American Power Conversion CTSLP-G User Manual

BroadBand CTSLP/G
Uninterruptible Power Supply 60 VAC
User Manual
990-5518A 10/2004
Chapter 1 General Information
The SLP/G Series Standby Power Supply provides an uninterruptible power source for broadband cable operations. Batteries are housed inside the module. A battery vault may be used to provide additional battery backup. Refer to the APC Web site, www.apc.com additional battery configurations.
Important Safety Instructions – Save These Instructions
This Safety Guide contains important instructions that should be followed during installation and maintenance of the APC equipment and batteries. It is intended for APC customers who setup, install, relocate, or maintain APC equipment.
Changes and modifications to this unit not expressly approved by APC could void the warranty.
Failure to observe these warnings may result in serious injury, death or damage to the equipment.
Electrical Warnings
Do not work alone under hazardous conditions.
Do not handle any metallic connector before the power has been disconnected.
Servicing this equipment may require working with protective covers removed and AC power connected. Use extreme caution during these procedures.
High short circuit current through conductive materials could cause severe burns.
for detailed information on
When grounding cannot be verified, disconnect the equipment from the utility power outlet before installing or connecting to other equipment. Reconnect the power cord only after all connections are made.
Check that the power cord(s), plug(s), and sockets are in good condition.
Replacement of fuses or other parts must be with identical types and ratings. Substitution of nonidentical parts may cause safety and fire hazards.
Overhead
Never stand underneath anything while it is hoisted. Always wear a hard hat.
Warnings
Lifting
Transformer modules are heavy. Use proper lifting techniques to avoid injury.
Warnings
Battery Warnings
1 990-5518 03/02
Danger of explosion if battery is incorrectly connected or replaced. Replace batteries only with same or equivalent type recommended by the manufacturer. Dispose of used batteries according to the manufacturer’s instructions.
Specifications
Environmental Specifications
Operating Temperature
Humidity
Physical Specifications
Characteristic Specification
Height Pole Mount Ground Mount
Width Pole Mount/Ground Mount
Depth Pole Mount/ Ground Mount
Weight
Pole Mount
without batteries with 3 batteries
Ground Mount
without batteries with 3 batteries
-40º F to +140º F (-40º C to +60º C)
5% to 95% noncondensing within enclosure
18 (45.7 cm) 25” (33 cm)
23 (58.4 cm)
16 (41 cm)
82 lbs (37.2 kg) 154 lbs (70 kg)
92 lbs (41.8 kg) 164 lbs (75.5 kg)
Electrical Specifications
Input Characteristic Input Specification
Input Voltage 120 VAC Nominal
Input Current 15 A Max
Input Frequency 60 Hz ± 1 Hz
Output Characteristic Output Specification
Output Voltage 60 VAC ± 3%
Output Current 9 A/15 A
Output Frequency 60 Hz ± 1%
Output Regulation
Normal Standby
Output Protection
Transfer Time
2 990-5518 03/02
220 VAC Nominal
± 3% ± 5%
20 A Circuit Breaker (optional)
<20 milliseconds
Chapter 2 Installation and Maintenance
Only trained service personnel should install and maintain the Power Supply.
Prior to installing the Power Supply AC line voltage must be routed to the enclosure. Local, state, federal and/or National Electric Code (NEC) regulations regarding location, permits and electrical wiring must be adhered to.
Do not operate the Power Supply where the temperature and humidity are outside the specified limits. See Specifications in this manual.
Unpacking
Inspect the unit upon receipt. Notify the carrier if there is damage.
The packaging is recyclable; save it for reuse or dispose of it properly.
Check the package contents. The package contains the Power Supply and product documentation.
SLG Enclosure SLP Enclosure
Mounting Bracket
Models Supported
Model Number Description
CTSLGH220S1 ENCL, SLG, 36V, 220VAC, SM Ready
CTSLPH120S1 ENCL, SLP, 36V, 120VAC, SM Ready
CTSLPH220S1 ENCL, SLP, 36V, 220VAC, SM Ready
CTSLGH710S1 ENCL, SLG, 36V, 120VAC, SM Ready
Installing the Power Supply Enclosure
Use 2” conduit with an outer diameter of 2.5” (5.1 cm/6.4 cm). The mounting holes are 1/2” in diameter.
3 990-5518 03/02