APC GALAXY 9000 User Manual

MGETM GalaxyTM 9000
50, 60 Hz 800 - 900 kVA
Installation manual
Single-unit UPS
Modular UPS
Parallel UPS with SSC
Frequency converters
Static Switch Cubicle
34006451EN/AC - Page 2
Contents
1. Characteristics
1.1 Characteristics common to all cubicles ............................................................................................ 4
1.2 Rectifier-inverter cubicle .................................................................................................................... 5
1.3 Static Switch Cubicle ........................................................................................................................... 5
1.4 Electrical parameters for selecting protective devices ................................................................... 6
1.5 Electrical parameters for determining cable cross-sections .......................................................... 7
2. Installation (to be carried out by qualified personnel only)
2.1 Handing .............................................................................................................................................. 10
2.2 Positioning the cubicles .................................................................................................................. 10
2.3 Floor loads (figure 5) ........................................................................................................................11
2.4 Cubicle layout on false floor or normal floor (figures 6, 7, 8) ........................................................11
2.5 Power circuit wiring diagrams ......................................................................................................... 13
2.6 Cubicle mounting and connection ................................................................................................... 17
2.7 Connection of power circuits ........................................................................................................... 19
2.8 Connection of "Media Contacts 9" standard auxiliary circuits (figure 16) ................................... 22
2.9 Connections between cubicles (modular UPSs or parallel UPSs with SSC) .............................. 23
2.10 Connections between rectifier-inverter cubicles and external maintenance bypass cubicle .26
2.11 Connection of "Media Contacts 15" additional auxiliary circuits
(figure 22) ................................................................................................................................... 27
2.12 Connection of the battery "Temperature Monitor" (optional) ...................................................... 28
2.13 Connection of the "LED" remote indications unit ....................................................................... 30
2.14 Connection of "Tele Monitor" remote control and indication unit (option) .............................. 30
2.15 Final installation steps .................................................................................................................. 30
3. Appendix (to be carried out by qualified personnel only)
3.1 Mains 2 line protection ..................................................................................................................... 31
3.2 Cubicle mounting and connection for 2000 kVA Static Switch Cubicle ....................................... 32
3.3 Details of earthing connections in the various cubicles ................................................................ 35
34006451EN/AC - Page 3
1. Characteristics
1.1 Characteristics common to all cubicles
TM
MGE
GalaxyTM 9000 UPS: example of a rectifier-inverter cubicle
A V k
5
%
12
20
1
.
in
%
M
00
50
1
r u
0%
Ho
0 1
0
0%
8
% 0 5
VA
0 k
% 0 5
00 40
60
XY
LA
GA
0
IQ
LE
el
AL
v
S
e
l
d a o L
0
e
m Ti p u
ck a B
d
le e t
b c
la
e
i
t
a v
ro
A p d
a o L
N 5
d
Q
a
e
o
t
L
n
om
e
H
m
ip qu e
s m
r a l A
1
Q e n i
nl O
1 F Q
nd e r T
C
l A a m r
s
c
o
i t
N
is t a t S
r
fie
ti ec R
S y r
4 e
Q
tt a B
05 20 5/
/0 0
3 er t
2
r
3
e
C
4:
A
nv
2
I
:
s
5
s
1 a p y
B
P B
s
Q3 s a
yp B
t u p
t u O
p
t u e S
Galaxy 6000
m
w w
w.m ge u
ps
.co
H
L
P
0 0 0
VA
6
k 5
y
0%
12
2 1
x la
a
Min. 0
00%
G
1
our 5
0% 0
H
1
0
%
w w
80
w
. m g e u p s . c
o m
% 0 5
A
% 0
400 kV
5
0 00 6 Y
AX AL G
0
IQ E
L
vel
SAL
e ad l
Lo 0 e m up Ti k
c a B
d
e
l e t
b
a
l ec t o
vai
r p
A d
Loa
N 5 Q
ad o
t
L
n
Home
equipme s m r a l A
Q1 ne i l n O
1 QF
nd e r T
s c i t
Normal AC tis a t S
er i tif c Re
