Chapter 1 General Information
The CTEP/G Series Enclosures provide housing for a power source for broadband cable operations.
Safety
This Safety Guide contains important instructions that should be followed during installation and maintenance of the APC equipment and batteries. It is intended for APC customers who setup, install, relocate, or maintain APC equipment. Changes and modifications to this unit not expressly
approved by APC could void the warranty.
Failure to observe these warnings may result in serious injury, death or damage to the equipment.
Electrical Warnings
Battery Warnings
Overhead Warnings
Lifting Warnings
Do not work alone under hazardous conditions.
Do not handle any metallic connector before the power has been disconnected.
Servicing this equipment may require working with protective covers removed and utility power connected. Use extreme caution during these procedures.
High current through conductive materials could cause severe burns.
When grounding cannot be verified, disconnect the equipment from the utility power outlet before installing or connecting to other equipment. Reconnect the power cord only after all connections are made.
Check that the power cord(s), plug(s), and sockets are in good condition.
Replacement of fuses or other parts must be with identical types and ratings. Substitution of nonidentical parts may cause safety and fire hazards.
Danger of explosion if battery is incorrectly connected or replaced. Replace batteries only with same or equivalent type recommended by the manufacturer.
Batteries must be recycled. Deliver the battery to an appropriate recycling facility or ship it to the supplier in the new battery packing material.
Never stand underneath anything while it is hoisted. Always wear a hard hat.
Modules are heavy. Use proper lifting techniques and equipment to avoid injury.
1
Chapter 2 Installation
Only trained service personnel should install and maintain the power supply enclosure.
Prior to installing the power supply enclosure, a utility breaker box must be installed on the pole. Utility line voltage must be routed to the enclosure. Local, state, federal and/or National Electric Code (NEC) regulations regarding location, permits and electrical wiring must be adhered to.
Do not operate the power supply where the temperature and humidity are outside the specified limits. See Specifications in this manual.
Specifications
Models Supported
Model Number Description
CTEP0-120 Encl, Pole 0 Batt 20 A, 120 VAC, 60 Hz
CTEP3-120 Encl, Pole 3 Batt 20 A, 120 VAC, 60 Hz
CTEP3-240 Encl, Pole 3 Batt 20 A, 240 VAC, 60 Hz
CTEP6-120 Encl, Pole 6 Batt 20 A, 120 VAC, 60 Hz
CTEP6-120GI Encl, Pole 6 Batt w/ Generator Interface, 20 A, 120 VAC, 60 Hz
CTEG0-120 Encl, Ground 0 Batt 20 A, 120 VAC, 60 Hz
CTEG3-120 Encl, Ground 3 Batt 20 A, 120 VAC, 60 Hz
CTEG6-120 Encl, Ground 6 Batt 20 A, 120 VAC, 60 Hz
CTEG6-120GI Encl, Ground 6 Batt w/ Generator Interface, 20 A, 120 VAC, 60 Hz
Environmental Specifications
Operating Temperature
Humidity
-40º F to140º F (-40º C to 60º C)
5% to 95% noncondensing within enclosure
Physical Specifications
Characteristic Specification
Height X Width X Depth CTEP0 CTEP3 CTEP6
Height X Width X Depth
CTEG0 CTEG3 CTEG6
Weight
CTEP/G0 CTEP/G3 CTEP/G6
2
14” x 24” x 16” (36 x 61 x 41 cm) 30” x 24” x 16” (76 x 61 x 41 cm) 39” x 24” x 16” (99 x 61 x 41 cm)
22” x 24” x 16” (56 x 61 x 41 cm) 38” x 24” x 16” (97 x 61 x 41 cm) 47” x 24” x 16” (119 x 61 x 41 cm)
23 lbs (10 kg) 50 lbs (23 kg) 77 lbs (35 kg)
(
r
r
Unpacking
Inspect the unit upon receipt. Notify the carrier if there is damage.
The packaging is recyclable; save it for reuse or dispose of it properly.
Check the package contents. The package contains the enclosure, battery cables, connectors and associated hardware and product documentation.
CTEP/G3: (5 cables); 15” black battery jumpers (2), 24” black (1), 27” red (2), 34” red (1).
CTEP/G6: (9 cables); 15” black battery jumpers (4), 25” black (1), 40” black (1), 60” black (1), 27” red (1), 34” red (1).
Installing the Enclosure
Pole Mount Installation
CTEP 0 Model
Top Hole .75” (2 cm)
18 cm)
7”
Bottom Hole .75” (2 cm)
Mounting Bracket
CTEP3 Model
12” (30 cm)
3
Bottom Edge of Housing
Top Hole .75” (2 cm)
Bottom Hole .75” (2 cm)
Bottom Edge of Housing
Mounting Bracket is permanently attached to enclosure.
is permanently attached to enclosure.
5/8” Pole Bolt and Square Washe
5/8” Pole Bolt and Square Washe
r
r
CTEP6 Model
12” (30 cm)
Top Hole .75” (2 cm)
Middle Hole .75” (2 cm)
Mounting Bracket is permanently attached to enclosure.
