American Power Conversion CTFLP User Manual

BroadBand CTFLP Series
Uninterruptible Power Supply
User’s Manual
990-5519 02/2003
Chapter 1 General Information
The CTFLP Series provides an uninterruptible power source for broadband cable operations. The enclosure is designed for mounting on either a pole or wall.
Safety
This Safety Guide contains important instructions that should be followed during installation and maintenance of the APC equipment and batteries. It is intended for APC customers who setup, install, relocate, or maintain APC equipment. Changes and modifications to this unit not expressly
approved by APC could void the warranty.
Failure to observe these warnings may result in serious injury, death or damage to the equipment.
Electrical Warnings
Overhead Warnings
Lifting Warnings
Do not work alone under hazardous conditions.
Do not handle any metallic connector before the power has been disconnected.
Servicing this equipment may require working with protective covers removed and utility power connected. Use extreme caution during these procedures.
High current through conductive materials could cause severe burns.
When grounding cannot be verified, disconnect the equipment from the utility power outlet before installing or connecting to other equipment. Reconnect the power cord only after all connections are made.
Check that the power cord(s), plug(s), and sockets are in good condition.
Replacement of fuses or other parts must be with identical types and ratings. Substitution of nonidentical parts may cause safety and fire hazards.
Never stand underneath anything while it is hoisted. Always wear a hard hat.
Transformer modules are heavy. Use proper lifting techniques and equipment to avoid injury.
1
Specifications
Environmental Specifications
Operating Temperature
Humidity
Physical Specifications
Characteristic Specification
Height X Width X Depth 11.4” X 8.5” X 7.1” (29 cm X 22 cm X 18 cm )
Weight 36 lbs (16 kg)
Electrical Specifications
Input Characteristic Input Specification
Input Voltage 120 VAC Nominal
Input Current 15 A Max
Input Frequency 60 Hz ± 1 Hz
Output Characteristic Output Specification
Output Voltage 60 VAC ± 3%
Output Current 15 A
Output Frequency 60 Hz ± 1%
Output Regulation
Normal Standby
-40º F to 158º F (-40º C to 70º C)
5% to 95% noncondensing within enclosure
220 VAC Nominal
± 3% ± 5%
Output Protection
Transfer Time
2
20 A Circuit Breaker (optional)
<20 milliseconds
Chapter 2 Installation and Maintenance
Only trained service personnel should install and maintain the Power Supply.
Prior to installing the Power Supply utility line voltage must be routed to the enclosure. Local, state, federal and/or National Electric Code (NEC) regulations regarding location, permits and electrical wiring must be adhered to.
Do not operate the Power Supply where the temperature and humidity are outside the specified limits. See Specifications in this manual.
Unpacking
Inspect the unit upon receipt. Notify the carrier if there is damage.
The packaging is recyclable; save it for reuse or dispose of it properly.
Check the package contents. The package contains the power supply and product documentation.
CTFLP Enclosure Side View Showing Mounting Bracket
Mounting Bracket
Models Supported
Model Number Description
CTFLPH120 ENCL, CTFLP 120VAC
CTFLPH220 ENCL, CTFLP 220VAC
3