S
ry
4
e
Q
t t Ba
05 0 2 / 5 0 0/ 3
r e t
2
r
3
e
: 4
AC
nv
2
I
15: ypass B
BP
s
Q3 s ypa B
put t u O
p u t e S
After moving them to their installation location on their pallets, MGE pallet-mover when the front, rear and side base panels are not mounted. The forks can be inserted from all four sides into 100 mm ±10 mm
TM
GalaxyTM 9000 cubicles can be moved short distances using a forklift or
high openings; the unadjusted cubicle height (H) is 1900/2000 mm; after lifting the cubicle, the height can be adjusted ±10 mm by screwing in or out the four feet; the bearing surface corresponds to the area of the four cylindrical foot pads (60 mm diameter) positioned in each corner of the cubicle; the cubicle depth (D) is 840 mm (800 mm without doors and panels); operating temperature range for rectifier-inverter, frequency converter or Static Switch Cubicles: 0 °C to 35 °C at rated output (40 °C for a maximum of 8 hours) and 30 °C maximum for overload conditions. Operation outside the specified temperature range will reduce service life; relative humidity: 95 % maximum; maximum operating altitude without derating: 1000 m; connection via the bottom for rectifier-inverter cubicles, or via the top with the addtion of an optional duct that can be installed on the right side of the cubicle. The auxiliary and Static Switch Cubicles are designed for connections via the top or bottom. the connection cables may be run in three ways: in a trench running under the cubicles, under a false floor, on the floor under the cubicles, in the free space equal to the height of the feet; in this case the cables should be run side by side to avoid blocking the flow of air for ventilation. the intercubicle connection cables are not supplied (except for the wires for auxiliary interconnections); normally the cubicles do not have to be secured to the floor; the footpads nevertheless have holes with an average depth of 12 mm designed for the fitting of M16 anchor bolts; the cubicle doors are secured by Ronis locks (key 405).
34006451EN/AC - Page 4
1.2 Rectifier-inverter cubicle
The parameters given in the table opposite can be used to determine the required rating of a single-unit or modular UPS, a frequency converter, or a parallel UPS with SSC.
Characteristics of rectifier-inverter cubicles
Characteristics
rated inverter output in kVA
800 3600 ±10 2000 840 4260 47 11233
900 3600 ±10 2000 840 4260 47 11233
(1) the width of the vertical side clearance bars (25 mm) on each side must be added to the indicated cubicle width, i.e. 50 mm in all per cubicle. This applies to all cubicle installation cases. Cubicle widths have been rounded off to the nearest cm.
(2) the indicated heat losses are those produced by the unit at full rated load and with the battery float charging. They must be taken into account when dimensioning the air conditioning system. The cubicles are cooled by forced ventilation. The air enters via the doors and grids at the bottom and is discharged via the roof.
1.3 Static Switch Cubicle
Characteristics of Static Switch Cubicles
rated SSC output in kVA
2000 2450 ±10 1900 ±10 840 1710 < 0.5 < 120
(1) 25 mm must be added on each side to the indicated cubicle width, i.e. 50 mm in all per cubicle. This applies to all cubicle installation cases. Cubicle widths have been rounded off to the nearest cm.
(2) the indicated heat losses are those produced by the unit at full rated load when operating on Mains 2. They are not to be taken into account when dimensioning the air conditioning system. The cubicles are cooled by forced ventilation.
cubicle width W in mm (1)
cubicle width W in mm (1)
cubicle height H in mm
cubicle height H in mm
cubicle depth D in mm
cubicle depth D in mm
maximum weight in kg
maximum weight in kg
heat losses (2)
in kW in cal./s
heat losses (2)
in kW in cal./s
34006451EN/AC - Page 5
Characteristics
1.4 Electrical parameters for selecting protective devices
The parameters given in the table below can be used to determine the required rating of the source side protective circuit breaker on Mains 1 of a single-unit or modular UPS, a frequency converter, or a parallel UPS with SSC.
Important:
It is essential to choose the type of circuit breaker according to its breaking capacity and the prospective short-circuit current at its place of installation.
Note:
For Mains 1 power supply voltages of 380, 400 and 415 V, the Mains 1 current is the same because it is a function of the DC voltage.
