Thank you for selecting an APC by Schneider Electric product to protect your electrical equipment.
The MGE
We recommend that you take the time to read this manual to take full advantage of the many features of your UPS.
TM
GalaxyTM 5000 range has been designed with the utmost care.
APC by Schneider Electric pays great attention to the environmental impact of its products.
Measures that have made MGE
◗ the eco-design approach used in product development,
◗ the elimination of harmonic disturbances reinjected into the AC source,
◗ production in an ISO 14001 certified factory,
◗ recycling of the MGE
TM
To discover the entire range of APC by Schneider Electric products and the options available for the MGE
TM
GalaxyTM 5000 a reference in environmental protection include:
GalaxyTM 5000 at the end of its service life.
TM
GalaxyTM 5000
range, we invite you to visit our web site, www.apc.com, or contact your local APC by Schneider Electric representative.
34001813EN/AE - Page 2
All products in the MGETM GalaxyTM 5000 range are protected by patents. They implement original technology not available to
competitors of APC by Schneider Electric.
To take into account evolving standards and technology, equipment may be modified without notice. Indications concerning
technical characteristics and dimensions are not binding unless confirmed by APC by Schneider Electric.
This document may be copied only with the written consent of Schneider Electric and its affiliated companies. Authorised copies
must be marked
TM
GalaxyTM 5000 Installation and user manual no. 3400181300".
"MGE
Safety rules
Safety of persons
The UPS must be installed in a room with restricted access (qualified personnel only, according to standard 62040-1-2).
A UPS has its own internal power source (the battery). Consequently, the power outlets may be energised even if the UPS is
disconnected from the AC-power source.
Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personnel.
The UPS must be properly earthed.
The battery supplied with the UPS contains small amounts of toxic materials.
To avoid accidents, the instructions below must be observed.
◗ Never operate the UPS if the ambient temperature and relative humidity are higher than the levels specified in the
documentation.
◗ Never burn the battery (risk of explosion).
◗ Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).
◗ Comply with all applicable regulations for the disposal of the battery.
◗ Caution, wait five minutes before opening the UPS to allow the capacitors to discharge.
◗ Caution, there is high leakage current, the earthing conductor must be connected first.
◗ The product must be installed on a non-inflammable surface (e.g. concrete).
◗ Caution, battery replacement must be carried out by qualified personnel.
Safety
Product safety
A protection circuit breaker must be installed upstream and be easily accessible.
◗ Never install the UPS near liquids or in an excessively damp environment.
◗ Never let a liquid or foreign body penetrate inside the UPS.
◗ Never block the ventilation grates of the UPS.
◗ Never expose the UPS to direct sunlight or a source of heat.
◗ When replacing battery cells, use the same type and number of cells.
Special precautions
◗ The UPS connection instructions contained in this manual must be followed in the indicated order.
◗ Check that the indications on the rating plate correspond to your AC-power system and to the actual electrical consumption
of all the equipment to be connected to the UPS.
◗ If the UPS must be stored prior to installation, storage must be in a dry place.
◗ The admissible storage temperature range is -25° C to +45° C.
◗ If the UPS remains de-energised for a long period, we recommend that you energise the UPS for a period of 24 hours, at
least once every month. This charges the battery, thus avoiding possible irreversible damage.
◗ The UPS is designed for normal climatic and environmental operating conditions concerning the altitude, ambient operating
temperature, relative humidity and ambient transport and storage conditions.
◗ Using the UPS within the given limits guarantees its operation, but may affect the service life of certain components,
particularly that of the battery and its autonomy. The maximum storage time of the UPS is limited due to the need to recharge
its integrated battery.
◗ Unusual operating conditions may justify special design or protection measures:
- harmful smoke, dust, abrasive dust,
- humidity, vapour, salt air, bad weather or dripping,
- explosive dust and gas mixture,
- extreme temperature variations,
- bad ventilation,
- conductive or radiant heat from other sources,
- cooling water containing acid or impurities which may cause scale, silt, electrolysis or corrosion of converter parts exposed
to water,
- strong electromagnetic fields,
- radioactive levels higher than those of the natural environment,
- fungus, insects, vermin, etc.,
- battery operating conditions.
◗ The UPS must always be installed in compliance with:
◗ the requirements of standard IEC 60364-4-42: Protection from thermal effects.
◗ standard IEC 60364-4-41: Protection from electric shock.
◗ standard IEC 60364-4-482: Electrical installations of buildings.
◗ in France, the requirements of standard NFC 15-100.
INTN card for auxiliary interconnections of parallel UPS units
192021
XMS02 XMS03
XMS04 XMS05
XMS06 XMS07
1.3 Cabinet layout (normal or false floor)
33.5
70.5
33.5
33.5
712
590
170
Front
33.5
33.5
850
70.5
33.5
(19) DB9 connectors: exchange-current
information
(20) Screw connectors: position information
on Q5N, Q4S and Q3BP switches, from the
external bypass
(21) DB9 connectors: CAN communication
information between UPSs
The four feet of the cabinet are cylindrical, 40
mm in diameter.
The measurements opposite include cabinet
siding (panels and door).
Cable-
running
zone
34001813EN/AE - Page 10
1.4 User-machine interface
1. Presentation
(30) Graphical display
(31) Load protected LED
(32) Minor fault LED
(33) Major fault LED
~
?
(34) Help key
(35) Function keys
(36) Menu key
1.5 Relay communication card
IO
3s
(38) OFF button
(37) ON button
(42) Load supplied LED
(40) UPS ON LED
(41) Operation on battery power LED
(43) Bypass in operation LED
(39) PFC ON LED
(50) Card cover screws
(51) Card screw holes
(52) Card cover
(53) Cable entry holes
(54) Output terminal block
6
5
4
3
2
1
B
A
(55) Input terminal block
(56) Cable clamping screws
34001813EN/AE - Page 11
2. Installation
2.1 Location
To ensure correct ventilation, leave nothing
0 - 600 mm*
>500 mm
on top of the UPS.
Leave one meter of free space in front of the
UPS for door opening.
The cabinet rests on four cylindrical feet,
40 mm in diameter, positioned in the four
corners of the cabinet to spread the weight.
If 500 mm of free space is not maintained
~
?
above the UPS, abnormal temperature rise
IO
3s
may occur.
The UPS must be installed in a room with
restricted access (qualified personnel
only).
(*) The UPS can operate correctly back to the
wall, but it is preferable to leave some space
for easier maintenance.
>1000 mm
2.2 Layout of cabinets
UPS cabinet
~
?
IO
3s
UPS cabinet
Battery cabinet
Battery cabinet 1
~
?
O
I
3s
Battery cabinet 2
34001813EN/AE - Page 12
2.3 Removing the cardboard protecting the batteries
In the UPS
The cardboard protecting the batteries must always be removed once the equipment is installed in its final location.
~
?
IO
s
3
1
2
3
2. Installation
1 - Remove the ties holding the cardboard (1).
2 - Remove the cardboard (2).
3 - Remove the struts (3).
In the external battery cabinet
The cardboard protecting the batteries must always be removed once the equipment is installed in its final location.
1 - Remove the battery support upright (1).
1
2 - Remove the ties holding the cardboard (2)
(1000 mm external battery cabinet).
3 - Remove the cardboard protecting the
batteries (3).
The circuit breakers recommended above respect the requirements for discrimination with the UPS fuses
Upstream circuit-breaker on
separate Normal AC input
Upstream circuit-breaker on
separate Bypass AC input
Upstream circuit-breakers on
common bypass and Normal AC
input
Stick a label with the following text on each upstream circuit breaker:
"Isolate Uninterrptible Power Supply (UPS) before working on this circuit".
Recommended downstream protection
UPS power ratingDownstream
circuit breaker
20-30-40 kVAC60NC 16A
C60NB 25A
60 kVAC60NC 20A
C60NB 32A
80 kVAC60NC 25A
C60NB 50A
100-120 kVAC60NC 32A
C120NB 63A
NS100TMG 50A
Note. See the simplified diagrams in the appendix for common or separate AC inputs, indicating the positions of the protection
devices, the characteristics of the internal UPS fuses and UPS line currents under overload conditions.
Trip unitCurve N for the downstream circuit breaker
may be replaced by curve H or L, depending
on the installation.
The indicated protection ensures
discrimination for each output circuit
downstream of the UPS, whether supplied by
via the normal or the Bypass AC source. If
these recommendations are not followed, a
short-circuit on an output circuit can result in
a break in power longer than 20 milliseconds
on all the other output circuits.
Earth-leakage current
UPS earth-leakage current is 1 A.
34001813EN/AE - Page 14
Required cable sizes
Cable sizes are determined for copper conductors (for aluminium conductors, increase the size by 30%). Size
calculations also take into account a voltage of 400 V and grouping of four cables.
2. Installation
UPS power
rating
20 kVA10 mm
30 kVA16 mm
40 kVA16 mm
60 kVA25 mm
80 kVA50 mm
100 kVA 50 mm
120 kVA 70 mm
Minimum sizes for
separate Normal AC
input copper cables
(<100 m)
2
2
2
2
2
2
2
Minimum sizes for
separate Bypass
AC input copper
cables (<100 m)
16 mm
16 mm
16 mm
25 mm
50 mm
70 mm
70 mm
Connections are made to pre-drilled terminals.
