet
have been lowered.
Route the cables from the
slanted back plate, up
through the punched
bracket, and into the cable
landing area.
Fasten the cables with
cable ties
IMPORTANT SAFETY INSTRUCTIONS
990-2258B-001
SAVE THESE INSTRUCTIONS
Warning: ALL safety instructions in the Safety Sheet
(990-2940) must be read, understood, and followed when
installing the UPS system. Failure to do so could result in
equipment damage, serious injury, or death.
Warning: After the UPS has been electrically wired, do
not start it up. Start-up is commissioned to authorized
personnel from Schneider Electric.
Caution: All electrical power and power control wiring
must be installed by a qualified electrician, and must comply
with local and national regulations for maximum power
rating.
*990-2258B-
9/2009
Floor Anchoring (if applicable)
Anchor the UPS enclosure to the floor
Note: Floor-anchoring bolts are not provided with the UPS.
Purchase the bolts locally (minimum size: M8). Follow the
specifications given by the manufacturer of the floor
anchoring system when bolting the UPS system to the floor.
Reuse the two transport brackets (one
on each side) that were used to secure the
UPS to the pallet during transport.
Drill two to six holes in the floor for
each bracket. Attach with bolts.
Note: A conduit box (part no. SUVTOPT001 or
SUVTOPT002) is available as an option.
Connect the AC Input and AC
J108 pin connections:
1 Normally open EPO
2 Normally open EPO return
3 Normally closed EPO
4 Normally closed EPO return
5 +24 V SELV supply
6 SELV ground
J106 pin connections:
8Ext. charging control return
7External control of charging
6Q3 active return
5Q3 active
4Battery measurement supply*
3Battery unit quantity*
2Max. battery temperature*
1Battery measurement return*
* Should be used with MGE Galaxy
3500 XR Enclosures
Dual mains
Connect the Communication
Output Cables
Warning: Use compression type lugs ONLY.
Do not loosen or add cables to any factory preinstalled
cables on busbars. Use the front part of busbar for
connection only.
See Also: For different grounding configurations please
see manual 990-3606.
Single mains
Connect the AC input cables
and the neutral to the input
cable landings.
Connect the AC output
cables and the neutral to the
output cable landings.
Connect the ground cables to
the studs (earth symbol
beneath) using a screw.
Remove the
three busbars A,
B, and C by
removing two M6
screws from each
busbar.
Connect the AC
input cables and
the neutral to the
input cable
landings.
Connect the
bypass cables and
the neutral to the
bypass cable
landings.
Connect the
output cables and
the neutral to the
output cable
landings.
Cables
Warning: Make sure that the UPS is completely OFF as
the connectors are very close to the power busbars.
J106 (XR Battery Enclosure) and J108 (EPO)
Note: Use only 1-1½ mm² copper wire for the connection of
the Emergency Power Off (EPO) and other optional
equipment.
Note: The UPS must be connected to either a dry contact or
a 24 VDC EPO (Emergency Power Off) switch.
Note: The external EPO +24 VDC, 1500 mA circuit can be
supplied through other vendors.
Note: Always follow the pin connection procedures from
the top and work down: J106 (8-1), J108 (1-6).
Connect the
ground cables to
the studs (earth
symbol beneath)
using a screw.
Connect the DC Battery Cables
(if applicable)
Connect battery cables BAT+,
BAT–, and N to the battery cable
landings.
2
EPO wiring – pin connections J108. Connect the EPO cable using
J108
1: Dry Contacts Normally Open
J108
EPO circuit
J108
EPO circuit
J108
EPO circuit
2: +24 V Normally Open
EPO is activated when an isolated SELV 24
VDC voltage is supplied on pin 1 with
reference to pin 2.
Connections: 3-5 and 4-6.
3: Dry Contacts Normally Closed
EPO is activated when a connection from
pin 3 to pin 5 is opened.
Connections: 4-6.
4: +24 V Normally Closed
EPO is activated when a SELV 24 VDC
voltage is removed from pin 3 with
reference to pin 4.
EPO circuit
+24 V
0 V
+24 V
0 V
EPO is activated when pin 1 is connected
to pins 3 and 5.
Connections: 2-4-6,
3-5 and 1 ( )
J106
Q3 switch
Charging control
switch
J200 (XR
Batteries)
Pins 1 to 4 are for battery measurement (only applicable to
MGE Galaxy 3500 XR Battery Enclosures (see J200 drawing).
Pins 5 and 6 are for external maintenance bypass Q3
(auxiliary switch N/C type).
When Q3 is closed, signals are fed back to the UPS controller
(see Q3 drawing).
Pins 7 and 8 are for external charge control. When 7 and 8 are
closed, the UPS charges batteries with a pre-defined
percentage (0-25-50-75-100%) of the maximum charging
power. To be used in generator applications, or if special
codes require control of charging.
When Q3 is closed, signals are fed back to the UPS
controller.
BATBA
T
XR battery enclosure
J200
Model:
Serial:
BATTER
Y U
NIT
Model:
Serial:
BATTER
Y U
NIT
Model:
Serial:
BATTER
Y U
NIT
Model:
Serial:
BATTER
Y U
NIT
Model:
Serial:
BATTER
Y U
NIT
Model:
Serial:
BATTERY U
NIT
Model
:
Serial:
BATTER
Y U
NIT
Model:
Serial:
BATTERY U
NIT
one of the following four wiring configurations.