Electrical parameters for Mains 1
rated inverter output in kVA
800 1555 1329 1819 2183 900 1555 1329 1819 2183
(1) the rated Mains 1 currents (In) have been determined for a rated phase-to-phase voltage of 380 V to 415 V, a battery with a 15 minute backup time (206 cells at 2 V per cell, i.e. 412 V) and at the beginning of its recharge cycle, and full rated load with a power factor of 0.9. (2) the rated Mains 1 currents (In) have been determined for a minimum float charging voltage of 423 V and full rated load with a power factor of 0.9. (3) the Mains 1 currents given for an overload of 25 % or 50 % are maximum values. They have been determined for a battery drawing the minimum float charging voltage and a load power factor of 0.9. When choosing the circuit breaker rating, use the "rated current" column and check that the circuit breaker tripping curves are compatible with the values in the overload columns.
The parameters given in the table below can be used to determine the required rating of the source side protective circuit breaker on the Mains 2 line for a single-unit or modular UPS.
Important:
– It is essential to choose the type of circuit breaker according to its breaking capacity and the prospective short-circuit current at its place of installation. This choice must also be made so as to protect the static switch semiconductors and ensure discrimination with respect to the UPS output fuses (refer to "appendix" chapter). – For an installation with a Static Switch Cubicle, the Mains 2 currents indicated in the table must be multipled by the number of parallel-connected rectifier-inverter cubicles required to supply the load power (i.e. without taking redundant rectifier­inverter units into account).
Remark:
If the installation includes a transformer on the Mains 2 input, allow for the inrush current caused by magnetization of the transformer windings.
Mains 1 current
rated current In for unit: for 25 %
with battery at start of charge cycle (1)
without battery (2)
overload (3)
for 50 % overload (3)
Electrical parameters for Mains 2 (415 V)
rated inverter output in kVA
800 1155 1444 1733 900 1299 1624 1949
(1) the Mains 2 currents have been determined for a rated phase-to-phase voltage of 415V, a load power factor of 0.9 and for full rated load as well as overloads of 25 % or 50 %. When choosing the circuit breaker rating, use the "rated curent" column and check that the circuit breaker tripping curves are compatible with the data in the overload columns. For a Mains 2 voltage of 380 V, multiply the currents indicated in this table by 1.09. For a Mains 2 voltage of 400 V, use the table in another language version of this manual.
Mains 2 current (1)
rated current In for 25 %
overload
for 50 % overload
34006451EN/AC - Page 6
1.5 Electrical parameters for determining cable cross-sections
– this table has been drawn up for rated phase-to-phase Mains and load voltages of 415 V. For voltages of 380 V, multiply the currents for Mains 2 and load by 1.09; for voltages of 400 V, use the table in another language version of this manual; – the current values and cable cross-sections for Mains 1 are given for full rated load with a power factor of 0.9 and a battery consuming its minimum float charging voltage; – the battery current values and cable cross-sections have been determined for a battery at the end of a charge cycle; – the current values and cable sections for Mains 2 and load are given for full rated load with a power factor of 0.9. For frequency converters, the parameters concerning Mains 2 are not applicable. The load parameters common to all the converters are given in the table below. For a parallel UPS, the parameters for Mains 2 and load are also provided in the table below.
For a modular UPS, the parameters for Mains 2 and load are also provided in the table below.
Parameters for single-unit UPS cables
Copper conductors
rated inverter output in kVA
800 1455 1155 2274 4 x 240 4 x 185 3 x 240
line currents absorbed in Amps cross-sectional area of cables in mm2 (2)
Mains 1 415 V
with or without battery (1)
Mains 2 and load
battery Mains 1 415 V
with or without battery (1)
Characteristics
battery Mains 2 and load
900 1455 1299 2274 4 x 240 4 x 240 3 x 240
Aluminium conductors
rated inverter output in kVA
800 1455 1155 2274 4 x 400 4 x 300 3 x 400
900 1455 1299 2274 4 x 400 4 x 400 3 x 400
(1) the rated Mains 1 currents (In) have been determined for a minimum float charging voltage of 423 V and full rated load with a power factor of 0.9. (2) the cable cross-sections are calculated according to permissible temperature rise and allow for line voltage drops over a maximum length of 100 m (AC circuits) or 25 m (DC circuits if cables not provided). For greater lengths, the cross-sections should be chosen to limit voltage drops to 3 % (AC) or 1 % (DC).