Hole diameter: 6.5 mm (8.5 mm for 120 kVA).
Earthing cables connect to the earthing plate.
Hole diameter: 6.5 mm (8.5 mm for 120 kVA).
Minimum sizes
for common
bypass and
Normal AC input
Minimum sizes
for copper loadcircuit cables
(<100 m)
Battery/terminal
connection
(<15 m)
copper cables
(<100 m)
2
2
2
2
2
2
2
16 mm
16 mm
16 mm
25 mm
50 mm
70 mm
70 mm
2
2
2
2
2
2
2
16 mm
16 mm
16 mm
25 mm
50 mm
70 mm
70 mm
2
2
2
2
2
2
2
2
16 mm
2
25 mm
2
35 mm
2
70 mm
2
95 mm
2 x 50 mm
2 x 70 mm
2
2
34001813EN/AE - Page 15
2. Installation
Required cable sizes for parallel UPS installations with an external bypass
Rated
power of
each UPS
unit
20 kVA2
30 kVA2
40 kVA2
60 kVA2
80 kVA2
Number of
parallel
UPS units
3
4
3
4
3
4
3
4
3
4
Total rated
power of
the UPS
40 kVA
60 kVA
80 kVA
60 kVA
90 kVA
120 kVA
80 kVA
120 kVA
160 kVA
120 kVA
180 kVA
240 kVA
160 kVA
240 kVA
320 kVA
Bypass AC
input or
load line
current
58 A
87 A
116 A
80 A
129 A
172 A
116 A
174 A
232 A
174 A
261 A
348 A
232 A
348 A
464 A
Cable
(1)
size
in mm
16
35
50
25
50
70
35
70
120
70
150
185
120
185
2 x 120
The table opposite is an example for an
2
installation with up to four UPS units.
◗ For installations with redundant units, take
into account only the number of units required
to supply the loads (e.g. in a three-unit
installation where one unit is redundant, only
two units count in determining the input and
load currents).
◗ This table is valid for 400 V input and load
phase-to-phase voltages, at rated load with a
power factor of 0.8. For voltages of 380 or
415 V, multiply the current values by 1.05 or
0.96 respectively and, if necessary, modify
the cable sizes accordingly.
◗ The cable sizes in this table concern the bold
sections in the diagram below.
(1) Cable sizes are determined for U1000
R02V type copper conductors (for aluminium
conductors, increase the size by 30%). Size
calculations also take into account a voltage
of 400 V and grouping of four cables.
100 kVA2
120 kVA2
Bypass AC
200 kVA
3
4
300 kVA
400 kVA
240 kVA
3
4
360 kVA
480 kVA
288 A
432 A
576 A
348 A
522 A
696 A
150
2 x 95
2 x 150
185
2 x 150
2 x 185
External bypass
Bypass AC
Normal AC
Bypass AC
Normal AC
Bypass AC
Normal AC
GALAXY 5000
1
GALAXY 5000
2
GALAXY 5000
3
Load
34001813EN/AE - Page 16
2.5 2.5 System earthing arrangements
This chapter lists the main system earthing arrangements and their wiring requirements. For system earthing arrangements
which are not listed in this document, please refer to the “SEA guide” reference 34002636XT..
TNS upstream and TNS downstream installation
For separate Normal AC and Bypass AC lines from a single source.
With differential circuit breaker:
The Normal and Bypass AC lines must be galvanically isolated
Upstream differential protection rating must be at least 3A
2. Installation
L1
L2
L3
Bypass AC
PE
Normal AC
MLVS
N
L1
L2
L3
Without differential circuit breaker:
L1
L2
L3
Bypass AC
PE
N
PFC
PFC
PE
SS
PE
SS
INV
INV
UPS
PE
L1
L2
L3
N
L1
L2
L3
N
Load
PE
Load
MLVS
Normal AC
L1
L2
L3
UPS
34001813EN/AE - Page 17
2. Installation
TNC upstream, TNS downstream
For separate Normal AC and Bypass AC lines from a single source
1.the UPS internal PEN bar must be connected to the Q4S neutral upstream of Q4S
2.The UPS internal PEN bar must be connected to the Q5N neutral downstream of Q5N
3.The UPS internal PE bar must be transformed into a PEN bar (cables supplied for TNC options)
L1
L2
L3
Bypass AC
PEN
PEN
Normal AC
MLVS
N
PFC
L1
L2
L3
Installation with upstream IT and downstream TNS
For separate Normal AC and Bypass AC lines from a single source
L1
R1
Bypass AC
L2
L3
N
PEN
SS
SS
PE
INV
UPS
L1
L2
L3
N
L1
L2
L3
N
PE
Load
PE
Load
INV
CPI2
UPS
MLVS
R2
Normal AC
CPI
PFC
L1
L2
L3
Installation with upstream TT and downstream TT (with upstream differential protection)
For separate Normal AC and Bypass AC lines from the same source
The upstream differential protection rating must be at least 3A
PE
UPS
L1
L2
L3
N
Load
Bypass AC
Normal AC
L1
L2
L3
N
L1
L2
L3
PFC
SS
INV
34001813EN/AE - Page 18
MLVS
Frequency converter (without Bypass AC input)
The UPS installation may be equipped with earth-leakage protection upstream on the condition that the protection
apply to:
- the normal and Bypass AC inputs
- all the parallel-connected UPSs.
Upstream and downstream: TT, TN or IT system with neutral distributed
2. Installation
Main lowvoltage
switchboard
(MLVS)
b
Normal AC
15
16
14
Load
Upstream and downstream: Neutral not distributed
Main lowvoltage
switchboard
(MLVS)
b
Normal AC
15
16
14
Load
Parallel configuration without external bypass cabinet and with common normal and Bypass AC
inputs (maximum two units in parallel)
The UPS installation may be equipped with earth-leakage protection upstream on the condition that the protection
apply to:
- the normal and Bypass AC inputs
- all the parallel-connected UPSs.
The requirements for the different system earthing arrangements (SEA) are similar to those for single UPS
configurations. In the diagrams on page 17, simply replace the single UPS units between points A and B by the
following parallel configuration.
Bypass AC
Normal AC
A
Bypass AC
Normal AC
15
16
14
B
15
16
14
34001813EN/AE - Page 19
2. Installation
Parallel configuration without external bypass cabinet and with separate normal and Bypass AC
inputs (maximum two units in parallel)
The UPS installation may be equipped with earth-leakage protection upstream on the condition that the protection
apply to:
- the normal and Bypass AC inputs
- all the parallel-connected UPSs.
The requirements for the different system earthing arrangements (SEA) are similar to those for single UPS
configurations. In the diagrams on page 18, simply replace the single UPS units between points A, B and C by the
following parallel configuration.
A
Bypass AC
15
B
Normal AC
Bypass AC
Normal AC
16
14
C
15
16
14
34001813EN/AE - Page 20
2. Installation
A
Parallel UPS with external bypass cabinet and separate Normal and Bypass AC network inputs (6
UPS in parallel for 4PN)
The UPS installation may be equipped with earth-leakage protection upstream on the condition that the protection
apply to:
- the normal and Bypass AC inputs
- all the parallel-connected UPSs.
The standard diagrams presented below may be adapted to your needs by qualified personnel.
The requirements for the different system earthing arrangements (SEA) are similar to those for single UPS
configurations. In the diagrams on page 18, simply replace the single UPS units between points A, B and C by the
following parallel configuration.
Q3BP
Q4S
B
B
B
Bypass AC
Normal AC
Bypass AC
Normal AC
Bypass AC
Normal AC
Bypass AC
15
Q5N
16
15
16
15
16
15
14
14
14
C
Normal AC
16
Connection for the Bypass AC input and the output cables to the external bypass cabinet must use cables having the same
length and size to ensure correct balancing of the Bypass AC input currents.
14
34001813EN/AE - Page 21
2. Installation
2.6 Connection of power cables in a single UPS unit
Interconnecting the cabinet earths
All the cabinet earths must be interconnected: external Bypass cabinet, external battery cabinet, etc.
UPS units with common normal and Bypass AC inputs
To access the connection terminal blocks, see section 1.2.
1 - The earthing conductors must be connected to the UPS earthing-plate
connectors (17) and (18).
2 - Connect the four conductors of the Normal AC source to terminal block
(15).
3 - Connect the three phases of the Normal AC input (16) with the three
phases of the Bypass AC input (15).
4 - Connect the four conductors supplying the load to terminal block (14).
5 - Tie the cables down to the frame.
6 - Put the cover back in place (see section 1.2).
370 mm
16
N L1 L2 L3L1 L2 L3
15
1718
14
N L1 L2 L3
UPS units with separate normal and Bypass AC inputs
To access the connection terminal blocks, see section 1.2.
1 - The earthing conductors must be connected to the UPS earthing-plate
connectors (17) and (18).
