Apc BX1100LI, BX1100LI-MS User Manual [ru]

bu389b
IEC jumper cable for PC connection
bu389a
BX1100LI-MS
BX1100LI
Back-UPS
BX1100LI Series
Safety and General Information
Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage.
Read the following reminders before installing the UPS.
User Guide
4
1
2
5
Status Indicators
On-line (Green)
Replace Battery
(Red)
Audible Alarm Condition
On -
Off
On-line - The Back-UPS is supplying AC power to the connected equipment
-On
Constant Tone
On Line Overload - The power being used by the connected equipment has exceeded the capacity of the unit. Disconnect some equipment
On -
Constant beeping
Over-temperature Warning - The unit is overheating and will shut down if the temperature is not lowered. Disconnect some of the connected equipment.
On -
4 beeps repeated
every 30 seconds
On-Battery - The Back-UPS is supplying battery power
Flashing -
Rapid Beeping
(every 1/2 second)
Low Battery Warning - The Back-UPS has 2 minutes of runtime remaining
Flashing Alternately
Constant tone
Bad Battery Detected - The battery needs to be charged, or is at end of life.
- Flashing
Chirp every 2
seconds
Charger Warning - The Back-UPS has experienced an internal problem, but is still providing power to the connected equipment. Contact Schneider Electric IT (SEIT) Technical Support
Off
Short beep every
4 seconds
Low Battery Shutdown - During On Battery operation the battery power was almost completely exhausted, and the Back-UPS is waiting for AC power to return to normal
Constant Tone
On Battery Overload - The connected equipment requires more power than provided by the Back-UPS battery. Unplug devices one at a time to remove overload. If the problem is not corrected, contact SEIT Technical Support
Constant Tone
Charger Fault - Back-UPS has an internal problem. The AC input is present but is no powering the load. Contact SEIT Technical Support
Long beep every
4 seconds
Over-temperature Protected - The Back-UPS has overheated and has shut down. Unplug connected devices one at a time or wait a few hours for system to cool down.
Connect the Battery
3
1 Connect the battery by pulling the battery connector handle
down, and then pushing it into the unit.
2 Replace PC’s input cord with the supplied IEC jumper cable,
and use the PC’s input cord to connect UPS. Note: BX1100LI-MS comes with an extra power cord for connection to a wall outlet.
3 Press the ON/OFF button to turn on the unit.
The green “Power On” indicator confirms that the Back-UPS is on and ready to provide protection.
The Back-UPS should charge for at least 10 hours to ensure sufficient runtime. The unit is being charged whenever it is connected to AC power, whether the unit is turned ON or OFF.
Features
Operational Features
Automatic Voltage Regulation
Automatic Voltage Regulation boosts/trims the AC voltage when it drops/exceeds safe levels. This allows the equipment that is connected to the Back-UPS to operate during low/high voltage conditions, conserving the battery power in the event of a power cut.
The Back-UPS will switch to battery power if the AC input voltage level becomes too low/high for the Automatic Voltage Regulation feature to compensate, or if the AC power is distorted.
If the Back-UPS switches to battery power too frequently or too infrequently, adjust the transfer voltage and sensitivity settings:
1 . Verify that the Back-UPS battery is connected. Connect the Back-UPS to a wall outlet. The
Back-UPS should be turned off.
2 . Press and hold the POWER ON/OFF button for 10 seconds. The LEDs will illuminate green and red
alternately, to indicate that the Back-UPS is in Program mode.
3 . The LEDs will flash either green, red or green and red alternately to indicate the current sensitivity level. The
Back-UPS will beep to indicate that No-load Shutdown is enabled. Refer to the table for an explanation of
the transfer voltage sensitivity levels. 4 . To select LOW sensitivity, press the ON/OFF button until the On Line LED flashes green. 5 . To select MEDIUM sensitivity, press the ON/OFF button until the Battery LED flashes red. 6 . To select HIGH sensitivity, press the ON/OFF button until the On Line and Battery LEDs flash green and
red alternately. 7 . To exit Program mode wait for five seconds and both LEDs will extinguish. Program mode is no longer
active.
No-load Shutdown
The UPS will shut down to conserve energy if while operating on battery power the UPS detects that connected equipment is using less than 15 W of energy for more than 15 minutes.
When the UPS is reconnected to AC power, the UPS will automatically switch on.