12” (30 cm)
Bottom Hole .75” (2 cm)
Bottom Edge of Housing
5/8” Pole Bolt and Square Washe
Ground Mount Installation
1. Install an APC approved concrete pad. Contact your dealer or see How to Contact APC, in this manual for more information.
2. Secure the enclosure to the pad.
0 Battery Enclosure:
Attach the ground skirt to the concrete pad.
3 Battery, 6 Battery Enclosures:
Place the enclosure on the pad. The holes on the enclosure must be aligned with the anchor hooks on the pad, (hardware not included).
This is a general representation of an enclosure mounted on a pad. Configurations may vary.
Attach the enclosure to the ground skirt.
Service Entrance/
Meter Base
Coax Housing
Load Cente
Coax Housing
4
pply
n
E
Wiring
Grounding
1. Install and interconnect ground rods appropriate for proper grounding according to local electrical code requirements.
2. Route ground wires from the ground system into the bus bar located on the enclosure.
Connecting Utility Power to the Enclosure
EP3 (EP6 has additional battery tray)
Tamper Switch Present on all Models
Site for Power Supply
EP0
Status Monitoring Lamp Present on all Models
Battery Tray
lectrical Input Output Box
Maintenance Bypass Switch
Auxiliary Power
Connectio
Su
1. Unlock and open the door of the enclosure.
2. Ensure that the utility power switch is OFF.
3. Install a high magnetic circuit breaker box
4. Using appropriate conduit connectors, run wires from the utility breaker box to the receptacle box inside the enclosure.
5. Connect the wires to the receptacle and install it in the enclosure.
6. Refer to the CTSP-EM User’s Manual for detailed installation instructions regarding the Interface Harness connections.
Grounding Wire
Output Connection to Coax
Optional External AC Generator Interface
To CTSP Utility Output Terminals
Output Voltage Sensor
5
Options
The CTEP/G6-120GI has an optional External AC Generator Interface.
For available options see your dealer or the APC web site, www.apc.com/support
Connecting the Batteries
The battery circuit breaker must OFF prior to battery installation.
Use normal precautionary measures when wiring and connecting the batteries.
Tape one end of each jumper cable prior to installation.
CTEP3
Bottom Shelf
27” Red to Circuit Breaker
25” Black to CTSP
34” Red to CTSP
Circuit Breaker
Top Shelf
.
CTSP Battery Connection
Cables from Battery and Circuit Breaker
6
r
CTEP6
60” Black to Circuit Beaker
Bottom Shelf
60” Black to Battery 3+
40” Black to Battery 1-
Middle Shelf
27” Red to Circuit Breaker
25” Black to CTSP
40” Black from Battery 6-
Top Shelf
7
34” Red to CTSP
Circuit Breake
CTSP Battery Connection
Cables from Battery 3- and Circuit Breaker
Chapter 3 Service, Contact and Warranty Information
Service
APC makes every effort to ensure parts and equipment arrive in working condition. Occasionally, it may be necessary to return parts or equipment that are not in working condition.
If the UPS requires service do not return it to the dealer. Instead, follow these steps:
1. Contact APC Customer Service through the APC web site, www.apc.com/support
Note the product model number, the serial number, and the date purchased. If you call APC
.
Customer Service, a technician will ask you to describe the problem and try to solve it over the phone. If this is not possible the technician will issue a Returned Material Authorization Number (RMA#).
If the product is under warranty, repairs are free. If not, there is a repair charge.
Procedures for servicing or returning products may vary internationally. Refer to the APC
web site. Select the appropriate country from the country selection field. Select Support from the tab at the top of the web page.
2. Pack the product in its original packaging. If the original packing is not available, refer to the APC web site for information on obtaining appropriate packing materials.
Pack the unit properly to avoid damage in transit. Never use Styrofoam beads for packaging.
Damage sustained in transit is not covered under warranty.
3. Mark the RMA# on the outside of the package.
4. Return the unit by insured, prepaid carrier to the address given to you by Customer Service.
How to Contact APC
In the USA … Outside the USA …
Refer to the APC web site,
www.apc.com/support
.
Refer to the APC web site, www.apc.com country from the country selection field. Select the Support tab at the top of the web page.
. Select the appropriate
8
Limited Warranty
American Power Conversion (APC) warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase. Its obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer support. Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase. This warranty does not apply to equipment that has been damaged by accident, negligence, or misapplication or has been altered or modified in any way. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase.
EXCEPT AS PROVIDED HEREIN, AMERICAN POWER CONVERSION MAKES NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation or exclusion of implied warranties; therefore, the aforesaid limitation(s) or exclusion(s) may not apply to the purchaser.
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL APC BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, APC is not liable for any costs, such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, costs of substitutes, claims by third parties, or otherwise.
Regulatory Approval
Entire contents copyright © 2002 by American Power Conversion Corporation. All rights reserved. Reproduction in whole or in part without permission is prohibited.
APC is a registered trademark of American Power Conversion Corporation. All other trademarks are the property of their respective owners.