16
370 mm
N L1 L2 L3L1 L2 L3
15
1718
14
N L1 L2 L3
2 - Connect the three phases of the Normal AC source to terminal block
(16).
3 - Connect the four conductors of the Bypass AC source to terminal block
(15).
4 - Connect the four conductors supplying the load to terminal block (14).
5 - Tie the cables down to the frame.
6 - Put the cover back in place (see section 1.2).
Frequency converter
To access the connection terminal blocks, see section 1.2.
1 - The earthing conductors must be connected to the UPS earthing plate.
2 - Connect the neutral conductor of the Normal AC source to the neutral
16
17
370 mm
15
N L1 L2 L3L1 L2 L3
14
N L1 L2 L3
18
terminal on terminal block (15).
3 - Connect the three phases of the Normal AC source to terminal block
(16).
4 - Connect the four conductors supplying the load to terminal block (14).
5 - Connect the neutral on terminal block (15) with the neutral of the
supplied loads on terminal block (14).
6 - Tie the cables down to the frame.
7 - Put the cover back in place (see section 1.2).
34001813EN/AE - Page 22
Do not connect anything to the three phases on the Bypass AC
source terminal block (15).
2. Installation
2.7 Earth-cable connection for a single unit in a TNC earthing system
16
370 mm
15
N L1 L2 L3
1718
14
N L1 L2 L3
1.Connect the power network cable PEN to the UPS earthing terminal
2.Connect the usage cable PEN to the UPS earthing terminal
3.Connect the Q4S (15) neutral terminal to the UPS earth using the cable
supplied
4.Connect the Q5N (14) neutral terminal to the UPS earth using the cable
supplied
34001813EN/AE - Page 23
2. Installation
2.8 Connection of power cables for parallel UPS units
Equipotential bonding between parallel-connected units
Connect the exposed conductive parts (ECP) of the parallel-connected UPS units using an additional earthing cable (not
supplied) with the following characteristics:
- size equivalent to that of the supply cables,
- as short as possible.
Connection of earth cable and tying of cables
Connections must be made according to the diagram below:
Redundant parallel configuration (maximum two UPS units for Pn)
This configuration does not have an external bypass.
UPS units with common normal and Bypass AC inputs
To access the connection terminal blocks, see section 1.2.
UPS 2
15
17
To normal / bypass
AC source
14
N L1 L2 L3N L1 L2 L3L1 L2 L3
18
400 mm
370 mm
16
UPS 1
To loadTo loadTo loadTo load
15
17
14
N L1 L2 L3N L1 L2 L3L1 L2 L3
N L1 L2 L3N L1 L2 L3L1 L2 L3
16
370 mm
18
2. Installation
To access the connection terminal blocks,
see section 1.2.
1 - The earthing conductors must be
connected to the earthing plate of each UPS.
2 - Connect the four conductors of the Bypass
AC source to terminal block (15) in each UPS
unit.
3 - Connect the three phases of the Normal
AC input (16) with the three phases of the
Bypass AC input (15) in each UPS unit.
4 - Connect the four conductors of the
supplied loads to terminal block (14) in UPS1.
5 - Connect terminal block (14) in UPS2 to
terminal block (14) in UPS1 using the four
load conductors.
6 - Tie the cables down to the cabinet frames.
7 - Put the covers back in place (see section
1.2).
UPS units with separate normal and Bypass AC inputs
To access the connection terminal blocks,
see section 1.2.
1 - The earthing conductors must be
connected to the earthing plate of each UPS.
2 - Connect the three phases of the Normal
AC source to terminal block (16) in each UPS
unit.
3 - Connect the four conductors of the Bypass
AC source to terminal block (15) in each UPS
unit.
4 - Connect the four conductors of the
supplied loads to terminal block (14) in UPS1.
5 - Connect terminal block (14) in UPS2 to
terminal block (14) in UPS1 using the four
load conductors.
6 - Tie the cables down to the cabinet frames.
7 - Put the covers back in place (see section
1.2).
16
370 mm
To load
UPS 1
15
17
14
N L1 L2 L3N L1 L2 L3L1 L2 L3
N L1 L2 L3N L1 L2 L3L1 L2 L3
18
To normal
AC source
16
UPS 2
370 mm
15
17
To by p a ss
AC source
14
N L1 L2 L3N L1 L2 L3L1 L2 L3
18
Caution. If the two UPSs are placed side by side, connect as indicated above. In the other configurations, always make sure
that the cables between the UPSs and Bypass AC source have the same cross-section and the same length. The same is
true for the cables between the UPSs and the load.
34001813EN/AE - Page 25
2. Installation
Frequency converter
UPS 1
16
17
To normal
AC source
15
14
18
To load
370 mm
16
L1 L2 L3
17
UPS 2
To access the connection terminal blocks,
see section 1.2.
1 - The earthing conductors of each UPS
must be connected to the UPS earthing plate.
14
15
N L1 L2 L3
N
18
2 - Connect the neutral conductor of the
Normal AC source to the neutral terminal on
terminal block (15) of UPS1.
3 - Connect the three phases of the Normal
AC source to terminal block (16).
4 - Connect terminal block (16) in UPS1 to
terminal block (16) in UPS2 using the three
conductors of the Normal AC source.
5 - Connect the neutral cable on terminal
block (15) in UPS1 to terminal block (15) in
UPS2.
6 - Connect the four conductors supplying the
load to terminal block (14).
7 - Connect terminal block (14) in UPS1 to
terminal block (14) in UPS2 using the four
load conductors.
8 - Connect the neutral on terminal block (15)
with the neutral of the supplied loads on
terminal block (14).
9 - Tie the cables down to the frame.
10 - Put the cover back in place (see section
1.2).
Do not connect anything to the three
phases on the Bypass AC source terminal
block (15).
34001813EN/AE - Page 26
UPS units with separate normal and Bypass AC inputs
/
/
/
2. Installation
UPS 1
UPS 2
To access the connection terminal blocks,
see section 1.2.
1 - The earthing conductors must be
16
15
14
N L1 L2 L3N L1 L2 L3L1 L2 L3
16
15
14
N L1 L2 L3N L1 L2 L3L1 L2 L3
connected to the earthing plate of each UPS.
2 - Connect the three phases of the Normal
AC source to terminal block (16) in each UPS
370 mm
17
18
370 mm
17
18
unit.
3 - Connect the four conductors of the Bypass
AC source to terminal (61) in the bypass
cabinet.
4 - Connect terminal blocks (15) in each UPS
63
Bypass
Q4S
Q3BP
Q5N
N
L1
L2
L3
N
L1
L2
L3
60
N
L1
L2
L3
61
N
L1
L2
L3
62
To
Normal
AC
source
The cables marked A must be identical,
AB AB
To
Normal
AC
source
unit to terminal (60) in the bypass cabinet,
using cables with identical lengths and sizes.
5 - Connect the four load conductors to
terminal (62) in the bypass cabinet.
6 - Connect terminal blocks (14) in each UPS
unit to terminal (63) in the bypass cabinet,
using cables with identical lengths and sizes.
7 - Tie the cables down to the frames of the
UPS cabinets and the bypass cabinet.
8 - Put the covers back in place (see section
1.2).
i.e. same size and length.
Similarly, the cables marked B must be
identical, i.e. same size and length.
To load
To bypass AC source
16
370 mm
To normal AC
To normal AC
To normal AC
To Normal AC
bypass AC
bypass AC
bypass AC
source
UPS 3
15
17
14
N L1 L2 L3N L1 L2 L3L1 L2 L3
18
B
To Normal AC
16
UPS 4
370 mm
15
17
14
N L1 L2 L3N L1 L2 L3L1 L2 L3
18
B
source
A
A
To avoid errors, it is advised to remove the handle on switch Q3BP (10) in each UPS.