line currents absorbed in Amps cross-sectional area of cables in mm2 (2)
Mains 1 415 V
with or without battery (1)
Mains 2 and load
battery Mains 1 415 V
with or without battery (1)
Mains 2 and load
battery
34006451EN/AC - Page 7
Characteristics
The table below serves as an example for an installation comprising up to four frequency converters or four parallel UPSs with a centralised SSC. – for installations with redundant units, take into account only the units required to supply the load power (e.g. for an installation made up of 3 parallel-connected rectifier-inverter cubicles, one being redundant, only 2 rectifier­inverter cubicles are used to determine Mains 2 and load currents and cable cross-sections); – this table has been drawn up for rated phase-to-phase Mains 2 and load voltages of 415 V and full rated load with a power factor of 0.9. For voltages of 380 or 400 V, multiply the indicated currents by 1.09 and 1.04 respectively, then modify the cable cross-sections accordingly if necessary. The cable cross-sections in this table are for the parts illustrated in bold on the following block diagrams (installation examples, figures 1 and 2).
Parameters for Mains 2 and load cables for an installation comprising frequency converters or parallel UPSs with a centralised SSC.
rated inverter output
number of parallel-connected inverters
total UPS rated output in kVA
Mains 2 or load line current in Amps
cable cross-section (1) in mm²
in kVA
800 2 1600 2310
3 2400 3465 4 3200 4620
900 2 1800 2598
3 2700 3897 4 3600 5196
(1) cable cross-sections are given for copper conductors of the U1000 R02V type (increase by 30 % for aluminium conductors). They are calculated according to permissible temperature rise and allow for line voltage drops over a maximum length of 100 m. For greater lengths, the cross-sections should be chosen to limit voltage drops to 3 %.
Please consult us* Please consult us* Please consult us* Please consult us* Please consult us* Please consult us*
* NF C 15-100 authorizes a maximum of 4 cables per phase.
Installation with parallel frequency converters I
mains 1
mains 1
mains 1
inverter 1
inverter 2
inverter 3
load
Fig. 1
Installation with parallel UPSs with a centralised SSC
mains 2
mains 1
mains 1
mains 1
Fig. 2
inverter 1
inverter 2
inverter 3
static switch cubicle
load
34006451EN/AC - Page 8
Characteristics
The table below serves as an example for an installation with up to four modular UPSs with an external maintenance bypass. – for installations with redundant units, take into account only the units required to supply the load power (e.g. for an installation made up of 3 parallel-connected rectifier-inverter cubicles, one being redundant, only 2 units are used to determine the currents on the maintenance bypass line and the load, and the cross-sectional areas of cables); – this table has been drawn up for rated phase-to-phase Mains 2 and load voltages of 415 V and full rated load with a power factor of 0.9. For voltages of 380 or 400 V, multiply the indicated currents by 1.09 and 1.04 respectively, then modify the cable cross-sections accordingly if necessary. The cable cross-sections in this table are for the parts illustrated in bold on the following block diagrams (installation example, figure 3); – important. In an installation with an external maintenance bypass, the power cables between each UPS and the
upstream protection devices must be the same length. The same holds for the power cables between each UPS cubicle and the external maintenance bypass.
rated inverter output
number of parallel-connected inverters
total UPS rated output in kVA
mains 2 or load line current in Amps
cable cross-section (1) in mm²
in kVA
800 2 1600 2310
Please consult us*
3 2400 3465 Please consult us* 4 3200 4620 Please consult us*
900 2 1800 2598 Please consult us*
3 2700 3897 Please consult us* 4 3600 5196 Please consult us*
(1) cable cross-sections are given for copper conductors of the U1000 R02V type (increase by 30 % for aluminium conductors). They are calculated according to permissible temperature rise and allow for line voltage drops over a maximum length of 100 m. For greater lengths, the cross-sections should be chosen to limit voltage drops to 3 %.
* NF C 15-100 authorizes a maximum of 4 cables per phase.
Installation comprising modular UPSs with an external maintenance bypass
maintenance Bypass cubicle
mains 1
mains 2
mains 1
mains 2
mains 1
mains 2
inverter 1
inverter 2
inverter 3
load
Fig. 3
34006451EN/AC - Page 9
2. Installation (to be carried out by qualified personnel only)
2.1 Handing
Unpacked cubicles may be moved using a forklift from the front or from the back. Distances must not exceed a few meters.