Note: When connecting the Q3 auxiliary signal, use goldplated N/C auxiliary switch.
Front panel removal.
Use a coin or similar to
turn the two black lock
devices on either side of the
display in the direction of
each other to a vertical
positon.
Push the front panel
upwards and pull it outwards
to disengage the locking
device at the top of the
enclosure.
Lift the front panel free of
the two slots at the bottom of
the enclosure.
Pin connections J106 (UPS).
Note: Reinstall the cable landing cover.
Connect APC communication options
Note: The cable routing of the power chute software and
the temperature sensor is identical.
Note: The temperature sensor is provided in a plastic bag
attached to the front of the UPS behind the front panel.
3
Remove the two screws
Network
Management
card
from the cable-inlet at the
front and remove the cable-
inlet plate.
Guide the cable through
the hole in the bottom plate
and up through the cable-
inlet.
Guide the cable through
the side panel hole and run
the cable upwards inside the
panel.
Specifications
Warning: The UPS must be supplied from a 380/220 V,
400/230 V or 415/240 V L1, L2, L3, N, PE, 50 Hz.
AC input
10 kVA
UPS ratings380 V 400 V 415 V
Input frequency (Hz)40-7040-7040-70
Nominal input current (A)
1
13.012.311.9
AC output
10 kVA
UPS ratings380 V 400 V 415 V
Nominal output current (A)15.214.413.9
15 kVA20 kVA
UPS ratings380 V 400 V 415 V380 V 400 V 415 V
Nominal output current (A) 22.821.720.930.428.927.8
Pull the cable out of the
side panel through the hole
closest to the Network
Management Card area.
Plug the cable into the
probe socket / PowerChute
inlet.
Reattach the cable-inlet
plate (
).
Max. input current (A)
Input current limit (A)
UPS ratings380 V 400 V 415 V380 V 400 V 415 V
Input frequency (Hz)40-7040-7040-7040-7040-7040-70
Nominal input current (A)
Max. input current (A)
Input current limit (A)
UPS ratings380 V 400 V 415 V380 V 400 V 415 V
Input frequency (Hz)40-7040-7040-7040-7040-7040-70
2
3
15 kVA20 kVA
1
19.418.517.826.024.723.8
2
21.420.319.628.627.226.2
3
25.225.225.233.833.833.8
30 kVA40 kVA
14.313.513.1
16.816.816.8
30 kVA40 kVA
UPS ratings380 V 400 V 415 V380 V 400 V 415 V
Nominal output current (A) 45.643.341.760.857.755.6
Battery input
UPS ratings
Nominal voltage (V)± 192± 192± 192± 192± 192
External battery fuse (A)125125125125125
10 kVA15 kVA20 kVA30 kVA40 kVA
1.6-1.75 V/cell (automatic, depending on load)
Nominal input current (A)
Max. input current (A)
Input current limit (A)
2
3
1
38.636.735.351.749.147.3
42.540.338.956.854.052.1
50.150.150.166.966.966.9
4
Bypass input
∞∞∞∞∞
Recommended current protection
Minimum breaker settings
10 kVA
UPS ratings380 V400 V415 V
Input frequency (Hz)
Nominal input current (A)
4
1
50±10 or
60±10
50±10 or
60±10
50±10 or
60±10
15.214.413.9
15 kVA20 kVA
UPS
ratings
Input
frequency
(Hz)
Nominal
380 V400 V415 V380 V400 V415 V
50±10 or
60±10
4
50±10 or
60±10
50±10 or
60±10
50±10 or
60±10
50±10 or
60±10
22.821.720.930.428.927.8
input
current
1
(A)
30 kVA40 kVA
UPS
ratings
Input
frequency
(Hz)
Nominal
380 V400 V415 V380 V400 V415 V
50±10 or
60±10
4
50±10 or
60±10
50±10 or
60±10
50±10 or
60±10
50±10 or
60±10
45.643.341.760.857.755.6
input
current
1
(A)
Notes
1
Input current based on rated load and batteries fully charged.
2
Input current based on full battery recharge, nominal voltage and rated load.
3
Current limitation through electronic current limiting is based on full battery
recharge and low input voltage.
4
Synchronization adjustable: ± 10Hz, ± 3Hz or ± 0.1Hz.
50±10 or
60±10
50±10 or
60±10
Note: AC input/output over-current protection and AC
input/output disconnect must be provided by the customer
1
Q1
Q3Q2
Utility inputBypass inputOutput
10 kVA
15 kVA
20 kVA
30 kVA
40 kVA
1
Required upstream current protection, mains input: gL type fuse.
161616
252525
353535
505050
636363
.
Recommended cable sizes
Note: The recommended cable sizes are based on an
environment with an ambient temperature of 30°C.
Battery input
2
[mm
] 75ºC
Wire
10 kVA
15 kVA
20 kVA
30 kVA
40 kVA
Mains input
2
[mm
]
AC output
[mm2]
2.52.5502.5
66506
10105010
16165016
25255025
Note: Use Molex lug type or equivalent, and crimp to
manufacturer’s specifications.
Warning: At 100% switch mode load, the neutral must
be rated for 200% phase current.