34001813EN/AE - Page 27
2. Installation
2.9 Connection of the 150 kVA external bypass cabinet
A
C
15,5
120
303
UPS 1
XMS04 /
XMS05
UPS 2
XMS04 /
XMS05
Q4S
Q3BP
123456
UPS 3
UPS 4
Q5N
317
317
15
B
N
L1
L2
L3
Q4S
D
N
L1
L2
L3
G
N
L1
L2
L3
E
Q3BP
H
N
L1
L2
L3
Q5N
F
N
L1
L2
L3
750
800
857,5
950
1000
1057,5
Key
A: top view of cabinet
B: front view of cabinet
C: 317 x 120 mm opening for cable running
D: connection of Bypass AC source to the UPSs
E: connection of auxiliary wires for position of Q4S, Q3BP and Q5N switches
F: connection of UPS load outputs
G: connection of Bypass AC source
H: connection of the load
34001813EN/AE - Page 28
2.10 Connection of the 360 kVA external bypass cabinet
A
BAA
2. Installation
C
D
E
1900
F
N
L1
L2
L3
Q4S
N
L1
L2
Q3BP
N
L1
L2
Q5N
N
L1
L2
L3
K
E
G
L3
H
L3
D
G
H
F
A
Q4S
Q5N
E
J
UPS 1
XMS04 /
XMS05
Q3BP
123456
I
L
UPS 2
XMS04 /
XMS05
UPS 3
UPS 4
Key
AA: section AA of cabinet
B: front view of cabinet
C: front
D: connection of Bypass AC source to the UPSs
E: connection of auxiliary wires for position of Q4S, Q3BP and Q5N switches
F: connection of UPS load outputs
G: connection of Bypass AC source
H: connection of the load
I : ventilation grate for air exit from cabinet
J: cable running through top, 460 x 197 mm opening and gland plate
K: protection fuses for RC voltage surge suppressor on the Bypass AC line (must be replaced when LED is ON)
L: top view of cabinet
34001813EN/AE - Page 29
2. Installation
2.11 Connection of the 600 kVA external bypass cabinet
A
B
AA
C
D
Q4S
D
E
Q3BP
Q5N
G
E
H
F
G
H
F
A
Q4S
Q5N
E
J
I
UPS 1
L
UPS 2
XMS04 /
XMS05
XMS04 /
XMS05
Q3BP
123456
34001813EN/AE - Page 30
UPS 3
UPS 4
Key
AA: section AA of cabinet
B: front view of cabinet
C: front
D: connection of Bypass AC source to the UPSs
E: connection of auxiliary wires for position of Q4S, Q3BP and Q5N switches
F: connection of UPS load outputs
G: connection of Bypass AC source
H: connection of the load
I : ventilation grate for air exit from cabinet
J: cable running through top, 460 x 197 mm opening and gland plate
L: top view of cabinet
2. Installation
2.12 Auxiliary interconnections between UPS units in parallel configurations
Redundant parallel configuration (maximum two UPS units)
Note. The supplied cables (10 m) limit the
For security reasons, the connections of the auxiliary interconnections of the parallel UPSs must be carried out
whilst all the UPSs are de-energised.
1010121210101212
XMS02 XMS03
UPS 1
XMS04 XMS05
CAN //
XMS06 XMS07
Blue
plug
XMS02 XMS03
UPS 2
XMS04 XMS05
CAN //
XMS06 XMS07
Red plug
Exchange-current interconnections
Link connectors XMS02 and XMS03 on the
two UPS units.
CAN // interconnections:
Fit a blue plug on connector XMS06 on
UPS1.
Link connector XMS07 on UPS1 to connector
XMS06 on UPS2.
Fit a red plug on connector XMS07 on U PS2.
distance between the two UPS units to
approximately six meters.
34001813EN/AE - Page 31
2. Installation
Parallel configuration for increased capacity (maximum four UPS units)
UPS 1
XMS02 XMS03
XMS04 XMS05
XMS06 XMS07
Blue
plug
11
External bypass cabinet
2 3 4 5 61
Q3BP
Q4S
Q5N
CAN //
XMS02 XMS03
Jumpers connected to
aux. terminal block of
external bypass cabinet
(if necessary)
XMS04 XMS05
UPS 2
CAN //
XMS06 XMS07
11
Interconnections with the external bypass
cabinet
◗ Interconnect terminals 1, 3 and 5 on the
auxiliary terminal block in the cabinet.
◗ Create a loop between the cabinet and the
UPS units for terminals 1, 2, 4 and 6 on the
auxiliary terminal block in the cabinet. The
order for the XMS04 and XMS05 connectors
in each UPS unit, from right to left, is
common, Q3BP, Q4S and Q5N.
Details of terminal blocks (11)
XMS 04 / XMS 05
11
UPS 4
XMS02 XMS03
XMS04 XMS05
CAN //
XMS06 XMS07
Red
plug
UPS 3
XMS02 XMS03
XMS04 XMS05
1010121210101212
11
CAN //
XMS06 XMS07
Q4S
Q5N
Q3BP
Common
Note. The interconnection cables for the
external bypass cabinet are not supplied
(size 2.5 mm
2
maximum).
Exchange-current interconnections (10):
Use the XMS02 and XMS03 connectors to
create a loop between the UPS units (all the
XMS02 XMS03
UPS 1
XMS04 XMS05
CAN //
XMS06 XMS07
Blue
plug
XMS02 XMS03
UPS 2
XMS04 XMS05
CAN //
XMS06 XMS07
XMS02 and XMS03 connectors must be
used).
CAN // interconnections (12):
Daisy-chain the UPS units using the XMS06
and XMS07 connectors. Fit a blue plug on the
first UPS unit and a red plug on the last unit
(all the XMS06 and XMS07 connectors must
be used).
Note. The supplied cables are ten meters
long.
XMS02 XMS03
XMS04 XMS05
UPS 4
CAN //
XMS06 XMS07
Red plug
XMS02 XMS03
UPS 3
XMS04 XMS05
CAN //
XMS06 XMS07
To ensure sufficient isolation of
exchange-current, CAN and external
bypass cabinet cables, they must be run
separately from the power cables
34001813EN/AE - Page 32
Fitting the protection cover for the auxiliary interconnection cables
The protection cover supplied with the parallel connected UPS units protects the user against direct contact with voltages
other than SELVs and ensures the auxiliary interconnection cables are maintained in position.
2. Installation
Note. Tie down the cables as indicated in the diagram in section 2.10.
2.13 Connection of general shutdown or emergency power off (EPO) terminal
block
XMB 08 XMB 07 XMS 06
7
Caution.
In the UPS, pressing the general shutdown button causes UPS shutdown and opening of the battery circuit breaker
(with opening of the bypass static switch depending on personalisation settings) .
The Emergency Power Off (EPO) notion is applicable to installations where pressing the button also causes the
upstream Normal AC source and Bypass AC source circuit-breakers to open.
In parallel configurations, there must be a single general shutdown button with a separate contact for each UPS unit.
1 - Remove the wire from terminal block (7).
2 - Connect the general shutdown NC contact to terminals 1 and 2 (SELV).
3 - Tie the cable down as illustrated in section 2.10.
34001813EN/AE - Page 33
2. Installation
2.14 Connection of the relay communications card
Isolate and lock-out all power sources for this card before making connections.
Never connect SELV (safety extra low voltage) and non-SELV circuits to the different outputs of the same card.
1 - Remove the cover (52) secured by the screws (50).
2 - Run the communications cables through the cable entry holes (53).
3 - Connect the conductors to the input (55) and output (54)terminal blocks.
6
5
4
3
2
1
B
A
55
52
4 - Put the cover back in place and secure it with the screws (50).
5 - Tighten the screws (56) to block the cables.
6 - Indicate the locations of the power sources on the labels.
7 - Insert the card in its slot.
8 - Secure the card with two screws (51).
54
53
51
34001813EN/AE - Page 34
5156
50
51
Characteristics of the contacts on the relay communications card.
Characteristics of the output contacts:
Permissible voltage: 250V AC, 30V DC.
Low battery warning
Load on battery power
Load on automatic bypass
Load on UPS
Battery fault
6
5
4
3
Permissible current: 2 A.
Cable : 4 x 0.93 mm
Characteristics of the input contacts:
Switched voltage: 5 V DC
Consumption: 10 mA.
Cable: 4 x 0.34 mm
2. Installation
2
, Ø 6.6 ± 0.3 mm.
2
, Ø 5 ± 0.5 mm.
General alarm
2
1
UPS OFF
UPS ON
BA
Communications card connection example
If a SELV (safety extra low voltage) source is used, it must always be possible to isolate the communications card from the
upstream source to ensure the safety of personnel working on the installation.
communication
AC
source
Disconnecting device that can be locked
Adding communication cards
carte decommunication
card
4
2
3
1
34001813EN/AE - Page 35
2. Installation
2.15 Running the control/communications cables
Single UPS
The following assembly recommendations must be followed to ensure correct positioning and support of the various strands
of the control and communication cables on the front face of the UPS.
Separate the control and communication
cables from the power cables.
Run the cables together in front of the
protection panels and tie them to the panels
as indicated in the figure opposite.
Slot for relay communications card
Free slot for optional communication cards
3
Cable descriptionInsulation levelLocation on illustration
4
Tie
Screw-type terminal block for connection of
EPO and battery circuit-breakers.
6
7
Ties
To ensure sufficient isolation of exchange-current, CAN and external bypass cabinet cables, they must be run
34001813EN/AE - Page 36
Relay communication cardSELV or LV3
Optional communication cardSELV4
General-shutdown cableSELV6
External battery circuit-breaker cablesSELV7
separately from the power cables. Reinforce the insulation of these control and communication cables if any risk of
contact with the power cables subsists.
Parallel UPS
2. Installation
1
Parallel-connection cables for connection to
the external bypass cabinet (not supplied
max. 2.5 mm
cables are supplied.
3
4
Relay communication card
Optional communications cards
Ties
2
). The CAN and I exchange
6
7
General-shutdown cable (not supplied, max.
2
2.5 mm
) and external battery circuit breaker
cable must be tied down separately
Ties
Cable descriptionInsulation levelLocation on illustration
External bypass cabinet cableELV1
CAN cablesSELV1
Exchange-current cablesSELV1
Relay communication cardSELV or LV3
Optional communication cardSELV4
General-shutdown cableSELV6
External battery circuit-breaker cablesSELV7
To ensure sufficient isolation of exchange-current, CAN and external bypass cabinet cables, they must be run
separately from the power cables. Reinforce the insulation of these control and communication cables if any risk of
contact with the power cables subsists.