Warranty
Register your product on-line. http://warranty.apc.com
The standard warranty is two (2) years from the date of purchase. SEIT standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact with an SEIT Technical Support representative. SEIT will ship the replacement unit once the defective unit has been received by the repair department, or cross-ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to SEIT. SEIT pays ground freight transportation costs to ship the replacement unit to the customer.
LED
Flashes
Audible
Indicator
Vo lt ag e
Sensitivity
Setting
Input
Vo lt ag e
Range
No-load
Shutdown Recommended Use
Green None Low 150-280 Disabled Use this setting with equipment that is
less sensitive to fluctuations in voltage or waveform distortions.
Green 4 beeps per
second
Low 150-280 Enabled Use this setting with equipment that is
less sensitive to fluctuations in voltage or waveform distortions.
Red None Medium 155-280 Disabled Use this setting for normal operation
conditions.
Red 4 beeps per
second
Medium (factory default)
155-280 Enabled Use this setting for normal operation
conditions.
Green and Red
None High 160-280 Disabled Use this setting when connected
equipment is sensitive to voltage fluctuations or waveform distortions.
Green and Red
4 beeps per second
High 160-280 Enabled Use this setting when connected
equipment is sensitive to voltage fluctuations or waveform distortions.
6
Troubleshooting and Service
1 . If the problem persists, contact Schneider Electric IT (SEIT) Customer Support through the Schneider
Electric Web site, www.apc.com.
a. Note the model number and serial number and the date of purchase. The model and serial numbers are
located on the rear panel of the unit and are available through the LCD display on select models.
b. Call SEIT Customer Support and a technician will attempt to solve the problem over the phone. If this
is not possible, the technician will issue a Returned Material Authorization Number (RMA#). c. If the unit is under warranty, the repairs are free. d. Service procedures and returns may vary internationally. Refer to the Schneider Electric Web site for
country specific instructions.
2 . Prepare to troubleshoot the problem over the phone. If this is not successful, and the unit is still under
warranty, the Technical Support Representative will provide all necessary information to return the unit for replacement
APC by Schneider Electric IT Customer Support Worldwide
For country specific customer support, go to the APC by Schneider Electric Web site, www.apc.com.
Specification BX1100LI BX1100LI-MS
Input
Voltage 220 - 240 Vac Frequency 50/60 Hz ±3 Hz (Auto-sensing) Brownout Transfer 155 Vac, typical Over-voltage Transfer 280 Vac, typical
Output
UPS Capacity (total) 1100 VA / 550 W Voltage On Battery 230 Vac rms Frequency on Battery 50/60 Hz ± 1 Hz Transfer Time 4 ms typical
Protection
AC Input Resettable circuit breaker
Battery
Type (maintenance free, lead acid)
12 V, 9 AH
Average Life
The battery typically lasts for three to five years.
Environmental factors impact battery life.
Elevated temperatures, high humidity, poor
quality mains power, and frequent, short duration
discharges will shorten battery life.
The battery in the Back-UPS BX1100LI Series
is not user-replaceable. Contact SEIT
Technical Support for a list of authorized
service centers near you.
Typical Recharge Time 6 hours
Physical
Net Weight 8.8 kg 9.2 kg Dimensions (H x W x D) 21.5 cm x 13 cm x 33.6 cm
e
On Line indicator
Circuit breaker
Battery indicator
Battery Backup + Surge Protection outlets
Power button
AC Power Inlet
Battery connector
Specifications
EN 990-5400-002 06/2014
© 2014 APC by Schneider Electric. APC, the APC logo, and Back-UPS are owned by Schneider Electric Industries S.A.S. or
their affiliated companies. All other trademarks are property of their respective owners.
• This UPS is intended for indoor use only.
• Connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords.
• When grounding cannot be verified, disconnect the equipment from the AC power outlet before installing or connecting to other equipment. Reconnect the power cord after all connections are made.
• Servicing of batteries should be performed by Schneider Electric IT (SEIT) Customer Support only.
• When replacing battery the UPS must be OFF, and its AC inlet unplugged.
• Do not dispose of batteries in a fire. The batteries may explode.
• Do not open or mutilate batteries. They contain an electrolyte that is toxic and harmful to the skin and eyes.
• To avoid harmful injury due to energy hazard, remove wrist watches and jewelry such as rings when replacing the batteries. Use tools with insulated handles.
• Replace batteries with the same number and type of batteries as originally installed in the