2.2 Positioning the cubicle
– prior to moving the cubicles to their final position, remove the packing material and withdraw the base panels from the space on the side created by the spacing uprights. The panels will be installed at the end of the installation procedure; – spacing uprights on the sides of the cubicles create a 50 mm clearance when cubicles are positioned next to each other, enabling users to open the doors (see figure 4). If a cubicle is installed next to a wall, leave additional space so that the cubicle is 50 mm from the wall; – when the spacing uprights are not required (cubicles are not positioned next to a wall or another cubicle), they may be removed: – loosen the four screws securing the upright, – lift the upright and pull it free, – replace the long gold-coloured screws with the black screws supplied in a bag attached to the cable terminals in the cubicle; – adjust the height of the feet until the first cubicle is perfectly vertical; adjust the feet of the subsequent cubicles so that the all the doors are perfectly aligned.
Side clearances provided by the spacing uprights
rear
s
50
50
Fig. 4
front
cubicle 1
spacing uprights of cubicle 1
cubicle 2
spacing uprights of cubicle 2
34006451EN/AC - Page 10
2.3 Floor loads (figure 5)
– the floor supports the weight of each cubicle via the four 60 mm diameter pads at the bottom of the feet screwed into the corners of the frame; – the exact locations of the footpads are indicated in the figure; – normally the cubicles do not have to be secured to the floor; the footpads nevertheless have holes with an average depth of 12 mm designed for the fitting of M16 anchor bolts; – to determine the stresses applied by the cubicle feet on the floor, divide the cubicle weight (see the first 3 tables of this manual) by the total area of the 4 footpads (110 cm
Cubicle footpads
Installation
2
).
rear
four 60 mm dia. footpads with 12 mm average depth holes for M16 anchor bolts
33 33
33
736
cubicle width less 66 mm
front
Fig. 5
2.4 Cubicle layout on false floor or normal floor (figures 6, 7, 8)
– the cubicles can be installed directly up against the rear wall; – an overall clearance of 400 mm must be left above the entire surface of the cubicles for ventilation; – a side clearance of 25 mm is provided by the vertical bars on the sides of the cubicles to allow door opening. For cubicles mounted side by side, the two adjacent bars ensure an inter-cubicle clearance of 50 mm; – a minimum clearance of 1000 mm is required in front of the cubicles to allow complete opening of the doors and easy access for maintenance work (replacement of subassemblies); – for extended battery backup times or high output systems, the UPS may have several battery cubicles (see the table at the end of the previous chapter). If this is the case, install the battery cubicles on the left side of the rectifier-inverter cubicle with the cubicle containing the battery circuit breaker QF1 closest to the rectifier-inverter cubicle (figure 7); – when an auxiliary cubicle is included in the UPS, it should be installed to the left of the battery cubicle(s);
connection via the bottom
The connection cables may be run in three ways: – in a cable trench running underneath the front of the cubicles (see trench dimensions and layout in figure 6), – under a false floor. A cutout must in this case be made in the floor for cable entry (see figure 6 for dimensions),
33
3333
34006451EN/AC - Page 11
Installation
Layout for a single-unit UPS with one battery cubicle
rear
>25
80
cubicle width W (see table)
battery cubicle
50
cubicle width W (see table)
rectifier-inverter cubicle
spacing uprights
front
cutouts necessary for cable entry from underneath a false floor: 200 mm x (W  160 mm)
Fig. 6
Layout for a single-unit UPS with several battery cubicles
rear
battery cubicle 1
battery cubicle 2
containing battery circuit breaker QF1
can equal 0
800
> 1000
rectifier-inverter cubicle
location of trench under cubicles (if applicable)
front
Fig. 7
– on the floor under the cubicles, in the free space equal to the height of the feet. In this case the cables should be run side by side to avoid blocking the flow of air for ventilation. The cables exit from the rear or sides of the cubicles;
connection via the top
– the Static Switch, filter and auxiliary cubicles are designed for connection via the bottom or top, – for the rectifier-inverter cubicles, a special 400 mm wide connection duct must be added to the right of the cubicle to allow connection via the top.
Layout for an installation with two parallel UPSs and a centralised SSC
rear
front
auxiliaries cubicle 2 (if applicable)
battery cubicle(s) 2
rect./inv. cubicle 2
auxiliaries cubicle1 (if applicable)
battery cubicle(s) 1
rect./inv. cubicle 1
static switch cubicle
34006451EN/AC - Page 12
Fig. 8
Loading...
+ 28 hidden pages