34001813EN/AE - Page 37
2. Installation
2.16 Power connections for an external battery cabinet
The earth on an external battery cabinet must be connected to the UPS
1
Q1 Q4S Q3BP Q5N
-
+
2.17 Assembly and connection of an empty battery cabinet
Mounting the battery circuit breaker kit
Secure:
1 - The base plate (60) supporting the circuit
breaker.
2 - Connector XR1.
x2
60
x4
Please contact our Sales department when
4
3 - The temperature sensor (3).
4 - The front plate (4), after connecting the
batteries to the circuit breaker.
Only one circuit breaker is necessary even if
there are several battery cabinets.
The coil control wires and the position
contact wires of circuit-breaker QF1 must
be connected to the UPS (see page 24).
selecting the battery circuit breaker.
34001813EN/AE - Page 38
XR1
3
Mounting the shelves and the battery cells
Caution. Assembly of the battery cabinet
2. Installation
must be carried out by certified personnel
1
(standard EN 50091-1-2).
1
1
2
3
3
Caution. The minimum clearance between
the top of battery cells and the next shelf
is 150 millimeters.
1 - Secure the angle supports (6 screws per
support).
For each shelf:
2 - position the shelf,
3 - secure the shelf with two screws in each
angle,
4 - install the battery cells, secure and
interconnect them.
5 - Interconnect all the shelves and then
connect the overall battery assembly to the
battery circuit breaker.
34001813EN/AE - Page 39
2. Installation
2.18 Control connections for an external battery cabinet
1 - Connect wires 1-2-3-4 on connector XR1 (QF1 position and coil) in the external battery cabinet to connector XMB07 (6)
(SELV) and wires 7-8-9-10 (temperature sensor) to connector XMD3 (22) (SELV).
22
XMD3
XMD3
+
12V
+
BC
BC
12V
Pass through
three times
5
XMB 08 XMB 07 XMB 06
Circuit breaker 2
Circuit breaker 1
6
Common
Open-close contact
QF1 command
-12V
+12V
BC+
BC-
QF1
XR1
8
7
6
5
4
3
2
1
34001813EN/AE - Page 40
Note. The wires for the screw-type terminal block are not supplied (max. size 2.5 mm
2
and total length less than 100 m).
2.19 Connection of an input isolating transformer
16
L1 L2 L3
17
N L1 L2 L
14
16
15
N L1 L2 L3L1 L2 L3
17
15
N L1 L2 L3
17
N L1 L2 L3
14
17
A
B
Q1 Q4S Q3BP Q5N
QF1
Cable not suppliedCable not supplied
2. Installation
Option
AC input
C
A - Connection of an input transformer for common normal and Bypass AC source.
B - Connection of a Bypass AC input transformer for separate normal and Bypass AC sources.
C - Connection of a Normal AC input transformer for separate normal and Bypass AC sources.
2.20 Connection of an output isolating transformer
Option
Q1 Q4S Q3BP Q5N
QF1
Cable not supplied
To load
Cable not supplied
34001813EN/AE - Page 41
3. Operation
All operations concerning system start-up and compliance with standards and regulations, including those related to the
battery cabinet, must be carried out by trained and certified personnel before using the UPS.
3.1 Shutting down a single UPS
The UPS remains energised unless it is shut down.
1 - Press a button to exit sleep mode.
2 - Confirm by pressing the function key (38) for 3 seconds.
Q1Q4SQ3BPQ5N
8
QF1
13
3.2 Restarting a single UPS
Check that switches Q4S (9) and Q5N (11) are closed. If this is the case, continue with this procedure, otherwise refer
to paragraph 4.4 "Return to the Normal position, Single UPS".
Q1Q4SQ3BPQ5N
9
8
QF1
13
IO
3s
11
38
The load is no longer protected by the UPS. It is supplied via the
bypass.
3 - Set the battery circuit-breaker QF1 (13) (or set the battery circuitbreakers of the auxiliary cabinets if any) to OFF.
4 - Set the input circuit-breaker Q1 (8) to OFF.
The charger no longer operates to keep the batteries fully charged.
5 - Open the upstream circuit-breakers of the Normal AC source and
Bypass AC source to completely power off the UPS.
1 - Set the Normal AC source input switch Q1 (8) to the ON position.
2 - Wait until the end of the start sequence.
3 - Set the battery circuit breaker QF1 (13) (or the battery circuit breakers
in the auxiliary cabinets) to the ON position.
The UPS unit starts automatically.
LED (31) is ON.
The load is protected by the UPS.
34001813EN/AE - Page 42
31 32 33
~
37
?
IO
3s
If LED (31) remains OFF, press the ON button (37)
If LED (31) still remains OFF and either of LEDs (32) or (33) is ON, a fault
has occurred (see section 4.1).
3.3 Shutting down a parallel configuration
1 - Press a button on each unit to exit sleep mode.
2 - Press the OFF button (38) on each unit for 3 seconds.
3. Operation
IO
Q1Q4SQ3BPQ5N
8
QF1
13
38
3s
3.4 Restarting a parallel configuration
Check that switches Q4S (9) and Q5N (11) are closed. If this is the case, continue with this procedure, otherwise refer
to paragraph 4.4 "Return to the Normal position, Parallel UPS...".
Q1Q4SQ3BPQ5N
9
8
QF1
13
11
The load is no longer protected by the UPSs. It is supplied via the
bypass.
3 - Set the battery circuit breaker QF1 (13) in each UPS unit to the OFF
position (or trip the battery circuit breakers in the auxiliary cabinets if
applicable).
4 - Set the input switch Q1 (8) in each UPS unit to the OFF position.
The charger no longer operates to keep the batteries fully charged.
5 - Open the upstream circuit-breakers of Normal AC source and Bypass
AC source to completely power off the installation.
1 - Check that the Bypass AC source input switch Q4S in the external
bypass cabinet is closed.
2 - Check that the output switch Q5N in the external bypass cabinet is
closed.
3 - Check that the bypass switch Q3BP in the external bypass cabinet is
open.
Then carry out steps 4 to 6 below on all the UPS units.
4 - Set the Normal AC source input switch Q1 (8) to the ON position.
5 - Wait until the end of the start sequence.
6 - Set the battery circuit breaker QF1 (13) (or the battery circuit breakers
in the auxiliary cabinets) to the ON position.
31 32 33
~
37
IO
3s
The UPS units start automatically. On each unit, LEDs (32) and (33) go
OFF and LED (31) goes ON.
?
35
The load is protected by the UPSs.
If LED (31) remains OFF, press the ON button (37) on each UPS unit (the
UPS is in manual start mode) and confirm if necessary by pressing the
function key (35) marked
If LED (31) still remains OFF and either of LEDs (32) or (33) is ON, a fault
has occurred (see section 4.1).
This is the standard operating mode, set by default in the factory. Two possible cases:
313233
313233
3. Operation
1 - Normal AC source available:
LED (31) is ON.
The load is protected by the UPS.
2 - Normal AC source not available:
LED (32) is ON.
The buzzer sounds intermittently.
The load is supplied by the UPS from battery power.
The display indicates any anomalies related to the AC source or the UPS as well as remedial action if applicable.
Press the function key (35) indicated by the display to turn the buzzer OFF.
ECO mode (single UPS only)
The main advantage of this mode is that it reduces the consumption of electrical power.
ECO mode may be selected exclusively via the control panel on the UPS.
313233
Three possible cases:
1 - Bypass AC source available:
LED (31) is ON.
The load is supplied in ECO mode.
2 - Bypass AC source not available:
LED (31) is ON.
The buzzer sounds intermittently.
The load is automatically supplied in normal mode via the Normal AC
input.
3 - Both normal and Bypass AC sources not available or out of
tolerance:
LED (32) is ON.
The buzzer sounds intermittently.
The load is supplied by the UPS from battery power.
313233
The display indicates the UPS operating status conditions and the required action.
34001813EN/AE - Page 45
3. Operation
3.7 Load on battery power
The load continues to be protected by the UPS when the Normal AC source is not available. Power is supplied by the battery.
Transfer to battery power
313233
End of battery power
313233
LED (32) is ON.
The buzzer sounds intermittently.
The load is supplied by the battery.
LED (33) is ON.
The buzzer sounds intermittently.
The load is transferred on the Bypass AC input if it is present.
3.8 UPS personalisation
Access to the personalisation functions
Personalisation must be carried out with switches Q1 (8) and Q5N (11) open (OFF) and switches Q4S (9) and Q3BP
(10) closed (ON).
~
?
IO
3s
The password is factory set.
To change the password, see the Settings menu.
ØØØ
35
36
1 - Press the menu key (36) .
2 - Select "Settings", then "Personalisation" using the function keys (35)
Ï or Ð.
3 - Confirm by pressing the function key (35)
4 - Enter the password by successively selecting each icon using the
corresponding function key.
5 - Confirm by pressing the function key (35)
6 - To save the personalisation settings, confirm by pressing the function
key (35)
4 minutes of battery backup time1 to X minutes of battery backup time
34001813EN/AE - Page 47
3. Operation
3.9 Relay contacts (communications card)
InputsFactory settingOptions (available on all contacts)
1.A
UPS ON
- Room temperature fault
- Transfer to bypass disabled
- Transfer to bypass disabled if Bypass AC source out of tolerance
- Desynchronise UPS from Bypass AC source
1.B
UPS OFF
OutputsFactory settingOptions (available on all contacts)
1.1
1.2
General alarm
Battery fault
(1)
- Overload
- PFC fault
- Inverter fault
- Charger fault
- Automatic-bypass fault
- Bypass AC source out of tolerance
1.3
Load on NORMAL source
- Battery-temperature fault
- Fan fault
- Emergency power off activated
1.4
Load on automatic bypass
- Battery circuit breaker(s) open (at least one)
- Phase-sequence fault on normal or Bypass AC
source
1.5
Load on battery power
- Blown fuse(s)
- Transfer to Bypass AC source disabled
- Operation in ECO mode
1.6
Low battery warning
- UPS on manual bypass
The indications 1.X become 2.X for a second identical card in the UPS.
Contacts are of the NO (normally open) type.
(1) The general alarm can be tested by opening the battery circuit breaker.
34001813EN/AE - Page 48
3.10 Display functions
3. Operation
Welcome screen
Load protected
01/Jan./2000 10:10
kVA min
8.8 8.8 8.9 32
Ph1 Ph2 Ph3 Battery
+++
VOLT
Battery measurements
Voltage measurements
Current measurements
Power measurements
Frecuency measurements
Ratios measurements
Parallel measurements
(option)
VOLT
01010
10101
01010
Measurements
Status
Main menu
Select
Measurements
Alarms
Status
Settings
Controls
Maintenance
Alarms
Settings
Press this key to return
to the main menu
Help key for information
?
on the pictogram functions
(must be held down)
Time stamped events
Statistics
Reset alarms
Inverter on
Inverter off
Force load transfer to inverter
Force load transfer to bypass
Controls
Desynchronize inverter from bypass
Resynchronize inverter and bypass
Tests leds
Buzzer OFF
Enable LCM indications
Disable LCM indications
Start-up
Language
Date / time
Start-up
UPS shutdown
Display contrast
Buzzer volume
Personalisation
Output voltage
Transfer to manual
bypass
Password
Dry-contact settings
34001813EN/AE - Page 49
4. Maintenance
4.1 Identification of alarms
Alarm conditions are identified by LEDs (31), (32), (33) and the buzzer.
LED (31)LED (32)LED (33)BuzzerSignification
-
--IntermittentUPS shut down following end of
--IntermittentUPS shut down on fault requiring
Detailed information on all alarms is supplied on the display.
1 - On the screen, select the alarm for which information is required.
2 - Hold down the corresponding function key to display the possible causes of the fault and the required action.
4.2 Life Cycle Monitoring (LCM)
~
-IntermittentNormal AC source not available
battery power
servicing by after-sales support
◗ The "Life Cycle Monitoring" function provides UPS maintenance advice
32
?
35
to guarantee installation availability for the user.
◗ The display gives 3 messages enabling the following to be identified:
- The end of the contractual legal warranty: "End of warranty check
recommended".
- Regular maintenance requirements and the end of service life for
consumable components: "Technical check recommended".
- The end of the battery service life: "Battery check required".
In addition to these messages, the minor fault LED (32) lights up and the
IO
3s
buzzer sounds.
These messages can be deleted by pressing the function key (35). This
also causes LED (32), to go out, the buzzer to stop and the removal of the
"Global Alarm" remote signalling.
To completely disable LCM indications, use the display to enter the
password required to disable the function.
34001813EN/AE - Page 50
4.3 UPS isolation
Single UPS
To isolate the UPS from the electrical power source and supply the load directly by the normal or Bypass AC source, follow
the instructions below.
The load is no longer protected by the UPS, but continues to be
IO
Q1Q4SQ3BPQ5N
9
8
QF1
10
13
3s
11
4. Maintenance
1 - Press a button to exit sleep mode.
2 - Shut down the UPS by pressing the OFF button (38) for 3 seconds.
The load is no longer protected by the UPS.
38
3 - Set bypass switch Q3BP (10) to ON.
4 - Set output switch Q5N (11) to OFF.
5 - Set the battery circuit-breaker QF1 (13) (or set the battery circuitbreakers of the auxiliary cabinets if any) to OFF.
6 - Set the input circuit-breaker Q1 (8) to OFF.
7 - Set the input circuit-breaker Q4S (9) to OFF.
8 - Wait until the display and LEDs go off.
supplied with AC power.
UPS maintenance or servicing can now be carried out.
Frequency converter
1 - Press a button to exit sleep mode.
2 - Shut down the UPS by pressing the OFF button (38) for 3 seconds.
The load is no longer protected by the unit.
3 - Set the battery circuit-breaker QF1 (13) (or set the battery circuit-breakers of the auxiliary cabinets if any) to OFF.
4 - Set the input circuit-breaker Q1 (8) to OFF.
5 - To ensure operator safety, open all Q4S (9) and Q5N (11) switches.
UPS maintenance or servicing can now be carried out.
UPS operating in ECO mode
If supplied by the network via the Bypass AC channel:
Q1Q4SQ3BPQ5N
8
The load is no longer protected by the UPS, but continues to be
QF1
1 - Check that the load is operating via the Bypass AC input.
2 - Set bypass switch Q3BP (10) to ON.
3 - Set output switch Q5N (11) to OFF.
4 - Set the battery circuit-breaker QF1 (13) (or set the battery circuit-
9
10
13
11
breakers of the auxiliary cabinets if any) to OFF.
5 - Set the input circuit-breaker Q1 (8) to OFF.
6 - Set the input circuit-breaker Q4S (9) to OFF.
supplied with AC power.
UPS maintenance or servicing can now be carried out.
34001813EN/AE - Page 51
4. Maintenance
If the load is supplied by the UPS with Bypass AC source present:
1 - Press a button to exit sleep mode.
Q1Q4SQ3BPQ5N
9
8
The load is no longer protected by the UPS, but continues to be
QF1
10
13
11
Parallel UPS configuration without external bypass cabinet
Shutdown and isolation of the first UPS unit:
2 - Shut down the UPS by pressing the OFF button (38) for 3 seconds.
3 - Set bypass switch Q3BP (10) to ON.
4 - Set output switch Q5N (11) to OFF.
5 - Set the battery circuit-breaker QF1 (13) (or set the battery circuitbreakers of the auxiliary cabinets if any) to OFF.
6 - Set the input circuit-breaker Q1 (8) to OFF.
7 - Set the input circuit-breaker Q4S (9) to OFF.
8 - Wait until the display and LEDs go off.
supplied with AC power.
UPS maintenance or servicing can now be carried out.
1 - Check that the two UPS units are operating.
2 - Press a button to exit sleep mode.
3 - Shut down the UPS by pressing the OFF button (38) for 3 seconds.
IO
38
3s
4 - Set output switch Q5N (11) to OFF.
5 - Set the battery circuit-breaker QF1 (13) (or set the battery circuit-
Q1Q4SQ3BPQ5N
9
8
QF1
10
13
11
breakers of the auxiliary cabinets if any) to OFF.
6 - Set the input circuit-breaker Q1 (8) to OFF.
7 - Set the input circuit-breaker Q4S (9) to OFF.
8 - Wait until the display and LEDs go off.
The load is still protected by the other UPS unit.
Maintenance or servicing can now be carried out on the UPS unit that
has been shut down.
Shutdown and isolation of the second UPS unit:
1 - Press a button to exit sleep mode.
2 - Shut down the UPS by pressing the OFF button (38) for 3 seconds.
3 - Set bypass switch Q3BP (10) to ON.
4 - Set output switch Q5N (11) to OFF.
5 - Set the battery circuit-breaker QF1 (13) (or set the battery circuit-breakers of the auxiliary cabinets if any) to OFF.
6 - Set the input circuit-breaker Q1 (8) to OFF.
7 - Set the input circuit-breaker Q4S (9) to OFF.
8 - Wait until the display and LEDs go off.
34001813EN/AE - Page 52
The load is no longer protected by the UPS, but continues to be supplied with AC power.
UPS maintenance or servicing can now be carried out.
Parallel UPS configuration with external bypass cabinet
Shutdown and isolation of one UPS unit
1 - First check that the total capacity of the remaining UPS units is
sufficient to supply the connected load.
2 - Press a button to exit sleep mode.
3 - Shut down the UPS by pressing the OFF button (38) for 3 seconds.
IO
38
3s
4 - Set output switch Q5N (11) to OFF.
Q1Q4SQ3BPQ5N
9
8
QF1
10
11
13
5 - Set the battery circuit-breaker QF1 (13) (or set the battery circuitbreakers of the auxiliary cabinets if any) to OFF.
6 - Set the input circuit-breaker Q1 (8) to OFF.
7 - Set the input circuit-breaker Q4S (9) to OFF.
8 - Wait until the display and LEDs go off.
The load is still protected by the other UPS units.
Maintenance or servicing can now be carried out on the UPS unit that
has been shut down.
4. Maintenance
Shutdown and isolation of all the UPS units:
N
L1
L2
60
63
Q4S
N
L1
L2
L3
61
Q3BP
N
L1
L2
L3
62
Q5N
N
L1
L2
L3
64
65
66
The load is no longer protected by the UPS, but continues to be
1 - On each UPS unit, press a button to exit sleep mode.
L3
2 - Shut down each UPS unit by pressing their OFF buttons (38) for 3
seconds.
3 - Set switch Q3BP (65) in the external bypass cabinet to ON.
4 - Set switch Q5N (66) in the external bypass cabinet to OFF.
5 - Set switch Q4S (64) in the external bypass cabinet to OFF.
6 - Set output switch Q5N (11) of each UPS unit to OFF.
7 - Set the battery circuit-breaker QF1 (13) of each UPS unit (or set the
battery circuit-breakers of the auxiliary cabinets if any) to OFF.
8 - Set the input circuit-breaker Q1 (8) of each UPS unit to OFF.
9 - Set switch Q4S (9) of each UPS unit to OFF.
10 - Wait until the control electronics of all UPS units have fully shut down.
supplied with AC power.
Maintenance or servicing can now be carried out.
34001813EN/AE - Page 53
4. Maintenance
4.4 Return to the normal position
Single UPS
Q1Q4SQ3BPQ5N
9
8
QF1
10
13
11
1 - Check that bypass switch Q3BP (10) is ON and that all other switches
are OFF.
2 - Set input switch Q4S (9) to ON.
3 - Set output switch Q5N (11) to ON.
4 - Wait until the display goes on and check that there are no faults on the
static-switch on the bypass line.
5 - Set bypass switch Q3BP (10) to OFF.
6 - Set the input circuit-breaker Q1 (8) to ON.
7 - Set the battery circuit-breaker QF1 (13) (or set the battery circuitbreakers of the auxiliary cabinets if any) to ON.
Frequency converter
8
~
?
313233
IO
3s
Q1Q4SQ3BPQ5N
9
QF1
10
13
11
The UPS unit starts automatically.
LED (31) is ON.
If LED (31) remains OFF, press the ON button (37)
(the system is in manual start mode).
If LED (31) still remains OFF and either of LEDs (32) or (33) is ON, a fault
has occurred (see section 4.1).
37
1 - Check that all switches are set to OFF.
2 - Set the input circuit-breaker Q4S (9) to ON (check that no cable is
connected on phase 1, phase 2 and phase 3).
3 - Set the input circuit-breaker Q1 (8) to ON.
4 - Set output switch Q5N (11) to ON.
5 - Set the battery circuit-breaker QF1 (13) (or set the battery circuitbreakers of the auxiliary cabinets if any) to ON.
34001813EN/AE - Page 54
~
313233
IO
6 - Press the ON button (37).
If LED (31) still remains OFF and either of LEDs (32) or (33) is ON, a fault
has occurred (see section 4.1).
?
37
3s
Parallel UPS configuration without external bypass cabinet
Restart the UPS unit for which switch Q3BP (10) is ON and the other switches are OFF.
4. Maintenance
Caution. It is imperative to restart this UPS unit. Otherwise, load power is cut if the other two UPSs are shut down.
1 - Set the input circuit-breaker Q4S (9) to ON.
2 - Set output switch Q5N (11) to ON.
Q1Q4SQ3BPQ5N
9
8
QF1
313233
10
13
11
3 - Check that the UPS is listed by the display, then confirm by pressing
the function keys (35).
4 - Set bypass switch Q3BP (10) to OFF.
5 - Set the input circuit-breaker Q1 (8) to ON.
6 - Set the battery circuit-breaker QF1 (13) (or set the battery circuitbreakers of the auxiliary cabinets if any) to ON.
The UPS unit starts automatically. LED (31) is ON.
The load is protected by the UPS.
If LED (31) remains OFF, press the ON button (37)
If LED (31) still remains OFF and either of LEDs (32) or (33) is ON, a fault
has occurred (see section 4.1).
IO
37
3s
Restart the UPS unit for which all switches are set to OFF.
1 - Set the input circuit-breaker Q4S (9) to ON.
Q1Q4SQ3BPQ5N
9
8
QF1
10
13
11
2 - Set output switch Q5N (11) to ON.
3 - Check that all the UPS units present in the installation are included in
the list on the display and confirm by pressing the function buttons (35).
4 - Set the input circuit-breaker Q1 (8) to ON.
5 - Set the battery circuit-breaker QF1 (13) (or set the battery circuitbreakers of the auxiliary cabinets if any) to ON.
The UPS restarts and LED (31) is ON.
If LED (31) remains OFF, press the ON button (37)
(the system is in manual start mode).
313233
43
IO
3s
If LED (31) still remains OFF and either of LEDs (32) or (33) is ON, a fault
has occurred (see section 4.1).
37
34001813EN/AE - Page 55
4. Maintenance
Parallel UPS configuration with external bypass cabinet
1 - Check that all switches on the UPS units are set to OFF.
Q1Q4SQ3BPQ5N
9
8
QF1
10
13
11
2 - Set switch Q4S in the external bypass cabinet to ON.
3 - Set switch Q4S (9) on each UPS unit to ON.
4 - Set output switch Q5N (11) on each UPS unit to ON.
5 - Check that all the UPS units present in the installation are included in
the list on the display and confirm by pressing the function button (35) on
each UPS unit.
6 - Set switch Q5N in the external bypass cabinet to ON.
7 - Set switch Q3BP in the external bypass cabinet to OFF.
8 - Set the input circuit-breaker Q1 (8) on each UPS unit to ON.
9 - Set the battery circuit-breaker QF1 (13) on each UPS unit to ON (or set
the battery circuit-breakers of the auxiliary cabinets if any)
~
?
313233
IO
3s
37
The UPS units start automatically. LED (31) is ON.
The load is protected by the UPS.
If LED (31) remains OFF, press the ON button (37) on each UPS unit (the
system is in manual start mode).
If LED (31) still remains OFF and either of LEDs (32) or (33) is ON, a fault
has occurred (see section 4.1).
34001813EN/AE - Page 56
4.5 Training centres
To allow you to use APC by Schneider Electric products effectively and carry out basic maintenance, we offer a complete
range of technical training courses in English and French.
Schneider Critical Power & Cooling Services 50
Hz training centres
4. Maintenance
Schneider Critical Power & Cooling Services 5060 Hz training centre
France Training Centre
140, Avenue Jean Kuntzmann
Innovallée
38334 - St Ismier Cedex - FRANCE
Denmark Training Centre
Silcon Allé
6000 Kolding
Denmark
Tél : +45 72 19 03 12
Singapore Training Centre
10 Ang MO Kio Street 65, #03-06/10
Techpoint Building
Singapore 569059
Tél : +65 6389 6792
China Training Centre
Floor 3, Building B10, Universal Plaza
10 juxianqiao Road
Chaoyang District, Beijing 100016
Tél : +86 10 6431 8899
Brazil Training Centre
Al. Xingu, 850-Alphaville
06455-030 Barueri, São Paulo
Brazil
Tél : +55 11 4689-8600
Internet : http://powerlearning.apc.com
Catalogue and registration available on line.
34001813EN/AE - Page 57
5. Environment
APC by Schneider Electric has implemented an environmental-protection policy.
Products are developed according to an eco-design approach.
Substances
This product does not contain CFCs, HCFCs or asbestos.
Packing
To improve waste treatment and facilitate recycling, separate the various packing components.
The cardboard we use includes over 50% of recycled cardboard.
Sacks and bags are made of polyethylene.
Packing materials are recyclable and bear the appropriate identification symbol .
MaterialAbbreviationSymbol
Polyethylene terephthalatePET01
High-density polyethyleneHDPE02
Polyvinyl chloridePVC03
Low-density polyethyleneLDPE04
number
PolypropylenePP05
PolystyrenePS06
Follow all local regulations for the disposal of packing materials.
End of life
APC by Schneider Electric will process products at the end of their service life in compliance with local regulations.
APC by Schneider Electric works with companies in charge of collecting and eliminating our products at the end of their
service life.
Product
The product is made up of recyclable materials.
Dismantling and destruction must take place in compliance with all local regulations concerning waste.
At the end of its service life, the product must be transported to a processing center for electrical and electronic waste.
Make the product unusable by cutting the internal supply cables.
Battery
The product contains lead-acid batteries that must be processed according to applicable local regulations concerning
batteries.
The battery may be removed to comply with regulations and in view of correct disposal.
The "Material Safety Data Sheets" (MSDS) for the batteries are available on our web site*.
(*) For more information or to contact the Product Environmental manager, use the "Environmental Form" on the site:
http://environment.apc.com
34001813EN/AE - Page 58
Backfeed option
This option opens the Bypass AC input or the Normal AC input if power fails. This option is mandatory to meet standard IEC
62040-1-2.
If an external backfeed protection system is used, it must comply with the requirements indicated in Annex L of standard IEC
62040-1-2.
NMC (Network Management Card) option
This option is a communications card for supervision and protection of a three-phase device. Each UPS can be equipped with
a maximum of four NMC communications cards.
Optional communications card with additional power relay
The UPS is already equipped with a relay communications card. But it is possible, with this option, to add another card with
programmable power-relay functions.
Optional serial communications card
This option is an RS232 or RS485 serial communications card operating under the JBUS protocol.
Telpac Power Services option
This option consists of a communications card operating under the JBUS protocol for Teleservice functions.
6. Available options
AS4I option
This option consists of a low-power relay card for shut-off and scheduling functions.
Multislot option
This option consists of communications cards to concentrate the communication of two parallel-connected UPSs.
External synchronisation module option
With this option, a SYNIN communications card and two circuit breakers are added to each UPS unit. The external
synchronisation module issues a reference frequency used to synchronise the UPS units. For more information, see
document no. 34000346.
Check the different input/output signal levels (LV, ELV, SELV) on the optional communication cards (4) and use
appropriate wiring.
IP32 option
This option protects the UPS against solid objects larger than 2.5 mm and falling drops of water from up to 15° from vertical.
For roof installation, See “IP32 installation”, page 67.
34001813EN/AE - Page 59
7. Appendices
7.1 Technical sheets
Center of gravity
H
P
UPS power rating (kVA)H (mm)W (mm)D (mm)
20/30/40/60 kVA950350360
80/100/120 kVA950350360
L
712 mm
Tip angle (to the rear)
UPS power rating (kVA)UPS on feetUPS on pallet
20/30/40/60 kVA17.5°22°
H
34001813EN/AE - Page 60
80/100/120 kVA17.5°22°
Electrical characteristics
Selection of protection devices
UPS unit with common normal and Bypass AC inputs
Normal AC
Bypass AC
UPS unit with separate normal and Bypass AC inputs
Bypass AC
Normal AC
Upstream
circuit breaker
(not supplied)
Upstream
circuit breaker
(not supplied)
Upstream
circuit breaker
(not supplied)
7. Appendices
15
Q4S
Input
Q1
Q4S
Q1
fuses
Input
fuses
14
15
14
Output
fuses
Output
fuses
16
Q5N
16
Q5N
Downstream
circuit breaker
(not supplied)
Downstream
circuit breaker
(not supplied)
Load
Load
When sizing the upstream circuit breakers, the parameters presented below must be taken into account:
Time/current curves for UPS input and output fuses:
10
10
10
10
1
10
10
10
10
t (s)
4
3
2
20-30-40 kVA : 80A
60 kVA : 125A
80 kVA : 160A
100-120 kVA : 315A
-
1
-
2
-
3
-
4
10
10
2
10
3
10
I (A)
4
UPS short-circuit current with inverter coupled and By-pass AC source out of tolerances:
Sn20 kVA30 kVA40 kVA60 kVA80 kVA100 kVA120 kVA
In29 A43 A58 A87 A115 A144 A173 A
Limitation190 A190 A190 A240A360 A480 A480A
34001813EN/AE - Page 61
7. Appendices
Line current values
Rated power of each
UPS unit
20 kVA29 A36 A44 A80 A
30 kVA43 A55 A65 A80 A
40 kVA58 A72 A87 A80 A
60 kVA87 A108 A130 A125 A
80 kVA115 A145 A174 A160 A
100 kVA144 A181 A217 A315 A
120 kVA173 A217 A260 A315 A
Continuous input
current at U=400V
Input current at
U=400V overload =
1.25 In limited to 10
min.
Input current at
U=400V overload =
1.5 In limited to 1 min.
Input/output fuse
ratings
Input / output characteristics
Normal AC source / Bypass AC source
Standard UPSUPS with backfeed
protection
Uin380 to 443 V380 to 443 V
Input voltage range permitted by the standard
according to the curve below
250 to 470 V340 to 470 V
Fin45 to 65 Hz45 to 65 Hz
Load output
Uout380 V400 V415 V+ 3%
- 3%
Power supplied as a function of
Permissible UPS overloads as a function of time
input voltage
P/Pn
I/In
2,2
100%
70%
2
1,8
250V 340V
470V
U
1,6
1,4
1,2
34001813EN/AE - Page 62
1
1010,1
10260600
10
3
10
4
10
t (s)
5
Maximum allowable power for parallel UPS units
Without external bypass cabinet:
~
?
O
I
s
3
= 1 x Pn
7. Appendices
~
?
O
I
s
3
~
?
O
I
s
3
+
With external bypass cabinet:
~
?
O
I
s
3
~
?
O
I
s
3
+
~
?
IO
s
3
~
?
O
I
s
3
+
~
?
IO
s
3
~
?
O
I
s
3
++
= 1 x Pn
= 2 x Pn
+
~
?
IO
s
3
= 3 x Pn
~
?
IO
s
3
+
~
?
IO
s
3
= 4 x Pn
~
?
IO
s
3
~
?
IO
s
3
~
?
IO
s
3
~
?
IO
s
3
~
?
IO
s
3
+++
~
?
IO
s
3
+++
~
~
?
?
O
IO
I
s
s
3
3
+
~
?
~
?
IO
s3
IO
s
3
+
~
?
O
I
s
3
= 4 x Pn
~
~
?
?
IO
IO
s
s
3
3
+
~
?
IO
s
3
= 4 x Pn
34001813EN/AE - Page 63
7. Appendices
The maximum allowable power for 4 parallel UPS units is limited to 4 x Pn.
Restrictions to parallel operation
EMC levelCategory C3Category C3
ECO modeYesNo
Frequency converterYesYes (for two UPSs)
Compatibility with the synchronisation moduleYesYes
(*) : except in ECO mode or bypass mode.
Thermal characteristics
◗ The operating temperature range is 0°C to +40°C (0°C to 30°C for overload conditions), however optimum operation is within
the +20°C to +25°C range.
◗ Battery backup time is adversely affected by high and low temperatures. It is significantly reduced at temperatures under
10°C.
Above 25°C, battery service life is cut in half every 10°C. Above 40°C, battery manufacturers no longer guarantee operation
due to the risk of thermal runaway.
.
UPS power ratingHeat lossesRecommended air
20 kVA2.4 kW1 332 m
30 kVA3 kW1 332 m
40 kVA3.4 kW1 332 m
60 kVA4.9 kW1 332 m
80 kVA5.8 kW2 556 m
100 kVA7 kW2 556 m
120 kVA8.4 kW2 556 m
Single UPSParallel UPS
throughput
3
/h
3
/h
3
/h
3
/h
3
/h
3
/h
3
/h
Air enters through the bottom.
Air exits through the top.
34001813EN/AE - Page 64
7. Appendices
General characteristics of MGE
UPS power in kVA2030406080100120
Normal AC input
Number of conductors3 phases
Reference voltage at Pn380 V to 443 V
Reference frequency45 Hz to 65 Hz
THDITypically 3% at Pn
Power factor>0.99
Bypass AC input
Number of conductors3 phases + neutral
Reference voltage at Pn380 V to 443 V
Reference frequency45 Hz to 65 Hz
Load output
Number of conductors3 phases + neutral
Set phase-to-phase voltages380 V or 400 V or 415 V
Set phase-to-neutral voltages220 V or 230 V or 240 V
TM
GalaxyTM 5000 UPSs
Voltage variation± 1%
Adjustable frequencies and tolerance
(on battery power)
Voltage variation for 0 to 100% load
step change
Permissible overloads150% for 1 minute, 125% for 10 minutes
THDU Ph-to-Ph and Ph-to-N for
nonlinear load
Battery
Standard battery technologySealed lead-acid battery (gas-recombination)
Inverter
Active power (kW)16243248648096
Heat losses in kW
Heat losses in calories/s
Storage temperature range-25°C to +45°C
Operating temperature range at Pn0°C to 40°C
Relative humidity20% to 95%
Maximum operating altitude without
derating
(1)
50 Hz or 60 Hz ± 0.1 Hz
± 1%
< 2% Ph-to-Ph
2.7
648
< 1000 m
3
720
3.54
850
4.7
1128
5.31
1275
6.5
1560
7.64
1834
(1)Losses are calculated for n-1%.
34001813EN/AE - Page 65
7. Appendices
General characteristics of MGETM GalaxyTM 5000 UPSs (cont.)
UPS power in kVA2030406080100120
Noise level (dBa)65656565636363
Width710 mm
Depth850 mm
Height1900 mm
Weight (kg)400400400400520520520
UPS components
Recommended upstream residual
current protection
Product standardsIEC 62040
Safety standardsIEC 62040-1-2
Protection standardsIEC 62040-3
EMC standardsIEC 62040-2
1 A
IGBT charger + neutral leg
IGBT PFC
IGBT inverter
Q1Q4SQ3BPQ5N
QF1
EXTN board
DC capacitors
Normal AC SS board + battery
Output fuse
Bypass AC SS and inverter board